Page 1: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

06.06.17

EMERGENCY BALLASTS

We light your world™

Page 2: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

22

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one lamp in the emergency mode for a minimumof 90-minutes.

• Provides a maximum initial lumen output of 500 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 2.4V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Compact design fits most fluorescent fixtures.

WARRANTY/LISTING

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic, standard and dimming AC ballasts.

• Operates one T5, T5HO, T8, T12, Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lamp in emergency mode. Referto the chart on the next page for a complete list of compatiblelamps.

DIMENSIONS

* When battery packs are remote mounted, the remote distance cannot exceed ½of the distance from ballast to lamp speci-fied by the A.C. ballast manufacturer. Themaximum allowable remote mountingdistance is 50 feet.

9.45”

1.5”

2.4”

STANDARD

ORDERING INFORMATION MODEL DESCRIPTION

BAL500TD 500 Lumens Fluorescent Ballast with Time Delay

BAL500TD

LED LED TTest switchswitch included.

Fluorescent Emergency Ballast 500 Lumens

Page 3: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

33

ELECTRICAL INFORMATION

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL500TD 2.5 2.7 0.27 0.25

LAMP COMPATIBILITY CHART

LAMP TYPE

WATTS INITIAL LUMENS

1-Lamp

T5 21 450

T5 28 500T5HO 24 475T8 25 375T8 28 425

LAMP TYPE

WATTS INITIAL LUMENS

1-Lamp

T8 32 500

T12 25 400T12 30 425T12 34 450CFL 2G11 36 375

LAMP TYPE

WATTS INITIAL LUMENS

1-Lamp

Circular T9 20 325Circular T9 32 350Circular T5 22 375U-Bend T8 32 425U-Bend T12 34 375

BAL500TDFluorescent Emergency Ballast 500 Lumens

Page 4: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

44

BAL650C-2Fluorescent Emergency Ballast 650 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one lamp in the emergency mode for a minimumof 90-minutes.

• Provides a maximum initial lumen output of 650 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• Long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

MOUNTING

• Suitable for installation inside, on top or in remote* of thefixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Provided with 2’ flex conduits on both ends.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one 13W-26W, 2-pin compact fluorescent lampswith GX23 and G24D bases. Refer to lamp compatibilitychart for a complete list of lamps.

DIMENSIONS

* When battery packs arremote mounted, the remotedistance cannot exceed ½of the distance from ballastto lamp specified by the A.C.ballast manufacturer. Themaximum allowable remotemounting distance is 50 feet.

LAMP INITIAL LUMENS

1-LAMP

2-Pin PL CF 13W 3802-Pin PL CF 18W 5502-Pin PL CF 26W 650

STANDARD

9½”

2⅜”

1½”

WARRANTY / LISTING

LELED Test swswitch included.

Page 5: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

55

ELECTRICAL INFORMATION

BAL650C-2Fluorescent Emergency Ballast 650 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL650C-2 2.8 2.6 0.270 0.260

Page 6: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

66

BAL650C-4ACTD

9½”

2⅜”

1½”

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 750 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 3.6V long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• AC output ensures compatibility with newer lamptechnologies and helps prolong lamp life.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

• Durable painted steel construction in white finish.

• Provided with 2’ flex conduits on both ends.

• Compact design fits most fluorescent fixtures.

WARRANTY / LISTING

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, Circular T9, U-bend T8/T12, 4-Pin CFL and Long CFL lamps in emergencymode. Refer to the chart on next page for a complete list ofcompatible lamps.

DIMENSIONS

* When battery packs arremote mounted, the remotedistance cannot exceed 1/2of the distance from ballastto lamp specified by the A.C.ballast manufacturer. Themaximum allowable remotemounting distance is 50 feet.

LED Test switch included.

STANDARD

MODEL DESCRIPTION

BAL650C-4ACTD 750 Lumens 4-pin CFL fluorescent emergency ballast with AC output and time delay

4-Pin CFL FluorescentEmergency Ballast 750 Lumens

HOHOUUSSIINNGG

Page 7: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

77

ELECTRICAL INFORMATION

BAL650C-4ACTDFluorescent Emergency Ballast 650 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL650C-4ACTD 3.8 3.8 0.270 0.270

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

14 T5 450 50021 T5 550 -28 T5 600 -39 T5HO 650 -25 T8 600 -32 T8 675 -

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

40 T8 700 -40 T12 650 -13 CFL G24q-1 450 50018 CFL G24q-2 500 57526 CFL G24q-3 575 -42 CFL G24q-4 750 -18 CFL 2G11 525 625

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

36 CFL 2G11 600 -40 CFL 2G11 650 -32 Circular T9 575 -40 Circular T9 625 -32 U-bend T8 650 -34 U-bend T12 600 -

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 8: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

88

BAL700TD Fluorescent Emergency Ballast 700 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or existingfluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 700 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 3.6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material andworkmanship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

DIMENSIONS

9.45”

1.5”

2.4”

* When battery packs arremote mounted, the remotedistance cannot exceed ½of the distance from ballastto lamp specified by the A.C.ballast manufacturer. Themaximum allowable remotemounting distance is 50 feet.

LED Test switch included.

STANDARD

MODEL DESCRIPTION

BAL700TD 700 Lumens Fluorescent Emergency Ballast with Time Delay

WARRANTY/LISTING

Page 9: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

99

ELECTRICAL INFORMATION

BAL700TD Fluorescent Emergency Ballast 700 Lumens

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL700TD 2.9 3.1 0.27 0.25

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 21 575 650T5 28 675 n/aT5 35 700 n/aT5HO 24 650 n/aT5HO 39 700 n/aT5HO 54 700 n/aT8 25 625 700T8 28 630 600T8 32 600 700T8 40 650 700T8HO 44 625 n/aT8 51 675 n/aT8 59 700 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T8HO 86 700 n/aT12 25 450 500T12 30 500 550T12 34 575 600T12 40 625 650T12 75 675 n/aT12 85 700 n/aT12HO 95 700 n/aT12HO 110 700 n/aCFL G24Q-5 57 675 n/aCFL 2G11 36 600 700CFL 2G11 40 625 n/aCFL 2G11 50 650 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 55 675 n/aCFL GR10q-4 28 550 600CFL GR10q-4 38 650 n/aCFL GR10Q-4 55 700 n/aCircular T9 20 400 500Circular T9 32 450 550Circular T9 40 500 n/aCircular T5 22 425 550Circular T5 40 600 700Circular T5 55 650 n/aU-bend T8 32 575 675U-bend T12 34 550 650U-bend T12 40 600 n/a

LAMP COMPATIBILITY CHART

Page 10: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1010

Bi-ColorLED Test switch included.

BAL1400C-4ACTD-SDT

13.4”

2.4”

1.5”

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-i ting fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1400 lumens.

ELECTRICAL

• Universal 120-277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• AC output ensures compatibility with newer lamptechnologies and helps prolong lamp life.

• Time delay enhancement to overcome end-of-life circuitprotection.

• Self-Diagnostics fetaure performs monthly, biannual andannual tests to ensure reliable operation and meet electricaland life safety code.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

WARRANTY / LISTING

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

DIMENSIONS

* When battery packs are remote mounted, the remote distance cannot exceed 1/2 of the distance from ballast to lamp specifieby the A.C. ballast manufacturer. The maximum allowable remote mounting distance is 50 feet.

STANDARD

MODEL DESCRIPTION

BAL1400C-4ACTD-SDT 1400 Lumens 4-pin CFL fluorescent emergency ballast with AC output, time delay and self-diagnostics.

4-Pin CFL Fluorescent Emergency Ballast 1400 Lumens with Self-Diagnostics

D bl i t d t lDurable painted steel construction in white finish.t ti i hit fi i h

Provided with 2’ flex conduits on both ends.

