ABB industrial drives Application guide ACS880-01 drives and ACS880-04 drive modules Common DC systems

Transcript of EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program...

Page 1: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

ABB industrial drives

Application guideACS880-01 drives and ACS880-04 drive modulesCommon DC systems

Page 2: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

List of related manuals

You can find manuals and other product documents in PDF format on the Internet. See section Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative.

Drive hardware manuals and guides Code (English)

ACS880-01 hardware manual 3AUA0000078093

ACS880-01 quick installation guide for frames R1 to R3 3AUA0000085966

ACS880-01 quick installation guide for frames R4 and R5 3AUA0000099663

ACS880-01 quick installation guide for frames R6 to R9 3AUA0000099689

ACS880-01 assembly drawing for cable entry boxes of IP21 frames R5 to R9

3AUA0000119627

ACS880-04 drive modules (200 to 560 kW, 300 to 700 hp) hardware manual

3AUA0000128301

ACS880-04 drive modules (200 to 560 kW, 300 to 700 hp) quick installation guide

3AUA0000128301

ACS-AP assistant control panels user’s manual 3AUA0000085685

Drive firmware manuals and guides

ACS880 primary control program firmware manual 3AUA0000085967

Quick start-up guide for ACS880 drives with primary control program

3AUA0000098062

Option manuals and quides

ACS880-01 drives and ACS880-04 drive modules Common DC systems application guide

3AUA0000127818

Manuals and quick guides for I/O extension modules, fieldbus adapters, etc.

ACS880-04 manualsACS880-01 manuals

Page 3: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Application guide

ACS880-01 drives and ACS880-04 drive modulesCommon DC systems

3AUA0000127818 Rev BEN

EFFECTIVE: 2014-04-17

2014 ABB Oy. All Rights Reserved.

Table of contents

Page 4: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common
Page 5: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

5

Table of contents

List of related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1. Introduction to the manual

Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Contents of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Categorization by frame size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Quick planning guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2. Operation principle and hardware description

Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Operation basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Overview of the common DC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Overview diagram of the common DC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Benefits of the common DC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Challenges of the common DC system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Overview diagram of the drive main circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Charging circuit types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Type A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Type B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Brake chopper types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

3. Planning – basics

Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Defining the DC link duty cycle and key variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Defining the DC link duty cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18DC link duty cycle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19DC link key variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Selecting the drives which are connected to AC power line . . . . . . . . . . . . . . . . . . . . . . 21The selection rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Calculating the rectifier power capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Verifying the charging capacity of the common DC system . . . . . . . . . . . . . . . . . . . . 22

Checking the total charging resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Checking the peak AC current at charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Checking the charging energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Handling the surplus energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Defining the energy absorbing capacity of the common DC link . . . . . . . . . . . . . . . . 26

Defining the maximum DC link voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Selecting the brake choppers and resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Brake chopper selection formulas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Page 6: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

6

Brake resistor selection formulas - system with one brake chopper . . . . . . . . . . 28Brake resistor selection formulas - system with several brake choppers and resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4. Planning – additional instructions

Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Requirements for the AC input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Constructing the DC link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Selecting the fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Selecting the AC input fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Selecting the DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Phase loss protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Selecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33DC contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

DC link separation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Brake resistor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Connecting the Ready and Start enable signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Setting the drive parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

5. Technical data

Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Rectifier power capacity (Prec,ave and Prec,max) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Power correction factor (k) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Frames R1 to R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Frames R5 to R9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Frames R10 to R11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

DC contactors between the drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Frames R1 to R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Frames R5 to R9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Frames R10 to R11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Charging resistance values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Charging circuit Er values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43DC link capacitance values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Brake chopper power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44DC voltage limits of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Further information

Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Page 7: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Introduction to the manual 7

1

Introduction to the manual

Contents of this chapterThis chapter contains information on this manual and a quick guide for planning a common DC system.

ApplicabilityThis manual is applicable with the ACS880-01 drives and ACS880-04 drive modules.

Safety instructionsObey the safety instructions in the drive’s hardware manual.

Target audienceThis manual is written for people who plan common DC systems. We expect the reader to be a qualified electrical engineering professional.

Contents of the manualThe chapters in this manual are:• Introduction to the manual

• Operation principle and hardware description

• Planning – basics

• Planning – additional instructions

• Technical data.

Page 8: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

8 Introduction to the manual

Related documentsSee section List of related manuals on page 2.

Categorization by frame sizeSome information in this manual is only valid for certain drive frame sizes. Such information includes the frame size indication, for example, frame R1. The type designation label of the drive shows the frame size. The frame size for each drive type is given in the drive hardware manual.

Quick planning guide

No. Step

1. Define a duty cycle diagram for each motor (shaft power). Select the motors and drives as usual with the DriveSize PC tool by ABB. Do not consider the common DC system yet.

2. Define a DC link duty cycle for the common DC system, and define the key variables Pmot,ave, Pmot,max, Pgen,ave and Pgen,max.

See section Defining the DC link duty cycle and key variables on page 18.

3. Select the drives that you will connect to the AC power line.

See section Selecting the drives which are connected to AC power line on page 21.

4. Define the means to handle the surplus DC link energy (motor braking energy).

See Handling the surplus energy on page 25.

5. Design the construction of the common DC link.

See section Constructing the DC link on page 31.

6. Select the fuses and phase loss guards.

See section Selecting the fuses on page 32 and section Phase loss protection on page 33.

7. Examine the need for DC contactors. If needed, select them.

See section DC contactors on page 34.

8. Plan the interlocking and safety.

• See Connecting the Ready and Start enable signals on page 36.

• Consider the use of safety circuits (such as emergency stop or Safe torque off) or control signal interlocking for safe and reliable operation.

9. Select the measures necessary for the EMC. See section Electromagnetic Compatibility (EMC) on page 35.

10. Repeat all design steps to verify the design.

Page 9: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Introduction to the manual 9

Terms and abbreviations

Note: The symbols used in the equations and formulas are explained in the context of use.

Term / abbreviation

Description

AVR Automatic voltage regulator

EMC Electromagnetic compatibility

Motoring mode Motor operation mode in which the motor rotates the load and takes power from the drive DC link (normal operation).

Generating mode Motor operation mode in which the motor decelerates (brakes) the load and generates energy back to the drive DC link.

This effect is also seen when the load is held at a fixed speed, but the mechanical load is trying to “pull” the motor to a higher speed, sometimes referred to as overhauling. Overhauling loads return energy to the DC link as well.

Page 10: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

10 Introduction to the manual

Page 11: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Operation principle and hardware description 11

2

Operation principle and hardware description

Contents of this chapterThis chapter contains a description of a common DC system. It also describes the drive features which are relevant in a common DC system.

Page 12: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

12 Operation principle and hardware description

Operation basicsThe main circuit of the drive consists of a rectifier, a DC link and an inverter. The rectifier (input bridge) converts the alternating current and voltage to direct current and voltage for the DC link. The DC capacitors in the DC link smooth the ripple and form a steady energy and power supply for the inverter. The inverter converts the intermediate circuit DC power to AC power for the motor.

