2
CABINET • 20 gauge galvanized pre-painted steel corrosion resistant • Cabinet liner: Polythylene Foam Rated UL94 HF-1 ELECTRONIC COMPONENTS • Electrical Input Voltage: 120 VAC/60Hz / 1-Phase. • Electrical Input Current: 1.0 Amps Max • Circuit output voltage: 5VDC nominal • Integrated auxiliary furnace interlock relay • RoHs compliant MOTORS • Two permanent sealed, lubricated variable speed PSC Motors. (Maintenance free) • Maximum RPM 2695 / Horsepower; 3/32 HP. Class F, thermally protected • CSA 22.2 #113-10, clause 8.3.5 – Backup protection – totally enclosed motor POLYPROPYLENE HRV CORE • Dimensions 12"x 12"x 10" depth (304.8 mm x 304.8 mm x 254 mm) • Corrugated cross-flow polypropylene layers, rated UL94 HB & HF-1 • Cross-flow that transfers sensible heat • Endure harsh temperatures; effective in cold climates • Water washable DUOTROL™ BALANCING SYSTEM • The system is balanced by adjusting each motor independently • No balancing dampers required • Connection terminals for optional wall controls • Quiet and energy efficient DEFROST • Advanced 5 th port damper defrost sequence • Defrost type: Recirculation Activated automatically at -5°C (23°F) • Recirculation of warm ambient air throughout the home DUCT CONNECTIONS • Insert Slide & Fix (ISF™), removable collars system • Five (5) 6" (152.5 mm) dia. round double collar. MOUNTING • Adjustable mounting strap system FILTERS • Two (2) Fiberbond washable - 11 11 16"x 9 3 4"x 5 8" (297 mm x 248 mm x 15.9 mm) • UL Class 2 WARRANTY • 10 year limited warranty on motors • 5 year limited warranty on parts • Lifetime limited warranty on Heat Recovery Core AIRFLOW XDH 7.15 HRV Model Heat Recovery Ventilator with Recirculation 30 CFM (14 L/s) to 150 CFM (71 L/s) Item No. 102610 (XDH 7.15 Greentek) ENGINEERING DATA PP1001/ JUNE2017 Imperial Air Technologies Inc. reserves the right to modify a product, without prior notice, whether in design, colour or specifications, in order to offer at all times a quality product that is highly competitive. Please consult your national and local building codes to find out whether the installation of electrical products requires the services of a certified technician or electrician. Greentek TM is a registered Trademark used under license by Imperial Sheet Metal Ltd. All rights reserved. Imperial Air Technologies 480 Ferdinand Blvd., Dieppe, NB Canada E1A 6V9 Toll free: 1 888 724-5211 Fax: 1 (506) 388-4633 Visit us at: www.greentek.ca / www.imperialgroup.ca FEATURES • 5 operating modes (Econo, Intermittent, Continuous, Recirculation* & High) • 100% variable speed • Integrated door pressure balancing taps • ISF TM 6" (152.5 mm) dia. collar system • Proportional defrost sequence • SPM TM Single Person Mounting system • Permanent lubrification PSC motors *Recirculation mode available with optional Vectra EHC 1.5 Control APPLICABLE REQUIREMENTS • HVI Certified • CSA C439 Standard - Packaged Heat/Energy Recovery Ventilators (HRV/ERV) • CSA Standard CSA 22.2 N O .113 - Fans and ventilators • UL Standard 1812. Ducted Heat/Energy Recovery Ventilators (HRV/ERV) • ENERGY STAR ® , SRE, TRE and fan efficancy minimum requirements OPTIONAL ACCESSORIES • MERV 8 Inline 6" (152.5 mm) filter box • R-2 Style high performance supply & exhaust ventilation hoods Recirculation of warm ambient air without unpleasant odors Recirculated warm ambient air to home Advanced Defrost Sequence / Recirculating Mode Fresh air from outside Exhaust air to outside Exhaust air from home Fresh air to home Continuous Ventilation Mode

Transcript of ENGINEERING DATA - Imperial Group 7.15... · Greentek TM is a registered Trademark used under...

CABINET• 20 gauge galvanized pre-painted steel corrosion resistant• Cabinet liner: Polythylene Foam Rated UL94 HF-1

ELECTRONIC COMPONENTS• Electrical Input Voltage: 120 VAC/60Hz / 1-Phase. • Electrical Input Current: 1.0 Amps Max• Circuit output voltage: 5VDC nominal• Integrated auxiliary furnace interlock relay• RoHs compliant

MOTORS• Two permanent sealed, lubricated variable speed

PSC Motors. (Maintenance free)• Maximum RPM 2695 / Horsepower; 3/32 HP.