Compact design fits most fluorescent fixtures.

Page 11: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1111

ELECTRICAL INFORMATION

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL1400C-4ACTD-SDT 8.4 8.4 0.120 0.070

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

14 T5 900 95021 T5 1050 110028 T5 1150 122535 T5 1200 -24 T5HO 1100 120039 T5HO 1200 130054 T5HO 1350 140017 T8 1000 110025 T8 1100 120028 T8 1150 125032 T8 1300 135040 T8 1350 140044 T8HO 1350 -51 T8 1400 -59 T8 1400 -86 T8HO 1400 -20 T12 700 775

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

25 T12 750 80030 T12 800 87534 T12 850 97540 T12 950 105075 T12 1300 -95 T12HO 1400 -110 T12HO 1400 -160 T12HO 1400 -215 T12HO 1400 -13 CFL G24q-1 725 85018 CFL G24q-2 800 87521 CFL G24q-3 850 90026 CFL G24q-3 950 100032 CFL G24q-3 1025 110042 CFL G24q-4 1160 125057 CFL G24q-5 1300 -18 CFL 2G11 900 95024 CFL 2G11 1000 107536 CFL 2G11 1050 1150

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

40 CFL 2G11 1100 -50 CFL 2G11 1200 -55 CFL 2G11 1300 -10 CFL GR10q-4 525 60016 CFL GR10q-4 650 75021 CFL GR10q-4 800 87528 CFL GR10q-4 900 97538 CFL GR10q-4 1050 115055 CFL GR10q-4 1300 -32 Circular T9 750 80040 Circular T9 900 105022 Circular T5 850 95040 Circular T5 1100 120055 Circular T5 1300 -32 U-bend T8 825 90034 U-bend T12 875 95040 U-bend T12 800 925

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

BAL1400C-4ACTD-SDT 4-Pin CFL Fluorescent Emergency Ballast 1400 Lumens with Self-Diagnostics

Page 12: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1212

by the A.C. ballast manufacturer. The maximum allowable remote mounting distance is 50 feet.

BAL1400TD Fluorescent Emergency Ballast 1400 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1400 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Compact design fits most fluorescent fixtures.

WARRANTY/LISTING

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

DIMENSIONS

9.413.4””

1.5”

2.4”

* When battery packs are remotmounted, the remote distancecannot exceed ½ the distance fromballast to lamp specified by the A.C.ballast manufacturer. The maximumallowable remote mounting distanceis 50 feet.

STANDARD

MODEL DESCRIPTION

BAL1400TD 1400 Lumens Fluorescent Emergency Ballast with Time Delay

LLELED Test swswitch included.

Page 13: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1313

ELECTRICAL INFORMATION

LAMP COMPATIBILITY CHART

BAL1400TD Fluorescent Emergency Ballast 1400 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL1400TD 3.5 3.8 0.27 0.25

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 900 950T5 21 1050 1100T5 28 1150 1225T5 35 1200 n/aT5HO 24 1100 1200T5HO 39 1200 1300T5HO 54 1350 1400T8 17 1000 1100T8 25 1100 1200T8 28 1150 1250T8 32 1300 1350T8 40 1350 1400T8HO 44 1350 n/aT8 51 1400 n/aT8 59 1400 n/aT8HO 86 1400 n/aT12 20 700 800T12 25 750 800

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T12 30 800 n/aT12 34 850 975T12 40 950 1050T12 75 1300 n/aT12HO 95 1400 n/aT12HO 110 1400 n/aT12HO 160 1400 n/aT12HO 215 1400 n/aCFL G24q-1 13 725 850CFL G24q-2 18 800 875CFL G24q-3 21 850 900CFL G24q-3 26 950 1000CFL G24q-3 32 1025 1100CFL G24q-4 42 1160 1250CFL G24q-5 57 1300 n/aCFL 2G11 18 900 950CFL 2G11 24 1000 1075CFL 2G11 36 1050 1150

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 40 1100 1175CFL 2G11 50 1200 1300CFL 2G11 55 1300 n/aCFL GR10q-4 10 525 600CFL GR10q-4 16 650 750CFL GR10q-4 21 800 875CFL GR10q-4 28 900 975CFL GR10q-4 38 1050 1150CFL GR10q-4 55 1300 n/aCircular T9 20 600 675Circular T9 32 750 800Circular T9 40 900 1050Circular T5 22 850 950Circular T5 40 1100 1200Circular T5 55 1300 n/aU-bend T8 32 825 900U-bend T12 34 875 950U-bend T12 40 800 925

Page 14: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1414* When battery packs are remote mounted, the remote distance cannot exceed 1/2 of the distance from ballast to lamp specifieby the A.C. ballast manufacturer. The maximum allowable remote mounting distance is 50 feet.

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1400 lumens.

ELECTRICAL

• Universal 120-277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

• Self-diagnostics feature performs monthly biannual andannual tests to ensure reliable operation and meet electricaland life safety codes.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

DIMENSIONS

9.413.4””

1.5”

2.4”

* When battery packs are remotmounted, the remote distancecannot exceed ½ the distance fromballast to lamp specified by the A.C.ballast manufacturer. The maximumallowable remote mounting distanceis 50 feet.

Bi-ColorLED Test switch included.

STANDARD

MODEL DESCRIPTION

BAL1400TD-SDT 1400 Lumens Fluorescent Emergency Ballast with Time Delay and Self-Diagnostics

WARRANTY/LISTING

BAL1400TD-SDT Fluorescent Emergency Ballast 1400 Lumens With Self-Diagnostics

Page 15: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1515

ELECTRICAL INFORMATION

LAMP COMPATIBILITY CHART

BAL1400TD-SDT Fluorescent Emergency Ballast 1400 Lumens With Self-Diagnostics

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL1400TD-SDT 8.4 8.4 0.12 0.07

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 900 950T5 21 1050 1100T5 28 1150 1225T5 35 1200 n/aT5HO 24 1100 1200T5HO 39 1200 1300T5HO 54 1350 1400T8 17 1000 1100T8 25 1100 1200T8 28 1150 1250T8 32 1300 1350T8 40 1350 1400T8HO 44 1350 n/aT8 51 1400 n/aT8 59 1400 n/aT8HO 86 1400 n/aT12 25 750 800

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T12 30 800 n/aT12 34 850 975T12 40 950 1050T12 75 1300 n/aT12HO 95 1400 n/aT12HO 110 1400 n/aT12HO 160 1400 n/aT12HO 215 1400 n/aCFL G24q-1 13 725 850CFL G24q-2 18 800 875CFL G24q-3 21 850 900CFL G24q-3 26 950 1000CFL G24q-3 32 1025 1100CFL G24q-4 42 1160 1250CFL G24q-5 57 1300 n/aCFL 2G11 18 900 950CFL 2G11 24 1000 1075CFL 2G11 36 1050 1150

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 40 1100 1175CFL 2G11 50 1200 1300CFL 2G11 55 1300 n/aCFL GR10q-4 10 525 600CFL GR10q-4 16 650 750CFL GR10q-4 21 800 875CFL GR10q-4 28 900 975CFL GR10q-4 38 1050 1150CFL GR10q-4 55 1300 n/aCircular T9 32 750 800Circular T9 40 900 1050Circular T5 22 850 950Circular T5 40 1100 1200Circular T5 55 1300 n/aU-bend T8 32 825 900U-bend T12 34 875 950U-bend T12 40 800 925

Page 16: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1616

BAL1400TD-CW

* When battery packs are remote mounted, the remote distance cannot exceed 1/2 of the distance from ballast to lamp specifieby the A.C. ballast manufacturer. The maximum allowable remote mounting distance is 50 feet.

Cold Weather Rated Fluorescent Emergency Ballast 1400 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1400 lumens.