From a common DC system point of view, the motor has two main operation modes: the motoring mode and the generating mode. In the motoring mode, the motor rotates the machinery. The energy flows from the AC power line to the motor through the rectifier, DC link and the inverter. In the generating mode, the machinery rotates the motor. This is the case for example when a hoist motor of a crane lowers a load (overhauling load). To keep the rotation speed steady, the motor brakes. During the braking, the motor generates energy back to the inverter which then conveys the energy further to the DC link.

In the generating mode the DC capacitors are charged by the inverters and the DC link voltage starts to rise. To prevent an excessive voltage rise, the drive must convey the surplus energy away from the DC link. There are three options: to convey the energy to the AC power line, to a brake resistor or to another drive. For the first option you need to have a special type of drive in use, a regenerative drive. If you have an ordinary drive with a rectifier (diode input bridge), regeneration is not possible so only the two other options remain. If you connect a brake chopper and resistor to the DC link, you can dissipate the energy in the resistor as heat. If you connect the DC link of the drive to another drive, you can use the surplus energy for charging the DC capacitors of the other drive and use the energy to rotate its motor. This is a common DC system.

No. Description

1. AC power line

2. Rectifier (input bridge)

3. DC link including DC capacitors (a), its charging circuit (b) and brake chopper (c)

4. Inverter

5. Motor

L1

L2

L3

U

V

W

R-

UD

C+

R+

UD

C-

M~3 ~3

1 2 3 4 5

a

b

c

Page 13: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Operation principle and hardware description 13

Overview of the common DC systemIn a common DC system, you connect the DC links of several drives together in order to share their DC link energy storages. In addition to this basic configuration, there is a wide variety of additional choices with which you can affect the performance of the system. For example, in certain applications you can: • connect only one of the drives to the AC power line, and supply the other drives only

through the common DC link

• connect a shared brake chopper and resistor to the common DC link to absorb the occasional surplus energy pulses that you cannot use in the drives

• connect one regenerative drive to a common DC link to convey the surplus motor braking energy pulses to the AC power line instead of brake resistors

• supply the DC link from a separate DC source.

Overview diagram of the common DC system

The diagram below shows an example of a common DC system.

1

2

3

4 5

1 AC power line

2 Common DC link

3 Drive

4 Motor

5 Brake resistor

Page 14: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

14 Operation principle and hardware description

Benefits of the common DC system

Benefits of the common DC system:

• You can save energy by using the braking energy of one drive in the others - less energy needs to be taken from the AC power line.

• DC capacitors of all drives form a high-capacity energy storage that can absorb short braking pulses of individual drives without a need for a brake chopper and resistor.

• If you need brake choppers and resistors, they can be optimized for the whole system. You do not have to use the chopper of every drive.

• You do not necessarily need to connect every drive to the AC power line.

Challenges of the common DC system

Challenges of the common DC system:• You cannot operate any of the drives in the common DC system if one of the drives

connected to the AC power line has an active fault. See section Connecting the Ready and Start enable signals on page 36.

• If you have drives with different type of charging circuits in the system, and you want to connect them to AC power line, you must add extra contactors to the system and arrange their control: For power up and charging, you must disconnect the DC links of the drives which have different type of charging circuits. You can connect the DC links together only after charging. See sections Charging circuit types on page 15 and Charging resistance values on page 43.

• You must make sure that the load imbalance between the drives that are connected to the AC power line is as small as possible. There is always slightly unequal AC input current distribution due to differences in the input cables, chokes and input bridges’ forward bias characteristics. If the voltage reduction over the input cable, rectifier and chokes is not the same in all drives, more current will flow through the rectifier which has the lowest voltage reduction.

• You must make sure that the common DC system complies with the relevant regulations and directives. The compliance of individual drives does not guarantee or cover the compliance of the common DC system.

• If you supply the drives from a totally separate DC source, the DC source:

• must be capable of powering the drives when motoring,

• must be protected to prevent regeneration onto the DC from causing any damage, or from effecting the devices supplying the DC source (for example AVR systems on generators).

Page 15: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Operation principle and hardware description 15

Overview diagram of the drive main circuitThe overview diagrams below show the main circuits of the drive modules. The differences between the drive modules, in regards of the use of the drives in a common DC system, are the charging circuit and brake chopper designs.

Charging circuit types

Type A

Charging resistor is in the DC link (frame sizes R1 to R4).

Type B

Charging resistor is in parallel with the input bridge (frame sizes R5 and larger).

Brake chopper types

• Brake chopper is included as standard in frame sizes R1 to R4.

• Brake chopper is a factory-installed option for frame sizes R5 and larger (option +D150).

L1

L2

L3

U

V

W

R-

UD

C+

R+

UD

C-

L1

L2

L3

U

V

W

BR

-

UD

C+

R+

UD

C-

R1, …, R4

R5, …, R11

1

2

1

2

1 Charging resistor2 Brake chopper

Page 16: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

16 Operation principle and hardware description

Page 17: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 17

3

Planning – basics

Contents of this chapterThis chapter contains the basics of planning a common DC system.

See section Quick planning guide on page 8 for a summary of planning steps.

Page 18: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

18 Planning – basics

Defining the DC link duty cycle and key variables

Defining the DC link duty cycle

1. Define the DC link duty cycle for each drive. See section DC link duty cycle diagram on page 19. Use the duty cycle diagram of the motor shaft power and: • Add the inverter and motor losses during the motoring mode of the motor.

• Subtract the inverter and motor losses during the generating mode of the motor.

2. Sum the DC link duty cycle diagrams of the individual drives to one common DC link duty cycle diagram for the common DC system. See section DC link duty cycle diagram on page 19.

3. On basis of the common DC link duty cycle diagram, define the key variables Pmot,ave, Pmot,max, Pgen,ave and Pgen,max for the whole system. See section DC link key variables on page 19.

Inverter losses

Motor losses

Pm

Pmot

keff Efficiency factor (1/efficiency) to include drive and motor losses. If not known, value 1.25 can be used

n Motor shaft speed [rpm]Pdc DC link power

Pmot Power that the motor takes from the DC link

Pgen Power that the motor supplies to the DC link

Pm Motor mechanical shaft power

T Torque [Nm] on motor shaft

Pmot = keff × Pm

Pgen = keff

Pm

Pm [kW] = 9550

T × n

Page 19: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 19

DC link duty cycle diagram

DC link key variables

Pmot

tDrive a

Drive b

Drive c

Total

M

a b c

M M

~

Pdc

Pdc

Pdc

~

Pgen

Pdc

Pmot

t

Pgen

Pmot

t

Pgen

Pmot

t

Pgen

Pmot Pgen

M

M

M

a

b

c

~

~

Pbr

Pmot

Pgen

Prec

Page 20: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

20 Planning – basics

Symbol Name Information

Pmot Motoring power Power that the motors take from the common DC link

Pmot,ave Average motoring power

Average power that the motors take from the common DC link. See the duty cycle diagram of the common DC link. Note: For long cycles times, define Pmot,ave over the worst-case 3 minutes time window.