Class F, thermally protected• CSA 22.2 #113-10, clause 8.3.5

– Backup protection – totally enclosed motor

POLYPROPYLENE HRV CORE• Dimensions 12"x 12"x 10" depth

(304.8 mm x 304.8 mm x 254 mm)• Corrugated cross-flow polypropylene layers,

rated UL94 HB & HF-1• Cross-flow that transfers sensible heat• Endure harsh temperatures; effective in cold climates• Water washable

DUOTROL™ BALANCING SYSTEM• The system is balanced by adjusting each

motor independently• No balancing dampers required• Connection terminals for optional wall controls• Quiet and energy efficient

DEFROST• Advanced 5th port damper defrost sequence• Defrost type: Recirculation Activated automatically

at -5°C (23°F)• Recirculation of warm ambient air throughout the home

DUCT CONNECTIONS• Insert Slide & Fix (ISF™), removable collars system • Five (5) 6" (152.5 mm) dia. round double collar.

MOUNTING• Adjustable mounting strap system

FILTERS• Two (2) Fiberbond washable - 1111⁄16"x 93⁄4"x 5⁄8"

(297 mm x 248 mm x 15.9 mm)• UL Class 2

WARRANTY• 10 year limited warranty on motors• 5 year limited warranty on parts• Lifetime limited warranty on Heat Recovery Core

AIRFLOW

XDH 7.15 HRV ModelHeat Recovery Ventilator with Recirculation30 CFM (14 L/s) to 150 CFM (71 L/s)Item No. 102610 (XDH 7.15 Greentek)

ENGINEERING DATA

PP1001/ JUNE2017

Imperial Air Technologies Inc. reserves the right to modify a product, without prior notice, whether in design, colour or specifications, in order to offer at all times a quality product that is highly competitive. Please consult your national and local building codes to find out whether the installation of electrical products requires the services of a certified technician or electrician. GreentekTM is a registered Trademark used under license by Imperial Sheet Metal Ltd. All rights reserved.

Imperial Air Technologies480 Ferdinand Blvd., Dieppe, NB Canada E1A 6V9

Toll free: 1 888 724-5211 Fax: 1 (506) 388-4633

Visit us at: www.greentek.ca / www.imperialgroup.ca

FEATURES• 5 operating modes

(Econo, Intermittent, Continuous, Recirculation* & High)• 100% variable speed• Integrated door pressure balancing taps• ISFTM 6" (152.5 mm) dia. collar system• Proportional defrost sequence• SPMTM Single Person Mounting system• Permanent lubrification PSC motors *Recirculation mode available with optional

Vectra EHC 1.5 Control

APPLICABLE REQUIREMENTS• HVI Certified• CSA C439 Standard - Packaged Heat/Energy Recovery

Ventilators (HRV/ERV)• CSA Standard CSA 22.2 NO.113 - Fans and ventilators• UL Standard 1812. Ducted Heat/Energy Recovery Ventilators

(HRV/ERV)• ENERGY STAR®, SRE, TRE and fan efficancy

minimum requirements

OPTIONAL ACCESSORIES• MERV 8 Inline 6" (152.5 mm) filter box• R-2 Style high performance supply & exhaust

ventilation hoods

Recirculation of warmambient air withoutunpleasant odors

Recirculatedwarm ambientair to home

Fresh airfrom outside

Exhaust airto outside

Exhaust airfrom home

Fresh airto home

Continuous Ventilation Mode

Advanced Defrost Sequence / Recirculating Mode

Recirculation of warmambient air withoutunpleasant odors

Recirculatedwarm ambientair to home

Fresh airfrom outside

Exhaust airto outside

Exhaust airfrom home

Fresh airto home

Continuous Ventilation Mode

Advanced Defrost Sequence / Recirculating Mode

DIMENSIONS DATA

MINIMUM CLEARANCE DATA

Dimension Data for DH 7.15

Minimum Clearance Data for DH 7.15

Front View

21.47"545.3 mm

6"152.5 mm

31.9"810.2 mm

2.8"72.4 mm

5"126 mm

15"381 mm

3"76.2 mm

12"305 mm

3"76.2 mm

15"381 mm

5.5"140.5 mm

11.3"287.9 mm

Top View

Front View

Minimum plugclearance

15"381 mm

Ceiling

Minimum clearance for drain fittingRecomended minimum clearancefor “P” trap of 10" (254 mm)