• Rated for extreme cold temperature applications (-20°C -+50°C).

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in white finish.

• Compact design fits most fluorescent fixtures.

WARRANTY/LISTING

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations.

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

DIMENSIONS

9.413.4””

1.5”

2.4”

* When battery packs are remotmounted, the remote distancecannot exceed ½ the distance fromballast to lamp specified by the A.C.ballast manufacturer. The maximumallowable remote mounting distanceis 50 feet.

STANDARD

MODEL DESCRIPTION

BAL1400TD-CW 1400 Lumens Cold Weather Rated Fluorescent Emergency Ballast with Time Delay

LLELED Test swswitch included.

Page 17: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1717

ELECTRICAL INFORMATION

BAL1400TD-CW Cold Weather Rated Fluorescent Emergency Ballast 1400 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL1400TD-CW 3.5 3.8 0.27 0.25

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 900 950T5 21 1050 1100T5 28 1150 1225T5 35 1200 n/aT5HO 24 1100 1200T5HO 39 1200 1300T5HO 54 1350 1400T8 17 1000 1100T8 25 1100 1200T8 28 1150 1250T8 32 1300 1350T8 40 1350 1400T8HO 44 1350 n/aT8 51 1400 n/aT8 59 1400 n/aT8HO 86 1400 n/aT12 20 700 800T12 25 750 800

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T12 30 800 n/aT12 34 850 975T12 40 950 1050T12 75 1300 n/aT12HO 95 1400 n/aT12HO 110 1400 n/aT12HO 160 1400 n/aT12HO 215 1400 n/aCFL G24q-1 13 725 850CFL G24q-2 18 800 875CFL G24q-3 21 850 900CFL G24q-3 26 950 1000CFL G24q-3 32 1025 1100CFL G24q-4 42 1160 1250CFL G24q-5 57 1300 n/aCFL 2G11 18 900 950CFL 2G11 24 1000 1075CFL 2G11 36 1050 1150

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 40 1100 1175CFL 2G11 50 1200 1300CFL 2G11 55 1300 n/aCFL GR10q-4 10 525 600CFL GR10q-4 16 650 750CFL GR10q-4 21 800 875CFL GR10q-4 28 900 975CFL GR10q-4 38 1050 1150CFL GR10q-4 55 1300 n/aCircular T9 20 600 675Circular T9 32 750 800Circular T9 40 900 1050Circular T5 22 850 950Circular T5 40 1100 1200Circular T5 55 1300 n/aU-bend T8 32 825 900U-bend T12 34 875 950U-bend T12 40 800 925

LAMP COMPATIBILITY CHART

Page 18: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1818

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 3000 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 14.4V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in red finish.

• Provided with 2’ flex conduit.

WARRANTY/LISTING

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO, Cir-cular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lampsin emergency mode. Refer to the chart on the next page for acomplete list of compatible lamps.

DIMENSIONS

16.316.4””

1.751.75””

5.55.6””

* When battery packs are remotmounted, the remote distancecannot exceed 1/2 of the distancefrom ballast to lamp specified bythe A.C. ballast manufacturer.The maximum allowable remotemounting distance is 50 feet.

LED Test switch included.STANDARD

MODEL DESCRIPTION

BAL3000TD 3000 Lumens Fluorescent Emergency Ballast with Time Delay

BAL3000TDFluorescent Emergency Ballast 3000 Lumens

Page 19: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

1919

ELECTRICAL INFORMATION

LAMP COMPATIBILITY CHART

BAL3000TDFluorescent Emergency Ballast 3000 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL3000TD 3.7 4.0 0.27 0.25

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 1150 1200T5 21 1650 1750T5 28 2250 2400T5 35 2700 2800T5HO 24 1750 1850T5HO 39 2650 2750T5HO 54 2900 3000T8 17 1150 1200T8 25 1650 1800T8 28 1700 1800T8 32 2850 2900T8 40 2900 2950T8HO 44 2900 n/aT8 51 3000 n/aT8 59 3000 n/aT8HO 86 2950 n/aT12 20 900 950T12 25 1100 1200T12 30 1550 1600

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T12 34 1700 1800T12 40 2250 2400T12 75 2950 n/aT12 85 3000 n/aT12HO 95 3000 n/aT12HO 110 3000 n/aT12HO 160 3000 n/aT12HO 215 3000 n/aCFL G24q-1 13 825 900CFL G24q-2 18 925 1000CFL G24q-3 21 1025 1100CFL G24q-3 26 1250 1300CFL G24q-3 32 1575 1700CFL G24q-4 42 1750 1850CFL G24q-5 57 2350 n/aCFL 2G11 18 1100 1200CFL 2G11 24 1350 1400CFL 2G11 36 1650 1800CFL 2G11 40 1750 1850CFL 2G11 36 1650 1800

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 40 1750 1850CFL 2G11 50 2200 2300CFL 2G11 55 2450 n/aCFL 2G11 80 2750 n/aCFL GR10q-4 10 575 650CFL GR10q-4 16 775 900CFL GR10q-4 21 1050 1200CFL GR10q-4 28 1450 1550CFL GR10q-4 38 1675 1800CFL GR10q-4 55 2350 2500Circular T9 20 750 800Circular T9 32 1100 1250Circular T9 40 1450 1600Circular T5 22 1400 1550Circular T5 40 1650 1800Circular T5 55 2250 2400U-bend T8 32 1100 1200U-bend T12 34 1025 1100U-bend T12 40 975 1050

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 20: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2020* When battery packs are remote mounted, the remote distance cannot exceed 1/2 of the distance from ballast to lamp specifieby the A.C. ballast manufacturer. The maximum allowable remote mounting distance is 50 feet.

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 3000 lumens.

ELECTRICAL

• Universal 120-277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 14.4V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp(s) for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

• Self-diagnostics feature performs monthly biannual andannual tests to ensure reliable operation and meet electricaland life safety codes.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Durable painted steel construction in red finish.

• Provided with 2’ flex conduit.

WARRANTY/LISTING

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO, Cir-cular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lampsin emergency mode. Refer to the chart on the next page for acomplete list of compatible lamps.

DIMENSIONS

16.316.4””

1.751.75””

5.55.6””

* When battery packs are remotemounted, the remote distancecannot exceed 1/2 of the distancefrom ballast to lamp specified bythe A.C. ballast manufacturer.The maximum allowable remotemounting distance is 50 feet.

Bi-ColorLED Test switch included.

STANDARD

MODEL DESCRIPTION

BAL3000TD-SDT 3000 Lumens Fluorescent Emergency Ballast with Time Delay and Self-Diagnostics

BAL3000TD-SDTFluorescent Emergency Ballast 3000 Lumens with Self-Diagnostics

Page 21: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2121

ELECTRICAL INFORMATION

LAMP COMPATIBILITY CHART

BAL3000TD-SDTFluorescent Emergency Ballast 3000 Lumens with Self-Diagnostics

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL3000TD 14.3 14..3 0.17 0.09

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 1150 1200T5 21 1650 1750T5 28 2250 2400T5 35 2700 2800T5HO 24 1750 1850T5HO 39 2650 2750T5HO 54 2900 3000T8 17 1150 1200T8 25 1650 1800T8 28 1700 1800T8 32 2850 2900T8 40 2900 2950T8HO 44 2900 n/aT8 51 3000 n/aT8 59 3000 n/aT8HO 86 2950 n/aT12 20 900 950T12 25 1100 1200T12 30 1550 1600

