ERITECH- H.N- IEC 62305

download ERITECH- H.N- IEC 62305

of 92

Transcript of ERITECH- H.N- IEC 62305

  • 7/29/2019 ERITECH- H.N- IEC 62305

    1/92

    ERITECH

    Lightning ProtectionHandbook

    Designing to the IEC 62305 Series

    of Lightning Protection Standards

  • 7/29/2019 ERITECH- H.N- IEC 62305

    2/92

    www.erico.com2

    Lightning Protection Consultant Handbook

    ERICO is dedicated to providing a cost-eective lightning protection solution or any given application. ERICO manuactures,using the ERITECH trade name, lightning protection systems in ull accordance with more than twelve national and international

    standards, as well as non-conventional systems or applications where these provide an advantageous solution or the customer.

    ERICO operates in every region o the world and supports the global market with an extensive distribution network to help ensurethat our products and expertise are available or any project, regardless o size or location.

    Founded in 1903 as the Electric Railway Improvement Company, ERICO developed the CADWELD exothermic welding process in1936. During the 1970s, ERICO pioneered the development and standardization o the copper bonded steel earthing electrode.

    Since that time, ERICO has developed novel lightning protection solutions and introduced new manuacturing processes to improvetraditional lightning protection hardware.

    NOTE IEC and national standards continue to evolve. This handbook was written with reerence to the current editions o thesestandards as o 2009.

    WARNINGERICO products shall be installed and used only as indicated in ERICOs product instruction sheets and training materials. Instruction sheets are available at www.erico.comand rom your ERICO customer service representative. Improper installation, misuse, misapplication or other ailure to completely ollow ERICOs instructions and warningsmay cause product malunction, property damage, serious bodily injury and death.

    WARRANTY

    ERICO products are warranted to be ree rom deects in material and workmanship at the time o shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED(INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICOPRODUCTS. Claims or errors, shortages, deects or nonconormities ascertainable upon inspection must be made in writing within 5 days ater Buyer's receipt o products.All other claims must be made in writing to ERICO within 6 months rom the date o shipment or transport. Products claimed to be nonconorming or deective must,upon ERICO's prior written approval in accordance with its standard terms and procedures governing returns, promptly be returned to ERICO or inspection. Claims notmade as provided above and within the applicable time period will be barred. ERICO shall in no event be responsible i the products have not been stored or used inaccordance with its specications and recommended procedures. ERICO will, at its option, either repair or replace nonconorming or deective products or which it isresponsible or return the purchase price to the Buyer. THE FOREGOING STATES BUYERS EXCLUSIVE REMEDY FOR ANY BREACH OF ERICO WARRANTY AND FOR ANYCLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR INJURY CAUSED BY THE SALE OR USE OF ANY PRODUCT.

    LIMITATION OF LIABILITYERICO excludes all liability except such liability that is directly attributable to the willul or gross negligence o ERICO's employees. Should ERICO be held liable its liabilityshall in no event exceed the total purchase price under the contract. ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIMEOR DELAY, LABOR, REPAIR OR MATERIAL COSTS OR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER.

    IntroductionThis handbook is written to assist in the understanding o the IEC 62305 series o lightning protection standards. This guidesimplies and summarizes the key points o the standards or typical structures, and as such, the ull standards should be

    reerred to or nal verication. This handbook does not document all IEC requirements, especially those applicable to lesscommon or high risk structures such as those with thatched roos or containing explosive materials. In many situations there

    are multiple methods available to achieve the same end result; this document oers ERICOs interpretation o the standardsand our recommended approach. In order to provide practical advice, inormation is included on industry accepted practices

    and rom other standards.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    3/92

    www.erico.com 3

    Key Terms and Abbreviations

    Term Denition

    Air-Termination

    Part o the lightning protection system to intercept the lightning fash (strike). For example,

    an air-terminal providing a protection angle to protected equipment, or horizontal or verticalconductor providing protection via the mesh method

    British Standards (BS) Body responsible or implementation o national British standards, identied by BS prex

    CENELECEuropean Committee or Electrotechnical Standardisation (essentially European standard or Norm,

    identied by EN or NE prex)

    Class (o LPS)Classication o lightning protection system. Class I, II, III, IV relate to the lightning protection level

    and dene, or example, the dierent rolling sphere diameters to be used

    Earth electrodesThose parts o the earth termination system in direct contact with the earth, such as ground rods,

    buried wires, oundation earthing, etc

    Earth-termination Part o the external LPS to dissipate lightning current into the earth

    External lightningprotection system

    Air-termination(s), down-conductor(s) and earth termination(s)

    Internal lightningprotection system

    Equipotential bonding and/or electrical isolation o the external LPS rom internal conductiveelements

    IEC International Electrotechnical Commission, responsible or ormation o International Standards

    Lightning protectionlevel (LPL)

    Number assigned to represent maximum and minimum lightning parameters that should not beexceeded by natural lightning

    Lightning protectionsystem (LPS)

    Complete system or lightning protection o structure. Includes internal and external lightningprotection measures

    Lightning protection zone(LPZ)

    Zone where lightning electromagnetic environment is dened

    Mesh method (MM) Method to determine position o air-termination system

    Protection angle method

    (PAM)Method to determine position o air-termination system

    Rolling sphere method(RSM)

    Method to determine position o air-termination system

    Separation distance Distance between two conductive parts where no dangerous sparking (fashover) can occur

    Services

    Circuits and pipes, etc, entering into structure rom external environment. Typically phone,

    power, TV, gas, water, sewerage systems, etc

    Surge protective device

    (SPD)Device or protecting electrical/electronic equipment rom transient voltage damage

  • 7/29/2019 ERITECH- H.N- IEC 62305

    4/92

    www.erico.com4

    Table of Contents

    1. IEC and EN Standards 6

    1.1 IEC 62305 series

    1.2 EN 50164 series

    1.3 Normative and inormative

    1.4 IEC terminology

    6

    6

    8

    8

    2. Theory o the lightning fash 9

    2.1 The thundercloud

    2.2 Mechanics o the lightning strike

    2.3 Lightning parameters

    2.4 Lightning damage and risk management

    10

    10

    11

    13

    3. Introduction to protection methods and risks 14

    3.1 Risks 15

    4. Risk management 17

    4.1 Overview o risk analysis 17

    5. Lightning protection zones 22

    6. Design process 23

    7. Material requirements 24

    7.1 Copper versus aluminum

    7.2 Use o dissimilar metals

    7.3 PVC covered and concealed conductors

    7.4 Tape, versus solid round, versus stranded

    24

    25

    27

    27

    8. Natural components 28

    8.1 Metallic acades, proles, rails, etc

    8.2 Use o steelwork

    8.3 Use o rebar in reinorced concrete

    28

    28

    28

    9. Design methods 33

    9.1 Rolling sphere

    9.2 Mesh method

    9.3 Protection angle method

    35

    37

    39

    10. Air-terminations 43

    10.1 Recommendation on positioning

    10.2 Masts and antennas10.3 Protection o other items protruding above the roo

    10.4 Bonding o roo top xtures

    10.5 Expansion joints and roo penetrations

    44

    4545

    48

    48

    11. Down-conductors 49

    11.1 Down-conductors or isolated and non-isolated LPS

    11.2 Down-conductor routing

    11.3 Fixing o down-conductors

    50

    50

    51

  • 7/29/2019 ERITECH- H.N- IEC 62305

    5/92

    www.erico.com 5

    Table of Contents (continued)

    12. Bonding and separation distances 52

    12.1 Bonding o services and external conductive parts

    12.2 Separation distance requirements

    12.3 Bonding o internal metallic items and other services

    52

    53

    54

    13. ERITECH

    Isolated Down-conductor 5513.1 Telecommunications applications

    13.2 Other applications

    13.3 Isolated Down-conductor design

    55

    56

    56

    14. Earthing 57

    14.1 Earthing resistance requirements

    14.2 Type A vertical and horizontal electrodes

    14.3 Type B ring electrode

    14.4 Comparison o Type A and Type B arrangements

    14.5 Foundation earth electrodes

    14.6 Special earthing measures

    14.7 General earthing advice

    57

    58

    59

    60

    60

    61

    62

    15. Inspection and testing 66

    16. Special situations 67

    16.1 Tall buildings 67

    17. Surge protective devices or low-voltage power distribution systems 68

    17.1 Surge Protection Devices and Transient Voltages

    17.2 General procedure or SPD selection and installation

    17.3 General inormation and terms

    17.4 SPD requirements or acilities with lightning protection system17.5 SPD requirements or acilities without lightning protection system

    17.6 Secondary SPD requirements

    17.7 Selection and connection conguration or common power distribution system types

    17.8 Other installation requirements

    17.9 High risk situations

    68

    71

    72

    7377

    77

    79

    83

    86

    18. Surge protective devices or telecommunications and signalling services 87

    19. Other surge protective device applications 88

    20. British Standard BS 6651 and EN/IEC standards 89

    20.1 BS 6651-1991 compared to BS EN 62305

    20.2 BS EN 62305-2 compared to IEC/EN 62305-2

    89

    90

    21. IEC design standard and EN component standard conficts 91

  • 7/29/2019 ERITECH- H.N- IEC 62305

    6/92

    www.erico.com6

    1. IEC and EN Standards

    The specication o a lightning protection system should require that the design complies with the IEC 62305 series o designstandards and that materials comply with the EN 50164 series o component standards.

    The International Electrotechnical Commission (IEC) is a body

    responsible or implementing international standards. Its technical

    committees are comprised o representatives rom variousmember national standards, where each country is entitled to onevote during the process o creation and issuing the standard. The

    standards generally have an IEC prex to their number (CEI orFrench versions). IEC standards are produced in English and French

    languages. For most countries the adoption o these standards isvoluntary, and oten selected content o the standard is absorbed

    and introduced as improvements to that countrys own standard.

