ENERGY AUDIT OF PUMPS & FANS

49
ENERGY AUDIT OF PUMPS & FANS Presented By M.V.Pande Dy.Director NPTI, Nagpur

description

ENERGY AUDIT OF PUMPS & FANS. Presented By M.V.Pande Dy.Director NPTI, Nagpur. WATER PUMPS IN POWER STATION. BOILER FEED WATER PUMP. - PowerPoint PPT Presentation

Transcript of ENERGY AUDIT OF PUMPS & FANS

Page 1: ENERGY AUDIT OF PUMPS & FANS

ENERGY AUDITOF

PUMPS & FANS

Presented By

M.V.Pande

Dy.Director

NPTI, Nagpur

Page 2: ENERGY AUDIT OF PUMPS & FANS

WATER PUMPS IN POWER STATION

Page 3: ENERGY AUDIT OF PUMPS & FANS

BOILER FEED WATER PUMP Boiler feed pump is the major power consumer among all power consuming equipment in the power plant. BFP may constitute about 25% of the total auxiliary power consumption.

BFP Main Parameters for 210 MW unit

Model Speed

RPM

Disch. head

mWC

Capacity

TPH

Motor Power kW

200 KHI 4320 1834.6 430 4000

FK 6D 30 5050 2104 398 3500

Page 4: ENERGY AUDIT OF PUMPS & FANS

BFP LAYOUT

Page 5: ENERGY AUDIT OF PUMPS & FANS

PUMP CURVES

Pump Operating PointPump Operating Point

System head curveSystem head curve Pump Head – Flow curvePump Head – Flow curve

Page 6: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION

Specifications and design details

Page 7: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION

Specifications and design details contd…

Page 8: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION Collect the above information for all pumps in the water circuit

Collect the Performance Characteristics curves of all pumps

Compile design, P. G. test, previous best and last energy audit values with of the pumping system being audited

If the pumps are operated in parallel, then it is advised to collect the performance curves for the parallel operation of the pumps

Schematic diagram of Water pumping network (which depict the source, pumps in operation & stand by, line sizes and users)

Water and pressure equipments at the users as per the design requirements

Brief description of the system, in which pumps are used

Page 9: ENERGY AUDIT OF PUMPS & FANS

INSTRUMENTS REQUIRED

• Power Analyzer: Used for measuring electrical parameters such as kW, kVA, pf, V, A and Hz

• Temperature Indicator & Probe

• Pressure Gauge: To measure operating pressure and pressure drop in the system

• Stroboscope: To measure the speed of the driven equipment and motor

• Ultra sonic flow meter or online flow meter

• The above instruments can be used in addition to the calibrated online / plant instruments

Page 10: ENERGY AUDIT OF PUMPS & FANS

PARAMETERS TO BE MEASURED Energy consumption pattern of pumps (daily / monthly /yearly consumption)

Motor electrical parameters (kW, kVA, Pf, A, V, Hz, THD) for individual pumps

Pump operating parameters to be monitored for each pump

Discharge Flow, Head (suction & discharge), Valve position, Temperature, Load variation, Simultaneous power parameters of pumps, Pumps operating hours and operating schedule, Pressure drop in the system (between discharge and user point), Pressure drop and temperatures across the users (heat exchangers, condensers, etc), Pump /Motor speed, Actual discharge pressure and required / prevailing pressure at the user end, User area pressure of operation and requirement

Page 11: ENERGY AUDIT OF PUMPS & FANS

OBSERVATIONS AND MEASUREMENTS

Operating efficiency and performance evaluation of pumps

Flow distribution

System Details: Detailed interactions with the plant personnel have to be carried out to get familiarization for system detail and operational details. The brief system should be briefed in the report

Energy consumption Pattern: If the plant is monitoring the energy consumption, it is suggested to record the data and monitor the daily and monthly consumption pattern

Collect the past energy consumption data (month wise for at least 12 months, daily consumption for about a week for different seasons, daily Consumption during the audit period)

Page 12: ENERGY AUDIT OF PUMPS & FANS

EFFICIENCY AND PERFORMANCE EVALUATION OF THE PUMPS

Performance parameters for water pumps

Page 13: ENERGY AUDIT OF PUMPS & FANS

EFFICIENCY AND PERFORMANCE EVALUATION OF THE PUMPS

Performance parameters for water pumps contd..