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T12 34 1700 1800T12 40 2250 2400T12 75 2950 n/aT12 85 3000 n/aT12HO 95 3000 n/aT12HO 110 3000 n/aT12HO 160 3000 n/aT12HO 215 3000 n/aCFL G24q-1 13 825 900CFL G24q-2 18 925 1000CFL G24q-3 21 1025 1100CFL G24q-3 26 1250 1300CFL G24q-3 32 1575 1700CFL G24q-4 42 1750 1850CFL G24q-5 57 2350 n/aCFL 2G11 18 1100 1200CFL 2G11 24 1350 1400CFL 2G11 36 1650 1800CFL 2G11 40 1750 1850CFL 2G11 36 1650 1800

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 40 1750 1850CFL 2G11 50 2200 2300CFL 2G11 55 2450 n/aCFL 2G11 80 2750 n/aCFL GR10q-4 10 575 650CFL GR10q-4 16 775 900CFL GR10q-4 21 1050 1200CFL GR10q-4 28 1450 1550CFL GR10q-4 38 1675 1800CFL GR10q-4 55 2350 2500Circular T9 20 750 800Circular T9 32 1100 1250Circular T9 40 1450 1600Circular T5 22 1400 1550Circular T5 40 1650 1800Circular T5 55 2250 2400U-bend T8 32 1100 1200U-bend T12 34 1025 1100U-bend T12 40 975 1050

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 22: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2222

BAL500LPTDLow Profile Fluorescent Emergency Ballast 500 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or existingfluorescent fixtures in to unobtrusive emergency lighting.

• Operates one lamp in the emergency mode for a minimumof 90-minutes.

• Provides a maximum initial lumen output of 500 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 4.8V long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material andworkmanship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• Suitable for use in sealed and gasketed fixtures.

• UL Listed for damp locations (0°C – 50°C).

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one T5, T5HO, T8, T12, Circular T5/T9, U-bend T8/T12 and 4-Pin long CFL lamp in emergency mode. Refer tothe chart on the next page for a complete list of compatiblelamps.

DIMENSIONS

* When battery packs are remotmounted, the remote distance cannotexceed 1/2 of the distance fromballast to lamp specified by the A.C.ballast manufacturer. The maximumallowable remote mounting distanceis 50 feet.

LED Test switch included.

STANDARD

MODEL DESCRIPTION

BAL500LPTD 500 Lumens Low-Profile Fluorescent Emergency Ballast with Time Delay

11.7”

2”

1.18”

WWAARRRRAANNTTYY // LILISSTTIINNGG

Page 23: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2323

ELECTRICAL INFORMATION

BAL500LPTDLow Profile Fluorescent Emergency Ballast 500 Lumens

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL500LPTD 3.0 3.0 0.130 0.130

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 21 450 n/aT5 28 500 n/aT5HO 24 475 n/aT8 25 375 n/aT8 28 450 n/aT8 32 475 n/aT8 40 500 n/aT12 30 400 n/aT12 34 425 n/aT12 40 450 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 36 375 n/aCFL 2G11 40 425 n/aCFL GR10q-4 38 400 n/aCircular T9 32 350 n/aCircular T9 40 425 n/aCircular T5 40 450 n/aCircular T5 55 500 n/aU-bend T8 32 425 n/aU-bend T12 34 375 n/aU-bend T12 40 425 n/a

LAMP COMPATIBILITY CHART

Page 24: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2424

BAL700LPTD Low Profile Fluorescent Emergency Ballast 700 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 700 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamps for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• Suitable for use in sealed and gasketed fixtures.

• UL Listed for damp locations (0°C – 50°C).

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lamps in emergencymode. Refer to the chart on the next page for a complete listof compatible lamps.

DIMENSIONS

* When battery packs are remotemounted, the remote distancecannot exceed 1/2 of the distancefrom ballast to lamp specified bythe A.C. ballast manufacturer.The maximum allowable remotemounting distance is 50 feet.

LED Test switch included.

STANDARD

11.7”

2”

1.18”

MODEL DESCRIPTION

BAL700LPTD 700 Lumens Low-Profile Fluorescent Emergency Ballast with Time Delay

WARRANTY / LISTING

Page 25: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2525

ELECTRICAL INFORMATION

BAL700LPTD Low Profile Fluorescent Emergency Ballast 700 Lumens

LAMP COMPATIBILITY CHART

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL700LPTD 3.2 3.2 0.13 0.13

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 21 575 650T5 28 675 n/aT5 35 700 n/aT5HO 24 650 n/aT5HO 39 700 n/aT8 17 575 625T8 25 625 675T8 28 630 n/aT8 32 650 n/aT8 40 700 n/aT12 30 500 n/aT12 34 575 n/aT12 40 625 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL G24q-4 42 675 n/aCFL 2G11 36 600 n/aCFL 2G11 40 625 n/aCFL 2G11 50 650 n/aCFL GR10q-4 38 650 n/aCircular T9 20 400 500Circular T9 32 450 550Circular T9 40 550 n/aCircular T5 40 600 n/aCircular T5 55 700 n/aU-bend T8 32 575 650U-bend T12 34 550 600U-bend T12 40 600 n/a

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 26: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2626

BAL1400LPTD Low Profile Fluorescent Emergency Ballast 1400 Lumens

14¼”

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1400 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 12V long life, maintenance-free, rechargeable sealed NiCdbattery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and workman-ship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, T8HO, T12HO,Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFLlamps in emergency mode. Refer to the chart on the nextpage for a complete list of compatible lamps.

* When battery packs are remote mountedthe remote distance cannot exceed 1/2 ofthe distance from ballast to lamp specified bythe A.C. ballast manufacturer. The maximumallowable remote mounting distance is 50 feet.

STANDARD

2⅛”

1¼”

MODEL DESCRIPTION

BAL1400LPTD 1400 Lumens low-profile fluorescent emergency ballast with time delay

WWAARRRRAANNTTYY / / LISTING

DIMENSIONS

LED TLED Teestst switch includswitch included.

Page 27: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2727

ELECTRICAL INFORMATION

BAL1400LPTDLow Profile Fluorescent Emergency Ballast 1400 Lumens

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BAL1400LPTD 3.1 3.1 0.130 0.130

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

14 T5 800 85021 T5 900 102528 T5 1250 -39 T5HO 1300 -54 T5HO 1350 -17 T8 1050 110025 T8 1250 130032 T8 1300 135040 T8 1350 140059 T8 1400 -86 T8HO 1400 -20 T12 700 80025 T12 800 85030 T12 900 975

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

34 T12 950 102540 T12 1050 110075 T12 1300 -85 T12 1400 -95 T12HO 1400 -110 T12HO 1400 -160 T12HO 1400 -215 T12HO 1400 -13 CFL G24q1 750 80018 CFL G24q2 900 100026 CFL G24q3 1025 110032 CFL G24q3 1200 125042 CFL G24q4 1300 -57 CFL G24q5 1350 -

WATTS LAMP TYPE

INITIAL LUMENS

1-LAMP 2-LAMP

18 CFL 2G11 900 105024 CFL 2G11 1100 115036 CFL 2G11 1200 127540 CFL 2G11 1250 -50 CFL 2G11 1325 -55 CFL 2G11 1350 -32 Circular T9 750 80040 Circular T9 900 105022 Circular T5 850 95040 Circular T5 1100 120050 Circular T5 1300 135032 U-bend T8 825 90034 U-bend T12 875 95040 U-bend T12 800 925

Page 28: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2828

BALT5-500TD Low Profile T5 Fluorescent Emergency Ballast 500 Lumens

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one lamp in the emergency mode for a minimumof 90-minutes.

• Provides a maximum initial lumen output of 500 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 3.6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamp for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

WARRANTY/LISTING

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one T5, T8, T12, Circular T5/T9 and U-bend T8/T12lamp in emergency mode. Refer to the chart on the next pagefor a complete list of compatible lamps.

DIMENSIONS

14.314.25””

1.251.21””

1.251.28””

LED Test switch included.