    Also, within Europe, there exists the European Committee

    or Electrotechnical Standardisation (CENELEC). The membercountries currently include Austria, Belgium, Cyprus, the Czech

    Republic, Denmark, Estonia, Finland, France, Greece, Hungary,

    Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, theNetherlands, Norway, Poland, Romania, Slovakia, Slovenia, Spain,Sweden, Switzerland and the United Kingdom. IEC and CENELEC

    generally work in parallel, and CENELEC members vote to adoptnew IEC standards as CENELEC standards. The committees o

    CENELEC may choose to make some alterations to the IEC version.Additionally, CENELEC produce their own standards to which

    IEC have no counterpart. CENELEC documents are produced inEnglish, French and German and an approved CENELEC standard

    will have an EN prex (or NE in the French language versions).

    The important act with CENELEC standards is that by rule themember countries are bound to adopt all CENELEC standards as

    national standards. In the process o adopting these standards,

    minimum changes are permitted. In-country clauses (exceptionsor changes) can only be made under very strict circumstances.When such standards are adopted at the national level, any

    conficting national standard must be withdrawn (an overlapperiod is permitted).

    For the EN IEC 62305 series o lightning protection standards,each member country has introduced these at a national level by

    November 2006 and has withdrawn any conficting standardsby February 2009.

    At each level (International, European, National) a dierentnaming prex convention is used For example:

    IEC62305-1(IECversion) EN62305-1(CENELECadoptedcopyoftheabove)

    BSEN62305-1(BritishNationalStandardadoptionofthe above)

    This document ocuses upon the IEC/EN standards and, or aspecic design, the applicable national standards should be

    reerred to in order to ascertain i dierences exist.

    Reerence in this document is given to standards being either

    design or component standards. Design standards are those usedby the lightning protection designer or installer to determine

    the type and placement o the lightning protection system.Component standards are those used by the manuacturer o

    the lightning protection hardware (components) to ensure thehardware is o adequate specication and quality.

    1.1. IEC 62305 series

    The IEC 62305 series o standards are primarily design standards,

    giving the user a tool kit o rules and options to provide lightningprotection or a structure. The standards cover structure protection

    and equipment protection with regard to the eects o direct andindirect lightning fashes.

    While the IEC 62305 series o standards introduces many newaspects, it is predominantly a European harmonization o the

    various supporting country lightning protection standards.

    IEC 62305 Protection Against Lightning is comprised o 4 parts

    (documents):

    IEC62305-1Part1:GeneralPrinciples

    IEC62305-2Part2:RiskManagement IEC62305-3Part3:PhysicalDamagetoStructureand

    Lie Hazard IEC62305-4Part4:ElectricalandElectronicSystems

    within Structures IEC62305-5Part5:Services(Thispartwasnotintroduced)

    IEC 62305 series o standards expands, updates and replaces the

    earlier IEC 1024-1-1 (1993) & IEC 1024-1-2 (1998), IEC 61622(1995 & 1996), IEC 61312-1 (1995), IEC 61312-2 (1998), IEC61312-3 (2000) & IEC 61312-4 (1998).

    Since the IEC 62305 series was parallel approved as a CENELECstandard, the EN version is identical to the IEC version. As a

    CENELEC standard this means that the EN 62305 standards havereplaced the various country source standards, such as BS 6651,

    NFC 17-100 and DIN VDE 0185.

    1.2. EN 50164 series

    Within Europe, the CENELEC has released the EN 50164 series

    o standards. The EN 50164 series are component standards towhich the manuacturers and suppliers o lightning protectioncomponents should test their products to veriy design and quality.

    The EN 50164 series currently comprises o:

    EN 50164-1 Lightning protection components (LPC)

    Part 1: Requirements or connection components EN 50164-2 Lightning protection components (LPC)

    Part 2: Requirements or conductors and earth electrodes EN 50164-3 Lightning protection components (LPC)

    Part 3: Requirements or isolating spark gaps EN 50164-4: Lightning Protection Components (LPC)

    Part 4: Requirements or conductor asteners

  • 7/29/2019 ERITECH- H.N- IEC 62305

    7/92

    www.erico.com 7

    1. IEC and EN Standards (continued)

    EN50164-5:LightningProtectionComponents(LPC)

    Part5:Requirementsforearthelectrodeinspectionhousings andearthelectrodeseals

    EN50164-6:LightningProtectionComponents(LPC) Part6:Requirementsforlightningstrikecounters

    EN50164-7:LightningProtectionComponents(LPC) Part7:Requirementsforearthingenhancingcompounds

    ThisseriesofstandardsiscurrentlybeingpublishedatIEClevelunderthenameIEC62561series.

    TheEN50164seriesofstandardsaregenerallycomponent

    standardstowhichthesupplieroftheequipmentshouldhavetestedtheirproducts.ERICOhascompletedanextensive

    regimeoftestingtothesestandards,anddetailsareavailableuponrequest.

    EN50164-1scopecoversconnectioncomponentssuchasconnectors,bondingandbridgingcomponentsandexpansion

    piecesaswellastestjoints.Theintentofthisstandardisthatanymechanicalconnectionbetweenthetipoftheair-terminalandthe

    bottomoftheearthelectrodeshouldbetested.Thiscoversthemoreobviousdown-conductorconnectors(cross-overconnectors,

    tapeclamps,etc)anddown-conductortestlinks,tothelessobviousair-terminal(rod)toair-terminalbaseconnectionand

    down-conductortoearthelectrodeconnection.

    EN50164-1testingclassiestheproductsaccordingtotheir

    capabilitytowithstandlightningcurrentbyanelectricaltest:

    ClassHHeavyDuty(testedwith100kA10/350s),or ClassNNormalduty(testedwith50kA10/350s)

    Standard Title Type

    IEC 62305-1

    (EN 62305-1)ProtectionagainstlightningPart1:Generalprinciples DesignStandard

    IEC 62305-2

    (EN 62305-2)ProtectionagainstlightningPart2:RiskManagement DesignStandard

    IEC 62305-3

    (EN 62305-3)ProtectionagainstlightningPart3:PhysicalDamagetoStructureandLifeHazard DesignStandard

    IEC 62305-4

    (EN 62305-4)ProtectionagainstlightningPart4:ElectricalandElectronicSystemswithinStructures DesignStandard

    EN 50164-1 Lightningprotectioncomponents(LPC)Part1:Requirementsforconnectioncomponents ComponentStandard

    EN 50164-2 Lightningprotectioncomponents(LPC)Part2:Requirementsforconductorsandearthelectrodes ComponentStandard

    EN 50164-3 Lightningprotectioncomponents(LPC)Part3:Requirementsforisolatingsparkgaps ComponentStandard

    EN 50164-4 Lightningprotectioncomponents(LPC)Part4:Requirementsforconductorfasteners ComponentStandard

    EN 50164-5Lightningprotectioncomponents(LPC)Part5:Requirementsforearthelectrodeinspection

    housingsandearthelectrodesealsComponentStandard

    EN 50164-6 Lightningprotectioncomponents(LPC)Part6:Requirementsforlightningstrikecounters ComponentStandard

    EN 50164-7 Lightningprotectioncomponents(LPC)Part7:Requirementsforearthingenhancingcompounds ComponentStandard

    Main IEC and EN standards relating to design and testing o lightning protection systems/components.Table 1.

    Andaccordingtoitsinstallationlocationbyenvironmentaltest:

    Aboveground(saltmist&sulphurousatmospheretests),and Buriedinground(chlorideandsulphatesolutiontest)

    EN50164-2scopecoversmetallicconductors,down-conductors(otherthannaturalconductorssuchasbuildingreinforcing

    steel)andearthelectrodes.Itshouldbenotedthatthemetallicconductorrequirementalsocoverstheair-terminals(rods).The

    testsincludemeasurementstoconrmcompliancewithminimum

    sizerequirements,resistivityandenvironmentaltesting.Earthelectrodesaresubjectedtotestsincludingbendtests,adhesion

    tests,andenvironmentaltests.Coupledearthelectrodesandthecouplingdevicearealsosubjectedtohammercompression

    (impacttesting)andtherequirementsofIEC62305-1.

    EN50164-3scopecoversisolatingsparkgapsusedinlightning

    protectionsystems,suchasthoseusedtobondmetalworktoalightningprotectionsystemwheredirectconnectionisnot

    permissibleforfunctionalreasons.

    EN50164-4scopecoverstestsproceduresandrequirementsformetallicandnon-metallicfastenersusedonmost(butnotall)

    wallandroofmaterialstosecureairterminationsystemsand

    downconductors.Fastenersusedinexplosiveatmospheresshouldbe

    subjectedtoadditionalrequirementsnotdenedinthisstandard.

    EN50164-5scopecoversrequirementsandtestsforearthpits

    andearthsealsmadeofsteel,plastic,concreteamongothers.Load-bearingcapacitytestsandsealqualitytestsarethekeytests

    coveredinthestandard.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    8/92

    www.erico.com8

    1. IEC and EN Standards (continued)

    Term Denition

    Lightning strokeSingle electrical discharge in a lightningfash to earth. The lightning fash mayhave multiple strokes

    Lightning fashElectrical discharge o atmospheric origin

    between cloud and earth consisting oone or more strokes

    Multiple strokeA lightning fash where more than onestroke (electrical discharge) occurs

    Point o strokePoint where lightning fash strikesearth/object

    Lightning current Current fowing at point o strike

    Main IEC terms associated with the lightning event.Table 2.

    Lightning is a common event. At any one time, there are some1700 electrical storms active throughout the world, producing in

    excess o 100 fashes per second. This equates to an aggregateo some 7 to 8 million fashes per day. O these, approximately

    90% are cloud-to-cloud fashes and the remaining arepredominately cloud-to-ground fashes. Tropical regions o the

    world have particularly high incidences o lightning as depictedby isokeraunic thunder day maps.

    Common Terminology IEC Terminology

    Lightning strike Lightning fash

    Discharge current Lightning current

    Common non-IEC terminology.Table 3.