Page 14: ENERGY AUDIT OF PUMPS & FANS

EFFICIENCY AND PERFORMANCE EVALUATION OF THE PUMPS

Pump hydraulic power can be calculated by the formula:

Hydraulic kW = Q x Total Head, (hd – hs) x x g

1000Parameter Details Unit

Q Water flow rate m3/s

Total head Difference between discharge head, hd & suction head, hs m

Density of water or fluid being pumped Kg/m3

g Acceleration due to gravity m2/s

Pump efficiency, Pump = Hydraulic power

Pump shaft power

Pump shaft power = Hydraulic power x Motor

Page 15: ENERGY AUDIT OF PUMPS & FANS

ENERGY CONSERVATION OPPORTUNITIES Compare the actual values with the design / performance test values if any deviation is found, list the factors with the details and suggestions to over come.

Compare the specific energy consumption with the best achievable value (considering the different alternatives). Investigations to be carried out for problematic areas..

Enlist scope of improvement with extensive physical checks / observations. Based on the actual operating parameters, enlist recommendations for action to be taken for improvement, if applicable such as:

Replacement of pumps

Impeller replacement

Impeller trimming

Variable speed drive application, etc

Page 16: ENERGY AUDIT OF PUMPS & FANS

Avoiding over sizing of pump

ENERGY CONSERVATION OPPORTUNITIES

Head

Head

Partially

closed valve

Const. Speed

A

B

C

Meters

Pump Efficiency 77%

82%

Pump Curve at

Full open valve

System Curves

Operating Points

500300

50 m

70 m

Static

42 m

Flow (m3/hr)

Oversize Pump

Required Pump

Page 17: ENERGY AUDIT OF PUMPS & FANS

28.6 kW

14.8 kW

Avoiding Over sizing of Pump by impeller trimming

ENERGY CONSERVATION OPPORTUNITIES

Page 18: ENERGY AUDIT OF PUMPS & FANS

Provision of variable speed drive

ENERGY CONSERVATION OPPORTUNITIES

Page 19: ENERGY AUDIT OF PUMPS & FANS

Energy Conservation Possibilities- Summary Improvement of systems and drives.

Use of energy efficient pumps

Replacement of inefficient pumps

Trimming of impellers

Correcting inaccuracies of the Pump sizing

Use of high efficiency motors

Integration of variable speed drives into pumps: The integration of adjustable speed drives (ASD) into compressors could lead to energy efficiency improvements, depending on load characteristics.

High Performance Lubricants: The low temperature fluidity and high temperature stability of high performance lubricants can increase energy efficiency by reducing frictional losses.

Booster pump application

Centralisation/ decentralisation

Categorising according to the pressure requirement

Page 20: ENERGY AUDIT OF PUMPS & FANS

ENERGY AUDIT OF FANS

Page 21: ENERGY AUDIT OF PUMPS & FANS

BACKGROUND

Thermal power plant has several fans such as Induced draft (ID) fans, Forced draft (FD) Fans, Primary air fans (PA fans). These fans contribute to significant auxiliary power consumption. ID fans alone contribute to about 12% of total auxiliary power consumption

ID Fan System

Data collection

Observations and Analysis

Exploration for energy conservation measures

Report preparation

Steps Involved

Page 22: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION Collect detailed design specification & operating parameters

Fans Parameters ( FD, ID and PA Fan )

Page 23: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION Collect detailed design specification & operating parameters

Fans Parameters ( FD, ID and PA Fan )- contd…

Page 24: ENERGY AUDIT OF PUMPS & FANS

DATA COLLECTION

Details of the fans and ducting system: Collect the schematic diagram / network of the ducting system Collect Performance characteristics of all fans

Compile design, P. G. Test, previous best and last energy audit values with respect to fans and draft system which include excess air

If the fans are operated in parallel then it is advised to collect the performance curve for the parallel operation

Air quality and pressure equipments at the users as per the design requirements

Page 25: ENERGY AUDIT OF PUMPS & FANS

INSTRUMENTS REQUIREDPower Analyzer: Used for measuring electrical parameters such as kW, kVA, pf, V, A and Hz

Temperature Indicator & Probe

Stroboscope: To measure the speed of the driven equipment and motor

Sling hygrometer or digital hygrometer

Anemometer

On line instruments – (calibrated)

Digital Manometer of suitable range and appropriate probes for measurement of pressure head and velocity head.

Pitot tubes

Additional pressure gauges with appropriate range of measurement and calibrated before audit.

