ENERGEX Armored Cables Type MC and AC OVER 180 YEARS OF EXPERIENCE 866-663-9267 www.nexansenergy.com LEAD FREE RoHS ®

Transcript of ENERGEX Armored Cables - Armored Cables ... cable size and type, and the selection of methods of...

Page 1: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

ENERGEX Armored CablesType MC and AC

O V E R 1 8 0 Y E A R S O F E X P E R I E N C E

8 6 6 - 6 6 3 - 9 2 6 7w w w . n e x a n s e n e r g y . c o m

LEAD FREERoHS

®

Page 2: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92671

Type MC and Type AC

ENERGEX® Armored Cables

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Applications Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

ENERGEX® MC 120 Aluminum Armored Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

ENERGEX® MC 120 Steel Armored Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

ENERGEX® MC 277 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

ENERGEX® MC 120 Aluminum Armored with PVC Jacket Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

ENERGEX® MC Mega Neutral Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

ENERGEX® MC Ground Plus Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

ENERGEX® MC Multi Conductor Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

ENERGEX® AC Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

ENERGEX® AC Health Care Facilities Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Page 3: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92672

Nexans is one of the largest wire and cable manufacturers in the world, and in North America . In North America we manufacture in locations across the United States and Canada . We design and produce a wide range of cables used in power, industrial, construction and communication applications .

With more than nine decades of experience as a leader in the industrial and power cable markets, Nexans is contracted by heavy industry and utilities world wide to provide turnkey solutions for the bulk transmission of power – from generating station through the transmission and distribution systems to commercial, residential and industrial areas .

This catalogue has been prepared for the convenience of those using electrical conductors in industrial, commercial and residential applications . The information included in the many tabulations will be of particular value to the architect, engineer, electrician, and layperson alike .

Introduction

Although we have listed the types of wires and cables suitable for most conditions, we are equipped to manufacture other types to suit special needs . We would be pleased to recommend the most suitable construction for any special condition that you may encounter .

The determination of the correct cable size and type, and the selection of methods of installation suitable for the type and location of particular circuits, should be made in accordance with local regulations . Any questions in this respect should be directed primarily to the local Electrical Inspection Authority .

We are pleased to note that all the cables in this catalog are LEAD FREE and RoHS compliant .

“Lead Free” indicates that the Nexans cable components have less than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of hazardous substances) regulations and below the level requiring labeling by California proposition #65 .

Page 4: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92673

Applications Guide

Nexans ENERGEX® MC and ENERGEX® AC series of armored cables are used in a wide variety of applications in accordance with various sections of the National Electric Code (NEC) . For ease of use, the following table summarizes typical application environments .

NEC Article 330 and 518

517

330

330 and 645

250.118(10), 517 and 645

300.22(C)

320 and 330

330

230.43, 330.10, 511.7(A)(1), 513.7(A), 514.7, 515.7(A), and 516.7(A)

Typical Application

Typical places of assembly for 100 or more peopleCommercial and Industrial

Health care facilities, such as hospitals, medical offices and nursing homes

Installations where multi-conductor runs are called for

Applications where computer and other business equipment, as well as electronic discharge lighting, are present

Applications where a redundant ground is required

Applications where environmental air handling spaces are present

Applications in hotels and multi-family dwellings where branch circuits are present

Factory installations, air conditioners, with wet and oily conditions

Direct buried applications and in hazardous locations up to Class I, Div. 2

ENERGEX® Type MC

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX®MC120,Aluminum,PVCJacket• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX®MCMegaNeutral

• ENERGEX® MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored• ENERGEX®MCMegaNeutral• ENERGEX® MC Multi-Conductor• ENERGEX®MCGroundPlus

• ENERGEX® MC 120 Steel Armored• ENERGEX® MC 120 and 277, Aluminum Armored

• ENERGEX® MC 120 Aluminum Armored with PVCJacket

• ENERGEX® MC 120 Aluminum Armored with PVCJacket

ENERGEX® Type AC

• ENERGEX® HCF

• ENERGEX® HCF

• ENERGEX® AC• ENERGEX® HCF

• ENERGEX® AC

Page 5: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92674

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC Article 330 . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY . Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid soft bare annealed copper per ASTM B3 .Stranded soft bare annealed copper per ASTM B3 and ASTM B787 for sizes #14 to #8 AWG and ASTM B8 for sizes #6 AWG and larger .

