Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

44

Click here to load reader

Transcript of Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Page 1: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Energy Savings for Occupancy-Based Control of VAV Systems Jian Zhang Ph.D. and Guopeng Liu Ph.D, PE, LEED AP Pacific Northwest National Laboratory Presented at Building Energy Simulation Forum Energy Trust of Oregon Portland OR Oct 21, 2015

PNNL-SA-113934

Page 2: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Content

Problem Statement Proposed Occupancy-Based Control Energy Saving Analysis Summary

October 21, 2015 2

Page 3: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

October 21, 2015 3

VAV Systems

Thermostat

Return Fan

VAV TerminalBox Controller

Damper HydronicReheat Coil

Flow Station Discharge air

Temperature

Terminal Box

To other Terminal Box

Outdoor Air

Relief Air

Advanced Occupancy

Sensor

Room Served by Terminal Box

Zone TempSensor

Return Air

AHUSupply Fan

Cooling Coil

Page 4: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

VAV Systems – Typical Control

Flow station controls the terminal box damper to maintain flow rate between minimum airflow set point (Vmin) and maximum airflow set point (Vmax) Code requirements for Vmin

30% of Vmax 0.4 cfm/ft2 of conditioned floor area, or 300 cfm

Common practice

October 21, 2015 4

Page 5: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

The minimum air flow setting for conference room normally is larger than the design maximum room occupancy ventilation requirement.

Are those rooms FULLY occupied ALL the time?

Problem Statement – Same Ventilation?

5 October 21, 2015

Page 6: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

The minimum air flow setting for conference room normally is larger than the design maximum room occupancy ventilation requirement.

Are those rooms FULLY occupied ALL the time?

Problem Statement – Same Ventilation?

6 October 21, 2015

Page 7: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

The minimum air flow setting for conference room normally is larger than the design maximum room occupancy ventilation requirement.

Are those rooms FULLY occupied ALL the time?

Problem Statement – Same Ventilation?

7 October 21, 2015

Page 8: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

The minimum air flow setting for conference room normally is larger than the design maximum room occupancy ventilation requirement.

Are those rooms FULLY occupied ALL the time?

Problem Statement – Same Ventilation?

8 October 21, 2015

Page 9: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Common Issues

Conference rooms designed for full occupancy Office space reconfiguration Overcooling and occupant discomfort Unnecessary reheat

9

Ski jacket

Foot heater

October 21, 2015

Page 10: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Challenges

GSA

October 21, 2015 10

Page 11: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Challenges

GSA

October 21, 2015 11

Page 12: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Challenges

GSA

October 21, 2015 12

Page 13: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Challenges

GSA

October 21, 2015 13

Page 14: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Problem Statement – Lighting

Occupancy sensors commonly used today to control lighting in conference rooms, lunch rooms and other places of assembly have significant limitations:

Long delay times for turning lights off – generally 20 to 30 minutes Lights turning off when occupants do not move frequently – delay times used to address this Cannot identify locations of occupants in rooms Are not suitable for other types of spaces, e.g., offices, rest rooms, and laboratories

Enhanced occupancy sensors used to control HVAC terminal boxes could control the operation of lights also.

October 21, 2015 14

Page 15: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Proposed Occupancy-Based Control (OBC)

October 21, 2015 15

Page 16: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Proposed OBC

Use monitored zone temperature and occupancy to determine terminal airflow rate Cooling mode: Vmin is reset based on the actual occupancy and ventilation standard Heating mode: higher value of

Vmin in cooling mode OR airflow required to prevent air stratification and/or short-circuiting.

No occupancy: Vmin = 0 OR area component

October 21, 2015 16

Page 17: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Proposed OBC

Control actions when “unoccupied” status is detected -“Stand-by Mode”

Turn off lighting Reduce minimum damper position Setback thermostat setpoint Reduce outdoor air intake (not included in this analysis)

October 21, 2015 17

Page 18: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Proposed OBC – Different from DCV

October 21, 2015 18

Exhaust air

Outdoor air

Heating coil Cooling coil Supply fan

CO2

Zone CO2 sensor

Signal converter

Typical single zone CO2 based demand control ventilation (DCV)

Page 19: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Sensor Technology

Common occupancy sensor (OS) Occupancy presence Motion sensing (infrared or ultrasonic) Low cost

Advanced occupancy sensor (OS)

Instantaneous head count Commercially available but expensive ($1000~ per hardware unit) Need further development for software

October 21, 2015 19

Page 20: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Project Status

October 21, 2015 20

Fiscal Year 2010 2011 2012 2013 2014 2015

Scoping Study OBC Control

Strategies Development

Impact Assessment (18% savings)

Algorithm Development

Occupancy Sensor Development

Occupancy-Based Control

Air Distribution Management Scoping Study

Development Plan Recommendations

Page 21: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Objective of Energy Saving Analysis