Page 26: ENERGY AUDIT OF PUMPS & FANS

MEASUREMENTS & OBSERVATIONS TO BE MADE

Energy consumption pattern of fans

Motor electrical parameters (kW, kVA, Pf, A, V, Hz, THD) of fans

Fan operating parameters to be measured/monitored for each Fans are:

1. Discharge / flow rates

2. Pressure (suction & discharge)

-Static pressure

-Dynamic pressure

-Total pressure

Page 27: ENERGY AUDIT OF PUMPS & FANS

MEASUREMENTS & OBSERVATIONS TO BE MADE

3. Damper position / guide vane position/ VSD Setting

4. Temperature of fluid handled

5. Load variation

6. Power parameters of fans

7. Fan operating hours and operating schedule

8. Pressure drop in the system (between discharge and user point)

9. Pressure drop and temperatures drop across the equipment

10. Fan /Motor speed

Page 28: ENERGY AUDIT OF PUMPS & FANS

MEASUREMENTS & OBSERVATIONS TO BE MADE

Oxygen content, flow, temperature and pressure measurement across in exhaust gas path

- Before and after air pre heater

- Before and after economizer

-Before and after ID fan

- Before and after ESP

- In case where flow measurement (for air pre heater and ESP) is not possible, it can be estimated based on mass balance principles, stoichiometric analysis,

Page 29: ENERGY AUDIT OF PUMPS & FANS

ENERGY CONSUMPTION PATTERN

If the plant is monitoring the energy consumption, it is suggested to record the data and monitor the daily and monthly consumption pattern. (Collect data for 12 months)

Work out the total consumption of fans to arrive at percentage to the total consumption of the auxiliary consumption

If the energy meters are not installed to fans, instantaneous measurements can be carried out, based on the loading pattern the daily consumption can be worked out as per following table-

Energy consumption pattern

Page 30: ENERGY AUDIT OF PUMPS & FANS

The parameters to be studied in detailed are:

Air /gas rates of fans / main ducts

Static pressure and dynamic pressure and total pressure

Power consumption of fan (for estimating the operating efficiency of the fans)

Monitor present flow control system and frequency of control valve operation if any (for application of variable speed drives)

Fill up the following data sheet for every fan

FAN OPERATING EFFICIENCY EVALUATION

Page 31: ENERGY AUDIT OF PUMPS & FANS

Performance parameters for fans

FAN OPERATING EFFICIENCY EVALUATION

Page 32: ENERGY AUDIT OF PUMPS & FANS

FAN OPERATING EFFICIENCY EVALUATION

Page 33: ENERGY AUDIT OF PUMPS & FANS

FAN LAWS

Flow ? Speed Pressure ? (Speed)2 Power ? (Speed)3

1 1

2 2

Q N

Q N

21 1

2 2

SP N

SP N

3

1 1

2 2

kW N

kW N

Varying the RPM by 10% decreases or increases air delivery by 10%.

Varying the RPM by 10% decreases or increases the static pressure by 19%.

Varying the RPM by 10% decreases or increases the

power requirement by 27%.

Where Q – flow, SP – Static Pressure, kW – Power and N – speed (RPM)