Insulation: Colored PVC/Nylon type THHN in accordance with UL 83, flame retardant, meeting UL VW-1 flame test for sizes #14 to #1 AWG . Colored cross-linked polyethylene type XHHW-2 per UL 44 for sizes 1/0 AWG and larger .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation (XHHW-2 for 1/0 and larger) .

Assembly: conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE) .

Specifications

•MeetsUL44:ThermosetInsulatedWires and Cables (#1/0 AWG and larger)

•MeetsUL83:ThermoplasticInsulatedWires and Cables (#14 to 1 AWG)

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to #2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ULlistedforuseinClassI,Div.2perNEC 501 .10(B)(6), Class II, Div .2 per NEC 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanical&physical

properties•Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulationonsizes#14-#1

AWG•Conductorsizeslargerthan#1/0

AWG

Page 6: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92675

Part Number of Conductor Ground Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Size Color Code over Armor Cable Weight

AWG AWG inches mm lb/kft kg/km amps

250 ft coil 1000 ft reel 618777 642876 2 14(1) 14(1) white/black 0.446 11.33 87 129 15618785 642884 3 14(1) 14(1) white/black/red 0.473 12.01 106 158 15670050 670051 4 14(1) 14(1) white/black/red/blue 0.505 12.83 123 183 15*618793 635045 2 12(1) 12(1) white/black 0.483 12.27 118 176 20618801 635052 3 12(1) 12(1) white/black/red 0.514 13.06 145 216 20618819 635060 4 12(1) 12(1) white/black/red/blue 0.550 13.97 173 257 20*618827 636977 2 10(1) 10(1) white/black 0.550 13.97 164 244 30618835 636985 3 10(1) 10(1) white/black/red 0.588 14.94 207 308 30618843 640177 4 10(1) 10(1) white/black/red/blue 0.643 16.33 244 363 30*642892 642900 2 12(19) 12(19) white/black 0.483 12.27 118 176 20644997 645002 3 12(19) 12(19) white/black/red 0.514 13.06 145 216 20645010 645028 4 12(19) 12(19) white/black/red/blue 0.550 13.97 173 257 20*672972 672980 2 10(19) 10(19) white/black 0.550 13.97 164 244 30672576 672584 3 10(19) 10(19) white/black/red 0.588 14.94 207 308 30670017 672634 4 10(19) 10(19) white/black/red/blue 0.643 16.33 244 363 30*200 ft reel 500 ft reel 670085 670190 2 8(19) 10(19) white/black 0.656 16.66 229 341 55670086 642918 3 8(19) 10(19) white/black/red 0.713 18.11 300 446 55670087 670208 4 8(19) 10(19) white/black/red/blue 0.777 19.74 371 552 55*125 ft reel 500 ft reel 670088 670182 2 6(19) 8(19) white/black 0.742 18.85 330 491 75670089 643445 3 6(19) 8(19) white/black/red 0.811 20.60 435 647 75670090 670174 4 6(19) 8(19) white/black/red/blue 0.886 22.50 541 805 75*680005 670539 3 4(19) 8(19) white/black/red 0.941 23.90 624 929 95——— 673830 4 4(19) 8(19) white/black/red/blue 1.056 26.82 855 1272 95*——— 673848 3 3(19) 6(19) white/black/red 1.016 25.81 795 1183 110——— 670237 4 3(19) 6(19) white/black/red/blue 1.129 28.68 1049 1561 110*——— 670521 3 2(19) 6(19) white/black/red 1.091 27.71 966 1438 130——— 673871 4 2(19) 6(19) white/black/red/blue 1.201 30.51 1245 1853 130*——— 670184 3 1(19) 6(19) white/black/red 1.203 30.56 1427 2124 150——— 670183 3 1/0(19) 6(19) white/black/red 1.272 32.31 1585 2359 170

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® MC 120

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 7: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92676

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation .

Assembly: conductors are cabled with grounding wire . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking galvanized steel tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to #2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Steel Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div .2 per NEC 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90oCdry•Excellentmechanical&physical

properties•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation

Page 8: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92677

Part Number of Conductor Ground Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Size Color Code over Armor Cable Weight AWG AWG inches mm lb/kft kg/km amps250 ft coil 1000 ft reel 670033 670040 2 14(1) 14(1) white/black 0.441 11.20 144 214 15670035 —- 3 14(1) 14(1) white/black/red 0.468 11.89 167 249 15670036 670043 4 14(1) 14(1) white/black/red/blue 0.499 12.67 189 281 15*670011 670044 2 12(1) 12(1) white/black 0.477 12.12 179 266 20670012 670045 3 12(1) 12(1) white/black/red 0.509 12.93 213 317 20670013 670046 4 12(1) 12(1) white/black/red/blue 0.544 13.82 247 368 20*670014 670047 2 10(1) 10(1) white/black 0.544 13.82 238 354 30670015 670048 3 10(1) 10(1) white/black/red 0.584 14.83 287 427 30670016 670049 4 10(1) 10(1) white/black/red/blue 0.628 15.95 333 496 30*——— ——— 2 12(19) 12(19) white/black 0.483 12.27 215 320 20——— ——— 3 12(19) 12(19) white/black/red 0.514 13.06 252 375 20——— ——— 4 12(19) 12(19) white/black/red/blue 0.550 13.97 290 432 20*——— ——— 2 10(19) 10(19) white/black 0.550 13.97 164 244 30——— ——— 3 10(19) 10(19) white/black/red 0.588 14.94 207 308 30——— ——— 4 10(19) 10(19) white/black/red/blue 0.643 16.33 244 363 30*——— ——— 3 8(19) 10(19) white/black/red 0.713 18.11 300 446 55——— ——— 3 6(19) 8(19) white/black/red 0.811 20.60 435 647 75

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® MC 120

Steel Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 9: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92678

ENERGEX® MC 277

Applications

ENERGEX® MC 277 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC Article 330 . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans MC 277 cable is Lead Free and RoHS compliant .

Construction

Conductor: Solid soft bare, annealed copper per ASTM B3 . Stranded soft bare annealed copper per ASTM B3 and ASTM B787 for sizes #14 to #8 AWG and ASTM B8 for sizes #6 AWG and larger .

Insulation: Colored PVC/Nylon type THHN per UL 83, flame retardant, meeting UL VW-1 flame test .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation .

Assembly: conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE) .

Specifications

•MeetsUL83:ThermoplasticInsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to #2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Aluminum Armored MC Cable277 Volt and Special Color Codes UL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div . 2 per NEC 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanical&physical

properties•Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation

Page 10: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-92679

Part Number of Conductor Ground Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Size Color Code over Armor Cable Weight