STANDARD

* When battery packs are remotemounted, the remote distancecannot exceed 1/2 of the distancefrom ballast to lamp specified bythe A.C. ballast manufacturer.The maximum allowable remotemounting distance is 50 feet.

MODEL DESCRIPTION

BALT5-500TD 500 Lumens Low Profile T5 Fluorescent Emergency Ballast with Time Delay

Page 29: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

2929

ELECTRICAL INFORMATION

BALT5-500TD Low Profile Fluorescent Emergency Ballast 500 Lumens

LAMP COMPATIBILITY CHART

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BALT5-500TD 2.7 2.7 0.130 0.130

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 21 450 n/aT5 28 500 n/aT8 32 425 n/aT12 34 400 n/aCircular T9 32 350 n/aCircular T5 22 375 n/aU-bend T8 32 425 n/aU-bend T12 34 375 n/a

Page 30: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3030

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 800 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 6V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamps for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuitprotection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lamps in emergencymode. Refer to the chart on the next page for a complete listof compatible lamps.

DIMENSIONS

17.7517.6””

1.251.19””

1.251.28””

* When battery packs are remotemounted, the remote distance cannotexceed 1/2 of the distance from ballastto lamp specified by the A.C. ballastmanufacturer. The maximum allowableremote mounting distance is 50 feet.

STANDARD

MODEL DESCRIPTION

BALT5-800TD 800 Lumens Low Profile T5 Fluorescent Emergency Ballast with Time Delay

BALT5-800TD Low Profile T5 Fluorescent Emergency Ballast 800 Lumens

WWAARRRRAANNTTYY / LI / LISTSTIINNGG

LELED TD estswitcswitch included.

Page 31: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3131

ELECTRICAL INFORMATION

BALT5-800TD Low Profile T5 Fluorescent Emergency Ballast 800 Lumens

LAMP COMPATIBILITY CHART

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BALT5-800TD 2.7 2.7 0.130 0.130

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 21 500 n/aT5 28 750 n/aT5 35 800 n/aT5HO 24 725 n/aT5HO 39 750 n/aT5HO 54 800 n/aT8 28 650 n/aT8 32 700 n/aT8 40 675 n/aT12 40 650 n/aCFL 2G11 36 675 n/aCFL 2G11 40 675 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 50 725 n/aCFL 2G11 55 725 n/aCFL GR10q-4 28 500 550CFL GR10q-4 38 600 n/aCircular T9 32 400 n/aCircular T9 40 475 n/aCircular T5 22 425 n/aCircular T5 40 650 n/aCircular T5 55 725 n/aU-bend T8 32 450 n/aU-bend T12 40 400 n/a

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 32: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3232

ILLUMINATION

• Works with or without an AC ballast to convert new or exist-ing fluorescent fixtures in to unobtrusive emergency lighting.

• Operates one or two lamps in the emergency mode for aminimum of 90-minutes.

• Provides a maximum initial lumen output of 1300 lumens.

ELECTRICAL

• Dual 120/277 voltage.

• Charge rate/power “ON” LED indicator light and push-to-testswitch for mandated code compliance testing.

• 8.4V long life, maintenance-free, rechargeable sealed NiCd battery.

• Internal solid-state transfer switch automatically connectsthe internal battery to fluorescent lamps for minimum90-minute emergency illumination.

• Fully automatic solid-state, two rate charger initiates batterycharging to recharge a discharged battery in 24 hours.

• Time delay enhancement to overcome end-of-life circuit protection.

MOUNTING

• Suitable for installation inside, on top or in remote* of the fixture.

• Can be used in both switched and unswitched fixtures.

• UL Listed for factory or field installation.

HOUSING

• Low profile galvanized steel construction.

• Compact design fits most fluorescent fixtures.

• Five year warranty against defects in material and work-manship (lamps excluded).

• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,Local and State Codes.

• UL Listed for damp locations (0°C – 50°C).

• Suitable for use in sealed and gasketed fixtures.

LAMP COMPATIBILITY

• Compatible with most one-, two-, three-, and four-lampelectronic standard and dimming AC ballasts.

• Operates one or two T5, T5HO, T8, T12, Circular T5/T9, U-bend T8/T12, 4-Pin CFL and long CFL lamps in emergencymode. Refer to the chart on the next page for a complete listof compatible lamps.

DIMENSIONS

21.521.5””

1.151.19””

1.221.28””

* When battery packs areremote mounted, the remotedistance cannot exceed 1/2of the distance from ballastto lamp specified by the A.C.ballast manufacturer. Themaximum allowable remotemounting distance is 50 feet.

iinn

STANDARD

MODEL DESCRIPTION

BALT5-1300TD 1300 Lumens Low-Profile T5 Fluorescent Emergency Ballast with Time Delay

BALT5-1300TD Low Profile T5 Fluorescent Emergency Ballast 1300 Lumens

LLED TED Teests switswitchch cluded.

WWAARRRRAANNTTYY / LI / LISTSTIINNGG

Page 33: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3333

ELECTRICAL INFORMATION

BALT5-1300TDLow Profile T5 Fluorescent Emergency Ballast 1300 Lumens

LAMP COMPATIBILITY CHART

CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A)

120V 277V 120V 277V

BALT5-1300TD 2.7 2.7 0.130 0.130

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

T5 14 750 800T5 21 850 950T5 28 1100 n/aT5 35 1250 n/aT5HO 24 800 n/aT5HO 39 1200 n/aT5HO 54 1300 n/aT8 17 950 1050T8 25 1000 1100T8 28 1050 1100T8 32 1150 n/aT8 40 1200 n/aT12 20 850 n/aT12 30 975 n/aT12 34 1050 n/aT12 40 1200 n/a

LAMP TYPE WATTS INITIAL LUMENS

1-Lamp 2-Lamp

CFL 2G11 36 1025 n/aCFL 2G11 40 1050 n/aCFL 2G11 50 1100 n/aCFL 2G11 55 1150 n/aCFL GR10q-4 28 775 850CFL GR10q-4 38 900 n/aCircular T9 20 600 675Circular T9 32 750 n/aCircular T9 40 850 n/aCircular T5 22 975 n/aCircular T5 40 1050 n/aCircular T5 55 1200 n/aU-bend T8 29 725 n/aU-bend T8 32 775 n/aU-bend T12 34 675 n/aU-bend T12 40 700 n/a

NOTE: In 2-lamp operation, lumens are equally split between the two lamps.

Page 34: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3434

SPS Series Inverters

STANDARD

DESCRIPTION

• Mini-electrical inverter systems for powering up to220W/250VA of incandescent, uorescent, induction or LEDlighting loads. Pulse width modulated (PWM) output designprovides clean, 60 Hz. sinusoidal emergency power to loads.

• Models are available for surface, recessed or T-Grid mountingas required.

ELECTRICAL SPECIFICATIONS

Input• Input Voltages: 120 or 277VAC ±10%• Input Frequencies: 60Hz ±2%• Input Protection: AC Line Fuses

Output• Output Voltages: (60Hz) 120 or 277VAC• Ef ciency Rating: 98% at full rated load (line)• Waveform: Sinusoidal (digitally controlled)• Static Voltage: ±5% during battery discharge. 0-100% linear load.• Output Frequencies: 60Hz. ±0.3Hz during emergency cycle• Output Distortion: Less than 3% THD (linear load)• Transfer Time: Less than 1.0 second• Load Power Factor Range: 0.44 Lead to 0.44 Lag• Minimum Loading: 0% of rated system capacity• Output Protection: Line and inverter fuses

HOUSING

• Heavy duty steel cabinet is nished in white baked-on powderpaint providing scratch and corrosion resistance.

• Optional special color paint (-SP) nishes are available,consult factory.

• Surface Mount (Standard Models): Surface mount modelsare designed for mounting to walls by means of keyhole slotsprovided in the back of the unit housing.