Wall

Wall Minimum door clearance

Top View

Dimension Data for DH 7.15

Minimum Clearance Data for DH 7.15

Front View

21.47"545.3 mm

6"152.5 mm

31.9"810.2 mm

2.8"72.4 mm

5"126 mm

15"381 mm

3"76.2 mm

12"305 mm

3"76.2 mm

15"381 mm

5.5"140.5 mm

11.3"287.9 mm

Top View

Front View

Minimum plugclearance

15"381 mm

Ceiling

Minimum clearance for drain fittingRecomended minimum clearancefor “P” trap of 10" (254 mm)

Wall

Wall Minimum door clearance

Top View

Front View

Front View

Top View

Top View

ENGINEERING DATA XDH 7.15 HRV

VENTILATION PERFORMANCE External Static Net Supply Gross Air Flow Gross Air Flow Pressure Air Flow Supply Exhaust Pa in. wg L/s CFM L/s CFM L/s CFM 25 0.1 77 163 78 165 85 180 50 0.2 70 148 71 150 80 170 75 0.3 64 136 65 138 73 155 100 0.4 57 121 58 123 67 142 125 0.5 50 106 50 106 59 125 150 0.6 44 93 44 93 51 108 175 0.7 36 76 36 76 44 93

cfm

(L/s

= n

x 0

.471

9)

External Static Pressurein wg (Pa = n x 248.36)

0

50

100

150

200

250

300ExhaustSupply

0.1 0.2 0.3 0.4 0.5 0.6 0.7

pcm

(L/s

= n

x 0

,471

9)

Pression statique externe(Pa = n x 248,36)

0

50

100

150

200

250

300ÉvacuationAlimentation

0.1 0.2 0.3 0.4 0.5 0.6 0.7

SPECIFICATIONS XDH 7.15 HRVDimensions 371⁄2" x 241⁄4" x 113⁄8" (952.5 mm x 616 mm x 287 mm)

Duct Connections Five (5) 6" (152.5 mm) dia. ISF double collar system

Airflow Rates 30 CFM (14 L/s) to 150 CFM (71 L/s)

Motor Two (2) PSC variable speed backward curved

Voltage 120 VAC @ 60 Hz / 1 Phase

Amperage 1.0 A / 100 watts

Type of heat exchanger Cross-flow Polypropylene

Exchange surface 85 ft2 (7.9 m2)

Defrost type Recirculation

Filters Two (2) Fiberbond washable

Drain Connection 1⁄2" (12.7 mm)

DuoTrol Integrated Balancing System

Actual Weight 50.5 lbs (22 Kg)

Shipping Weight 56 lbs (25 Kg)

Certification HVI, ENERGY STAR, CCSAUS, CSA 22.2 NO.113 Complies with UL 1812

OPTIONAL WALL CONTROLSDigital EHC1.0TC and EHC1.5DC

Mechanical RD-1, RD-2, RD-3P and RD-4P

Timers T3 (20, 40, 60 minutes)

WALL CONTROL DIMENSIONSEHC1.0 & EHC1.5

Mechanical

T3 Timer

Quoted by: Date:

Project: Remarks:

Quantity:

Model:

Site:

Architect:

Engineer:

Contractor:

ENERGY PERFORMANCE Supply Temperature Net Air Flow Power Consumed Sensible Recovery Efficiency Adjusted Sensible Recovery Efficiency °C °F L/s CFM Watts SRE % ASRE %

0 32 30 64 52 71 76

0 32 40 85 60 68 73

0 32 50 106 72 65 69

-25 -13 32 68 59 64 67HE

AT

ING

This product earned the ENERGY STAR® by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA. It meets ENERGY STAR® requirements only when used in Canada.

2.75”(69.9 mm)

1.26”(32 mm)

2.64”(67 mm)

4.50”(114 mm)

0.62”(15.75 mm)

2.75 po(69.9 mm)

1.26 po(32 mm)

2.64 po(67 mm)

4.50 po(114 mm)

0.62 po(15.75 mm)

2.75”(69.9 mm)

1.26”(32 mm)

2.64”(67 mm)

4.50”(114 mm)

0.62”(15.75 mm)

2.75 po(69.9 mm)

1.26 po(32 mm)

2.64 po(67 mm)

4.50 po(114 mm)

0.62 po(15.75 mm)

6”(150mm)

1.73”(44mm)

1.46”(37mm)

4.07”(103.4mm)

6 po(150mm)

1.73 po(44mm)

1.46 po(37mm)

4.07 po(103.4mm)