AWG AWG inches mm lb/kft kg/km amps

250 ft coil 1000 ft reel 654269 652537 2 12(1) 12(1) brown/gray 0.483 12.27 118 176 20654251 671917 2 12(1) 12(1) orange/gray 0.483 12.27 118 176 20654244 671925 2 12(1) 12(1) yellow/gray 0.483 12.27 118 176 20672956 672964 2 12(1) 12(1) purple/gray 0.483 12.27 118 176 20676205 676213 2 12 (1) 12 (1) brown/yellow 0.483 12.27 118 176 20652263 670570 2 12 (1) 12 (1) red/white 0.483 12.27 118 176 20652271 670554 2 12 (1) 12 (1) blue/white 0.483 12.27 118 176 20669762 669770 3 12(1) 12(1) brown/orange/gray 0.514 13.06 145 216 20674937 674945 3 12(1) 12(1) brown/purple/gray 0.514 13.06 145 216 20674952 674960 3 12(1) 12(1) purple/yellow/gray 0.514 13.06 145 216 20674978 674986 3 12(1) 12(1) brown/yellow/gray 0.514 13.06 145 216 20675991 676006 3 12(1) 12(1) red/blue/white 0.514 13.06 145 216 20676015 676031 3 12(1) 12(1) black/blue/white 0.514 13.06 145 216 20671891 669812 4 12(1) 12(1) brown/orange/yellow/gray 0.550 13.97 173 257 20*676049 676056 4 12(1) 12(1) brown/purple/yellow/gray 0.550 13.97 173 257 20*672915 672923 2 10(1) 10(1) brown/gray 0.550 13.97 164 244 30672931 672949 3 10(1) 10(1) brown/orange/gray 0.588 14.94 207 308 30672592 672600 4 10(1) 10(1) brown/orange/yellow/gray 0.643 16.33 244 363 30*——— ——— 2 12(19) 12(19) brown/gray 0.483 12.27 118 176 20——— ——— 3 12(19) 12(19) brown/orange/gray 0.514 13.06 145 216 20——— ——— 4 12(19) 12(19) brown/orange/yellow/gray 0.550 13.97 173 257 20*——— ——— 2 10(19) 10(19) brown/gray 0.550 13.97 164 244 30——— ——— 3 10(19) 10(19) brown/orange/gray 0.588 14.94 207 308 30——— ——— 4 10(19) 10(19) brown/orange/yellow/gray 0.643 16.33 244 363 30*500 ft reel 1000 ft reel 642918 ——— 3 8(19) 10(19) brown/orange/gray 0.713 18.11 300 446 55643445 ——— 3 6(19) 8(19) brown/orange/gray 0.811 20.60 435 647 75

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (gray) conductor is a grounded phase conductor (neutral) .

ENERGEX® MC 277

Aluminum Armored MC Cable277 Volt and Special Color CodesUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 11: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926710

ENERGEX® MC 120

Applications

ENERGEX® MC 120 cables may be used in standard commercial and industrial power, control, and lighting circuits . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) with the jacket removed . The cables may also be installed in direct burial applications .

Nexans MC 120 cable is Lead Free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation .

Assembly: conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Jacket: Black PVC jacket .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Aluminum Armored, PVC Jacketed MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div . 2 per NEC 502 .10(B)(1) and Class III, Div . 1 & 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Suitablefordirectburial•Excellentmechanical&physical

properties•Lightweightaluminumarmor•LeadFree Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHW-2insulation

Page 12: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926711

Number of Conductor Ground Circuit Conductor Nominal Diameter Nominal Diameter Approximate Net Ampacity Conductors Size Size Color Code over Armor over Jacket Cable Weight

AWG AWG inches mm inches mm lb/kft kg/km amps

2 14(1) 14(1) white/black 0.446 11.33 0.550 13.97 147 219 15 3 14(1) 14(1) white/black/red 0.473 12.01 0.578 14.68 166 247 15 2 12(1) 12(1) white/black 0.483 12.27 0.588 14.94 183 272 20 3 12(1) 12(1) white/black/red 0.514 13.06 0.619 15.72 210 313 20 4 12(1) 12(1) white/black/red/blue 0.550 13.97 0.655 16.64 238 354 20* 2 10(1) 10(1) white/black 0.550 13.97 0.655 16.64 239 356 30 3 10(1) 10(1) white/black/red 0.568 14.94 0.693 17.60 283 421 30 4 10(1) 10(1) white/black/red/blue 0.643 16.33 0.748 19.00 319 475 30* 2 8(19) 10(1) white/black 0.656 16.66 0.761 19.33 309 460 55 3 8(19) 10(1) white/black/red 0.713 18.11 0.818 20.78 380 566 55 4 8(19) 10(1) white/black/red/blue 0.777 19.74 0.882 22.40 451 671 55* 2 6(19) 8(19) white/black 0.742 18.85 0.847 21.51 410 610 75 3 6(19) 8(19) white/black/red 0.811 20.60 0.916 23.27 515 766 75 4 6(19) 8(19) white/black/red/blue 0.886 22.00 0.991 25.17 612 911 75* 3 4(19) 8(19) white/black/red 0.941 23.90 1.046 26.57 714 1063 95 4 4(19) 8(19) white/black/red/blue 1.056 26.82 1.161 29.49 945 1406 95* 3 2(19) 6(19) white/black/red 1.091 25.88 1.196 30.38 1086 1616 130 4 2(19) 6(19) white/black/red/blue 1.201 30.51 1.306 33.17 1345 2002 130*