Pmot,max Maximum motoring power

Maximum power that the motors take from the common DC link. See the duty cycle diagram of the common DC link.

Pgen Generating power Power that the motors supply to the common DC link

Pgen,ave Average generating power

Average power that the motors feed to the common DC link when they are in generating mode (braking the load). See the duty cycle diagram of the common DC link. Note: If you will use the brake choppers of the drives in the system, determine Pgen,ave over the worst-case 30

seconds time window.

Pgen,max Maximum generating power

Maximum power that the motors feed to the common DC link when they are in generating mode (braking the load). See the duty cycle diagram of the common DC link.

Prec Rectifier power Power that the drive input bridges (rectifiers) feed to the common DC link. See section Selecting the drives which are connected to AC power line on page 21 for the calculation instructions.

Prec,ave Average rectifier power capacity

The drives that are connected to the AC power line can feed this average power to the common DC link.

Prec,max Maximum rectifier power capacity

The drives that are connected to the AC power line can feed this power to the common DC link at the maximum.

Pbr Braking power Surplus power that the brake resistors take from the common DC link. (Alternatively: Power that the drive feeds to the AC power line if a regenerative type of drive is in use.) See section Handling the surplus energy on page 25.

Pbr,cont Continuous braking power

Continuous braking power that the brake resistors take from the common DC link. The braking is continuous if the braking time exceeds 30 seconds.

Pbr,max Maximum braking power

Maximum braking power that the brake resistors take from the common DC link. Brake choppers withstand this braking power for 5 second within every minute.

Page 21: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 21

Selecting the drives which are connected to AC power lineThis section contains instructions for selecting the drives which are connected to the AC power line. However, you can also connect more drives, for example, for backup reasons.

The selection rules

1. At the very least, connect the drive with the highest power rating to the AC power line. Then the second largest, etc. until both the rectifier power capacity and charging capacity of the system are high enough.

2. Make sure that you connect only the allowed combination of drives to the AC power line. See section Power correction factor (k) on page 41.

3. Make sure that you have enough rectifier power capacity in the system. See subsection Calculating the rectifier power capacity on page 21.

4. Make sure that you have enough charging capacity in the system. See section Verifying the charging capacity of the common DC system on page 22.

Calculating the rectifier power capacity

The drives which you connect to the AC power line must supply the rectifier power for the common DC link, and further to the motors. Make sure that the system complies with these formulas:

Prec,ave > Pmot,ave

Prec,max > Pmot,max

Use these equations to calculate Prec,ave and Prec,max:

Prec,ave = Prec,ave1 + k × (Prec,ave2 + Prec,ave3 +….)

Prec,max = Prec,max1+ 0.9 × k × (Prec,max2 + Prec,max3 +….)

k Power correction factor for a common DC system. See section Power correction factor (k) on page 41.

Pmot,ave Average motoring power of the common DC system during the worst 3 minutes time window. See section DC link key variables on page 19.

Pmot,max Maximum motoring power of the common DC system. See section DC link key variables on page 19.

Prec, ave Average rectifier power capacity of the common DC system. See section DC link key variables on page 19.

Prec, ave1 Average rectifier power capacity of drive 1. Drive 1 has the highest power rating of the drives which are connected to AC power line. See section Rectifier power capacity (Prec,ave and Prec,max) on page 40.

Prec,ave2 Average rectifier power capacity of drive 2. Drive 2 has the second highest power rating of the drives which are connected to AC power line. See section Rectifier power capacity (Prec,ave and Prec,max) on page 40.

Prec, max Maximum rectifier power of the common DC system allowed for 10 s. See section DC link key variables on page 19.

Prec, max1 Maximum rectifier power capacity of drive 1. See section Rectifier power capacity (Prec,ave and Prec,max) on page 40.

Prec,max2 Maximum rectifier power capacity of drive 2. See section Rectifier power capacity (Prec,ave and Prec,max) on page 40.

Page 22: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

22 Planning – basics

Example 1

Common DC system: The DC links of three converters ACS880-01-11A0-5, 5.5 kW (frame size R1), ACS880-01-034A-5, 18.5 kW (frame size R3) and ACS880-01-034A-5, 18.5 kW (frame size R3) are connected together. The input terminals of the 5.5 kW converter are left unconnected.

Calculating the rectifier power capacity

According to the table, k = 0.9 when two converters of frame size R3 are connected to the AC power line, and Prec,ave becomes:

Prec,ave = 18.5 kW + (0.9 ×18.5 kW) = 35.15 kW

Example 2

Common DC system: The DC links of three converters ACS880-01-124A-5, 75 kW (frame size R6), ACS880-01-180A-5, 110 kW (frame size R7) and ACS880-01-414A-5, 250 kW (frame size R9) are connected together. All three converters are connected to the AC power line.

Calculating the rectifier power capacity

According to the table, k = 0.9 when converters of frame size R6 and R7 are connected to the AC power line, and k = 0.3 when converters of frame size R6 and R9 are connected to the AC power line. The lowest factor is used in the calculations, that is, k = 0.3, and Prec,ave becomes:

Prec,ave = 250 kW + (0.3 × 110 kW) + (0.3 × 75 kW) = 305.5 kW

Verifying the charging capacity of the common DC system

After you select the drives that you will connect to the AC power line, you must verify that there is enough charging capacity available.

Select the appropriate verification method and obey the related instructions:

1. If you only use drives with Type A charging circuit, make sure that both of these conditions are true:• The total charging resistance is high enough. See section Checking the total

charging resistance on page 23.

• The fuses, main contactor and other AC line-side components can withstand the peak current during the charging. See section Checking the peak AC current at charging on page 24.

2. If you use drives with Type B charging circuit, obey the instructions in subsection Checking the charging energy on page 24.

Note: If you use both drives with Type A and Type B charging circuits and you connect only Type B drives to the AC power line, select the verification method number 2 above.

Note: If you use both drives with Type A and Type B charging circuits AND you connect both types of drives to the AC power line, you must separate the DC links of those drives from each other during the charging. Then you actually have two (or several) separate DC links from the charging capacity point of view, and you can verify the charging capacity of each DC link separately. Select the appropriate verification method (number 1 or 2) above.

Page 23: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 23

Checking the total charging resistance

Use this method for verifying the charging capacity if there are only drives with Type A charging circuits in the common DC system.

The total charging resistance must comply with this formula:

Rtot > Rmin

Calculate the value Rtot as follows:

Define the value Rmin as follows:

1. If you connect only one drive to the AC power line, Rmin is equal to the minimum charging resistance defined for that drive. See section Charging resistance values on page 43.

2. If you connect several drives to the AC power line, calculate Rmin. Use this equation:

Rtot Calculated total charging resistance for the common DC system.

Rmin Minimum charging resistance allowed for the common DC system.

Ra Charging resistance of drive a in the common DC system. See section Charging resistance values on page 43.