    EN 50164-6 scope covers test procedures and requirements or

    lightning strikes counters used in lightning protection systemsbut also in surge protection systems. Mechanical, electrical and

    corrosion tests are described in this standard and electromagneticcompatibility is also addressed.

    EN 50164-7 scope covers the requirements and tests or earth

    enhancing compounds used to increase the contact surace areao earth electrodes. Rell materials are not part o this standard.Among the tests included in the standard are conductivity

    tests, chemical tests (pH, solubility in acid environments), andcomposition tests (sulur).

    At this time, while EN 50164-1, EN 50164-2 and EN 50164-3are CENELEC standards and thus compliance is required, the

    IEC 62305 series do not ully reer to these standards. That is tosay, while you must use EN 50164-1/2/3 approved components,

    IEC/EN 62305 series, or example, does not actually speciy orwhich circumstances EN 50164-1 Class H or Class N materials

    are required. It is strongly recommended that Class H be used

    in all applications, but with Class N devices being permitted orbonding to items not subject to the ull lightning current.

    It should also be known that there are some small dierencesbetween the material requirements o the EN component

    standards and the material specications in the IEC designstandards, such as minimum conductor sizes and tolerance.

    Thereore it is possible or example, to have a conductor thatmeets the requirements o design standard IEC 62305-3, but not

    the component standard EN 50164-2. Reer to Section 21 orurther inormation.

    Manuacturers and suppliers o lightning protection components

    should be able to provide test reports or each o their products

    stating compliance to these standards. Importantly, theclassication (class and environment) should be stated togetherwith the scope o testing. Note that the approval is only valid or

    the combinations o conductor sizes and congurations tested.For example, the approval is unlikely to be valid i the connector

    is used with non-standard conductor sizes.

    1.3. Normative and inormative

    It should be understood that the main body o standards arenormative. That is, the requirements given are mandatory (unless

    otherwise indicated in the text). At the rear o the standard,annexes provide additional support inormation and examples.

    The annexes may be headed as normative or inormative. Anormative annex means any requirements are mandatory, while an

    inormative annex is or inormation purposes and any containedrequirements are recommendations (i.e. non-mandatory).

    To summarize earlier inormation, with the exception oCENELEC member countries, the requirements o IEC 62305

    series, EN 50164 series, or a national version o one o thesedocuments is only mandatory i the country has specically

    adopted the standard. Any local national standard will takeprecedence. For CENELEC member countries the standards

    are mandatory with compliance being required to the nationalimplementation i existing, or otherwise the EN version.

    1.4. IEC terminology

    Where practical, this document uses IEC dened terms anddenitions. For example the term earthing is used in

    preerence to grounding. Within the lightning protectionindustry there is oten indiscriminate use o incorrect terms

    associated with the lightning event. The ollowing explains thepreerred terms.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    9/92

    www.erico.com 9

    Header Goes Here2. Theory of the Lightning Flash

    With increasingly complex and sophisticated buildings and equipment, a single lightning stroke can result in physical damage

    and catastrophic ailure. It can initiate re, cause major ailures to electrical, telephone and computer services and simultaneouslycause substantial loss o revenue through down-time.

    World thunder day map; note the high lightning density areas are regionalized around the equator.Figure 1.

    EUROPE

    AFRICA

    AUSTRALIA

    NORTH

    AMERICA

    ASIA

    SOUTH

    AMERICA

    EQUATOR

    THUNDERSTORM DAYS

  • 7/29/2019 ERITECH- H.N- IEC 62305

    10/92

    www.erico.com10

    Header Goes Here

    2.2. Mechanics o the lightning strike

    The separation o electrical charge within a cloud allows electricpotentials to increase to a point where a neutralizing discharge

    must occur. For lightning protection, we are mainly concernedabout the cloud-to-ground discharge. This is a two-staged

    process, with one process being initiated rom the cloud, whilethe second is initiated rom the ground or structure.

    Ionization occurs at the bottom o the cloud to orm coronadischarges. A leader initiates and begins to propagate towards

    the ground. The presence o wind shear tends to blow away theionized air, halting the progression momentarily until sucient

    ionization develops to cause breakdown and allow the dischargeto progress in the next discrete step. This stepped leader

    progresses rapidly towards the ground and may branch intomany "ngers" in an attempt to reach ground.

    As the leader approaches the ground, the electric eld rapidlyincreases, accelerating local ground ionization. At this point, the

    potential dierence between the leader and the earth may beas great as 100 million volts, resulting in nal breakdown o the

    air. The ground discharge begins to move up (upward leader)towards the downward leader, intercepting at some tens to

    hundreds o meters above ground level.

    6-12 km

    1-6 km

    Heavy, cold air mass Warm air mass

    2.1. The thundercloud

    Lightning is a natural phenomenon which develops when theupper atmosphere becomes unstable due to the convergence

    o a warm, solar heated, vertical air column on the cooler upperair mass. These rising air currents carry water vapor which,

    on meeting the cooler air, usually condense, giving rise toconvective storm activity. Pressure and temperature are such that

    the vertical air movement becomes sel-sustaining, orming the

    basis o a cumulonimbus cloud ormation with its center corecapable o rising to more than 15,000 meters.

    To be capable o generating lightning, the cloud needs to be

    3 to 4 km deep. The taller the cloud, the more requent thelightning. The centre column o the cumulonimbus can have

    updrats exceeding 120 km/hr, creating intense turbulence withviolent wind shears and consequential danger to aircrat. This

    same updrat gives rise to an electric charge separation whichultimately leads to the lightning fash. Figure 2 shows a typicalcharge distribution within a ully developed thunder cloud.

    Lightning can also be produced by rontal storms where a

    ront o cold air moves towards a mass o moist warm air. Thewarm air is lited, thus generating cumulonimbus clouds and

    lightning in a similar mechanism to that described earlier. One

    major dierentiation o this type o event is that the cold rontcan continue its movement and result in cumulonimbus cloudsspread over several kilometers width. The surace o the earth

    is negatively charged and the lower atmosphere takes on anopposing positive space charge. As rain droplets carry charge

    away rom the cloud to the earth, the storm cloud takes onthe characteristics o a dipole with the bottom o the cloud

    negatively charged and the top o the cloud positively. It isknown rom waterall studies that ne precipitation acquires

    a positive electrical charge. Larger particles acquire a negativecharge. The updrat o the cumulonimbus separates these

    charges by carrying the ner or positive charges to highaltitudes. The heavier negative charges remain at the base o the

    cloud giving rise to the observance that approximately 90% oall cloud-to-ground fashes occur between a negatively charged

    cloud base and positively charged earth (i.e. negative lightning).

    Approximately 90% o all lightning fashes are cloud-to-cloud

    with the other 10% being cloud-to-ground fashes.

    Ground-to-cloud fashes are extremely rare and generally only

    occur rom high mountain tops or tall man-made structures they are typically positive strokes (positive lightning).Figure 2. Typical charge distribution in

    cumulonimbus cloud.

    Figure 3. Cumulonimbus cloudsgenerated by rontal storms.

    2. Theory of the Lightning Flash (continued)

  • 7/29/2019 ERITECH- H.N- IEC 62305

    11/92

    www.erico.com 11

    Header Goes Here2. Theory of the Lightning Flash (continued)

    Figure 4. The stepped leader progressingtowards earth.

    Figure 5. Upward leader completes theionized channel.

    Oncetheionizedchannelhasbeencompletedbythejunctionoftheupwardanddownwardleaders,alowimpedancepath

    betweenthecloudandgroundexistsandthemainstrokecommences.Thisischaracterizedbyarapidlyincreasingelectric

    currentwhoserateofriseistypically10kA/s.Peakcurrentsaveragingaround30kAaretypical,withminimumcurrents

    beingafewkA.Maximumlightningcurrentsexceeding200kAhavebeenrecorded.

    Itisalsopossibletohaveconsecutivestrokesdownthesame

    channel.Thisoccurswhentheinitialdischargeneutralizesthelocalizedchargecellinthecloud.Nearbycloudcellsthenash

    acrosstotheionizedchannelanduseittodischargetoground.Inthismanner,upto16strokeshavebeenobservedusingthe

    onechannel.Thesemultiplestrokeswithintheonelightningasharesometimesreferredtoasre-strikes.

    Theaverageenergyreleasedinalightningashis55kWhr,asignicantamountofenergybymoderngenerationstandards.

    Thedangerofthelightningcurrentliesinthefactthatalltheenergyisexpendedinonly100to300microsecondsand

    thatthepeaklightningcurrentisreachedinonly1to2microseconds.

    Thedifferencebetweenpositiveandnegativelightningisthattheleaderinthecaseofpositivelightningisgenerallynot

    steppedandtherearerarelymultiplestrokes.Thereistypicallyonlyonereturnstroke,afterwhichacontinuouscurrentows

    todischargethecloud.

    2.3. Lightning parameters

    Lightningisanaturalphenomenonwhere,forthepurposeofanalysisanddesign,astatisticalapproachistaken.Data

    fromInternationalCouncilofLargeElectricalSystems(CIGRE)indicatesthat:

    5%ofrst,negativelightningstrokesexceed90kA(averageis33kA)

    5%ofpositivelightningstrokesexceed250kA(averageis34kA)

    5%ofnegativesubsequentstrokesexceedarateofcurrentriseof161kA/s

    IntheIEC62305series,fourlightningprotectionlevelsareintroducedandthedesignrulesarebasedontheLPSbeing

    abletoprotectagainstmaximumvalues(sizingefciency)andminimumvalues(interceptionefciency)ofcurrent.LPLI

    offersthehighestprotectionlevel(greatestlevelofprotection),withLPLIVofferingthelowestlevelofprotection.

    Table 4indicatesfortheselightningprotectionlevelsthe

    maximumcurrentexpectedandtheprobabilitythatthismaybeexceeded.Thestandardensuresthatair-termination,conductor

    andearthterminationsizearesufcienttowithstandtheexpectedmaximumcurrent.