• Recess Mount (SPS-55/125, SPS-110/125 Only): Recess modelsprovide recess mounting holes on both sides of the enclosure.

• T-Grid Mount (SPS-55/125, SPS-110/125 Only): Housingdesign allows simple drop-in installation between T-grid runs.Safety wires (supplied by others) are required for attachmentto building structure.

WARRANTY / LISTING

• Unit: (excluding lamps) Full coverage against defects inmaterials and workmanship for 3 years from date of shipment.

• Battery: 3 years full warranty plus an additional 7 years ofpro-rata coverage.

• All models are UL924 Listed and meet NFPA 101 Life SafetyCode, NEC, OSHA, Local and State Codes. Optional T-Gridmodels are plenum rated.

• UL Listed for damp locations (20° - 30°C).

DIMENSIONS

Surface Mount MoModelsdels

13⅛”

18⅛”

Optional Ceiling T-grid Mount Housing

8”

23⅞” 63/16”

89/16”

4¾”

Optional RecessedMount Housing

RecessedMount Models

Standard Surface Mount Housings

11¾”

16¾” 6⅜” 4⅜”(models SPS-

55/125 & SPS-110/125)

(models SPS-220/250

& SPS-110/250)

TEST AC CHG INV

PUSH ON ON ON

TEST AC CHG INV

PUSH ON ON ON

eiliiliCeilingngT-GGrid Mount Modelsrid Mount Models

Emergency Power Systems

MMOUOUNNTITINNGGTTrTrr

Oe Sin

Output Powere Sinusoidalusuuuu

Page 35: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3535

GENERAL SPECIFICATIONS

MODEL NUMBER

INPUT / OUT-PUT VOLTS

CAPACITY for 1½ Hrs. SYSTEM WEIGHT* ON-LINESYSTEM

EFFICIENCY (full load)

NUMBERof BAT-TERIES

BATTERY VOLTAGE

(VDC)

BATTERY CUR-RENT(amps)

AC INPUT CURRENT THERMAL OUTPUT in BTUs

WATTS VA Lbs. Kg. 120VAC (max)

277VAC (max)

ON-LINE EMER-GENCY

SPS-55/125 120/277 55 125 30.0 14 98% 2 24 3.4 1.2 0.52 9 90SPS-110/125 120/277 110 125 42.0 17 98% 2 24 5.7 1.2 0.52 9 95SPS-110/250 120/277 110 250 45.2 21 98% 4 48 3.3 2.4 1.10 18 163SPS-220/250 120/277 220 250 60.0 27 98% 4 48 5.6 2.4 1.10 18 167* System weights shown include installed batteries

FEATURES

• For powering incandescent, uorescent, induction and LED xtures *• Sinusoidal output eliminates compatibility problems• Universal 120/277VAC, 60Hz. input/output• Unit capacities up to 220W/250VA• “Soft Start” design reduces xture inrush current• Unit may be installed up to 1,000 feet from controlled xture(s)• Surface, recessed or T-Grid mount models• Lumen output from xture is 100% of nominal• Unique design eliminates compatibility problems with LED

drivers as well as uorescent and induction ballasts• Compatible with dimming ballasts• Normally-ON and/or Normally-OFF load output• Provisions for local switching capability - Always on during

emergency conditions regardless of local switch position• Emergency xtures can be ON, OFF or SWITCHED• Solid-state, line latched low voltage disconnect provides

protection against battery deep discharge• Long life, maintenance-free lead-calcium battery• Momentary test switch• AC-ON, Charge-ON and Inverter-ON LED indicators

* Consult factory for compatibility for other lamp type

WIRING

Connection to an unswitched AC circuit is required by the NEC. Wiring access is provided for by conduit knockouts in the unit housing. SPS-55/125 and SPS-110/125 models also provide knockouts in the back of the housing for rear wiring from standard electrical boxes when surface mounting.

LOAD COMPATIBILITY

SPS model’s clean, sinusoidal AC output will operate incandescent lamps as well as all common uorescent, induction and LED lamp types. Consult factory for compatibility with all other lamp types.

Lighting loads are driven at 100% output for the entire emergency power cycle. This outstanding feature translates into greater occupant egress vision and safety.

SYSTEM OPTIONSADD SUFFIX DESCRIPTION

-S Surface Mount Housing-R Recess Mount Housing (3)

-T Plenum Rated Ceiling T-Grid Mount Housing (3)

-SP Special Housing Color (specify)-4C 4 Output Circuit Switching-RTS Remote Test Switch Panel-AO Adjustable Output/Dimmer Bypass

(1) (2)

(1) Other options available. Consult factory.(2) Some options may impact product UL listing. Consult factory.(3) Available with SPS-55/125 and SPS-110/125 models only.

The SPS Series is designed to provide up to 220W/250VA of emergency power to incandescent, uorescent, induction and/or LED xtures. The SPS unit provides clean, sinusoidal AC output power allowing it to be remotely mounted up to 1,000 feet away from the controlled xture(s). Unlike a ballast uorescent emergency pack, the SPS provides power to the input side of the xture, (including the ballast) eliminating any chance of incompatibility. The SPS Series is designed primarily for surface mounting, however, the SPS-55/125 and SPS-110/125 models provide optional housings for recessed or ceiling T-Grid mounting if required. All SPS systems will provide emergency power output for a minimum of 90-minutes.

SPS Series InvertersEmergency Power Systems

Page 36: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3636

Upon failure of the normal utility power the SPS unit is automatically turned on by a solid-state switching circuit and provides a minimum of 90-minutes of emergency power to the connected load. Lumen output willbe maintained at 100% of the lamp’s rating throughout the entire duration.

A solid-state low voltage disconnect circuit is used to protect the battery from being severely damaged by a deep discharge. When normal utility power is restored, the unit switches the load back to normal utility operation and the fully automatic, temperature compensated, dual mode charger begins to restore the battery; bringing it to full charge within UL924 speci ed parameters. A brownout sensing circuit insures proper operation during “low line” conditions.

All SPS Systems provide a monitoring panel on the front of the unit to show operating status at all times. The panel provides a test switch for user initiated system tests and a 3-LED array that provides an intuitive visual indication of unit readiness.

The SPS System’s sinusoidal AC output design eliminates voltage drop and proximity concerns. This allows added exibility in installation location as SPS units can be installed hundreds of feet from the units they power. This means SPS units to be located conveniently out of sight in closets or utility rooms without interrupting architectural aesthetics.

In lighting applications, no special or additional emergency xtures are necessary. Simply designate and connect existing lighting xtures, either interior or exterior, to the SPS unit for emergency operation eliminating the need for exposed, stand-alone emergency luminaires.

Compared to traditional discrete emergency lighting units, the SPS Series provides emergency illumination from a single power source resulting in lower maintenance overhead and routine testing expenses.

SPS units lower installation costs by powering existing lighting xtures during emergencies. And because connected xtures are driven at full brilliancy, they provide far superior egress lighting and deliver improved occupant safety.

IMPROVED AESTHETICS

SPS SYSTEM ADVANTAGES

SYSTEM STATUS MONITORING PANEL

BATTERIES AND CHARGER

BatteryBattery: Sealed Lead Calcium (10 year life)

Battery Voltage: 24VDC for SPS-55/125, SPS-110/125 models and 48VDC for SPS110/250, SPS220/250 models

Runtime: 90-minutes standard - based on battery performance at (25ºC). Other runtimes available, consult factory.

Battery Protection: Low Voltage Battery Disconnect protects the battery from being severely damaged by deep discharge during prolonged power failures.

DC Overload and Short Circuit Protection provided by a DC input breaker and fuse.