Rb Charging resistance of drive b in the common DC system. See section Charging resistance values on page 43.

Rmin,1 Minimum charging resistance of drive 1 connected to the AC power line. See section Charging resistance values on page 43.

Rmin,2 Minimum charging resistance of drive 2 connected to AC power line. See section Charging resistance values on page 43.

Rtot

Ra

1

Rb

1

Rn

1+ + +

1=

Rmin

Rmin,1

1

Rmin,2

1

Rmin,n

1+ + +

1=

Page 24: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

24 Planning – basics

Checking the peak AC current at charging

If you only have drives with Type A charging circuits in the common DC system, make sure that the AC line-side components (fuses, contactors, etc.) can withstand the peak current at charging. Use the rule of thumb below, or calculate the peak current and compare it to the allowed peak current data for the AC line-side components.

Rule of thumb: There can not be more than three drives which are not connected to the AC power line per one connected drive.

Calculation: Calculate the peak current with this equation:

Checking the charging energy

Use this method to verify the charging capacity if there are drives with Type B charging circuit in the common DC system.

The drives that you connect to the AC power line must supply the total charging energy for all of the DC capacitors in the common DC system at the power up. The charging capacity must comply with this formula:

Erconnected > Etot

Calculate the charging energy for a drive and the common DC system with these equations:

Etot = Ea + …+ En = 1/2 × (CDCa +…+CDCn) × (1.35 × Unet)2

E1 = 1/2 × CDCa × (1.35 × Unet)2

Iac,peak Peak AC current at charging.

Uac AC input voltage.

Rtot Total charging resistance (see page 23).

Erconnected Total energy pulse that the charging resistors of the drives connected to the AC power line can withstand. See subsection Charging circuit Er values on page 43.

Etot Total charging energy of the DC capacitors of all drives in the common DC system.

CDC Capacitance of drive DC capacitors. CDCa is the capacitance of drive a. See subsection DC

link capacitance values on page 43.Ea Charging energy of drive a.

Unet Main voltage of the AC power line which the common DC system is connected to.

tot

acpeakac R

UI

×=

2,

Page 25: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 25

Example 1

Common DC system: The DC links of three converters ACS880-01-169A-3 (frame size R7), ACS880-01-246A-3 (frame size R8) and ACS880-01-430A-3 (frame size R9) are connected together. The main supply voltage is 400 V.

Questions: Is the charging capacity of the largest drive sufficient for the whole common DC system? Can you connect only the largest drive to the AC power line and leave the others unconnected?

Calculations:

The total charging energy of the capacitors is:

Etot = 1/2 × (3800 μF + 5600 μF + 8800 μF) × (1.35 × 400 V)2 × 10-6 = 2653 J

The charging capacity of the ACS880-01-430A-3 (frame size R9) is sufficient since:

Er = 5600 J > 2653 J (Etot)

Conclusion: It is sufficient to connect only the largest drive to the AC power line.

Example 2

Common DC system: The DC links of two ACS880-01-240A-5 converters (frame size R8) and three ACS880-01-361A-5 converters (frame size R9) are connected together. The main supply voltage is 500 V.

Question: How many frame size R9 drives you must connect to the AC power line to supply the charging energy for the whole system?

Calculations:

The total charging energy of the DC link capacitors is:

Etot = 1/2 × (2 ×5600 μF + 3 ×8800 μF) × (1.35 ×500 V)2 ×10-6 = 8566 J

The charging capacity of the ACS880-01-361A-5 (frame size R9):

One frame size R9 drive: Er = 5600 J < 8566 J (Etot)

Two frame size R9 drives: 2 × Er = 112 000 J > 8566 J (Etot)

Conclusion: It is sufficient to connect two frame size R9 drives to the AC power line.

Handling the surplus energy

Background

When a motor brakes, it generates energy to the DC link. If the other drives in the common DC system cannot use the energy at the same time, the DC link voltage starts to rise. The capacitors in the DC link can absorb a small energy pulse. If that is not enough and the voltage keeps rising, you must convey the surplus energy to the braking chopper and resistors, or to the AC power line. For the latter case you need a special type of drive, a regenerative drive. For more information of the electrical braking, see Technical guide No. 8 Electrical braking in ABB Drives - Technical Guide Book (3AFE64514482 [English]).

This sections contains:• instructions in defining the energy absorbing capacity of the common DC link

• instructions in dimensioning brake choppers and resistors.

This section does not contain instructions in selecting the regenerative drive.

Page 26: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

26 Planning – basics

Defining the energy absorbing capacity of the common DC link

Use formula 1 below to examine if the common DC link capacitors can absorb the surplus energy of the common DC system. If the condition is true, the energy absorbing capacity is sufficient and you do not need a brake chopper and a resistor to handle the surplus energy.

Wdc > Egen (1)

Cdca Capacitance value of drive a

Cdcb Capacitance value of drive b

Egen Generating energy of the common DC link during one duty cycle

Pg1 Generating power of the common DC link during time tg1

Pg2 Generating power of the common DC link during time tg2

Pgen(t) Generating power of the common DC link as a function of time over one duty cycle.

T Duty cycle timetg1 Duration of generating power Pg1

tg2 Duration of generating power Pg2

Uac AC power line voltage

Udc Nominal DC link voltage. See section DC voltage limits of the drive on page 45.

Udc,lim Maximum DC link voltage. See section Defining the maximum DC link voltage on page 27.

Wdc Energy absorbing capacity of the common DC link

(Cdca + Cdcb + Cdcc… + Cdcn)× (Udc,lim

2 - Udc2)Wdc =

2

Udc,lim = 2 × Uac

Egen = ʃPgen(t) ×dt = Σ((Pg1 × t1) + … + (Pgn × tn))0

T

tDrive a

Common DC

M M M

P

duty cycle

tduty cycle

tDrive bduty cycle

tDrive cduty cycle

Pg1Pg2

tg2

Ttg1

P

P

P

a b c

Page 27: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 27

Defining the maximum DC link voltage

The table below shows how you can define the maximum DC link voltage Udc,lim. See section DC voltage limits of the drive on page 45 for the explanation of the symbols.

1) Parameter 30.30 Overvoltage control in the ACS880 primary control program.

2) You must have some margin to the limit to avoid fault trips.

3) The resistor braking starts when the voltage exceeds the limit.

Selecting the brake choppers and resistors

You must use brake choppers and resistors in the common DC system if the DC link capacitors cannot absorb the surplus energy, and there is no regenerative drive in the system.

Depending on the drive frame size, the brake chopper is either a standard or optional device. See section Brake chopper types on page 15. If the chopper is available as an option, you can order it from ABB as factory-installed.

You must acquire and install the brake resistors separately. See the drive hardware manual for ABB brake resistors for each drive. Use can use either the default ABB brake resistors defined for each drive or other resistors that meet the selection criteria.

Select the choppers and resistors as follows:

1. Select the choppers:• Examine if the chopper load capacity of the drive with the highest power rating is

high enough for the surplus power of the common DC link. See section Brake chopper selection formulas on page 28.