    LPL I LPL II LPL III LPL IV

    Maximumpeakcurrent(kA10/350s) 200 150 100 100

    Probabilitycurrentisgreater(%) 1 2 3 3

    Maximum current levels (related to sizing efciency) or lightning protection levels I to IV and probability o exceedingTable 4.these levels.

    Stepped leader movesprogressively from cloudto ground and can followone or several paths.

    Strikin

    g

    dis

    tance

  • 7/29/2019 ERITECH- H.N- IEC 62305

    12/92

    www.erico.com12

    Header Goes Here2. Theory of the Lightning Flash (continued)

    LPL I LPL II LPL III LPL IV

    Minimumcurrent(kA) 3 5 10 16

    Probabilitycurrentisgreaterthanminimum(%)

    99 97 91 84

    Rollingsphereradius(m) 20 30 45 60

    Minimum current levels (related to interceptionTable 5.

    efciency) or lightning protection levels I to IV.

    10 s

    350 s

    50%

    10%

    90%

    t

    100%

    (+ve)

    Ground

    Strikingdistance

    Respondingupward leader

    Downwardleader

    (-ve)r = 10 Ip0.65

    r20 m

    44 m

    91 m

    200 m

    I p3 kA

    10 kA

    30 kA

    100 kA

    Figure 6. Waveshape.

    Figure 7. Striking Distance.

    Thelowerlightningprotectionlevels(LPL II, III & IV)eachincreasetheair-terminalspacing,reducingtheirabilitytocapture

    smallerlightningashes,thusreducingoverallthepercentageoflightningeventstheycanprotectagainst.

    Table 5alsodetailstherollingsphereradiususedintherolling

    spheredesignmethod.Therollingspheremethodisthepreferredmethodfordeterminingpositioningofair-terminals

    (protectionanglemethodandmeshmethodaredescribedlater).Theradiusofthesphereisequaltothestrikingdistance(using

    earlierformula)associatedwiththeminimumcurrentlevelfor

    thechosenlightningprotectionlevel.Thisimaginarysphereisrolledoverthestructure.Thesurfacecontactpointstracedoutbythespheredenepossiblepointsthatmaylaunchanupward

    leadertointerceptwiththedownwardleader.Allthesepointsaredeemedtorequireprotection,whilsttheuntouchedpoints

    donot.Generallyalightningprotectionsystemisdesignedsuchthattherollingsphereonlytouchesthelightningprotection

    systemandnotthestructure.

    TofurtherexplainTable 5,alightningprotectionsystemto

    provideLPLIV,designedusingtherollingspheremethod,woulduseair-terminalsplacedusingarollingsphereradiusof60m.

    Whiletheactualwaveshapeofthelightningcurrentvariesfromeventtoevent,researchshowsthatastatisticalprobabilitycan

    bedeterminedforoccurrenceofagivenwaveshape.ForthepurposeofsimplicationthemaximumvaluesinTable 4are

    speciedusinga10/350swaveshape.AsshowninFigure 6,fora10/350seventthefronttime(alsoknownasrisetime)is

    10sdurationandthetimetodecayto50%is350s.

    Forair-terminalplacement,themainconsiderationisthe

    minimumvalueofexpectedcurrentandtheabilityofthelightningprotectionsystemtointerceptthesesmallerashes.

    Asnotedearlier,asthelightningdownwardleaderapproachesthegroundorstructure,theelectriceldincreasestothepoint

    thatthegroundorstructurelaunchesanupwardleaderthatmayeventuallyinterceptthedownwardleader.Thisistermed

    thestrikingdistance.Thelargertheamountofchargecarriedbythelightningleader,thegreaterwillbethedistanceatwhich

    thishappens.Thelargerthechargeoftheleader,thelargertheresultinglightningcurrent.Itisgenerallyacceptedthat

    thestrikingdistancerisgivenby:

    r= 10I0.65

    WhereIisthepeakcurrentoftheresultingstroke.

    Thisformulashowsthatitismoredifcultforanair-terminal

    tointerceptasmallerlightningashthanalargerash,asthesmallerashmustapproachclosertotheair-terminalbefore

    theupwardleaderislaunched.Toprotectthestructureagainstsmallerlightningashes,air-terminalsmustbespacedcloser

    together.Forsmallerlightningashesthereisariskthatanair-terminalmaynotbecloseenoughtointerceptthedownleader,

    thusacloserstructuralpointreleasesanupwardleaderwhichinterceptstheash(i.e.thebuildingisstruck).

    Foreachofthelightningprotectionlevels,aminimumcurrentleveltobeprotectedagainsthasbeendetermined(selected).

    Table 5detailsthesecurrentlevels,togetherwithprobabilitypercentagesthatlightningmaybegreaterthantheselevels.For

    example,LPLIpositionsterminalssuchthat99%ofalllightningashesareintercepted(allthoseof3kAorgreater).Thereisonly

    a1%probabilitythatlightningmaybesmallerthanthe3kAminimum,andmaynotbecloseenoughtoanair-terminaltobe

    intercepted.Itshouldbenotedthatashesoflessthan3kAarerare,andtypicallywouldnotbeexpectedtocausedamageto

    thestructure.ProtectiongreaterthanLPLI(99%)wouldrequiresignicantlymorematerial,isnotcoveredbythestandardand

    generallyisnotrequiredforcommercialconstruction.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    13/92

    www.erico.com 13

    Header Goes Here2. Theory of the Lightning Flash (continued)

    These air-terminals would be positioned such that they would

    capture all lightning fashes o 16 kA or greater, thus oeringprotection to at least 84% o the lightning (the term at least is

    used to indicate that the percentage o lightning captured mightbe greater, since smaller lightning fashes could be captured i

    they were closer to the air-terminal). To oer a greater lightningprotection level (e.g. LPL I, II or III) a smaller rolling sphereradius would be used. This would result in a reduced spacingbetween air-terminals (more air-terminals), thus positioning the

    air-terminals to capture smaller lightning fashes, and increasingthe total percentage o lightning fashes captured.

    2.4. Lightning damage & risk management

    No lightning protection system is 100% eective. A systemdesigned in compliance with the standard does not guarantee

    immunity rom damage. Lightning protection is an issue ostatistical probabilities and risk management. A system designed

    in compliance with the standard should statistically reduce therisk to below a pre-determined threshold. The IEC 62305-2 risk

    management process provides a ramework or this analysis.

    An eective lightning protection system needs to control a

    variety o risks. While the current o the lightning fash createsa number o electrical hazards, thermal and mechanical hazards

    also need to be addressed.

    Risk to persons (and animals) include:

    Directash

    Steppotential

    Touchpotential

    Sideash

    Secondaryeffects:

    asphyxiation rom smoke or injury due to re

    structural dangers such as alling masonry rompoint o strike

    unsae conditions such as water ingress rom roopenetrations causing electrical or other hazards,

    ailure or malunction o processes, equipment andsaety systems

    Risk to structures & internal equipment include:

    Fireand/orexplosiontriggeredbyheatoflightningash,its attachment point or electrical arcing o lightning

    current within structures

    Fireand/orexplosiontriggeredbyohmicheatingof

    conductors or arcing due to melted conductors

    Puncturesofstructureroongduetoplasmaheat

    at lightning point o strike

    Failureofinternalelectricalandelectronicsystems

    Mechanicaldamageincludingdislodgedmaterialsat

    point o strike

  • 7/29/2019 ERITECH- H.N- IEC 62305

    14/92

    www.erico.com14

    Header Goes Here

    SeparationDistance

    Internal

    Earth-terminationSystem

    Service

    entrancebox

    Foundation earthing electrode

    Equipotential bonding for heating,air-conditioning, and sanitation

    SPD for AC services

    SPD fortelephone line

    Down-conductorSystem

    Figure 8. External and internal lightning protection system.

    3. Introduction to Protection Methods & Risks

    The design o a lightning protection system needs to:

    Intercept lightning fash (i.e. create a preerred pointo strike)

    Conduct the lightning current to earth

    Dissipate current into the earth

    Create an equipotential bond to prevent hazardouspotential dierences between LPS, structure and

    internal elements/circuits

    3. Introduction to protection methodsand risks

    The inancy o the science o lightning protection is best

    attributed to Benjamin Franklin. The story o his kite fyingexperiment to prove that lightning was the same type o

    electricity as that stored in a Leyden jar, is well documentedand has become a modern day legend. The rst mention o the

    traditional lightning rod was published by Franklin in 1750 in

    Gentlemans Magasine [sic]and then later in his treatises on thesubject published in 1751. In this he recommends the use olightning rods to ... Secure houses, etc, rom Lightning.

    In 1876, Franklins research was taken urther by James ClerkMaxwell who suggested that by completely enclosing a building

    with metal cladding, lightning current would be constrained tothe exterior o the building and no current would fow within

    the building itsel. This concept has given rise to a relativelymore cost eective approach known as the Faraday Cage (mesh

    method), in which a matrix o conductors is used to orm an

    equipotential cage around the structure to be protected.

    In achieving this the lightning protection system must:

    Not cause thermal or mechanical damage to the structure

    Not cause sparking which may cause re or explosion

    Limit step and touch voltages to control the risk o injury

    to occupants

    Limit damage to internal electrical and electronic systems

    The lightning protection system is generally considered in

    two parts. The external lightning protection system intercepts,conducts and dissipates the lightning fash to earth. The

    internal lightning protection system prevents dangeroussparking within the structure (using equipotential bonding

    or separation distance).

  • 7/29/2019 ERITECH- H.N- IEC 62305

    15/92

    www.erico.com 15

    Header Goes Here3. Introduction to Protection Methods & Risks (continued)

    Non-Isolated Isolated

    Figure 9. Non-isolated protection concepts.

    Lightning protection systems typically ollow two approaches:

    Non-isolated system where potentially damaging voltage dierentials are limited by bonding the lightning protectionsystem to the structure

    Isolated system where the lightning protection system is isolated rom the structure by a specied separation distance.This distance should be sucient that energy is contained on the LPS and does not spark to the structure. Isolated systems

    are well suited to structures with combustible materials such as thatched roos, or telecommunication sites that want to avoidlightning currents being conducted on masts and antenna bodies

    The standard provides simple geometric orms o design whichare compromises between cost, eectiveness and simplicity in

    design. The design methods are:

    Mesh method

    Rolling sphere method (RSM)

    Protection angle method (PAM)

    These methods (described in Section 9) are used to determinethe optimum location o the air-terminations and the resultingdown-conductor and earthing requirements.