ChargerCharger Type: Fully automatic, temperature compensated, dual-mode charger

Power Consumption (Charger Only):

15W maximum (2.5W in standby) for SPS-55/125, and SPS-110/125 models

30W maximum (5W in standby) for SPS110/250, and SPS220/250 models

Recharge Duty Cycle: Meets UL924 requirements

Battery Circuit Breaker: Also used as battery isolator

Controls: Momentary test switch, AC-ON,

Charge-ON and Inverter-ON LED indicator lights

Safety Circuitry: AC Lockout prevents battery discharge prior to initial unit power-up.

Brownout Protection automatically switches the unit to emergency mode when utility voltage is signi cantly reduced.

EnvironmentalAltitude: < 10,000 feet (3,000m) above sea level without derating.

Operating Temperature Range: 20ºC to 30ºC

NOTE: Optimum system performance between 20°C and 30°C; temperatures outside of this range will affect battery performance and life.

Relative Humidity: 95% non-condensing

OPERATION

SPS Series InvertersEmergency Power Systems

Page 37: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3737

WIRING DIAGRAMS

120VAC Connections

277VAC Connections

SUGGESTED SPECIFICATIONS

An inverter system with sinusoidal output shall be supplied capable of powering any combination of lighting xtures, including incandescent, uorescent, induction and/or LED light sources without compatibility problems.

The system shall transfer in less than 1.0 second to reliably back up lighting xtures without loss of illumination and operate any and all connected lighting xtures at full lumen output during the complete 90-minute discharge cycle.

The input voltage shall be the same as the output voltage and shall be single phase 120/277 volts, 60 Hz. Output capacity will be (55W/125VA) / (110 Watts/125VA) / (110 Watts/250VA) / (220 Watts/250VA) for a minimum duration of 90-minutes.

The design shall be a standby, off-line inverter with on-line ef ciency of 98%; on-line double conversion UPS systems shall not be considered acceptable alternatives. SPS System output shall be a PWM generated sine wave with less than 3% total harmonic distortion. The system shall also provide short circuit and overload protection as standard.

An intuitive three LED display shall provide system operational information at a glance and alert user to any malfunction in system performance. Authorized maintenance personnel shall have access to the system’s controls while being protected from any live exposed connections.

Protective devices shall include AC Line fuses, DC input breaker and a DC input fuse. The entire SPS system, including batteries, shall be incorporated into compact cabinetry which shall have provisions for (surface, recessed or T-Grid) mounting.

System shall utilize a sealed lead calcium battery with a 10 year design life. The charger shall be temperature compensated, dual mode type, and recharge the batteries as per UL924 guidelines. Entire system shall be tested, approved, and labeled to UL924 Emergency Lighting and Power Systems standards. T-Grid models will be plenum rated.

SPS Series InvertersEmergency Power Systems

Page 38: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3838

STANDARD

DESCRIPTION

• MPS Series inverter systems are designed to providesinusoidal AC emergency power to connected incandescent, uorescent or LED xtures of between 20 and 55 watts.

• Surface, recessed or ceiling T-Grid mount models are designedfor easy installation either on or near controlled xtures. MPSmodels support Normally-ON, Normally-OFF, switched operationor any combination thereof (see wiring diagram).

ELECTRICAL SPECIFICATIONS

Input• Input Voltages: 120 or 277VAC ±10%• Input Frequencies: 60Hz ±2%• Input Protection: Provided by Service Panel, Rated 20A max.

Output• Output Voltages: 120 or 277VAC (60Hz)• E ciency Rating: 98% at full rated load (line)• Waveform: Sinusoidal (digitally controlled, PWM design)• Static Voltage: ±5% during battery discharge. 0-100% linear load.• Output Frequencies: 60Hz. ±0.3Hz during emergency cycle• Output Distortion: Less than 3% THD (linear load)• Transfer Time: Less than 1.0 second• Load Power Factor Range: 0.44 Lead to 0.44 Lag• Minimum Loading: 0% of rated system capacity• Output Protection: Inverter fuse

HOUSING

• Heavy duty steel cabinet is nished in white baked-on powderpaint providing scratch and corrosion resistance.

• Optional paint color (-SP) nishes available, consult factory.

MOUNTING

• Surface Mount: Surface mount models are designed formounting to walls by means of keyhole slots provided in theback of the unit housing.

• Recess Mount: Recess models provide recess mounting holes onboth sides of the enclosure.

• T-Grid Mount: Housing design allows simple drop-ininstallation between t-grid runs. Safety wires (supplied byothers) are required for attachment to building structure.

WARRANTY / LISTING

• Unit: (excluding lamps) Full coverage against defects inmaterials and workmanship for 3 years from date of shipment.

• Battery: 3 years (Lead-Acid-5 yrs NiCd) full warranty plus anadditional 7 years of pro-rata coverage.

• All models are UL924 Listed and meet NFPA 101 Life SafetyCode, NEC, OSHA, Local and State Codes. Optional T-Gridmodels are plenum rated.

• UL Listed for damp locations (0° - 50°C for NiCad models and20° - 30°C for lead-calcium models).

DIMENSIONSStandard Surface Mount Housings

Recessed Mount Housings

7⅜”

14¾” 4⅜” 3⅛”(models MPS-20

& MPS-32)

(models MPS-35

& MPS-55)

els

True SinusoidalOutput Power

8⅞”

16¼” ½” Extrusion from wall after installation

TEST AC CHG INV

PUSH ON ON ON

MModod

Optional Ceiling T-grid Mount Housing

8”

23⅞” 63/16”

89/16”

4¾”

MPS Series InvertersEmergency Micro Power Systems

SurSurface Mount

Page 39: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

3939

GENERAL SPECIFICATIONSMODEL

NUMBERHOUSING

SIZEINPUT / OUT-PUT VOLTS

90 min. CAPACITY (Watts/VA)

SYSTEM WEIGHT* BATTERY TYPE

TEMP. RANGE

(°C)

POWERCONSUM.

(Max.)

BATTERY VOLTAGE

(VDC)

DC INPUT CURRENT

(Adc)

INPUT CURRENT THERMAL OUTPUT in BTUs

Lbs. Kg. 120VAC (max)

277VAC (max)

STANDBY EMERGENCY

MPS-32 Small 120/277 32/32 14.0 6.4 Lead-Calc 20-30° 9W 12 3.4 0.34A 0.15A 7 32MPS-55 Large 120/277 55/55 18.0 8.2 Lead-Calc 20-30° 9W 12 5.7 0.54A 0.23A 7 47MPS-20 Small 120/277 20/20 11.0 5.0 NiCad 0-50° 9W 12 2.1 0.25A 0.11A 31 22MPS-35 Large 120/277 35/35 12.0 5.4 NiCad 0-50° 9W 12 3.8 0.37A 0.16A 31 35* System weights shown include installed batteries

FEATURES

• For powering incandescent, uorescent, and LED xtures *• True sinusoidal AC pulse width modulated (PWM) design

provides clean 60Hz. emergency output• Universal 120/277VAC, 60Hz. input/output• Unit capacities up to 20W to 55W• “Soft Start” design reduces xture inrush current• Surface, recessed or T-Grid mount models• Lumen output from xture is 100% of nominal• Unique design eliminates compatibility problems with LED

drivers as well as uorescent ballasts• Normally-ON and/or Normally-OFF load output• Provisions for local switching capability - Always-ON during

emergency conditions regardless of local switch position•

Temperature compensated, dual-mode charger includeslow voltage disconnect feature to provide protection againstbattery deep dischargeMaintenance-free Lead-Calcium and premium grade Nickel-Cadmium battery models offeredControl panel with momentary test switch, AC-ON, Charge-ON and Inverter-ON LED indicators

• Battery circuit fuse protected• Reverse battery and AC lockout protection

* Consult factory for compatibility for other lamp type

WIRING

Connection to an unswitched AC circuit is required by the NEC. Wiring access is provided for by conduit knockouts in the unit housing. MPS Series models also provide knockouts in the back of the housing for rear wiring from standard electrical boxes when surface mounting.