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® MC 120

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 13: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926712

Applications

ENERGEX® MC Mega Neutral cables are for use in applications where increased neutral capacity is required due to non-linear switching loads which can cause additive harmonic currents to be present on the neutral conductors . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . It is also suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans MC Mega Neutral Cable is Lead Free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Neutral Conductor: bare copper, with white THHN insulation and colored stripe where indicated . Cable has either one neutral per phase conductor or one over-sized neutral per two phase conductors .

Ground Wire(s): bare copper, sized in accordance with NEC and UL, one with green THHN insulation, one with green THHN insulation with a yellow stripe (in cables with two grounds) .

Assembly: conductors are cabled with neutrals and grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Specifications

•MeetsUL83:ThermoplasticInsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

ENERGEX® MC Mega Neutral

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div . 2 per NEC 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHWinsulation

Page 14: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926713

Part Number of Conductor Neutral Ground Circuit Conductor White Neutral Nominal Diameter Approximate Net Ampacity* Number Power Size Size Size Color Code Stripe Color over Jacket Cable Weight

Conductors

AWG AWG AWG inches mm lb/kft kg/km amps250 ft coil 1000 ft reel 671628 671602 2 12(1) 2x12(1) 2x12(1) black/red black/red 0.515 13.08 120 179 20671636 671586 3 12(1) 3x12(1) 2x12(1) black/red/blue black/red/blue 0.528 13.41 163 243 20——— ——— 4 12(1) 3x12(1) 2x12(1) black/red/pink/tan none/pink/tan 0.549 13.94 191 284 20——— ——— 2 10(1) 2x10(1) 2x10(1) black/red black/red 0.603 15.32 226 336 30675413 675405 3 10(1) 3x10(1) 2x10(1) black/red/blue black/red 0.655 16.64 300 446 30

Oversize Neutral Conductor (ONC)

Part Number of Conductor Neutral Ground Circuit Conductor White Neutral Nominal Diameter Approximate Net Ampacity* Number Power Size Size Size Color Code Stripe Color over Jacket Cable Weight

Conductors

AWG AWG AWG inches mm lb/kft kg/km amps250 ft coil 1000 ft reel——— 672097 1 12(1) 10(1) 12(1) black nostripe 0.515 13.08 120 179 20——— 671644 2 12(1) 10(1) 12(1) black/red nostripe 0.528 13.41 163 243 20——— 671578 3 12(1) 10(1) 12(1) black/red/blue nostripe 0.549 13.94 191 284 20——— 671651 3 12(1) 8(19) 12(1) black/red/blue nostripe 0.603 15.32 226 336 20——— 672212 4 12(1) 2x10(1) 2x12(1) black/red/blue/pink none/pink 0.655 16.64 300 446 20——— 670588 2 10(1) 8(19) 10(1) black/red nostripe 0.595 15.11 215 320 30——— 670596 3 10(1) 6(19) 10(1) black/red/blue nostripe 0.575 14.61 320 476 30——— 674911 4 10(1) 2x8(19) 2x10(1) black/red/blue/pink none/pink 0.790 20.07 400 595 30

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*If there are more than three current carrying conductors ampacity must be derated as shown in NEC Table 310 .15(B)(2)(a) .

ENERGEX® MC Mega Neutral

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Neutral Per Leg (NPL)

Page 15: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926714

ENERGEX® MC Ground Plus

Applications

ENERGEX® MC Ground Plus cables are for use in applications where isolated , dedicated or redundant ground is required . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are also suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans MC Ground Plus cable is Lead Free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Ground Wires: bare copper, sized in accordance with NEC and UL, one with green THHN insulation, one with green THHN insulation with a yellow stripe .

