Errata
NFPA 2001
Standard on Clean Agent Fire Extinguishing Systems
2000 Edition
Reference: Various
Errata No.: 2001-00-2 The Committee on Halon Alternative Protection Options notes the following errors in the
2000 edition of NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems.
1. Add the following isometric diagrams for HFC-236fa see Figure A-2-1.4.1 (ii)
through (ll) enclosed.
2. In Table 1-6.1.2.1 (a), the % LOAEL for HFC-23 should be changed from“>5”to
“>50”.
3. In Table A-1-5.1 (a), in the tenth row with the heading Heat of Vaporization at
Boiling Point, delete “at 25°C”.
4. In Table A-1-5.1 (c) in the second Row, change the Heading from “Boiling Point
at 19.7 psia” to “Boiling Point at 14.7 psia.”
5. In Figures A-2-1.4.1 (c) through (h) change “FE-25” to “HFC-125” in the Figure
Headings.
6. In Figures a-2-1.4.1 (d), (h), and (v) change the comas to decimal points.
7. Replace Table 2-2.1.1 (a) with the enclosed new version:
8. In Table 2-2.1.1 (b) change the row for 600 psig container pressure for HFC-227ea to read as follows:
![Page 2: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/2.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 2/8
Agent
Agent Container
Maximum Fill Density
(lb/ft3)
Agent Container
Charging Pressure at
70°F (21°C)
(psig)
Agent Container
Pressure at 130°F (55°C)
(psig)
Minimum Piping Design
Pressure at 70°F (21°C)
(psig)
HFC-227ea 72 600* 1025 820
In Table A-1-5.1 (c) in the second row, change the heading from Boiling Poi19.7
9. Change paragraph 2-2.1.2 to read as follows:
2-2.1.2 Cast-iron pipe, steel pipe conforming to ASTM A 120, Specifications for Pipe,
Steel, Black, and Hot-Dipped Zinc Coated, Welded and Seamless for Ordinary Uses , ornonmetallic pipe shall not be used.
10. Delete Table A-2.2.1.1 (d)
11. In A-2.2.1.1 (e) second paragraph, change the reference from “Table A-2.2.1.1 (i)(1) and Table A-2.2.1.1 (i) (2).”to “Table 2.2.1.1(a) and Table 2.2.1.1 (b).”
12. In A-2.2.1.1 (e) last paragraph, change the second sentence to read:
“ In this case, the governing criteria of 2-2.1.1 (2) is 80 percent of the pressure in the
agent container at 160°F.”
13. In A-2.2.1.1 (h) (1) change the reference from “Table A-2.2.1.1 (i) (1)” to “Table
2-2.1.1 (a).”
14. In A-2.2.1.1 (h) (2) change the reference from “Table A-2.2.1.1 (1)(2)” to “Table
2.2.1.1 (b).”
15. In Table A-3.5.1 (e) change the headings of the columns to read as follows:
Temp.t
(°F)c
Specific
VaporVolume
s (ft 3 /lb)d
Weight Requirements of Hazard Volume, W/V (lb/ft 3)b
Design Concentration (% by Volume )e
8.6 9 10 11 12 13 14 15
Issue Date: December 20, 2000
![Page 3: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/3.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 3/8
Copyright © 2000 All Rights Reserved
NATIONAL FIRE PROTECTION ASSOCIATION
2000
1800
1600
1400
1200
1000
800
600
400
200
020 40 60 80 100 120 140 160 180 2000
P r e s s u r e ,
P S
I G
Temperature °F
75 lb/ft3
70 lb/ft3
65 lb/ft3
![Page 4: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/4.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 4/8
140.0
120.0
100.0
80.0
60.0
40.0
20.010 20 30 40 50 60 70 80 90 1000
b a r , g a u g e
Temperature, °C
1042 kg/m3
1122kg/m3
1202kb/m3
2400
2200
2000
1800
1600
1400
1200
1000
800
600
40020 40 60 80 100 120 140 160 180 2000
P r e s s u
r e ,
( p s i )
Temperature (°F)
75 lb/ft3
70 lb/ft3
65 lb/ft3
![Page 5: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/5.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 5/8
180
160
140
120
100
80
10 20 30 40 50 60 70 80 90 1000
b a r , g a u g e
Temperature, °C
1042 kg/m3
1122kg/m3
1202kb/m3
60
40
20
![Page 6: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/6.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 6/8
![Page 7: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/7.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 7/8
![Page 8: Errata2001-00-2](https://reader035.fdocuments.net/reader035/viewer/2022081806/577d21cd1a28ab4e1e95eb85/html5/thumbnails/8.jpg)
8/3/2019 Errata2001-00-2
http://slidepdf.com/reader/full/errata2001-00-2 8/8
Table 2-2.1.1(a) Minimum Design Working Pressure for Inert Gas Clean Agent System Piping
Minimum Design Pressure at 70°F (21°C)
Agent Container
Charging Pressure at
70°F (21°C)
Agent Container
Charging Pressure at
130°F (55°C)
Piping Upstream of
Pressure Reducer
Piping Downstream of
Pressure ReducerAgent psig kPa psig kPa psig kPa psig kPa
IG-01 2,371 16,347 2,650 18,271 2,371 16,347 975 6,723
2,964 20,436 3,306 22,778 2,964 20,436 975 6,728
IG-541 2,175 14,997 2,575 17,755 2,175 14,997 1,000 6,895
2,900 19,996 3,433 23,671 2,900 19,996 1,000 6,895
IG-55 2,222 15,320 2,475 17,065 2,222 15,320 950 6,550
2,962 20,424 3,300 22,753 2,962 20,424 950 6,550
4,443 30,633 4,950 34,130 4,443 30,635 950 6,550
IG-100 2,404 16,575 2,799 19,300 2,404 16,575 1,000 6,895
3,236 22,311 3,773 26,014 3,236 22,311 1,000 6,895