• If the chopper load capacity of one drive is not enough, use also the chopper with the second highest power rating, etc. until the total load capacity meets the criteria.

2. Select the brake resistors:• If you plan to use one chopper and resistor only, either verify the default ABB

brake resistor selection, or select a user-defined resistor. See section Brake resistor selection formulas - system with one brake chopper on page 28. If the resistor does not meet the criteria, try another resistor, or take the next biggest chopper and its resistor in use as well.

• If you plan to use several choppers and resistors, verify each resistor selection. See section Brake resistor selection formulas - system with several brake choppers and resistors on page 29. If a resistor does not meet the criteria, try another resistor, or take the next biggest chopper and its resistor in use as well. Repeat the verification until each resistor meets the criteria.

Overvoltage control1)

Brake choppers and resistors

Udc,lim

Enabled Not in use Udc,lim = UDC,ovc

Disabled Not in use Udc,lim < UDC,ovt 2)

Disabled In use Udc,lim = UDC,brcl 3)

Page 28: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

28 Planning – basics

Brake chopper selection formulas

Use these formulas to select the choppers and verify the selection:

Pbr,cont > Pgen,ave

Pbr,max > Pgen,max

Pbr,cont = Pbr,cont1 + 0.8 × (Pbr,cont2 + Pbr,cont3 +…)

Pbr,max = Pbr,max1 + 0.7 × (Pbr,max2 + Pbr,max3 +…)

Brake resistor selection formulas - system with one brake chopper

Use these formulas to select the brake resistor, and to verify the resistor selection:

Pgen,ave Average generating power of the common DC link. See DC link duty cycle diagram on page 19.

Pgen,max Maximum generating power of the common DC link. See DC link duty cycle diagram on page 19.

Pbr,cont Continuous braking power of the common DC link. The braking is continuous if the braking time exceeds 30 seconds.

Pbr,max Maximum braking power of the common DC link. Choppers withstand this braking power for 5 second within every minute.

Pbr,cont1 Continuous braking power of the chopper 1. See section Brake chopper power ratings on page 44.

Pbr,max1 Maximum braking power of the chopper 1. See section Brake chopper power ratings on page 44.

Er Energy pulse that the resistor can withstand and dissipate during a predefined period. See the drive hardware manual (ABB brake resistors) or resistor data sheet.

Pg1 Generating power of the common DC link during time tg1. See tg1 and the graph in section

Defining the energy absorbing capacity of the common DC link on page 22.Pgen(t) Generating power of the common DC link as a function of time over one duty cycle.

Pgen,max Maximum generating power of the common DC link.

PN,r Nominal power of the brake resistor

Rbr Resistance of the brake resistor

Rmin Minimum resistance of the brake resistor that you can use with the drive. See the drive hardware manual.

tg1 Duration for generating power Pg1. See the graph in section Defining the energy absorbing

capacity of the common DC link on page 22.Uac AC power line voltage

Udc,h = 2.1 × Uac (high DC link voltage value but clearly below the trip level)

Rbr > Rmin

Rbr < Udc,h

Pgen,max

2

Er > ʃPgen(t) ×dt = Σ((Pg1 × t1) + … + (Pgn × tn))

PN,r > Pgen,ave

Page 29: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – basics 29

Brake resistor selection formulas - system with several brake choppers and resistors

Use these formulas to select the brake resistor for each chopper, and to verify the resistor selection:

Rbr(i) > Rbr,min(i)

Er(i) Energy pulse that individual brake resistor i can withstand and dissipate during one load cycle. See the drive hardware manual (ABB brake resistors) or resistor data sheet.

Rbr(i) Resistance of individual brake resistor i. See the drive hardware manual (ABB brake resistors) or resistor data sheet.

Rbr,min(i) Minimum resistance of brake resistor i that you can use with individual drive (brake chopper). See the drive hardware manual.

Pbr,cont(i) Continuous braking power of individual brake chopper. See the drive hardware manual (ABB brake resistors) or resistor data sheet.

Pg1 Generating power of the common DC link during time tg1. See the graph in section Defining

the energy absorbing capacity of the common DC link on page 26.Pgen(t) Generating power of the common DC link as a function of time over one duty cycle.

Pgen,max Maximum generating power of the common DC link.

PN,r(i) Nominal power of individual brake resistor i. See the drive hardware manual (ABB brake resistors) or resistor data sheet.

Pbr,contr(i) Continuous power of brake chopper supplying the individual brake resistor i. See section Brake chopper power ratings on page 44.

Pbr,max(i) Maximum power of brake chopper supplying the individual brake resistor i. See section Brake chopper power ratings on page 44.

tg1 Duration for generating power Pg1. See graph in section Defining the energy absorbing

capacity of the common DC link on page 22.Uac AC power line voltage

Udc,h = 2.1 × Uac High DC link voltage value but clearly below the trip level

max,2max,1max,

2

)()

...)()max(,

genbrbr

dcibri

PPP

iPbrU

++

<<

( ) )(2,1,

)(,

... iRgencontbrcontbr

icontbr EdtPPP

P<×

++

( ) )(,,2,1,

)(,

... iRNavegencontbrcontbr

icontbr PPPP

P<×

++

Page 30: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

30 Planning – basics

Page 31: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – additional instructions 31

4

Planning – additional instructions

Contents of this chapterThis chapter contains some additional instructions for planning a common DC system.

Requirements for the AC input connectionSee the drive hardware manual for the electric power network specification of the drive.

Supply all drives which you connect to the AC power line from the same transformer. All drives must have equal supply-side impedance. The supply-side impedance is an important parameter which influences the current distribution.

Constructing the DC linkIf the system consists of more than two drives, construct either common DC bus bars or common DC terminals for the whole system. Connect the DC cabling of every drive to this common connection point. Do not use the DC terminals of one of the drives for this purpose, nor chain the DC link from one drive to another. This ensures that the drives terminals do not overheat.

Page 32: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

32 Planning – additional instructions

Selecting the fusesThere must be fuses both at the AC supply side of the drive and at the DC connection. They protect the cabling and limit the drive damage in case of a short circuit.

Selecting the AC input fuses

Equip every drive which you connect to the AC power line with fuses. The default AC fuses for each drive are given in the drive hardware manual. Obey these guidelines if you select other fuses:• Fuse type: Only use the default fuse types (aR, T, etc.). See the drive hardware

manual.

• Voltage rating: According to the drive AC voltage rating, except use 500 V fuses for the 380 … 500 V AC supply.

• Nominal current of the fuses IF,N ≈ 1.6 × Irec,ave

• Irec,ave is the average rectifying current of the drive.

• Factor 1.6 covers the influence of cyclic load and ambient conditions.

• If you do not know the average rectifier current of the drive, use the rated input current of the drive instead. See the drive hardware manual.

• Make sure that the operation time of the fuse is below the limit given for the default fuses. See the drive hardware manual.

Selecting the DC fuses

Equip every drive with DC fuses. Install a fuse on both DC+ and DC- cable that you connect from the common DC link connection point to the drive.