Evaluate the savings from OBC of VAV and lighting using

Common occupancy sensors Advanced occupancy sensors

October 21, 2015 21

Page 22: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Baseline – Candidate Buildings

Building Type Total Floor Space (Million Square

Feet)

Fraction of Total Commercial Floor

Space (%)

Total Annual Energy

Consumption (Trillion Btu/y)

Post-1980 Buildings with VAV (% of Total Floor

Space)

Pre-1980 Buildings with VAV (% of Total Floor

Space)

Large Office 4,354 6.1% 455 84 72 Medium Office 3,647 5.1% 342 65 40 Small Office 4,207 5.9% 336 18 13 Warehouse 10,078 14.1% 456 22 12 Retail 4,317 6.0% 319 12 10 Schools (K-12) 7,265 10.1% 525 53 33 Colleges 1,421 2.0% 221 88 49 Hospitals/Impatient Health Care 1,905 2.7% 475 95 67 Food Sales 1,255 1.8% 251 17 10 Grocery Stores 715 1.0% 153 31 8 Restaurants/Cafeterias 1,062 1.5% 245 31 23 Fast Food 262 0.4% 118 12 40 Hotels and Motels 2,952 4.1% 288 42 23

October 21, 2015 22

Source: CBECS 2003

Page 23: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Baseline – Large Office

500,000 sf 12 floors (one VAV AHU per story) and a basement (CAV) 40% WWR Air-cooled chiller and natural gas boiler VAV terminal boxes with dampers and hot-water reheating coils Construction weighting factors for 15 climate zones

October 21, 2015 23

Source: DOE Commercial Prototype Building Models https://www.energycodes.gov/commercial-prototype-building-models in EnergyPlus

Page 24: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Baseline - Changes to Large Office Prototype

To capture OBC savings Zone description

Specified space types (conference room, private office, and open office) Occupancy density Occupancy profile Ventilation rate

To represent 1980s construction HVAC sizing

Increased sizing factors Revised interior loads used for sizing

System OA calculation Changed from 62.1’s multiple-zone calculation to sum of the zone ventilation

October 21, 2015 24

Page 25: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Baseline - Changes to Zone Description

October 21, 2015 25

Page 26: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Lighting

October 21, 2015 26

Category Controlled

Zone Baseline Common OS Advanced OS

Lighting

Private Office Conference Room

No OBC Turn off after 15-minute

Turn off after 5-second

Open Office No OBC No OBC No OBC

𝐿𝐿𝐿𝐿𝐿𝐿𝑂𝑂𝑂𝑂𝑂𝑂 = 𝐿𝐿𝐿𝐿𝐿𝐿𝑂𝑂𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵𝐵 × 1 − 𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭 𝑺𝑺𝑭𝑭𝑺𝑺𝑭𝑭𝑭𝑭𝑺𝑺𝑺𝑺

Page 27: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Lighting

Data in blue diamonds from Von Neida et al. (2000) Extrapolated to savings with delay time of 5 seconds October 21, 2015 27

Common OS

Advanced OS

Page 28: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Minimum Air Flow

October 21, 2015 28

Category Controlled

Zone Baseline Common OS Advanced OS

Terminal Box Minimum Air-flow

Private Office

30% (constant)

30% (occupied) 0 (unoccupied)

0 ~ 30% based on occupancy

Open Office, Occupied

30% (constant)

30% (constant) 0 ~ 30% based on occupancy

Conference Room

50% (constant)

50% (when occupied) 0 (when

unoccupied)

0 ~ 50% based on occupancy

Page 29: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Minimum Air Flow – Common OS

October 21, 2015 29

Page 30: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Minimum Air Flow – Advanced OS

October 21, 2015 30

Page 31: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC - Occupancy in Private Office

Source: Wang et al. 2005 October 21, 2015 31

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Prob

abili

ty o

f Occ

upan

cy

Private Office Weekday

Hour of Day

Page 32: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC - Occupancy in Private Office

Probability of a 3-private-office zone being all unoccupied

October 21, 2015 32

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Prob

abili

ty

Private Office Weekday

Hour of Day

𝑷𝑷𝟑𝟑−𝑭𝑭𝒐𝒐𝒐𝒐𝑭𝑭𝑭𝑭𝒐𝒐 𝒛𝒛𝑭𝑭𝑭𝑭𝒐𝒐 𝒃𝒃𝒐𝒐𝑭𝑭𝑭𝑭𝑺𝑺 𝒖𝒖𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝑭𝒖𝒖𝒖𝒖𝑭𝑭𝒐𝒐𝒖𝒖 = 𝟏𝟏 − 𝑷𝑷𝑭𝑭𝑭𝑭𝒖𝒖𝑭𝑭𝑺𝑺𝑭𝑭𝒖𝒖𝒖𝒖𝑭𝑭𝑭𝑭 𝑭𝑭𝒐𝒐𝒐𝒐𝑭𝑭𝑭𝑭𝒐𝒐𝟑𝟑

Page 33: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC - Conference Room Occupancy

Source: Hart 2012

October 21, 2015 33

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Occ

upan

cy F

ract

ion

Hour of Day

Weekday Conference Room Occupancy Profile

Page 34: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Modeled OBC for Thermostat Setpoints

Setback to standby mode only when the probability of the 3-office zone being all unoccupied is 50% or greater.