x x x

Page 34: ENERGY AUDIT OF PUMPS & FANS

FANS PERFORMANCE ASSESSMENT

• Static pressure– Potential energy put into the system by the fan

• Velocity pressure– Pressure arising from air flowing through the duct. This

is used to calculate velocity

• Total pressure – Static pressure + velocity pressure

– Total pressure remains constant unlike static and velocity pressure

Page 35: ENERGY AUDIT OF PUMPS & FANS
Page 36: ENERGY AUDIT OF PUMPS & FANS
Page 37: ENERGY AUDIT OF PUMPS & FANS

TRAVERSE POINTS FOR VELOCITY MEASUREMENT

Page 38: ENERGY AUDIT OF PUMPS & FANS

Fan total kW = Q in m3/ s x total pr. developed by fan in mmwc 102

Fan static kW = Q in m3/ s x static pr. developed by fan in mmwc 102

Fan static efficiency % Fan static kW x 100 Input kW to motor x m

=

Fan mechanical Efficiency = Fan total kW x 100 Input kW to motor x m

Parameter Details Unit

Q Air flow rate m3/ s

Static pressure Difference between discharge & suction pressure mmwc

Fan static/ total kW Static / total power consumption of the fan kW

Input kW to motor Measured power consumption of the motor kW

m Efficiency of the motor at operating load

Total pressure Difference between discharge & suction pressure mmwc

FAN OPERATING EFFICIENCY EVALUATION

Page 39: ENERGY AUDIT OF PUMPS & FANS

FAN OPERATING EFFICIENCY EVALUATION

Corrected air density, = 273 X 1.293

273 + Air temperature in 0 C

Parameter Details Unit

Cp Pitot tube constant 0.85 or as given by manufacturer

Density of air or gas at test condition Kg / m3

Velocity in m / s =Cp x 2 x 9.81 x Diff. velocity pr. in mmwc x

Volumetric flow (Q), m3/s = Velocity, m/s x Area, m2

Page 40: ENERGY AUDIT OF PUMPS & FANS

FAN OPERATING EFFICIENCY EVALUATIONIn case of gas flow measurement of ID fans, where it is not possible to measure the gas flow, then the mass flow method can be adopted, provided the oxygen content and actual coal flow measurements are available. For flow estimation through this method, the following are required:

Stoichiometric air requirement (work out based on the coal composition)

Oxygen content at ID fan inlet (measured)

Excess air (estimate)

% Excess air = (%O2 in flue gas x 100) / (21 – O2 in flue gas)

Coal flow (based on actual measurement or on average basis)

Fly ash content (assumed based on past data)

Page 41: ENERGY AUDIT OF PUMPS & FANS

While in case air flow measurement for FD and PA fans the following instruments (which ever are suitable) can be used

Thermal anemometer

Vane type anemometer

Pitot tube along with micro manometer can be used

Online measuring instrument

If the fans are operating in parallel, it is advised to measure all above parameter for every fan separately to evaluate the individual performance. However combined parameters of flow and head need to be verified with Performance curve for parallel operation

FAN PERFORMANCE ANALYSIS

Page 42: ENERGY AUDIT OF PUMPS & FANS

FAN PERFORMANCE ANALYSISCompare the actual values with the design / performance test values if any deviation is found, list the factors with the details and suggestions to over come.

The investigations for abnormality are to be carried out for problems.

Enlist scope of improvement with extensive physical checks / observations.

Based on the actual operating parameters, enlist recommendations for action to be taken for improvement, if applicable such as- Replacement of fans, Impeller replacement, VFD application.

Cost analysis with savings potential for taking improvement measures.

Page 43: ENERGY AUDIT OF PUMPS & FANS

Recirculation

Damper

IGV

VFD

Ideal

Power

Flow

25 7550 100

100

75

50

25

FAN PERFORMANCE ANALYSISFlow controlFlow control

Page 44: ENERGY AUDIT OF PUMPS & FANS

FAN PERFORMANCE ANALYSIS

System characteristics and Fan curves

Impact of speed reduction

Page 45: ENERGY AUDIT OF PUMPS & FANS

FAN PERFORMANCE ANALYSIS

Visual survey of insulation & the ducting system:

Insulation status (measure the surface temperature with the aid of surface thermocouple / infrared pyrometer or by using thermal imaging cameras)

Bends and ducting status

Physical condition of insulation Identification of locations where action is required to improve the insulation (provide with detailed techno-economics)

Improvement options for ducting systems if any

Sources of air ingress

Page 46: ENERGY AUDIT OF PUMPS & FANS

FAN PERFORMANCE ANALYSIS

Study of air ingress in to the system:

Before and after air preheater Before and after ESP Before and after ID fanThe difference in the oxygen gives the extent of air ingress in to the system. Measurements of oxygen content across all units in flue gas path, indicates the locations where ingress is occurring

Page 47: ENERGY AUDIT OF PUMPS & FANS

EXPLORATION OF ENERGY CONSERVATION POSSIBILITIES

Improvement of systems and drives:

Use of energy efficient fans

Change of impeller with energy efficient impeller

Correcting inaccuracies of the fan sizing

Use of high efficiency motors

Fan speed reduction by pulley diameter modifications for optimisation

Option of two speed motors or variable speed drives for variable duty conditions

High Performance Lubricants: The low temperature fluidity and high temperature stability of high performance lubricants can increase energy efficiency by reducing frictional losses

Use of energy efficient transmission systems (Use of latest energy efficient transmission belts)

Page 48: ENERGY AUDIT OF PUMPS & FANS

EXPLORATION OF ENERGY CONSERVATION POSSIBILITIES

Improvement in operations:

Minimising excess air level in combustion systems to reduce FD fan and ID fan load.

Minimising air in-leaks in hot flue gas path to reduce ID fan load and cold air in-leaks

Minimising system resistance and pressure drops by

improvements in duct system / Insulation aspects

Deviations in air flow rates

Measures to up keep the performance

After the identification of energy conservation measures, detailed techno-economic evaluation has to be carried out

Page 49: ENERGY AUDIT OF PUMPS & FANS