Suitable fuses for each drive type are listed in section DC fuses on page 46. Obey these guidelines if you select the fuses on your own:• Fuse type: aR (ultra-rapid, fast)

• Voltage rating: Select according to the nominal DC voltage (UDC). See section DC voltage limits of the drive on page 45.

• Nominal current: IF,N ≈ 1.6 x Idc,ave(i)

Make sure that the fuses also protect the DC cabling connected to the drive.

1.6 Factor which covers the influence of the cyclic load and ambient conditionsIdc,ave Average DC link current

IF,N Nominal current of the fuse

Pdc,ave(i) Maximum average DC link power in the DC connection terminals of the individual drive i. (during a worst case 3 min time window)

Udc actual DC link voltage = 1.35 x Uac

Idc,ave =Pdc,ave(i)

Udc

Page 33: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – additional instructions 33

Phase loss protectionWe recommend that you use phase loss guard in the AC supplies of the drives which you connect to the AC power line. If one AC fuse blows, the semiconductors of the drives can be overloaded and be damaged if you do not have the phase loss protection. The internal phase loss detection of the drive will not work, as the addition DC capacitors on the system may prevent the DC ripple becoming large enough to be detected internally.

Selecting the power cables

• Obey the instructions in the drive hardware manual.

• Size the conductor cross-sectional area of the drive DC cable the same as the conductors of the drive input power cable (AC).

• Use shielded DC cables, or only run them inside the cabinet. Ground the cable shield at the other end only.

• Make sure that the lengths of the individual input power cables (AC) do not differ by more than 15% from each other.

• Make sure that the total cable length of the DC cables between any two drives is no longer than 50 m (164 ft).

Page 34: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

34 Planning – additional instructions

DC contactors

DC link separation

If you connect drives with different type of charging circuits to the AC power line, you must separate their DC link with a DC contactor. The DC links of drives with Type B charging circuit may not be connected to the DC link of drives with Type A charging circuit during the charging. See the table in section Power correction factor (k) on page 41.

The contactor must be open during the power up until the separate DC links are charged and the drives are in Ready state. Then you can close the contactor and connect the DC links.

Select the DC contactor in the DC link using these values:

Udc_max = 1.21 × 1.35 × U1

IdcN = PDC / Udc

PDC ≈ Pcont.max

Brake resistor protection

If you use resistor braking, you must make sure that if the chopper fails and it cannot switch off, the system will cut off the power supply for the brake resistor. • If you use the chopper in a drive with Type B charging circuit, and that drive is the only

one that you connect to the AC power line, you do not need extra protection: The drive detects the chopper fault, and its input bridge cuts off the power supply from the AC power line to DC link and further to the resistor.

• If you use the chopper in a drive with Type A charging circuit, or connect several drives to the AC power line, install a DC contactor between the chopper and brake resistor, and wire the chopper fault relay to open the contactor control circuit after the chopper fault.

Select the DC contactor for the chopper using these values:

Udc = 1.35 × U1

Ip = (1.25 x Udc) / Rbrake

Irms= (Pbr / Rbrake ) ½

IdcN Nominal DC current in the DC link

Pcont.max Power rating of the larger drive to be separated (See the drive hardware manual.)

U1 AC input voltage of the drive

Udc_max Maximum voltage over the contactor in the DC link

Ip Peak current during the resistor braking

Irms Nominal rms current during the resistor braking

Pbr Motor braking power that the resistor must dissipate

Rbrake Resistance of the brake resistor

U1 AC input voltage of the drive

Udc Voltage over the contactor during the braking

Page 35: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – additional instructions 35

Electromagnetic Compatibility (EMC)To ensure that the common DC link system complies with electromagnetic compatibility (EMC) rules and does not interfere with other systems, obey the following guidelines:• Obey the electrical installation instructions in the drive hardware manual.

• To minimize the conducted emissions, order a relevant EMC filter option for the drive that will be connected to AC power line. See the drive hardware manual for the possible EMC filter options.

• To minimize the radiated emissions:

• Keep the power cable runs as short as possible. Especially important is to keep the DC cabling and the brake resistor cabling short.

• Make 360-degree grounding of the cable shields at the drive cable connection box, using either a metal gland or the clamps supplied. If you install the drives inside a cabinet, make the 360 degree earthing at the cabinet cable entry.

• Use shielded power cables.

For more information of the general EMC guidelines, see Technical guide, EMC compliant installation and configuration for a power drive system (3AFE61348280 [English]).

Note: ABB has not tested the various common DC systems against the EMC product standard (EN 61800-3:2004) requirements stated for drives. An EMC plan may be required to gain CE compliance.

Page 36: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

36 Planning – additional instructions

Connecting the Ready and Start enable signalsAll drives which you connect to the AC power line must be ready (charging complete) before you can start to load any of the drives. If a drive on the common DC system starts its motor too early, it can cause damage to the charging contactor or resistor.

To make sure that starting is not possible during the charging:

1. Connect the Ready signals of all drives with the AC power line connection in series and supply the circuit with +24 V from one drive. This becomes the common Ready signal for all drives.

Note: Relay output RO1 of the drive indicates the Ready signal in ACS880 primary control program when the Factory macro is selected. If you have another macro or control program in use, or want to use another relay output instead, see the drive firmware manual for the parameter settings (parameter group 10 Standard DI, RO).

2. Connect the common Ready signal to digital input DI6 of all drives.

3. Connect the ground of the 24 V DC supply in all drives to each other (DICOM terminals in ZCU control unit). We also recommend that you separate it from the digital I/O ground (DIOGND terminal) in all drives. (Switch J6 in ZCU control unit.)

4. Set the digital input DI6 as the source for the Start enable signal in the drive control program in all drives. (parameter 20.19 Enable start command in the ACS880 primary control program.)

The diagram below shows the control connections with a solid line.

3

2

XD

241 2 3

DII

L+

24V

DIC

OM

XR

O1

1 2 3N

OC

OM

NC

ZCU Control unit

M~3

3

2 2

J6: OFF

M~3

3

M~3

3

XD

I6

DI6

XD

24

1 2 3

DIIL

+24

VD

ICO

M

XR

O1

1 2 3N

OC

OM

NC

ZCU Control unit

J6: OFF

XD

I6

DI6

XD

24

1 2 3

DIIL

+24

VD

ICO

M

XR

O1

1 2 3N

OC

OM

NC

ZCU Control unit

J6: OFF

XD

I6

DI6

3

Page 37: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Planning – additional instructions 37

Setting the drive parametersCheck the settings of the drive parameters against the recommendations below. This is not the complete list of settings, just settings for the common DC system to work effectively. The list is valid for the ACS880 primary control program.• Recommendation: Set parameter 99.04 Motor ctrl mode to DTC in all drives.

• Set parameter 30.26 Power motoring limit to the maximum motoring power of the drive load cycle.

• Set parameter 30.27 Power generating limit to the maximum generating power of the drive load cycle.

