EM-FCS – SPARK DETECTION AND EXTINGUISHMENT MODEL: EM-FCS-CU1610. BASE UNIT IS CAPABLE OF PROTECTING UP TO 5 DUCTS Includes IP55 rated (Dust Tight) enclosure, battery back-up as well as audible and visual alarms Allows for double security protection in 5 ducts (E.G. Detect / Extinguish / Detect / FireBreak) Modular design allows for easy installation of additional modules for larger systems. Can be connected to abort gates on return air lines for simultaneous abort or by re-detection after the Dust Collector. Can be connected to shut down dust collection equipment and to a building fire alarm system. SPARK DETECTORS OPERATE ON “PULSE COUNT” FEATURE TO ALLOW FOR INSTALLATION IN METAL WORKING APPLICATIONS WITH HIGH NUMBER OF SPARKS OPTIONAL THERMAL MONITORING CONTROLS AND SENSORS COMPLETE EXTINGUISHING SOLUTIONS CURRENTLY BEING FM APPROVED AND IS ATEX CERTIFIED PENDING

Transcript of EM-FCS – SPARK DETECTION AND...

Page 1: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

• MODEL: EM-FCS-CU1610. BASE UNIT IS CAPABLE OF PROTECTING UP TO 5 DUCTS • Includes IP55 rated (Dust Tight) enclosure, battery back-up as well as audible and visual alarms • Allows for double security protection in 5 ducts (E.G. Detect / Extinguish / Detect / FireBreak) • Modular design allows for easy installation of additional modules for larger systems. • Can be connected to abort gates on return air lines for simultaneous abort or by re-detection after the

Dust Collector. • Can be connected to shut down dust collection equipment and to a building fire alarm system.

• SPARK DETECTORS OPERATE ON “PULSE COUNT” FEATURE TO ALLOW FOR

INSTALLATION IN METAL WORKING APPLICATIONS WITH HIGH NUMBER OF SPARKS

• OPTIONAL THERMAL MONITORING CONTROLS AND SENSORS

• COMPLETE EXTINGUISHING SOLUTIONS

• CURRENTLY BEING FM APPROVED AND IS ATEX CERTIFIED PENDING

chriss
Stamp
Page 2: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

EM-FCS-SD, SPARK DETECTORS ARE IP65 RATED (OUTDOOR) OPERATE ON INFRARED LIGHT AND FEATURE INTERNAL TEST LAMP FOR FUNCTIONALITY. EM-FCS-TL, EXTERNAL TEST LAMPS IP65 RATED (OUTDOOR) AND AN AVAILABLE OPTION TO TEST IF THE DETECTOR LENS IS COMPRISED BY A BUILD UP OF DUST EM-FCS-MK, MOUNTING KITS ARE REQUIRED FOR THE INSTALLATION OF THE SPARK DETECTORS AND TEST LAMPS EM-FCS-TP, THERMAL PROBE FOR ACTIVATION ON RAPID TEMPERATURE RISE AND/OR THRESHOLD

Page 3: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

POSITIONING AND SIZING SPARK DETECTORS

Fig.8 - PLACEMENT (long side of the support):

1) parallel to the duct (air flow)

2) perpendicular to the duct (air flow)

Fig.9 - DUCT D. 150-500mm

n° 1 Detector (position

on the top or on the sides)

Fig.10 - DUCT D. 500-1000mm

n° 2 Detectors (opposed, over 900

recommended 3, see Fig.11)

Fig.11 - DUCT D.> 1000mm

n° 3 Detectors

(opposed at 120°)

AIR FLOW

6” thru 20” * 20” thru 40” 40” + Recomended 33”+

• For best results, it is recommended that at least 2 detectors be mounted on opposing sides of the ductwork

SPARK DETECTORS DETECT INFRARED LIGHT

“PULSE COUNT” FEATURE AVAILABLE IN CENTRAL CONTROL FOR APPLICATIONS WITH HIGH NUMBER OF SPARKS SPARK DETECTORS MUST BE INSTALLED WITH EM-FCS-MK MOUNTING KIIT

Page 4: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

fig. 11

BAG BAG

EXAMPLE THERMAL PROBE LOCATIONS FOR DUST COLLECTORS AND SILOS

A minimum of 2 probes to be installed in as follows:

1) Dirty air inlet and air clean air outlet

2) 2 opposing probes installed in clean air plenum(above

filter bags)

3) 1 probe in clean air plenum (above filter bags) and 1 in the

dust collector hopper

4) Silos require 1 probe in clean air plenum (above filter

bags) and 1 in the internal storage area.

N.B. 1 Dust collectors longer than 16.5 ft (5m) should install

of 4 probes that are equally divided between filter and hopper

sections.

N.B. 2 for Silos / Dust Bins larger than 13 ft (4m) should

install 4 probes that are equally divided between filter and

storage sections

THERMAL PROBES MAY BE INSTALLED IN DUCTS.

Regardless of diameter, we recommend installing a probe

every 23 – 26 feet (7-8 meters)

Page 5: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

EM-FCS-EG1, COMES PREPLUMBED WITH T-FITTING AS SHOWN (2) O-EM-FCS-SSN34, ¾” NOZZLE WITH SHUTTER ARE PROVIDED ARE TO BE FIELD CONNECTED BY THE INSTALLER.

fig. 11

WATER FILTER O-EM-FCS-WF (GMFLTO-1P)

PRESSURE SWITCH O-EM-FCS-PS1 (GMPST24-EX)

SOLENOID VALVE O-EM-FCS-SV24 (GMELV24-1P-EX)

BALL VALVE O-EM-FCS-BV (GMBV-1P)

CONNECTION BOX O-EM-FCS-CB (GMEXG-P-O1)

EXTINGUISHING GROUP EM-FCS-EG1

T-FITTING (NOT SHOWN)

Shutter Closed Shutter Open Spray Detail

Requires

approximately 15.83

U.S. Gallons per

minute ( 60L/min)

@ a pressure of 4 bar (58.8 psi)

0.47”

0.31”

0.59”

Page 6: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

DESIGNED FOR DOUBLE SECURITY PROTECTION STANDARD – DETECT/EXTINGUISH/DETECT/FIREBREAK CAN BE USED AS STANDARD DETECT AND EXTINGUISH ONLY OR DETECT AND ISOLATION BY FIREBREAK

Page 7: EM-FCS – SPARK DETECTION AND EXTINGUISHMENTtotalairenergy.com/wp-content/uploads/Spark-Detection...EM-FCS – SPARK DETECTION AND EXTINGUISHMENT • MODEL: EM-FCS-CU1610. BASE UNIT

EM-FCS – SPARK DETECTION AND EXTINGUISHMENT

Speed (ft/min) 0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600 8000 8400 8800Distance (ft) 0,0 1,7 3,3 5,0 6,7 8,3 10,0 11,7 13,3 15,0 16,7 18,3 20,0 21,7 23,3 25,0 26,7 28,3 30,0 31,7 33,3 35,0 36,7

0,0 1,

7 3,3 5,

0 6,7 8,

3 10,0 11

,7 13,3 15

,0 16,7 18

,3 20,0 21

,7 23,3 25

,0 26,7 28

,3 30,0 31

,7 33,3 35

,0 36,7

0,0

5,0

10,0

15,0

20,0

25,0

30,0

35,0

40,0

0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600 8000 8400 8800

Dis

tanc

e (ft

)

Speed (ft/min)

chart for the calculation of the minimum distance between the sparks detectors and extinguishing group

5x dia before re-detection

Response time is based on solenoid at no more than 3.28 ft (1 meter) from water supply.