Assembly: conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Aluminum Armored Isolated Ground MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div . 2 per NEC 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHWinsulation

Page 16: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926715

Part Number of Conductor Ground Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Size Color Code over Armor Cable Weight

AWG AWG inches mm lb/kft kg/km amps

250 ft coil 1000 ft reel——— ——— 2 14(1) 2x14(1) white/black 0.475 12.07 106 158 15——— ——— 3 14(1) 2x14(1) white/black/red 0.485 12.32 123 183 15——— ——— 4 14(1) 2x14(1) white/black/red/blue 0.525 13.34 140 208 15*671818 671826 2 12(1) 2x12(1) white/black 0.514 13.06 145 216 20671834 671859 3 12(1) 2x12(1) white/black/red 0.550 13.97 173 257 20——— ——— 4 12(1) 2x12(1) white/black/red/blue 0.583 14.81 201 299 20*——— ——— 2 10(1) 2x10(1) white/black 0.580 13.97 207 308 30——— ——— 3 10(1) 2x10(1) white/black/red 0.620 15.75 244 363 30675447 675439 4 10(1) 2x10(1) white/black/red/blue 0.675 17.15 281 418 30*——— ——— 2 8(19) 2x10(1) white/black 0.660 16.76 300 446 55——— ——— 3 8(19) 2x10(1) white/black/red 0.750 19.05 371 552 55——— ——— 4 8(19) 2x10(1) white/black/red/blue 0.825 20.96 442 658 55*——— ——— 2 6(19) 2x8(19) white/black 0.822 20.88 435 647 75——— ——— 3 6(19) 2x8(19) white/black/red 0.900 22.86 541 805 75——— ——— 4 6(19) 2x8(19) white/black/red/blue 0.977 24.82 647 963 75*

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® MC Ground Plus

Aluminum Armored Isolated Ground MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 17: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926716

ENERGEX® MC Multi Conductor

Applications

ENERGEX® MC Multi Conductor cables are designed for applications that require six or more conductors . They may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230 .43, 300 .22(C), 330, 396, 518, 520, 530 and 645 . These cables may be installed in approved raceways and as open runs of cable on a messenger . They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans MC Multi Conductor cables are lead free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation .

Assembly: conductors are cabled with grounding wires . A marker tape/core protection tape combination assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: NEXANS TYPE MC 600 VOLT FOR CT USE (SIzE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

Color Code:(tan is stripe color)6 conductor: black, red, white, black/tan, red/tan, white/tan8 conductor: black, red, white, blue, black/tan, red/tan, white/tan, blue/tan

Specifications

•MeetsUL83:Thermoplastic-InsulatedWires and Cables

•TestedtoUL1479:FireTestsofThrough-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)

•MeetsUL1569:MetalCladCables•MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeMCperNECArticle330

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Product features

•CablesareULlistedasTypeMC,600 V

•ULlistedinsulatedconductors•FireWallPenetrationrated

depending on type of installation and fire-stop system used

•ULlistedforuseincabletraysperNEC 330 .10(A)(6)

•ForuseinClassI,Div.2perNEC501 .10(B)(6), Class II, Div . 2 per NEC 502 .10(B)(1) and Class III, Div . 1 and 2 per NEC 503 .10(A) and (B) with approved termination fittings .

•Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts•XHHWinsulation

Page 18: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926717

Part Number of Conductor Ground Nominal Diameter Approximate Net Ampacity* Number Conductors Size Size over Armor Cable Weight