• When you use a brake chopper:

• Set parameter 30.30 Overvoltage control to Disable in all drives.

• Set parameter 43.06 Brake chopper to Enabled with thermal model or Enabled without thermal model in those drives that you use the chopper.

• Set parameter 31.23 to No action in all drives to prevent unnecessary fault trips.

For more information, see the drive firmware manual.

Page 38: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

38 Planning – additional instructions

Page 39: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Technical data 39

5

Technical data

Contents of this chapterThis chapter contains the technical data that you need in the planning of a common DC system.

Page 40: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

40 Technical data

Rectifier power capacity (Prec,ave and Prec,max)

Uac: AC input voltage.

Prec,ave is the average rectifier power capacity of the drive over a 3-minutes time window. The average power

taken from AC power line must be lower than this value during any 3-minutes time window. 1) Value 630 applies to 600…690 V AC.

Prec,max is the maximum rectifier power capacity of the drive allowed for max. 10 s. The instantaneous power

taken from AC power line must never exceed this limit.

R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.R10a: ACS880-04 types -505A-3 and -460A-5.R10b: ACS880-04 types -585A-3, -650A-3, -583A-5, -635A-5, -330A-7 and -370A-7.

Frame Prec,ave Prec,max depending on Uac

208…240 V AC

(ACS880-01-xxxx-2)

380…415 V AC

(ACS880-01/-04-xxxx-3)

380…500 V AC

(ACS880-01/-04-xxxx-5)

600…690 V AC

(ACS880-01/-04-xxxx-7)

R1 5.5 7 7 6 -

R2 11 13 13 10 -

R3 18.5 26 26 24 -

R4 30 37 37 32 -

R5a 15 - - - 24

R5b 45 63 63 59 54

R6 75 92 92 79 81

R7 110 153 153 144 150

R8 160 228 228 212 208

R9 250 - 317 262 304

R10a 250 - 340 420 -

R10b 355 - 420 500 510

R11 500/630 1) - 620 700 850

Page 41: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Technical data 41

Power correction factor (k)The tables below shows the power correction factor (k) for calculating the sum rectifying capacity of the drives connected to the AC power line. Choose the lowest k factor of the possible choices.

The tables also show the combinations of drives that you may connect to the AC power line. Connect only the drives visible in the same table. Connect only combinations which are visible in the same table and which are not marked as prohibited. The other combinations are not allowed.

Example for choosing the k:

If you connect frames R5, R4 and R2 to the AC power line, possible values for k are:• 0.7 for combination of frames R5 and R4

• 0.8 for combination of frames R5 and R2

• 0.8 for combination of frames R4 and R2.

Choose the smallest value (0.7) and use it in the calculations.

Frames R1 to R5

Frames R5 to R9

Uac = 208…240, 380…415, 380…500

Uac = 600…690

R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.

The smaller drive may not be connected to the AC power line.

Frame R1 R2 R3 R4 R5

R1 0.9 0.4 0.9

R2 0.4 0.9 0.7 0.8 0.8

R3 0.9 0.7 0.9 0.6 0.4

R4 0.8 0.6 0.9 0.7

R5 0.8 0.4 0.7 0.9

Frame R5 R6 R7 R8 R9

R5 0.9 0.3

R6 0.3 0.9 0.9 0.5 0.3

R7 0.9 0.9 0.7 0.6

R8 0.5 0.7 0.9 0.9

R9 0.3 0.6 0.9 0.9

Frame R5a R5b R6 R7 R8 R9

R5a 0.9 0.9 1 1 0.7 0.9

R5b 0.9 0.9 0.7 0.5 0.2

R6 1 0.7 0.9 1 0.8 0.7

R7 1 0.5 1 0.9 0.9 0.8

R8 0.7 0.2 0.8 0.9 0.9 1

R9 0.4 0.7 0.8 1 0.9

Page 42: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

42 Technical data

Frames R10 to R11

R10a: ACS880 types -505A-3 and -460A-5.R10b: ACS880 types -585A-3, -650A-3, -583A-5, -635A-5, -330A-7 and -370A-7.Uac: AC input voltage.

DC contactors between the drivesTables below show when you need a DC contactor between the drives in the DC link. If both frame sizes exist in the common DC system, and both of them are connected to the AC power line, you must have a DC contactor between the DC terminals of these drives. The DC contactor must isolate the drives until charging is complete.

Frames R1 to R5

Frames R5 to R9

Frames R10 to R11

R10a: ACS880 types -505A-3 and -460A-5.R10b: ACS880 types -585A-3, -650A-3, -583A-5, -635A-5, -330A-7 and -370A-7.

Frame R10a R10b R11

R10a 0.9 0.7 0.5

R10b 0.7 0.9 0.9

R11 0.5 0.9 0.9

Contactor is not needed.

X Contactor is needed.

The smaller drive may not be connected to the AC power line.

Frame R1 R2 R3 R4 R5

R1

R2 X

R3 X

R4 X

R5 X X X

Frame R5 R6 R7 R8 R9

R5

R6

R7

R8

R9

Frame R10a R10b R11

R10a

R10b

R11

Page 43: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Technical data 43

Charging resistance values

R: Charging resistance of the drive module.

Rmin: Minimum resistance that the charging circuit can supply (in case the circuit must supply charging current

of several drives).

Charging circuit Er values

Er: Maximum energy pulse that the charging circuit of the drive can withstand.

DC link capacitance values

Uac: AC input voltage.

R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.

Frame R [ohm] Rmin [ohm]

R1, R2, R3 50 16

R4 25 6

R5 20 N/A

R6, R7 36 N/A

R8, R9 18 N/A

R10 3.3 N/A

R11 10 N/A

Frame Er [J]

R5 411

R6 1400

R7 1400

R8 5600

R9 5600

R10 5600

R11 7400

Frame CDC [microF] depending on Uac

208…240 V AC

(ACS880-01-xxxx-2)

380…415 V AC

(ACS880-01/-04-xxxx-3)

380…500 V AC

(ACS880-01/-04-xxxx-5)

600…690 V AC

(ACS880-01/-04-xxxx-7)

R1 300 300 300 -

R2 500 500 500 -

R3 1000 1000 1000 -

R4 4100 1000 1000 -

R5a - - - 350

R5b 6200 1500 1500 700

R6 10500 2600 2600 1200

R7 15300 3800 3800 1700

R8 22500 5600 5600 2500

R9 - 8800 8800 3900

R10 - 15800 15800 5267

R11 - 23700 23700 10533

Page 44: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

44 Technical data

Brake chopper power ratings

Pbr,cont: Continuous braking power of the chopper. The braking is considered continuous if the braking time

exceeds 30 seconds.

Rbr,min: The minimum allowed resistance of the brake resistor used with the brake chopper.

Note: Pbr,max= UDC,brcl2 / Rbr, min: This is the theoretical maximum braking power which

the brake chopper can withstand for a short time. Thermal protection of the brake chopper can limit the available braking power to a lower value.