    A risk assessment is generally undertaken to determine the levelo risk or a specic structure, in order to make a comparison

    with a pre-determined value o acceptable risk. Protectionmeasures, at an appropriate lightning protection level (LPL), are

    then implemented to reduce the risk to or below the acceptablerisk. The lightning protection level determines the spacing o the

    mesh, radius o rolling sphere, protective angle, etc.

    It should be noted that while lightning protection is typicallyimplemented as a bonded network o air-terminals and down-conductors, other methods are permitted:

    To limit touch and step potential risks:

    Insulation o exposed conductive parts

    Physical restriction and warning signs

    To limit physical damage:

    Fire proong, re extinguishing systems, protected

    escape routes

    3.1. Risks

    To understand why typical conventional l ightning protection

    systems require rigorous equipotential bonding and earthing,it is important to understand how the risk o injury due to

    step/touch potentials and side fashing occur.

    3.1.1. Step potential

    When lightning current is injected into the earth, a large voltage

    gradient builds up around the earth electrode with respect toa more distant point. The earth can be imagined as a sequence

    o overlapping hemispheres. The greater the distance rom theelectrode, the larger the surace area o the hemisphere and

    the more parallel paths through the soil. Thus the voltage rise isgreatest near the electrode where current density is highest.

    The normal step distance o a person is near to 1 meter. At thetime o discharge being close to the earth electrode means the

    voltage dierential across this distance can be large enough tobe lethal depending upon circumstances such as condition o

    ootwear, etc, substantial current can fow through one lowerleg to the other.

    In the case o animals, a larger risk exists. The distance betweenthe ront and rear legs o larger animals can be in the order o

    2 meters, and the current path fows through the more sensitiveregion o the heart.

    The hazard is considered to be reduced to tolerable level i:

    The probability o persons approaching, or duration opresence within 3 m o the down-conductor is very low

    limiting access to the area can be a solution

    Step potential is reduced by use o 5 k ohm.m insulating

    barrier such as 50 mm o asphalt or 150 mm o gravel within

    3 m o the electrode

    An equipotential earthing system such as mesh system iscorrectly used

    It is also good practice or the upper section o the conductorentering into the earth to be insulated. Heat shrink (2 mm

    polyethylene) or 4 mm thick PVC protecting the rst 2-3 mo conductor/electrode is sucient to reduce step potential

    hazards. Where a conductor is insulated and buried, anyinsulated portion should not be considered as contributingto the earthing requirements o Section 12.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    16/92

    www.erico.com16

    Header Goes Here3. Introduction to Protection Methods & Risks (continued)

    Touch potential

    Steppotential

    3.1.2. Touch potential

    Touchpotentialisduetoasimilarreasonassteppotential,but

    thevoltagedifferentialbeingconsideredisthatwhichexistsbetweenthehandand(generally)feet.Theriskofelectrocution

    duetotouchpotentialisgreaterthanforsteppotential,asthepassageofcurrentowsclosetotheheartregion.

    Thehazardisconsideredtobereducedtotolerablelevelif:

    Theprobabilityofpersonsapproaching,ordurationofpresenceisverylowlimitingaccesstotheareacanbe

    asolution

    Naturaldown-conductorsareusedwhereextensivemetal

    frameworkorsteelworkisinterconnected

    Asurfacelayerwith 5kohm.minsulatingbarriersuchas

    50mmofasphaltor150mmofgravelisused

    Thedown-conductorisinsulatedwithatleast100kV

    1.2/50simpulseinsulation(3mmPVC)

    3.1.3. Side ashing

    Alldown-conductorshavearesistanceand,moreimportantly,inductance.Duringthelightningashtherapidrateof

    currentrisecancausetheinductivevoltageriseoftheconductortoreachamagnitudewheresufcientvoltage

    existsfortheconductortoashovertoanearbyconductiveandearthedobject.

    Sideashingcanbecontrolledby:

    Usinganumberofparalleldown-conductorstoreducethe

    currentineach

    Ensuringtheseparationdistancebetweenthetwoobjectsis

    sufcientnottobreakdowntheinterveningmedium;or

    Bondingtotheobjecttoeliminatethepotentialdifference

    (theobjectmaycarryapartiallightningcurrent)

    Thedown-conductorandbondingrequirementsofthestandard

    addresstheseissues.

    Figure 10. Step and touch voltage gradients.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    17/92

    www.erico.com 17

    4. Risk Management

    4. Risk management

    IEC 62305-2 provides a lightning risk management procedurethat provides a tolerable limit o risk, methods to calculate the

    actual risk, and then evaluates the protection methods requiredto reduce the actual risk to be equal or lower than the tolerable

    risk. The main outcome rom this risk assessment is to determinei lightning protection is required and i so, to select the

    appropriate lightning class. The lightning class determines the

    minimum lightning protection level (LPL) that is used within thelightning protection design.

    Lightning protection can be installed even when the riskmanagement process may indicate that it is not required.

    A greater level o protection than that required may alsobe selected.

    It should be noted that the IEC 62305-2 document is over100 pages in length and is extremely comprehensive and

    complex. A ull manual analysis o all risks can take tens o

    hours to complete. Thereore or most situations a reducedanalysis is conducted, preerably with an electronic tool.For this purpose, the IEC standard comes with sotware,

    and additional third-party sotware is also available.

    For complex or high risk structures/situations, a more

    detailed analysis should be considered using the ull standard.This would include, but is not limited to:

    Locations with hazardous or explosive materials

    Hospitals or other structures where ailure o internal systems

    may cause a lie hazard

    Note that with the national implementation o the BS EN62305-2 Risk Management standard some minor adjustmentsto the procedures and values has occurred to better refect

    the localized conditions and acceptable local tolerable risk.Use the national standard appropriate to the country o

    installation, or select a national standard where that countryexperiences similar lightning risk (ground fash density/

    thunderdays) and similar social/economic values.

    4.1. Overview o risk analysis

    It is beyond the scope o this document to describe the ullrisk management requirements. Conceptually the risk analysis

    ollows the general process o:

    Identiying the structure to be protected and its environment1.

    Evaluating each loss type and associated risk (R2.1

    to R3)

    Comparing R3.1

    to R3

    to the appropriate tolerable risk RT

    todetermine i protection is needed

    Evaluating protection options so R4.1

    to R3 R

    T

    Note that separate RT

    gures exist or risk o losses R1

    to R3.

    Lightning protection is required such that R1, R

    2& R

    3are all

    equal or lower than the respective tolerable risk (RT).

    Lightning protection may also be justied upon the economic

    risk R4

    and the respective economic benet. A separate

    procedure in IEC 62305-2 is ollowed or this analysis.

    Each o the ollowing risks are broken down into individual riskcomponents (sub categories), which are then evaluated with

    regard to direct and indirect lightning eects upon the structureand on the services. This requires the computation o the

    number o dangerous events, which is related to the structuresize and lightning fash density.

    The simplied analysis sotware considers:

    Structures dimensions

    Structures attributes

    Environmental infuences

    Eect o services entering acility

    Existing protection measures

    The simplied sotware is IEC 62305-2 compliant, but is

    conservative in nature. That is, worst case or conservative valuesare assumed. In situations where multiple identical structures are

    to be constructed, it may be appropriate to conduct a ull riskanalysis in case a small economic saving can be obtained and

    applied across the many structures.

    Loss Risk to Structure Risk to Services

    L1 loss o human lie R1

    Risk o loss o human lie

    L2 loss o essential services R2 Risk o loss o essential services R

    2 Risk o loss o essential services

    L3 loss o cultural heritage R3 Risk o loss o cultural heritage

    L4 economic loss R4 Risk o economic loss R

    4 Risk o economic loss

    Risk assessment losses.Table 6.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    18/92

    www.erico.com18

    4. Risk Management (continued)

    S1

    S2

    S3

    S4

    Lightning flashto the structure

    Lightning flashto the service

    Lightning flashnear the service

    Lightning flashnear the structure

    4.1.1. Sources o damage, type o damage,type o loss and risk o loss

    For those interested in a better understanding o the riskmanagement process, or a desire to manually calculate a

    structures risk, the remaining sections o this chapter provide an

    introduction to the topic. It should be helpul in understandingthe eect o selection o parameters in risk assessment toolsbased on IEC 62305-1/2, and i a manual assessment is to be

    undertaken, help introduce the concepts o the standards whichshould be ollowed.

    It is important to understand the sources o damage, types odamage and types o losses as the procedure to assess the risk

    evaluates various combinations considering structure, contents,services and environment with the source and type o damage.

    IEC 62305-1 introduces the concepts o sources o damage

    (Figure 11) where:

    S1 Lightning fash to the structure

    S2 Lightning fash near the structure

    S3 Lightning fash to the services

    S4 Lightning fash near to the services

    With the possible sources o damage due to lightning fash

    dened, three possible types o damage are identied:

    D1 Injury o living beings (humans and animals) due to

    touch and step potential

    D2 Physical damage (re, explosion, mechanical destruction,chemical release)

    D3 Failure o internal electrical/electronic systems due tolightning electromagnetic impulse

    Figure 11. Sources o damage

    With each type o damage, our types o losses are identied:

    L1 Loss o human lie

    L2 Loss o essential service to the public

    L3 Loss o cultural heritage

    L4 Economic loss (structure and its contents, service and

    loss o activity)

    Care is required with the term services, as it is dependant

    upon its context within the standard. This may reer to thephysical services connected to the building (water, power,

    gas, uel or data/telecommunications), or services provided tothe public (e.g. inormation services). The scope o services to

    the public includes any type o supplier who, due to lightningdamage, can not provide their goods or service to the public.

