    Chapter 12Electric Motor Drive Start-up Procedures

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    2/19

    PowerPoint Presentation

    Chapter 12

    Electric Motor Drive Start-up

    Procedures

    Initial Checks Secondary Checks

    Final Checks

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    3/19

    Chapter 12Electric Motor Drive Start-up Procedures

    Electric motor drive voltage is tested at the line power

    terminal strip, load power terminal strip, DC bus termin-

    al strip, and the control terminal strips.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    4/19

    Chapter 12Electric Motor Drive Start-up Procedures

    A motor and load must be secured in place and

    correctly aligned, and the shafts must be rotated to

    detect mechanical problems.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    5/19

    Chapter 12Electric Motor Drive Start-up Procedures

    A conductor and motor

    winding insulation spot-

    test connects a megohm-

    meter between a load

    conductor and groundand stresses the insula-

    tion with a voltage.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    6/19

    Chapter 12Electric Motor Drive Start-up Procedures

    An insulation spot-test

    identifies a problem as

    either with the conductors

    to a motor or the motor

    windings.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    7/19

    Chapter 12Electric Motor Drive Start-up Procedures

    An ESD-safe vacuum with accessories is used to

    safely remove debris from an electric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    8/19

    Chapter 12Electric Motor Drive Start-up Procedures

    A DMM set to measure

    resistance is used to

    check for grounds in an

    electric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    9/19

    Chapter 12Electric Motor Drive Start-up Procedures

    A DMM set to the diode

    check mode is used to

    test the diodes in the

    converter section of an

    electric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    10/19

    Chapter 12Electric Motor Drive Start-up Procedures

    A DMM set to the diode

    check function is used to

    test the transistors and

    fly-back diodes in the

    inverter section of anelectric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    11/19

    Chapter 12Electric Motor Drive Start-up Procedures

    Power supply voltage to

    an electric motor drive is

    measured on the line

    side of the disconnect

    with a DMM.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    12/19

    Chapter 12Electric Motor Drive Start-up Procedures

    The line conductors, grounds, and control wiring mustbe tight and must terminate at the correct positionson an electric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    13/19

    Chapter 12Electric Motor Drive Start-up Procedures

    DIP switches or jumpers are used on electric motor

    drives to select various functions for a specific

    application.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    14/19

    Chapter 12Electric Motor Drive Start-up Procedures

    Overload relays must be sized for the nameplate

    current of a motor and are available in a variety of

    configurations.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    15/19

    Chapter 12Electric Motor Drive Start-up Procedures

    Power is applied to an electric motor drive after DIP

    switches, jumpers, wiring, and overload protection

    are set or configured correctly.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    16/19

    Chapter 12Electric Motor Drive Start-up Procedures

    The functionality of an

    electric motor drive is

    tested by running the

    drive without the motor

    conductors connected.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    17/19

    Chapter 12Electric Motor Drive Start-up Procedures

    To compare the measured

    current reading with the

    nameplate current rating

    of a motor, the motor must

    be operated at a speed of60 Hz.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    18/19

    Chapter 12Electric Motor Drive Start-up Procedures

    The electric motor drive,

    motor, and driven load

    test verifies that a 4 mA

    20 mA signal from a

    mixing process providesproper speed reference to

    the electric motor drive.

    http://localhost/var/www/apps/conversion/tmp/scratch_4//ATPNT1/EDITORIAL/CD%20Final/NEW/Virtual%20CD%20HVCRG/ppt/HVCRGTOC.PPT
  • 7/29/2019 EMD12 (1)

    19/19

    Chapter 12Electric Motor Drive Start-up Procedures

    The operation of a

    bypass contactor must

    be tested before the

    start-up of an electric

    motor drive is complete.