Drive type ACS880-01-

Pbr,

cont

[kW]

Rbr,

min

[ohm]

Drive type ACS880-01-

Pbr,

cont

[kW]

Rbr,

min

[ohm]

Drive type ACS880-01-

Pbr,

cont

[kW]

Rbr,

min

[ohm]

Drive type ACS880-01-

Pbr,

cont

[kW]

Rbr,

min

[ohm]

04A6-2 0.75 65 02A4-3 0.75 78 02A1-5 0.75 78 07A3-7 6 18

06A6-2 1.1 65 03A3-3 1.1 78 03A0-5 1.1 78 09A8-7 8 18

07A5-2 1.5 65 04A0-3 1.5 78 03A4-5 1.5 78 14A2-7 11 18

10A6-2 2.2 65 05A6-3 2.2 78 04A8-5 2.2 78 018A-7 17 18

16A8-2 4.0 18 07A2-3 3.0 78 05A2-5 3.0 78 022A-7 23 18

24A3-2 5.5 18 09A4-3 4.0 78 07A6-5 4.0 78 026A-7 28 18

031A-2 7.5 13 12A6-3 5.5 78 11A0-5 5.5 78 035A-7 33 18

046A-2 11 12 017A-3 7.5 39 014A-5 7.5 39 042A-7 45 18

061A-2 11 12 025A-3 11 39 021A-5 11 39 049A-7 45 18

075A-2 18.5 6 032A-3 15 19 027A-5 15 19 061A-7 55 13

087A-2 22 6 038A-3 18.5 19 034A-5 18.5 19 084A-7 65 13

115A-2 30 3.5 045A-3 22 13 040A-5 22 13 098A-7 90 8

145A-2 37 3.5 061A-3 22 13 052A-5 22 13 119A-7 110 8

170A-2 45 2.4 072A-3 37 8 065A-5 37 8 142A-7 132 6

206A-2 55 2.4 087A-3 45 8 077A-5 45 8 174A-7 160 6

274A-2 75 1.8 105A-3 55 5.4 096A-5 55 5.4 210A-7 200 4

145A-3 75 5.4 124A-5 75 5.4 271A-7 250 4

169A-3 90 3.3 156A-5 90 3.3

206A-3 110 3.3 180A-5 110 3.3

246A-3 132 2.3 240A-5 132 2.3

293A-3 132 2.3 260A-5 132 2.3

363A-3 160 2 302A-5 160 2.3

430A-3 160 2 361A-5 160 2.3

414A-5 160 2.3

Page 45: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Technical data 45

DC voltage limits of the drive

Uac: AC input voltage. Set also parameter 95.01 Supply voltage in the drive control program to this value. All

drives on the common DC system must have the same setting. Set parameter 95.02 Adaptive voltage limits to Disabled.

Udc: Nominal DC link voltage = 1.35 × Uac in normal motoring operation mode of the drive.

UDC,chr: Charging limit. Drive opens the charging circuit when the DC voltage reaches this limit at power up.

UDC,ovc, UDC,uvc: Overvoltage control limit and Undervoltage control limit. The overvoltage and undervoltage

control of the DC link voltage level are enabled by default. The drive limits the motoring and generating torque when necessary to keep the DC link voltage within the control limits. When a brake chopper and resistor are in use, you must disable the overvoltage control.

UDC,ovt, UDC,uvt: DC overvoltage trip limit and DC undervoltage trip limit. The drive trips and gives a fault

message if the DC link voltage reaches these levels.

UDC,brcl, UDC,brch: Brake chopper limit low and Brake chopper limit high. The brake chopper starts operation

when the DC link voltage reaches the low level and you have enabled the chopper with the drive parameter. If the DC link voltage level reaches the high level, the brake chopper will be at its maximum load.

Symbol DC voltage value depending on Uac

208…240 V AC 380…415 V AC 440…480 V AC 500 V AC 525…600 V AC 660…690 V AC

R1-R3 R4-R8

UDC 281…324 V DC 513…560 V DC 594…648 V DC 675 V DC 709…810 V DC 891…932 V DC

UDC,chr 225 V DC 410 V DC 475 V DC 540 V DC 567 V DC 713 V DC

UDC,ovc 389 V DC 700 V DC 778 V DC 810 V DC 1013 V DC 1118 V DC

UDC,uvc 239 V DC 436 V DC 505 V DC 574 V DC 602 V DC 757 V DC

UDC,ovt 489 440 800 V DC 878 V DC 880 V DC 1113 V DC 1218 V DC

UDC,uvt 168 V DC 308 V DC 356 V DC 405 V DC 425 V DC 535 V DC

UDC,brcl 375 V DC 648 V DC 749 V DC 780 V DC 936 V DC 1077 V DC

UDC,brch 403 V DC 697 V DC 806 V DC 806 V DC 1008 V DC 1159 V DC

3AXD10000114906 - 2013-10-24

Page 46: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

46 Technical data

DC fuses

Drive type

ACS880-01-

Fuse [A] Drive type

ACS880-01-

Fuse [A] Drive type

ACS880-01-

Fuse [A] Drive type

ACS880-01-

Fuse [A]

04A6-2 10 02A4-3 10 02A1-5 10 07A3-7 16

06A6-2 16 03A3-3 10 03A0-5 10 09A8-7 20

07A5-2 16 04A0-3 10 03A4-5 10 14A2-7 32

10A6-2 20 05A6-3 10 04A8-5 10 018A-7 40

16A8-2 32 07A2-3 16 05A2-5 10 022A-7 40

24A3-2 50 09A4-3 20 07A6-5 16 026A-7 50

031A-2 63 12A6-3 25 11A0-5 20 035A-7 63

046A-2 100 017A-3 32 014A-5 32 042A-7 80

061A-2 125 025A-3 50 021A-5 40 049A-7 100

075A-2 160 032A-3 63 027A-5 50 061A-7 125

087A-2 160 038A-3 80 034A-5 63 084A-7 160

115A-2 250 045A-3 100 040A-5 80 098A-7 200

145A-2 315 061A-3 125 052A-5 100 119A-7 250

170A-2 315 072A-3 160 065A-5 125 142A-7 315

206A-2 400 087A-3 160 077A-5 160 174A-7 350

274A-2 500 105A-3 200 096A-5 200 210A-7 400

145A-3 315 124A-5 250 271A-7 500

169A-3 315 156A-5 315

206A-3 400 180A-5 350

246A-3 450 240A-5 450

293A-3 550 260A-5 500

363A-3 700 302A-5 550

430A-3 800 361A-5 700

414A-5 800

Page 47: EN / ACS880-01 drives and ACS880-04 drive modules common ... · ACS880 primary control program firmware manual 3AUA0000085967 ... ACS880-01 drives and ACS880-04 drive modules Common

Further information

Product and service inquiries

Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.

Product training

For information on ABB product training, navigate to www.abb.com/drives and select Training courses.

Providing feedback on ABB Drives manuals

Your comments on our manuals are welcome. Go to www.abb.com/drives and select Document Library – Manuals feedback form (LV AC drives).