    For example a supermarket closed due to damage to cashregister/check-out systems, or a insurance company unable to

    transact business due to phone or website ailure.

    Table 7summarizes the types o damage and types o loss oreach o the our sources o damage [rom IEC 62305-1 Table 3].For each o the rst three types o losses (L1, L2 & L3), the

    procedure o IEC 62305-2 evaluates the risk o these respectivelosses (R

    1, R

    2& R

    3) and compares them to tolerable levels.

    For Loss L4, the economic cost o the loss, with and withoutlightning protection, is compared to the cost o the protection

    measures.

    Table 8details the types o damages and losses associated witha service. As the loss and calculation o the risk o loss is dierentto that o the structure, the convention L2 & L4 are used to

    dierentiate these losses.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    19/92

    www.erico.com 19

    4. Risk Management (continued)

    Source o damage(Point o strike)

    Type o damage Type o loss

    S1Lightning fash to the structure

    D1 - InjuryL1 Loss o human lie

    L4 Economic loss (1)

    D2 Physical damage

    L1 Loss o human lie (2)

    L2 Loss o serviceL3 Loss o heritage

    L4 Economic loss

    D3 Failure o systemsL1 Loss o human lie (2)

    L2 Loss o service

    L4 Economic loss

    S2Lightning fash near the structure

    D3 Failure o systems

    L1 Loss o human lie

    L2 Loss o serviceL4 Economic loss

    S3Lightning fash to the services

    D1 - InjuryL1 Loss o human lieL4 Economic loss (1)

    D2 Physical damage

    L1 Loss o human lie

    L2 Loss o serviceL3 Loss o heritageL4 Economic loss

    D3 Failure o systems

    L1 Loss o human lie (2)

    L2 Loss o serviceL4 Economic loss

    S4Lightning fash near to the services

    D3 Failure o systemsL1 Loss o human lie (2)

    L2 Loss o service

    L4 Economic loss

    Notes:(1) Only or properties where animals may be lost(2) Only or structures with risk o explosion and or hospitals or other structures where ailure o services or internal systems endangers human lie

    Damages and losses in a structure or dierent sources.Table 7.

    Source o damage(Point o strike)

    Type o damage Type o loss

    S1Lightning fash to the structure

    D2 Physical damage

    L2 Loss o service

    L4 Economic loss

    D3 Failure o systems

    S3

    Lightning fash to the services

    D2 Physical damage

    D3 Failure o systems

    S4Lightning fash near to the services

    D3 Failure o systems

    Damages and losses in a structure or dierent sources.Table 8.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    20/92

    www.erico.com20

    4. Risk Management (continued)

    Types o lossR

    T(y-1)

    IEC 62305-2 BS EN 62305-2

    Loss o human lie10-5

    (risk o 1 in 100,000)

    10-5

    (risk o 1 in 100,000)

    Loss o service to the public10-3

    (risk o 1 in 1,000)

    10-4

    (risk o 1 in 10,000)

    Loss o cultural heritage10-3(risk o 1 in 1,000)

    10-4(risk o 1 in 10,000)

    Tolerable risk RTable 9.T.

    Install further protective measures in order to reduce R1, 2, 3

    NO

    Structure is sufficiently protected against this type of loss

    For each loss, identify and calculate the riskR

    1, 2, 3

    3

    Identify the types of loss relevant to the structure to be protected Rn

    R1 risk of loss of human lifeR

    2risk of loss of services to the public

    R risk of loss of cultural heritage

    Identify the tolerable level of risk for each lossR

    T

    YES

    R1, 2, 3

    RT

    30 mm

    > 30 mm > 30 mm

    > 30 mm

    20d

    100% I imp

    10%

    10%*

    *Assuming 10 earth pointsand perfect current share

    or

    Figure 19. Use more secure connections or high current density locations.

    Figure 21. Overlap requirements or rebar.

    Figure 20. Rebar welding requirements or connections in concrete.

    d

  • 7/29/2019 ERITECH- H.N- IEC 62305

    31/92

    www.erico.com 31

    Header Goes Here

    Figure 23. Rebar clamps and CADWELD or connection to concrete reinorcing steel.

    8. Natural Components (continued)

    Figure 22. LENTON termination o rebar provides good electrical connection.

    Suitable or connection to air termination Suitable or connection to ground electrode

    CADWELD Exothermic connections

    Mechanical connection to EN50164-1

    RebarClamp

    to LightningProtection System

  • 7/29/2019 ERITECH- H.N- IEC 62305

    32/92

    www.erico.com32

    Header Goes Here8. Natural Components (continued)

    For ease o construction and installation, a grounding plateis recommended or connection o the LPS to the concrete

    member. I a grounding plate is not used, then attentionshould be given to corrosion protection at the air/concrete

    interace. I the rebar is brought out then 100 mm o siliconrubber or bitumen covering should be used. Interace corrosion

    protection is not required or copper, PVC covered copper orstainless steel conductors.

    Figure 24. Ground plates are convenient and eliminatethe need or corrosion protection.

    I welding is not permitted to the rebar, then an alternative is

    to use a dedicated lightning protection down-conductor that isembedded in the concrete. This conductor should be wire tied

    or clamped periodically to the rebar.

    General practice is to nominate specic rebars in the main

    structural columns as down-conductors, and to ensure thatthese are continuous through the entire route to ground.

    The connection path should be vertical.

    Full interconnection should be made to horizontal elements

    such as foors and walls. For structures such as data processingcentres this is more critical, and precast aade elements should

    also be bonded to provide eective electromagnetic shielding.

    8.3.1. Precast concrete

    Precast concrete rebar is permitted to be used as above.However precast members such as foors do not normally have

    external access to rebar connections. For ull interconnection,terminations should be provided or connection to columns and

    other members.

    8.3.2. Prestressed concrete

    Prestressed reinorced concrete is most commonly used orfooring, and rarely in vertical columns hence it is not oten

    used as a natural down-conductor. I it is to be used, careis recommended due to possible unacceptable mechanical

    consequences resulting rom the lightning current orinterconnection to the LPS. Only cables o 10 mm diameter

    or greater should be used, and several parallel cables should

    be used.

    Note that prestressed concrete is oten used or acades, and in

    the construction process the stressing cables are oten isolatedrom the other structural members. Should a side fash occur,

    there may be cracking o the acade with damage to thecorrosion protection concrete grout used around the stressing

    cable. These cables are highly susceptible to corrosion. In suchsituations, both ends o the cables should be bonded to the LPS.

    CorrosionProtection

    Ground

    Plate

  • 7/29/2019 ERITECH- H.N- IEC 62305

    33/92

    www.erico.com 33

    9. Design Methods

    9. Design methods

    The rolling sphere method, mesh method and protectionangle method are used to determine the required positioning

    o the lightning protection air-terminations. While there arelimits on the application o the protection angle and mesh

    methods, generally the standard considers the three methodsas equivalent.

    The rolling sphere method is recommended as the most

    universal method, while the mesh method is more suitable orthe protection o fat suraces. The protection angle method

    can only be used with limited vertical distances. Dierentdesign methods can be applied to dierent regions o a single

    lightning protection system, provided the zones aorded byeach method overlap to protect the entire structure.

    Any o these methods can be used to determine placemento the air-terminations. Permitted air-terminations are:

    Rods (including masts and ree standing masts)

    Meshed conductors (on building surace or elevated)

    Catenary wires

    Natural components

    detalosIdetalosinoN

    Air-terminations

    Meshedconductors

    Only practical forspecific circumstances

    Catenarywires

    S

    S = Separationdistance requirement

    S

    S S

    Meshed conductors used as air-terminations should not beconused with the mesh method. While the mesh method requires

    the use o surace mounted meshed conductors (a grid) to protectfat suraces, the rolling sphere and protection angle method can

    also be used to determine protection provided by elevated meshedconductors to protect a variety o compound suraces.

    While the standard considers the three methods to be equivalent,recent research has questioned the true eectiveness o the mesh

    method. ERICO recommends the rolling sphere method as themost eective. Rod air-terminations o height in the region o

    0.5 m are preerable to shorter rods or conductors on the buildingsurace. The rolling sphere method generally provides the most

    optimized design and the vertical air-terminal is ar more eectiveat capturing lightning fashes than mesh conductors installed

    upon, or just above structure surace. Reer to Section 10.1or urther inormation.

    The radius o the rolling sphere, the mesh size and the anglesused in the protection angle method are related to the class

    o the lightning protection system. Lightning protection classI, II, III & IV relate to protection level I, II, III, & IV respectively.

    For example i the risk assessment determines that a lightningprotection system with lightning protection class II is required to

    reduce the risk to below the tolerable level, then the design othe lightning protection system will need to be in accordance

    with the requirements o lightning protection level II (or higher).The greater the level o lightning protection (LPL I being the

    greatest), the larger the resulting material requirement or thelightning protection system.

    Figure 25.Air-Terminations.

    The Class o LPS/LPL infuences the:

    Rolling sphere radius, mesh size

    and protection angle

    Typical distances between down-

    conductors and between ringconductors

    Separation distances

    Minimum length o earthelectrodes

  • 7/29/2019 ERITECH- H.N- IEC 62305

    34/92

    www.erico.com34

    9. Design Methods (continued)

    80

    70

    60

    50

    40

    30

    20

    10

    0

    0 10 20 30 40 50 602

    I II IIIIV

    Class oLPS

    h

    Class o LPSLightning protection

    level (LPL)

    I I (highest)

    II II

    III III

    IV IV (lowest)

    Air-terminationProtection method

    Rolling sphere Mesh method Protection angle

    Rod 444 44

    Meshed conductors (on structure surace)

    4(1)

    Meshed conductors (elevated rom structure)

    44 44

    Catenary wires 44 44

    Note:(1)Mesh method is appropriate or the evaluation o the protection o the bound at surace. Rolling sphere and protection angle methods

    can be used to determine protection o adjacent areas.

    Suitability o air-termination methods and design methods.Table 17.

