8/3/2019 Errata2001-00-2 http://slidepdf.com/reader/full/errata2001-00-2 1/8  Errata NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2000 Edition Reference: Various Errata No.: 2001-00-2 The Committee on Halon Alternative Protection Options notes the following errors in the 2000 edition of NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems. 1. Add the following isometric diagrams for HFC-236fa see Figure A-2-1.4.1 (ii) through (ll) enclosed. 2. In Table 1-6.1.2.1 (a), the % LOAEL for HFC-23 should be changed from“>5”to “>50”. 3. In Table A-1-5.1 (a), in the tenth row with the heading Heat of Vaporization at  Boiling Point, delete “at 25 ° C”. 4. In Table A-1-5.1 (c) in the second Row, change the Heading from “Boiling Point at 19.7 psia” to “Boiling Point at 14.7 psia.” 5. In Figures A-2-1.4.1 (c) through (h) change “FE-25” to “HFC-125” in the Figure  Headings. 6. In Figures a-2-1.4.1 (d), (h), and (v) change the comas to decimal points. 7.  Replace Table 2-2.1.1 (a) with the enclosed new version: 8. In Table 2-2.1.1 (b) change the row for 600 psig container pressure for HFC- 227ea to read as follows:

Transcript of Errata2001-00-2

Page 1: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 1/8

 Errata

NFPA 2001

Standard on Clean Agent Fire Extinguishing Systems 

2000 Edition

Reference: Various

Errata No.: 2001-00-2 The Committee on Halon Alternative Protection Options notes the following errors in the

2000 edition of NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems.

1. Add the following isometric diagrams for HFC-236fa see Figure A-2-1.4.1 (ii)

through (ll) enclosed. 

2. In Table 1-6.1.2.1 (a), the % LOAEL for HFC-23 should be changed from“>5”to

“>50”. 

3. In Table A-1-5.1 (a), in the tenth row with the heading Heat of Vaporization at 

 Boiling Point, delete “at 25°C”.

4. In Table A-1-5.1 (c) in the second Row, change the Heading from “Boiling Point

at 19.7 psia” to “Boiling Point at 14.7 psia.”

5. In Figures A-2-1.4.1 (c) through (h) change “FE-25” to “HFC-125” in the Figure

 Headings. 

6. In Figures a-2-1.4.1 (d), (h), and (v) change the comas to decimal points.

7.   Replace Table 2-2.1.1 (a) with the enclosed new version:

8. In Table 2-2.1.1 (b) change the row for 600 psig container pressure for HFC-227ea to read as follows:

Page 2: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 2/8

 

Agent

Agent Container

Maximum Fill Density

(lb/ft3)

Agent Container

Charging Pressure at

70°F (21°C)

(psig)

Agent Container

Pressure at 130°F (55°C)

(psig)

Minimum Piping Design

Pressure at 70°F (21°C)

(psig)

HFC-227ea 72 600* 1025 820

In Table A-1-5.1 (c) in the second row, change the heading from Boiling Poi19.7

9. Change paragraph 2-2.1.2 to read as follows:

2-2.1.2 Cast-iron pipe, steel pipe conforming to ASTM A 120, Specifications for Pipe,

Steel, Black, and Hot-Dipped Zinc Coated, Welded and Seamless for Ordinary Uses , ornonmetallic pipe shall not be used.

10. Delete Table A-2.2.1.1 (d)

11. In A-2.2.1.1 (e) second paragraph, change the reference from “Table A-2.2.1.1 (i)(1) and Table A-2.2.1.1 (i) (2).”to “Table 2.2.1.1(a) and Table 2.2.1.1 (b).”

12. In A-2.2.1.1 (e) last paragraph, change the second sentence to read:

“ In this case, the governing criteria of 2-2.1.1 (2) is 80 percent of the pressure in the

agent container at 160°F.”

13. In A-2.2.1.1 (h) (1) change the reference from “Table  A-2.2.1.1 (i) (1)” to “Table

2-2.1.1 (a).”

14. In A-2.2.1.1 (h) (2) change the reference from “Table A-2.2.1.1 (1)(2)” to “Table

2.2.1.1 (b).”

15. In Table A-3.5.1 (e) change the headings of the columns to read as follows:

Temp.t

(°F)c

Specific

VaporVolume

s (ft 3 /lb)d 

Weight Requirements of Hazard Volume, W/V (lb/ft 3)b 

Design Concentration (% by Volume )e 

8.6 9 10 11 12 13 14 15

Issue Date: December 20, 2000 

Page 3: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 3/8

 

Copyright © 2000 All Rights Reserved

NATIONAL FIRE PROTECTION ASSOCIATION 

2000

1800

1600

1400

1200

1000

800

600

400

200

020 40 60 80 100 120 140 160 180 2000

   P  r  e  s  s  u  r  e ,

   P   S

   I   G

Temperature °F

75 lb/ft3

70 lb/ft3

65 lb/ft3

Page 4: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 4/8

140.0

120.0

100.0

80.0

60.0

40.0

20.010 20 30 40 50 60 70 80 90 1000

   b  a  r ,  g  a  u  g  e

Temperature, °C

1042 kg/m3

1122kg/m3

1202kb/m3

2400

2200

2000

1800

1600

1400

1200

1000

800

600

40020 40 60 80 100 120 140 160 180 2000

   P  r  e  s  s  u

  r  e ,

   (  p  s   i   )

Temperature (°F)

75 lb/ft3

70 lb/ft3

65 lb/ft3

Page 5: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 5/8

180

160

140

120

100

80

10 20 30 40 50 60 70 80 90 1000

   b  a  r ,  g  a  u  g  e

Temperature, °C

1042 kg/m3

1122kg/m3

1202kb/m3

60

40

20

Page 6: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 6/8

Page 7: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 7/8

Page 8: Errata2001-00-2

8/3/2019 Errata2001-00-2

http://slidepdf.com/reader/full/errata2001-00-2 8/8

 

Table 2-2.1.1(a) Minimum Design Working Pressure for Inert Gas Clean Agent System Piping

Minimum Design Pressure at 70°F (21°C)

Agent Container

Charging Pressure at

70°F (21°C)

Agent Container

Charging Pressure at

130°F (55°C)

Piping Upstream of 

Pressure Reducer

Piping Downstream of 

Pressure ReducerAgent psig kPa psig kPa psig kPa psig kPa

IG-01 2,371 16,347 2,650 18,271 2,371 16,347 975 6,723

2,964 20,436 3,306 22,778 2,964 20,436 975 6,728

IG-541 2,175 14,997 2,575 17,755 2,175 14,997 1,000 6,895

2,900 19,996 3,433 23,671 2,900 19,996 1,000 6,895

IG-55 2,222 15,320 2,475 17,065 2,222 15,320 950 6,550

2,962 20,424 3,300 22,753 2,962 20,424 950 6,550

4,443 30,633 4,950 34,130 4,443 30,635 950 6,550

IG-100 2,404 16,575 2,799 19,300 2,404 16,575 1,000 6,895

3,236 22,311 3,773 26,014 3,236 22,311 1,000 6,895