October 21, 2015 34

Category Status Base Case Common OS Advanced OS

Cooling Setpoint

Occupied 75°F 75°F 75°F

Unoccupied 75°F

(no setback) 79°F (standby)

Conference Rooms

79°F (standby) Conference RM and

Private Offices*

Heating Setpoint

Occupied

70°F

70°F 70°F

Unoccupied 70°F

(no setback) 66°F (standby)

Conference Rooms

66°F (standby) Conference RM and

Private Offices*

Page 35: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Results – Site EUI Comparison

October 21, 2015 35

0

10

20

30

40

50

60

70

Site

EU

I (kB

tu/s

f-yea

r)

Climate Zone and Location

Baseline Common OS Advanced OS

Page 36: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Results – Energy Cost Savings

October 21, 2015 36

0

0.05

0.1

0.15

0.2

0.25

Ene

rgy

Cost

Sav

ings

($/s

f)

Climate Zone and Location

Advanced OS Common OS

Page 37: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Results – Savings of Advanced OS

October 21, 2015 37

Page 38: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Results – Baseline vs Advanced OS for Lighting and HVAC

Major Savings from reduction to reheat energy Significant improvement from OBC with common OS to advanced OS

October 21, 2015 38

National Weighted Average Site Energy Use (kBtu/sf-yr) Energy Savings

Interior Lights Cooling Heating Fans Pumps Whole

Building kBtu/sf-

yr %

Baseline 9.8 6.9 9.0 2.1 2.3 47.8 - - Common OS 9.2 6.5 7.4 1.9 2.2 45.0 2.8 5.9% Advanced OS 8.9 5.9 3.0 1.5 2.2 39.3 8.5 17.9%

Page 39: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Summary

Proposed OBC addresses issues of VAV systems with additional lighting saving benefits. Both common and advanced OS can be used Advanced OS are under development

Control strategies Field testing Cost barrier

Simulation analysis of large office buildings retrofitted with OBC of Lighting Minimum airflow of VAV terminal boxes Thermostat setpoint

October 21, 2015 39

Page 40: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Summary

Both common and advanced OS yield significant savings, most from HVAC energy use. Advanced OS substantially increases savings comparing to common OS. Site energy savings of advanced OS could be 12 kBtu/ft2-y (20% or $0.2/sf-yr) in the cold climate zones and national weighted average savings of 8.5 kBtu/ft2-y (of 18%) Simulation models with OBC didn’t result in significant increase in load not-met hours. OBC with advanced OS is a very promising technology.

October 21, 2015 40

Page 41: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

References

Zhang J, RG Lutes, G Liu, and MR Brambley. 2013. Energy Savings for Occupancy-Based Control (OBC) of Variable-Air-Volume (VAV) Systems. PNNL-22072, Pacific Northwest National Laboratory, Richland, WA. Liu G, AR Dasu, and J Zhang. 2012. Review of Literature on Terminal Box Control, Occupancy Sensing Technology and Multi-zone Demand Control Ventilation (DCV). PNNL-21281, Pacific Northwest National Laboratory, Richland, WA. DOE Commercial Prototype Building Models (16 prototypes in all US climates) https://www.energycodes.gov/commercial-prototype-building-models EIA. 2003. Commercial Building Energy Consumption Survey 2003. U.S. Department of Energy. Washington, DC. http://www.eia.doe.gov/emeu/cbecs/ Wang, D., C.C. Federspiel, and F. Rubinstein. 2005. “Modeling occupancy in single person offices,” Energy and Buildings 37(2):121–126. Hart, R. 2012. RE: Impact of Recent ASHRAE 62.1 Standard Committee Interpretations on 2013 Title 24 Code Ventilation Proposals. California Energy Commission- Docket 12-BSTD-1, February 2012, PECI, Inc., Portland, OR.

October 21, 2015 41

Page 42: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

October 21, 2015 42

42

Wireless occupancy sensor network

Occupancy Sensor Network

Micro-controller (Arduino, Pi, etc.)

Terminal Box Controller

VAV Box

Page 43: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Acknowledgement

Research funded by U.S. Department of Energy

PNNL project team

Michael Brambley Guopeng Liu Jian Zhang Robert Lutes Linda Sandahl

October 21, 2015 43

Page 44: Energy Savings for Occupancy-Based Control of Variable-Air-Volume Systems

Thank you

Questions

[email protected] [email protected]