    Class o LPS (lightningprotection level)

    Rolling sphere radius (m) Mesh size (m) Protection angle

    I 20 5 x 5

    Refer Figure 25II 30 10 x 10

    III 45 15 x 15

    IV 60 20 x 20

    Maximum values or design methods.Table 18.

    Figure 26. Protection angle graph.

    Class o LPS andTable 19.lightning protection level.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    35/92

    www.erico.com 35

    r

    H < 60 m H < 60 m

    r

    H > 60 m

    H < 120 m

    H > 60 m

    H < 120 m0.8 H 0.8 H

    H > 120 m

    120 m

    H > 120 m

    120 m

    Figure 27. Rolling sphere protection method.

    9. Design Methods (continued)

    9.1. Rolling sphere

    As discussed in Section 2.3, with the rolling sphere method,an imaginary sphere is rolled over the surace o the structure.

    Where the sphere touches the structure, this point is vulnerableto a lightning fash and air-termination(s) are required. The air-

    termination system is placed such that the sphere only touchesthe air-terminations, and not the structure.

    = 2rh h22d

    Equation 2

    Where d= distance between two rods (m)

    r= radius o the rolling sphere (m)

    h = height o the rods (m)

    R

    Protected zone

    Protection required

    Figure 28. Rolling sphere protection method.

    The simplicity o the rolling sphere method is that it can be

    applied in scale to a building model, or or simple buildings tosectional drawings. As detailed in Section 10, air-terminationsmay be rods, meshed conductors, catenary wires or naturalcomponents.

    Note that or structures less than 60 m high the risk o fashes

    to the sides o the building is low, and thereore protection isnot required or the vertical sides directly below protected areas(Figure 27). In the IEC standards, or buildings above 60 m,protection is required to the sides o the upper 20% o height,reer to Section 16.1.

    9.1.1. Calculations or rolling spheremethod with rod air-terminations

    When rods are to be used as the air-termination or the

    protection o plane suraces, the ollowing calculation(Equation 2) is useul:

  • 7/29/2019 ERITECH- H.N- IEC 62305

    36/92

    www.erico.com36

    Equation 3

    where p = penetration distance (m)

    r= radius o the rolling sphere (m)

    d= distance between the two rods (m)

    9. Design Methods (continued)

    Height orod (m)

    Distance between air-terminations (m)

    LPL Ir = 20 m

    LPL IIr = 30 m

    LPL IIIr = 45 m

    LPL IVr = 60 m

    0.5 8.8 (6.2) 10.9 (7.7) 13.3 (9.4) 15.4 (10.9)

    1 12.4 (8.8) 15.3 (10.8) 18.8 (13.3) 21.8 (15.4)

    1.5 15.2 (10.7) 18.7 (13.2) 23.0 (16.2) 26.6 (18.8)

    2 17.4 (12.3) 21.5 (15.2) 26.5 (18.7) 30.7 (21.7)

    Note: Distances in brackets provide grid distances.

    When rods are to be used as the air-termination or protection

    o roo top items, the ollowing calculation (Equation 3) o

    sphere penetration distance is useul:

    2

    2

    2

    =d

    rrp

    Examples o rolling sphere protection distance.Table 20.

    Distancebetween rods

    D (m)

    Penetration distance (m)

    LPL Ir= 20 m

    LPL IIr= 30 m

    LPL IIIr= 45 m

    LPL IVr= 60 m

    1 0.01 0.00 0.00 0.00

    2 0.03 0.02 0.01 0.01

    3 0.06 0.04 0.03 0.02

    4 0.10 0.07 0.04 0.03

    5 0.16 0.10 0.07 0.05

    6 0.23 0.15 0.10 0.08

    7 (5 x 5 m) 0.31 0.20 0.14 0.10

    8 0.40 0.27 0.18 0.13

    9 0.51 0.34 0.23 0.17

    10 0.64 0.42 0.28 0.21

    14 (10 x 10 m) 1.27 0.83 0.55 0.41

    15 1.46 0.95 0.63 0.47

    20 2.68 1.72 1.13 0.84

    21 (15 x 15 m) 2.98 1.90 1.24 0.93

    28 (20 x 20 m) 5.72 3.47 2.34 1.66

    30 6.77 4.02 2.57 1.91

    Note:Figures in brackets are the mesh size o the correspondingdiagonal distance.

    Rolling sphere penetration distance.Table 21.

    Figure 29. Penetration distance o rolling sphere.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    37/92

    www.erico.com 37

    9. Design Methods (continued)

    Figure 30. Example o rolling sphere method.

    9.1.2. Calculations o rolling sphere methodand mesh/catenary conductors

    Where the rolling sphere method is to be used to evaluate theprotection provided by mesh conductors or network o catenary

    wires, the preceding two calculations (Equations 2 & 3) can

    be used. The distance/height o the mesh/catenary replaces therod distance/height. In Figure 29 note that the distance orpenetration or protection distance is the diagonal o the grid

    (distance between points A & B).LPL Mesh Size

    I 5 m x 5 m

    II 10 m x 10 m

    III 15 m x 15 m

    IV 20 m x 20 m

    Table 22. Mesh size or mesh method.

    9.2. Mesh method

    For protection o a plane (fat) surace, the mesh method is

    considered to protect the whole bound surace i meshedconductors are:

    Positioned on the edges (perimeter) o the surace

    The mesh size is in accordance with Table 22

    No metallic structures protrude outside the volume(Reer to Section 10.3 consider air-terminals andRSM/PAM method to protect these)

    From each point, at least two separate paths exist to

    ground (i.e. no dead ends), and these paths ollowthe most direct routes

    Natural components may be used or part o the mesh grid,or even the entire grid. The mesh method is recommended or

    fat roo suraces. It is also recommended or the protection othe sides o tall buildings against fashes to the side (reer to

    Section 16.1).

  • 7/29/2019 ERITECH- H.N- IEC 62305

    38/92

    www.erico.com38

    9. Design Methods (continued)

    A

    Figure 31. Protection via mesh method.

    Figure 32. Mesh method or compound shapes.

    The mesh method should not be used on curved suraces,but can be used on non-horizontal plane suraces and

    compound suraces. For example on the vertical sides o tall

    buildings or protection against fashes to the side, or oncompound suraces such as industrial roos. For compoundsuraces, conductors should be placed on the roo ridge

    lines i the slope exceeds 1/10.

    The protective area provided by the mesh method is the area

    bounded by the mesh. The protection to areas adjacent tothe mesh (e.g. building sides and lower structural points) is

    determined by the protection angle method or rolling sphere

    method (reer to Figure 33).

    The protection provided by meshed conductors not placed

    in ull accordance with the mesh method, e.g., those raisedabove the building surace, should be determined with an

    alternative design method, i.e., PAM or RSM, applied to theindividual conductors. I the RSM is used, Table 21 providesa simple rule o thumb or determining what minimumdistance above the building surace the mesh conductors

    would be required to be raised in order to conorm to therolling sphere method. It can be seen that this distance is

    0.31, 0.83, 1.24 and 1.66 m or mesh method grids spacedto requirements o LPL I, II, III and IV respectively.

    Mesh

    Method

    ProtectionAngle

    Methodh1

    r

    1

    Rolling

    SphereMethod

    Protected

    Volume

    Protected

    Volume

    Figure 33. Volume protected by meshed conductorsaccording to PAM and RSM method.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    39/92

    www.erico.com 39

    h1

    h2

    Protected

    Notprotected

    Protected

    d2

    2

    1

    d1

    Figure 36. Protection angle method applied toinclined surace.

    Figure 34. Protection angle method.

    Figure 35. Combination protection.

    9.3. Protection angle method

    Air-terminations (rods/masts and catenary wires) are located

    so the volume dened by the protection angle (reer toFigure 34) covers the structure to be protected. The heighto the air-termination is measured rom the top o the air-termination to the surace to be protected. The protection

    angle method is limited in application to heights that areequal to or less than the corresponding rolling sphere radius.

    Where the protection angle method alone is employed, multiplerods are generally required or most structures. However the

    protection angle method is most commonly used to supplementthe mesh method, providing protection to items protruding rom

    the plane surace.

    The protection angle method can be used on inclinedsuraces, where the height o the rod is the vertical height,

    but the protection angle is reerenced rom a perpendicularline rom the surace to the tip o the rod.

    h

    90

    9. Design Methods (continued)

  • 7/29/2019 ERITECH- H.N- IEC 62305

    40/92

    www.erico.com40

    Header Goes Here9. Design Methods (continued)

    Height hof air-

    termination(m)

    Distance d (m) and protection angle (rounded down to nearest degree)