AWG AWG inches mm lb/kft kg/km amps

1000 ft reel 671669 6 12 (1) 12 (1) 0 .570 14 .48 225 335 20 671677 8 12 (1) 12 (1) 0 .645 16 .38 290 432 20 ——— 10 12 (1) 12 (1) 0 .700 17 .78 320 476 20 ——— 12 12 (1) 12 (1) 0 .750 19 .05 350 521 20 ——— 14 12 (1) 12 (1) 0 .800 20 .32 410 610 20 ——— 16 12 (1) 12 (1) 0 .825 20 .96 465 692 20 ——— 18 12 (1) 12 (1) 0 .835 21 .21 475 707 20 ——— 20 12 (1) 12 (1) 0 .870 22 .10 565 841 20 ——— 24 12 (1) 12 (1) 0 .950 24 .13 650 967 20 673707 6 10 (1) 10 (1) 0 .675 17 .15 340 506 30 673699 8 10 (1) 10 (1) 0 .760 19 .30 390 580 30 ——— 10 10 (1) 10 (1) 0 .825 20 .96 470 699 30 ——— 12 10 (1) 10 (1) 0 .880 22 .35 560 833 30 ——— 14 10 (1) 10 (1) 0 .940 23 .88 635 945 30 ——— 16 10 (1) 10 (1) 0 .980 24 .89 730 1086 30 ——— 18 10 (1) 10 (1) 0 .990 25 .15 805 1198 30 ——— 20 10 (1) 10 (1) 1 .025 26 .04 915 1362 30 ——— 24 10 (1) 10 (1) 1 .130 28 .70 1130 1682 30

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*For derating ampacity of multi-conductor cables see NEC Table 310 .15(B)(2)(a) .

ENERGEX® MC Multi Conductor

Aluminum Armored MC CableUL Type MC, 600 V, 90°C dry rated - Lead Free Copper Conductors

Page 19: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926718

ENERGEX® AC

Applications

ENERGEX® AC cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They are suitable for installations in accordance to NEC Article 320 . These cables may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans ACTHH cable is lead free and RoHS compliant .

Aluminum Armored AC CableUL Type ACTHH, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Bond Wire: longitudinal aluminum bond wire in contact with armor .

Assembly: conductors are individually paper wrapped and cabled with a marker tape/core protection tape combination which assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOT TO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFG DATE)

Specifications

•MeetsUL4:ArmoredCable•MeetsUL83:Thermoplastic-Insulated

Wires and Cables •MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•MeetsUL2556:WireandCable Test Methods

•DesignatedTypeACperNECArticle320

Product features

•CablesareULlistedasTypeACTHH,600 V

•ULlistedinsulatedconductors•ULlistedforuseincabletraysper

NEC 320 .10(2) •Temperatureratingof90oC dry •Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts

Page 20: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926719

Part Number of Conductor Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Color Code over Armor Cable Weight

AWG inches mm lb/kft kg/km amps

250 ft coil 1000 ft reel 675470 675462 2 14(1) white/black 0.475 12.07 89 132 15 675504 675496 3 14(1) white/black/red 0.495 12.57 109 162 15 675561 675553 2 12(1) white/black 0.502 12.75 109 162 20 675595 675587 3 12(1) white/black/red 0.524 13.31 137 204 20 675629 675611 4 12(1) white/black/red/blue 0.560 14.22 168 250 20* 675652 675645 2 10(1) white/black 0.564 14.33 146 217 30 675686 675678 3 10(1) white/black/red 0.591 15.01 190 283 30 250 ft coil 500 ft reel 675710 675702 4 10(1) white/black/red/blue 0.635 16.13 236 351 30* ——— 676437 3 8(19) white/black/red 0.635 16.13 246 366 55 ——— 676445 3 6(19) white/black/red 0.737 18.72 357 531 75

Bend Radius: 7 × overall diameter installed

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® AC

Aluminum Armored AC CableUL Type ACTHH, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Page 21: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926720

Applications

ENERGEX® AC cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction . They may be used in patient areas of hospitals, out-patient centers and medical and dental offices . They are not permitted where hazardous anesthetizing is performed . They may also be used in applications which require AC cable with a redundant ground in accordance with NEC Article 250 .118(8) . They are suitable for installations in accordance to NEC Article 320 . These cables may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300 .22(C) ONLY .

Nexans AC HCF cable is lead free and RoHS compliant .

Construction

Conductor: bare, annealed copper conforming to ASTM B3 .

Insulation: PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test .

