Energy Audit
1
1. Common Irregularities Found in EA Submission
2. Composite Buildings
3. Display of EA Form
4. Applicability of EA Requirement
![Page 2: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/2.jpg)
2
Missing
information
Incomplete
contact
information
Form EE-EA
(Checklist)
Missing / incomplete information
![Page 3: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/3.jpg)
3
Incomplete contact
information
should attach a
list of contact info
of the owners w/
the Form
Form EE-EA
Missing / incomplete information
![Page 4: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/4.jpg)
4
Missing
information
Form EE-EAes
Missing / incomplete information
![Page 5: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/5.jpg)
5
Missing
information
Form EE-EAes
Missing / incomplete information
![Page 6: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/6.jpg)
6
Misleading / confusing information Form EE-EA
Should be “no”
if there is no
previous audit
![Page 7: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/7.jpg)
7
Form EE5
Misleading / confusing information
Form EE-EAes Part 2
Not consistent
![Page 8: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/8.jpg)
8
Should provide
estimation
even measured
figure not
available
Form EE-EAes
Missing / incomplete information
![Page 9: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/9.jpg)
9
Missing
information
Form EE-EAes
Missing / incomplete information
![Page 10: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/10.jpg)
10
Misleading / confusing information Form EE-EAes
Should have
explanation in the
EA report
e.g. bldg wholly
occupied by the
bldg owner
![Page 11: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/11.jpg)
11
Misleading / confusing information Form EE-EAes
Misleading information
• No energy
consumption under
bldg owners’
account
very unlikely
![Page 12: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/12.jpg)
12
• Common area in
commercial portion
• BSI owned by building
owner CBSI
Residential area
BSI not solely
serving
commercial
portion EA
not applicable
BSI if owned by
individual tenant
not CBSI
Composite Building (Typical)
![Page 13: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/13.jpg)
13
BSI if
owned by
tenant
not CBSI
BSI if owned
by tenant
not CBSI
• Common area in commercial portion
• BSI owned by building owner CBSI
BSI not solely serving
commercial portion EA N/A
Composite Building (Typical)
![Page 14: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/14.jpg)
14
Composite Building Applying for Exemption (Case 1)
BSI owned by
building owner
CBSI
Residential
area
BSI not solely serving
commercial portion
BSI owned
by tenant
not CBSI
G/F 1/F
![Page 15: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/15.jpg)
15
Composite Building Applying for Exemption (Case 1)
BSI not solely serving
commercial portion
BSI owned
by tenant
not CBSI
BSI owned by
building
owner
CBSI
2/F 3/F
Exemption will lapse if
≤ 195 m2; and/or
≤ 100A, 1-phase
are no longer met
![Page 16: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/16.jpg)
16
Composite Building Applying for Exemption (Case 2)
BSI owned
by tenant
not CBSI
Entrance to shop
unit on 1/F
G.I.C.
G.I.C.
Residential
area
![Page 17: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/17.jpg)
17
• Shop unit occupied by one tenant
• BSI owned by tenant
• not CBSI
Composite Building Applying for Exemption (Case 2)
![Page 18: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/18.jpg)
18
Chillers for shop units
Composite Building Applying for Exemption (Case 2)
∴ Case rejected
![Page 19: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/19.jpg)
19
Display of EA Forms
Acceptable cases
![Page 20: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/20.jpg)
20
At information centre near main entrance
Display of EA Forms
Acceptable cases
![Page 21: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/21.jpg)
21
Display of EA Forms
Not acceptable cases
Inside private office LCD display
![Page 22: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/22.jpg)
Applicability of EA Requirement
(I)
Q: FOC obtained for a commercial building
May apply for exemption from EA?
22
A: No, EA is still required even FOC
obtained.
![Page 23: Energy Audit - EMSD (EA).pdf · Energy Audit 1 1. Common Irregularities Found in EA Submission 2. Composite Buildings 3. Display of EA Form 4. Applicability of EA Requirement](https://reader030.fdocuments.net/reader030/viewer/2022021510/5ab49c557f8b9ab7638bf337/html5/thumbnails/23.jpg)
Applicability of EA Requirement
(II)
Q: Commercial area (shopping centre) left unoccupied and
not in operation for several years since the granting of
OP. Is EA applicable?
23
A:
• Apply for exemption for the BSIs from EA requirement
[S25(1)] for operational reasons [S25(3)]
• Approval of exemption considered case by case
• Exemption will lapse once the commercial area is put in
operation (occupied)