    LPL I LPL II LPL III LPL IV

    Distance Angle Distance Angle Distance Angle Distance Angle

    1 2.75 70 3.27 73 4.01 76 4.70 78

    2 5.49 70 6.54 73 8.02 76 9.41 78

    3 7.07 67 8.71 71 10.46 74 12.99 77

    4 7.52 62 9.42 67 12.31 72 13.95 745 8.32 59 10.25 64 14.52 71 16.35 73

    6 8.57 55 10.82 61 14.14 67 17.43 71

    7 9.29 53 11.65 59 15.72 66 18.24 69

    8 9.53 50 12.32 57 16.40 64 18.85 67

    9 9.65 47 12.85 55 16.93 62 20.21 66

    10 10.00 45 13.27 53 17.32 60 20.50 64

    11 9.90 42 14.08 52 19.05 60 19.84 61

    12 10.07 40 14.30 50 19.20 58 20.78 60

    13 10.16 38 14.44 48 19.27 56 21.64 59

    14 9.80 35 14.50 46 19.27 54 22.40 58

    15 9.74 33 15.00 45 19.91 53 23.10 57

    16 9.61 31 14.92 43 20.48 52 22.85 55

    17 9.04 28 15.31 42 20.99 51 23.40 54

    18 8.78 26 15.65 41 21.45 50 23.89 53

    19 8.86 25 15.94 40 21.86 49 25.21 53

    20 7.68 21 15.07 37 21.45 47 25.60 52

    21 14.70 35 21.75 46 25.93 51

    22 14.84 34 22.00 45 26.22 50

    23 14.94 33 22.21 44 27.41 50

    24 14.42 31 22.38 43 26.65 48

    25 14.43 30 22.51 42 26.81 47

    26 13.82 28 21.82 40 27.88 47

    27 13.17 26 22.66 40 27.96 46

    28 13.06 25 21.88 38 28.00 45

    29 12.91 24 21.85 37 28.00 44

    30 12.73 23 21.80 36 28.97 44

    31 21.71 35 28.91 43

    32 21.58 34 28.81 42

    33 21.43 33 28.69 4134 21.25 32 28.53 40

    35 21.03 31 28.34 39

    36 20.78 30 29.15 39

    37 20.51 29 28.91 38

    38 20.20 28 28.64 37

    39 19.87 27 29.39 37

    40 19.51 26 29.06 36

    41 19.12 25 29.79 36

    42 18.70 24 30.51 36

    43 18.25 23 30.11 35

    44 18.68 23 28.57 33

    45 18.18 22 29.22 33

    46 28.74 32

    47 28.24 31

    48 27.71 3049 28.29 30

    50 28.87 30

    51 28.27 29

    52 28.82 29

    53 29.38 29

    54 28.71 28

    55 28.02 27

    56 27.31 26

    57 26.58 25

    58 25.82 24

    59 25.04 2360 25.47 23

    Table 23. Height versus horizontal distance using protection angle method.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    41/92

    www.erico.com 41

    Header Goes Here

    ss

    1

    1

    2

    2 s

    ss

    Catenary Wire

    Taut Wire or Rod

    Figure 37. Examples oprotection angle method.

    9. Design Methods (continued)

  • 7/29/2019 ERITECH- H.N- IEC 62305

    42/92

    www.erico.com42

    Header Goes Here

    Protection overestimated bythe protection angle method

    Protection underestimated bythe protection angle method

    Figure 38. Origin o protection angle.

    The knowledge that the protection angle method is derived

    rom the rolling sphere method helps to understand acommon question about its implementation. With reerence

    to Figure 34, it may not be apparent why oc2 is less thanoc1 I a second air-terminal is installed to the let o the

    existing air-terminal, then oc1 and oc2 or the second terminalwould be equal. The reason that h2 is used or oc2 is an

    attempt to duplicate the protection indicated by the rollingsphere method.

    9. Design Methods (continued)

    9.3.1. Background o the protectionangle method

    While the protection angle method appears to be similar

    to the historic and simple cone o protection method, theprotection angle method is actually a derivative o the rolling

    sphere method. The angles or the protection angle methodare obtained rom a rolling sphere analysis as shown in

    Figure 38. This is why the protection angle method is limitedto the maximum height o the equivalent rolling sphere.

    Consider a 50 m structure with rod air-termination. As a45 m rolling sphere (LPL III) would touch the side o the

    structure, protection to objects at the ground level can notbe protected using protection angle with LPL III. Considering

    LPL IV, a 60 m rolling sphere would not touch the side o thestructure, thus protection angle LPL IV can be used with the

    rod air-termination to determine what objects at the groundlevel would be protected.

    The virtue o the protection angle method is its simplicity

    in application, but its drawback is that it is a urthersimplication o the rolling sphere method, hence maynot be as reliable or ecient.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    43/92

    www.erico.com 43

    Header Goes Here

    Figure 40. Typical air-terminations.

    Figure 41. Rod designs to reduce risk o impalement.

    Figure 39.Air-terminal interconnections.

    10. Air-terminations

    10. Air-terminations

    Air-terminations are those items specically placed to capturethe lightning fashes. Permitted air-terminations are:

    Rods (including masts and ree standing masts)

    Meshed conductors (on building surace or elevated)

    Catenary wires

    Natural components

    Air-terminations are placed in accordance with the selected

    design method to provide protection to the structure.Additionally:

    Air-terminations should be interconnected at eachstructure level

    Air-terminations should be connected to down-conductors

    as per Section 11

    Mesh and air-termination interconnections should be

    provided with expansion joints (reer to Section 10.5)

    Rod air-terminations should be located or designed

    (suitable height or tip shape) to avoid the creation oan impalement hazard

    In placing conductors upon the roo, several additionalconsiderations should be taken:

    Install as close as practical to roo edges

    Secure per requirements provided in Table 26

    Select materials to reduce risk o corrosion

    Do not introduce trip hazards upon roo surace

    Do not locate in areas where water may pool (e.g. gutters)

    Avoid penetrations into roo or xing o conductors

  • 7/29/2019 ERITECH- H.N- IEC 62305

    44/92

    www.erico.com44

    Header Goes Here10. Air-terminations (continued)

    h

    d

    d h is recommendedto be 0.25m-0.5mminimumd is recommendedto be 0.5hmaximum

    Figure 43. Recommended distances or placement.

    This research does not bode well or horizontal conductorsplaced on the building via the mesh or other design methods,

    as the height o the conductor is the conductor thickness,

    typically 2 to 8 mm. The above research concludes that theconductor would need to be installed 1 to 4 mm rom thestructure edge. Generally, this is impossible due to the need to

    install clips to asten the conductor. As these are oten screwedin place, they can not be installed close to the edge.

    In accordance with the design requirements o the rollingsphere method, any horizontal conductor on a building edge

    (and intended to be part o the air-termination network)would need to be virtually on the exact edge to stop the

    rolling sphere rom touching the edge o the structure. TheIEC standards do not give any assistance or recommendations

    on this issue. BS 6651-1991 iners that 0.1 m maximumdistance is acceptable, yet this appears to be unsubstantiated.

    Due to perormance concerns, ERICO would not recommendthe use o the mesh method where horizontal conductors

    (or use as air-terminations) are installed directly onto thesurace to be protected. The addition o vertical air-terminations

    (rods) improves the perormance o the system considerably.For non mesh method designs, raising any horizontal air

    terminations at least 0.25 m above the surace improvesperormance. I the building edge uses a coping (metallic

    covering), then provided that the requirements or naturalair-terminations are met, the coping eliminates the conductor

    placement concern. In many cases, at the design stage o thebuilding, the use o coping, installation o metallic hand rails or

    careul selection o building materials and other structural itemscan signicantly improve perormance and reduce the visual

    impact o the lightning protection system.

    I the horizontal conductor is not part o the air-terminationnetwork (i.e. is part o the bonding network joining air-

    terminals), then placement is not as critical provided the otherair-terminations provide protection to the desired level.

    10.1. Recommendation on positioning

    IEC 62305-3 provides general statements on positioning o

    air-terminations, such as on corners, exposed points and edges.However, no specic dimensions or tolerances are given. Oten

    the question occurs rom the installers, how close is closeenough?. The strict answer is that the positioning o air-

    terminations should be compliant with the design method used(i.e. rolling sphere, protection angle or mesh method). Thereore

    a good design will document exact requirements to the installeror add a saety margin to design to cover normal variances. For

    example, air-terminals (rods) may be required on a parapet edgeand a good design will allow sucient height so that protection

    is provided regardless o whether the rods are installed on topo the parapet, or on the inside or outside edge.

    While the IEC standards allow any height o air-terminal (rod)to used, research shows that or eective protection, both the

    minimum height and the relationship o the height o the air-termination to distance rom the structure edge is critical.

    For air-terminals o less than 0.5 m height, these need to beless than hal their height rom the edge to be most eective.

    It is recommended that a minimum height o 0.25 m beselected (0.5 m preerred), and placed as close as practical to

    any edge being protected (at least within 0.5 x rod height).

    Figure 42.Adhesive bases, mounting blocks and standing seamsavoid need or penetrative mounting o conductor fxings.

  • 7/29/2019 ERITECH- H.N- IEC 62305

    45/92

    www.erico.com 45

    10. Air-terminations (continued)

    10.2. Masts and antennas

    Masts and fag poles, etc, on the structure can be used as parto the air-termination system where they meet the requirements

    o natural components and do not contain electrical circuits.The masts should be bonded into the LPS system.

    Antennas (communication and TV aerials, etc) and mastswith electrical equipment (e.g. obstruction lighting) should beprotected by an air-termination system, preerably an isolated

    system where the antenna and its mast does not conductlightning currents.

    Figure 44. Protection o antenna.

    For simple applications such as domestic roo top TV antennasit is permissible to simply bond the mast to the air-termination

    system, but damage to antenna/mast and cabling can beexpected. Class I surge protection must be installed.

    I the antenna is exposed to lightning fashes, then surgeprotection (Class I) must be installed. I the antenna is protected

    by an air-termination, then surge protection (Class II) shouldbe installed. The preerred location or the SPD is as close as

    possible to the entry point o the cable into the structure, andwhere possible the cable should enter into the building near to,

    and be connected to an equipotential bonding bar. Screenedcables should have the screen bonded to the antenna/air-

    termination and the equipotential bonding bar.

    The ERITECH isolated down-conductor system provides anair-terminal and isolated down-conductor that can be mounted

    directly on the mast/antenna structure to reduce the risk o direct

    or partial lightning currents. The isolated down-conductor hasa special construction that allows it to be mounted directly onthe mast, but provides the equivalent separation distance o

    1000 mm o air. Reer to Section 13 or urther inormation.

    10.3. Protection o other items protrudingabove the roo

    The design o the lightning protection system should be suchthat air-terminations are positioned to provide protection against

    lightning fashes to the roo and all items located upon it (vents,skylights, air-handling units, pipes, etc). However, in some cases,

    protection is not required or smaller or non-conductive items.

    Table 24 summarizes the requirements or determining i air-termination protection is required.

    Note that the bonding requirements or these items requires

    separate consideration, reer to Section 10.4.

    Table 24. Roo fxtures not requiring protection.

    Roo xtures do not require protection i thesedimensions are not exceeded:

    Metal RooFixtures

    Height above the roo level: 0.3 m

    The total area o the superstructure: 1.0 m2

    The length