Bond Wire: longitudinal aluminum bond wire in contact with armor .

Ground Wire: bare copper, sized in accordance with NEC and UL, with green THHN insulation .

Assembly: conductors are individually paper wrapped and cabled with a marker tape/core protection tape combination which assembles the core in an essentially round configuration .

Armor: interlocking aluminum tape armor applied directly over the core .

Marker Tape Print: ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOT TO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFG DATE)

Specifications

•MeetsUL4:ArmoredCable•MeetsUL83:Thermoplastic-Insulated

Wires and Cables •MeetsUL1581:ReferenceStandard

for Electrical Wires, Cables, and Flexible Cords

•DesignatedTypeACperNECArticle320

•MeetsUL2556:WireandCable Test Methods

•MeetsNEC:250.94,250.118(8),300 .22(C), 320, 517 .13 and 645

ENERGEX® AC HCF

Aluminum Armored Health Care Facilities CableUL Type AC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Product features

•CablesareULlistedasTypeAC,600 V

•ULlistedinsulatedconductors•ULlistedforuseincabletraysper

NEC 320 .10(2) •Temperatureratingof90°Cdry•Excellentmechanicalandphysical

properties •Lightweightaluminumarmor•LeadFree

Options

The following constructions can be provided on special orders:•Specialconductorcounts

Page 22: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926721

Part Number of Conductor Ground Circuit Conductor Nominal Diameter Approximate Net Ampacity Number Conductors Size Size Color Code over Armor Cable Weight

AWG AWG inches mm lb/kft kg/km amps

250 ft coil 1000 ft reel 671560 672170 2 12(1) 12(1) white/black 0.487 12.37 133 198 20672188 672196 3 12(1) 12(1) white/black/red 0.521 13.23 157 234 20673426 673434 4 12(1) 12(1) white/black/red/blue 0.547 13.89 187 278 20*673715 673723 2 10(1) 10(1) white/black 0.503 12.78 181 269 30673731 673749 3 10(1) 10(1) white/black/red 0.537 13.64 226 336 30673756 673764 4 10(1) 10(1) white/black/red/blue 0.585 14.86 279 415 30*——— 676460 2 12(19) 12(19) white/black 0.487 12.37 133 198 20676478 676486 3 12(19) 12(19) white/black/red 0.521 13.23 157 234 20

Bend Radius: 7 × overall diameter

Notes:Dimensions and weights shown are nominal values . They are subject to standard industry tolerances .AmpacityinaccordancewithTable310.16ofNECforcopperconductorsat30°Cambienttemperatures.*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral) .

ENERGEX® AC HCF

Aluminum Armored Health Care Facilities AC CableUL Type AC, 600 V, 90°C dry rated - Lead FreeCopper Conductors

Page 23: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

1-866-663-926722

WARNING

FLAMMABLENon-metallic covering of electrical cables will burn and under certain conditions may transmit fire when ignited .

TOXICBurning non-metallic coverings may emit acid gases, which are highly toxic, and may generate dense smoke .

CORROSIVEEmission of acid gases may corrode metal in the vicinity, such as sensitive instruments and reinforcing rod in concrete .

NOTICE

Nexans has endeavoured to ensure the accuracy of the data in this publication, however we cannot be liable for the consequences of errors or omissions . All data is subject to change without notice . The installer and / or user assumes all liability for the consequences of the installation and / or use of any of our products in contravention of any applicable law, regulation or code .

Page 24: ENERGEX Armored Cables -   Armored Cables ... cable size and type, and the selection of methods of installation ... AWG AWG inches mm lb/kft kg/km amps

U.S. Sales Office:25 Oakland Avenue, Chester, New York 10918

Tel:1-866-663-9267/ (845) 469-2141Fax: (845) 469-9935

International Sales Office:140 Allstate Parkway

Markham, Ontario, Canada L3R 0Z7Tel: (905) 944-4300 / Fax (905) 944-4330

LEAD FREERoHS

w w w . n e x a n s e n e r g y. c o m

Prin

ted

inC

anad

a09

/200

8