LOAD COMPATIBILITY

MPS model’s clean, sinusoidal AC output will operate incandescent lamps as well as all common uorescent and LED lamp types. Consult factory for compatibility with all other lamp types.

Lighting loads are driven at 100% output for the entire emergency power cycle. This outstanding feature translates into greater occupant egress vision and safety.

SYSTEM OPTIONS ADD SUFFIX DESCRIPTION

-S Surface Mount Housing-R Recess Mount Housing-T Plenum Rated Ceiling T-Grid Mount Housing-SP Special Housing Color (specify)-RTS Remote Test Switch Panel

(1) (2)

(1) Other options available. Consult factory.(2) Some options may impact product UL listing. Consult factory.

The MPS Series is designed to provide 20W to 55W of emergency power to incandescent, uorescent, and/or LED xtures. The MPS unit provides clean, sinusoidal AC output power allowing it to be remotely mounted up to 1,000 feet away from the controlled xture(s). Unlike a ballast uorescent emergency pack, the MPS provides power to the input side of the xture, (including the ballast) eliminating any chance of incompatibility. MPS Series models are available for surface, recessed or ceiling T-Grid mounting if required. All MPS systems will provide emergency power output for a minimum of 90-minutes.

MPS Series InvertersEmergency Micro Power Systems

Page 40: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

4040

Upon failure of the normal utility power the MPS unit is automatically turned on by a solid-state switching circuit and provides a minimum of 90-minutes of emergency power to the connected load. Lumen output willbe maintained at 100% of the lamp’s rating throughout the entire duration.

A solid-state low voltage disconnect circuit is used to protect the battery from being severely damaged by a deep discharge. When normal utility power is restored, the unit switches the load back to normal utility operation and the fully automatic, temperature compensated, dual mode charger begins to restore the battery; bringing it to full charge within UL924 speci ed parameters. A brownout sensing circuit insures proper operation during “low line” conditions.

All MPS systems provide a monitoring panel on the front of the unit to show operating status at all times. The panel provides a test switch for user initiated system tests and a 3-LED array that provides an intuitive visual indication of unit readiness.

The MPS system’s sinusoidal AC output design eliminates voltage drop and proximity concerns. This allows added exibility in installation location as MPS units can be installed hundreds of feet from the units they power. This means MPS units to be located conveniently out of sight in closets or utility rooms without interrupting architectural aesthetics.

In lighting applications, no special or additional emergency xtures are necessary. Simply designate and connect existing lighting xtures, either interior or exterior, to the MPS unit for emergency operation eliminating the need for exposed, stand-alone emergency luminaires.

Compared to traditional discrete emergency lighting units, the MPS Series provides emergency illumination from a single power source resulting in lower maintenance overhead and routine testing expenses.

MPS units lower installation costs by powering existing lighting xtures during emergencies. And because connected xtures are driven at full brilliancy, they provide far superior egress lighting and deliver improved occupant safety.

IMPROVED AESTHETICS

MPS SYSTEM ADVANTAGES

SYSTEM STATUS MONITORING PANEL

BATTERIES AND CHARGER

Battery

Battery: Sealed Lead Calcium (10 year life) or Sealed Nickel-Cadmium (15 year life)

Battery Voltage: 12VDC for all MPS models

Runtime: 90-minutes standard. Other runtimes available, consult factory.

Battery Protection: Low Voltage Battery Disconnect protects the battery from being severely damaged by deep discharge during prolonged power failures.

DC Overload and Short Circuit Protection provided by a DC input fuse.

ChargerCharger Type: Fully automatic, temperature compensated, dual-mode charger

Power Consumption: 9W max. (All models)

Recharge Duty Cycle: Meets UL924 requirements

Controls: Momentary test switch, AC-ON, Charge-ON and Inverter-ON LED indicator lights

Safety Circuitry: AC Lockout prevents battery discharge prior to initial unit power-up.

Brownout Protection automatically switches the unit to emergency mode when utility voltage is signi cantly reduced.

EnvironmentalAltitude: < 10,000 feet (3,000m) above sea level without derating.

Operating Temperature Range: Lead-Calcium Models: 20ºC to 30ºCNickel-Cadmium Models: 0ºC to 50ºC

NOTE: Optimum system performance between 20°C and 30°C; temperatures outside of this range will affect battery performance and life.

Relative Humidity: 95% non-condensing

OPERATION

MPS Series InvertersEmergency Micro Power Systems

Page 41: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

4141

An inverter system with sinusoidal output shall be supplied capable of powering any combination of lighting xtures, including incandescent, uorescent, induction and/or LED light sources without compatibility problems.

The system shall transfer in less than 1.0 second to reliably back up lighting xtures without loss of illumination and operate any and all connected lighting xtures at full lumen output during the complete 90-minute discharge cycle.

The input voltage shall be the same as the output voltage and shall be single phase 120/277 volts, 60Hz. Output capacity will be (20 Watts/32 Watts) / (35 Watts/55 Watts) for a minimum duration of 90-minutes.

The design shall be a standby, off-line inverter with on-line ef ciency of 98%; on-line double conversion UPS systems shall not be considered acceptable alternatives. MPS system output shall be a PWM generated sine wave with less than 3% total harmonic distortion. The system shall also provide short circuit and overload protection as standard.

An intuitive three LED display shall provide system operational information at a glance and alert user to any malfunction in system performance. Authorized maintenance personnel shall have access to the system’s controls while being protected from any live exposed connections.

Diag. 1 Diag. 2

Diag. 3 Diag. 4

NOTE: Voltage selection plug is shipped loose from factory. User installation required.

SUGGESTED SPECIFICATIONS

AC INPUT CONNECTION Protective devices shall include DC input fuse, AC input overcurrent protection for live circuits to be provided by service panel rated 20A maximum. AC lockout, reverse battery connection, low voltage battery disconnect (LVD), short circuit and overload protection shall be provided standard on all models. The entire MPS system, including batteries, shall be provided in compact cabinetry which shall have provisions for surface, recessed, T-Grid mounting.

System shall utilize a sealed lead calcium battery with a 10 year design life or a sealed Nickel-Cadmium battery with a 15 year design life. The charger shall be temperature compensated, dual mode type, and recharge the batteries as per UL924 guidelines. Entire system shall be tested, approved, and labeled to UL924 Emergency Lighting and Power Systems standards. T-Grid models will be plenum rated.

WIRING DIAGRAMS

MPS Series Inverters

Page 42: EMERGENCY BALLASTS - americanlite90-minute emergency illumination. • Fully automatic solid-state, ... • Suitable for use in sealed and ... • Charge rate/power “ON” LED indicator

R

Specifications and dimensions subject to change without notice. 42

WarrantyAmericanlite® is pleased to provide a 5 year limited warranty covering the ballasts in this catalogue. Americanlite® warrants that the ballasts comply with Americanlite®’s published specifications and are free from defects in materi-als and workmanship.

All our equipment is CE, TUV, FCC or UL approved and manufactured with approved compo-nents. Americanlite® reserves the right to change or improve the design or components of any of its products due to parts availability or changes in standards, without assuming any obligation to modify any product previously manufactured and without notice. All equipment is tested and inspected before shipment.

This warranty is void if the product is operated outside of its normal operating conditions. The foregoing warranty does not apply to failures caused by acts of God or as a result of any abuse, misuse, abnormal use, or use in violation of any applicable standard, code or instructions for use in installations, including, but not limited to, those contained in the Standards for the International Electrotechnical Commission. Americanlite® reserves and has the right to examine failed ballast to determine the cause of failure, excessive lumen depreciation and patterns of usage.

Warranty