Eltek Valere - x Series Rectifier

2
316 Cassette/Rack AC/DC Rectifiers 5600W X Series - Front end products Features 180VAC to 264VAC input Up to 92% efficiency Power factor correction Hot pluggable Front panel LED indicators 12C Serical communications bus AC and DC fail alarm Overtemperature alarm Specifications INPUT Universal AC 180-264VAC. Frequency 47-63Hz. Current See table. Inrush current 30A peak. Power factor .99 @ typ @ 230VAC, full load. DC input versions See table. OUTPUT Voltage 12V. Sink current 100mA. Regulation ±1%. Current See table. Current limit setpoint See table. Short circuit current See table. Noise 40mV rms typ (10kHz to 20MHz). 30 dBrnc (measured without external battery). 150mV p-p (10kHz to 20Mhz). Rise time 400msec max. Dynamic response 3% max. Turn on delay 3.5 sec max. Load sharing ±5% of full load. Reverse output current 0.5A. Efficiency 90-92% depending on output voltage. ENVIRONMENTAL Operating temperature See table. Storage temperature –40°C to +85°C. GENERAL Dimensions 404.8 x 81.3 x 131.5 mm. Weight 6.8 kg. STANDARDS Safety standard EN60950, UL60950/UL1801. EMI/EMC Conforms to EN55022, Level B. Conductive Emissions EN55022, Level B & FCC Class B NEBS EMC, Surge Standards, and Electrical Safety per GR- 1089-CORE. IEEE-C62.41 IEEE Recommended Practice on Surge Voltages in Low-Voltage AC. Power Circuits. Category A2. EN61000-3-2 Limits for harmonic current emissions for class D equipment. EN61000-3-3 Limits for voltage fluctuations and flicker in low-voltage systems. EN61000-4-2 Electrostatic discharge immunity test. Level 4. All user accessible ports. Damage free, operational and non- operational. Criterion B. EN61000-4-3 Radiated, radio-frequency, electromagnetic field immunity test. Level 3: 10 V/m. EN61000-4-4 Electrical fast transient/burst immunity test. Level 4 EN61000-4-5 Surge immunity test. Installation Class 4. 6 kV: Line to Line, Criterion A. 6 kV: Line to Ground, Criterion A. EN61000-4-6 RF Common Mode. Level 3, Criterion A. EN61000-4-8 Magnetic Field. Level 3, Criterion A. EN61000-4-11 Voltage dips, short interruptions and voltage variations. CE Yes, meets 73/23/EEC and 93/68/EEC directives.

description

Eltek Valere - x Series Rectifier

Transcript of Eltek Valere - x Series Rectifier

Page 1: Eltek Valere - x Series Rectifier

316

Cassette/Rack

AC/DC Rectifiers 5600WX Series - Front end products

Features• 180VAC to 264VAC input

• Up to 92% efficiency

• Power factor correction

• Hot pluggable

• Front panel LED indicators

• 12C Serical communications bus

• AC and DC fail alarm

• Overtemperature alarm

SpecificationsINPUTUniversal AC 180-264VAC.Frequency 47-63Hz.Current See table.Inrush current 30A peak.Power factor .99 @ typ @ 230VAC, full load.DC input versions See table.

OUTPUTVoltage 12V.Sink current 100mA.Regulation ±1%.Current See table.Current limit setpoint See table.Short circuit current See table.Noise 40mV rms typ (10kHz to 20MHz). 30 dBrnc (measured

without external battery). 150mV p-p (10kHz to 20Mhz).Rise time 400msec max.Dynamic response 3% max.Turn on delay 3.5 sec max.Load sharing ±5% of full load.Reverse output current 0.5A.Efficiency 90-92% depending on output voltage.

ENVIRONMENTALOperating temperature See table.Storage temperature –40°C to +85°C.

GENERALDimensions 404.8 x 81.3 x 131.5 mm.Weight 6.8 kg.

STANDARDSSafety standard EN60950, UL60950/UL1801.EMI/EMC Conforms to EN55022, Level B.Conductive Emissions EN55022, Level B & FCC Class BNEBS EMC, Surge Standards, and Electrical Safety per GR-

1089-CORE.IEEE-C62.41 IEEE Recommended Practice on Surge Voltages in

Low-Voltage AC. Power Circuits. Category A2.EN61000-3-2 Limits for harmonic current emissions for class D

equipment.EN61000-3-3 Limits for voltage fluctuations and flicker in low-voltage

systems.EN61000-4-2 Electrostatic discharge immunity test. Level 4. All user

accessible ports. Damage free, operational and non-operational. Criterion B.

EN61000-4-3 Radiated, radio-frequency, electromagnetic fieldimmunity test. Level 3: 10 V/m.

EN61000-4-4 Electrical fast transient/burst immunity test. Level 4EN61000-4-5 Surge immunity test. Installation Class 4. 6 kV: Line to

Line, Criterion A. 6 kV: Line to Ground, Criterion A.EN61000-4-6 RF Common Mode. Level 3, Criterion A.EN61000-4-8 Magnetic Field. Level 3, Criterion A.EN61000-4-11 Voltage dips, short interruptions and voltage

variations.CE Yes, meets 73/23/EEC and 93/68/EEC directives.

Page 2: Eltek Valere - x Series Rectifier

317Download datasheet – www.craftec.info

Cassette/Rack

INPUT INPUT Vo SET OUTPUT CURRENT LIMIT SHORT CIRCUITVOLTAGE CURRENT POINT CURRENT SETPOINT CURRENT

VAC 180/208VAC V MIN/MAX A RMS A

X2500A1 180-264 19/17 42/48/56 0/50 55 20X5000A1 180-264 36/32 42/48/56 0/100 110 35X5000A2 200-277 32/30 42/48/56 0/100 110 35X7500A1 180-264 52/45 42/48/56 0/150 155 50X2500B1 180-264 14/12 21/24/28.5 0/100 105 35X3750B1 180-264 27/23 21/24/28.5 0/150 155 50

AC/DC Rectifiers 5600WX Series - Front end products

TOP

SIDE

FRONT BACK

DC INPUT VERSIONS OUTPUT OUTPUT INPUT INPUT TEMPERATUREDCX SERIES CONVERTERS VOLTAGE CURRENT (max) VOLTAGE CURRENT (max) RANGE

DCX0750BA 48V 15A 24V 40A –40°C to +65°CDCX1500BA 48V 30A 24V 80A –40°C to +56°CDCX2000BA 48V 40A 24V 100A –40°C to +65°C