ELG4125: Lecture 2

Power Transformers

The Ideal Transformer

The Real Transformer

Equivalent Circuits for Practical Transformers

The Per-Unit System

Three-Phase Transformers

Autotransformers

Page 2: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformers in Power Systems

• Typically in power systems, voltages get transformed approximately five times between generation and delivery to the users.

• Generation in power systems, primarily by synchronous generators, takes place at around 20-kV level.

• Transmission voltages of 230 kV, 345 kV, 500 kV, and 765 kV is common.

• At the load, these voltages are stepped down to 120/240 V single-phase in residential usage.

• Another advantage of transformers in many applications is to provide electrical insulation for safety purposes.

Page 3: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

3

Transformer Types

Power Transformers

Current Transformers

Voltage Transformers

Series Transformers

Transformer Purchasing Issues

Efficiency

Audible Noise

Installation Costs

Manufacturing Facilities

Performance Record

Real Transformers

Transformer Connections

Each leg is a single phase transformer

Y-Y connections (no phase shift)

D-D connections (no phase shift)

Y-D connections (-30 degrees phase shift)

D-Y connections (+30 degrees phase shift)

Page 4: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Nameplate Information

• kVA is the apparent power.

• Voltage ratings for high and low side are no-load values. The symbol between the values indicate how the voltages are related:

• Long dash (—) From different windings.

• Slant (/) …from same winding: • 240/120 is a 240 V winding with a center tap.

• Cross (X) Connect windings in series or parallel. Not used in wye-connected winding:

• 240X120 two part winding connected in series for 240 or parallel for 120.

• Wye (Y) A wye-connect winding.

Page 5: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Basic Principles of Transformer Operation

• Transformers consist of two or more coupled windings where almost all of the flux produced by one winding links the other winding.

Page 6: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformer Exciting Current

• Transformers use ferromagnetic materials that guide magnetic flux due to their high permeability, require small ampere-turns to produce the desired flux density.

• The magnetising current is that current which flows in the primary winding when the primary voltage is applied with the secondary unloaded. It is the necessary current that satisfies the excitation condition as determined by the fundamental transformer equation.

• In modern power transformer of large kVA ratings, the magnetizing currents in their normal operating region are very small, for example, well below 0.2% of the rated current at the rated voltage.

Page 7: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Voltage Transformation

• The EMF of a transformer at a given flux density increases with frequency. By operating at higher frequencies, transformers can be physically more compact because a given core is able to transfer more power without reaching saturation and fewer turns are needed to achieve the same impedance. However, core loss and conductor skin effect also increase with frequency.

• Aircraft and military equipment employ 400 Hz power supplies which reduce core and winding weight. Conversely, frequencies used for some railway electrification systems were much lower (16.7 Hz and 25 Hz) than normal utility frequencies (50/60 Hz) for historical reasons concerned mainly with the limitations of early electric traction systems.

• As such, the transformers used to step down the high over-head line voltages (15 kV) were much heavier for the same power rating than those designed only for the higher frequencies.

dt

dN e v P PP

dt

d N e v SSS

Page 8: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

• Where VP is the RMS value of the applied voltage with the assumption that eP = VP. The second Equation shows that the flux is determined by the applied voltage, the frequency of operation, and number of turns in the winding.

maxmax 4442

2 φ f N. φ f Nπ

E PPP

P

P

f N.

V

444 max

Page 9: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Example

Page 10: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformer Equivalent Circuit Viewed from the Primary Side

Page 11: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Modeling a Real Transformer

Page 12: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Equivalent Circuit with Parameters Moved to the Primary Side

Page 13: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformer Phasor Diagram

Page 14: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current
Page 15: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

15

Transformer Tests

Test to Determine Transformer Parameters, we require to conduct

Open Circuit Test:

Energize Low voltage winding at rated voltage, leaving other winding open

Measure Current (Ioc) and Power (Poc) into energized winding.

Calculate parameters

Short Circuit Test:

Energize Low current (high voltage) winding at rated current with a solid short circuit applied across the other winding

Measure Voltage and Power at terminals of energized winding

Calculate parameters

Page 16: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformer Test

Open-Circuit Test

Short-Circuit Test

22

and ,

S

C

S

e

S

C

S

S

CS

C

I - I I

V

P I

Sm

SSm

SC

SSC

I

V X

I

V R

and ,2SC

SCT

I

P R

2

2

T

SC

SC

TR

I

V X -

Page 17: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Example 1

Page 18: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Example 2

Page 19: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

The Per unit system

• In the per-unit system, the voltages, currents, powers,

impedances, and other electrical quantities are

expressed on a per-unit basis by the equation:

• It is customary to select two base quantities to define a

given per-unit system. The ones usually selected are

voltage and power.

Quantity per unit =

Actual value

Base value of quantity

Page 20: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

ratedbVV ratedb SS

Then compute base values for currents and impedances

b

b

b

V

SI

b

b

b

b

b

S

V

I

VZ

2

Page 21: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

b

actualup

V

VV ..

b

actualup

I

II ..

b

actualup

S

SS ..

b

actual

up

Z

ZZ

..

%100% .. upZZ

Page 22: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Example 1

Page 23: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

23

Example 2

An electrical load is rated 120 volts, 500 watts. Compute

the per-unit and percent impedance of the load. Give the

per unit equivalent circuit.

Power factor = 1.0

8.28500

)120( 222

P

VR

R

VP

08.28Z

Page 24: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

24

Select base quantities

Compute base impedance

The per-unit impedance is

VASb 500

VVb 120

8.28500

)120( 22

b

bb

S

VZ

.p.u018.28

08.28..

bup

Z

ZZ

Page 25: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

25

Percent impedance:

Per-unit equivalent circuit:

%100% Z

..01 upZ ..01 upVS

Page 26: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

26

Per-unit System for Single Phase Circuits

One-phase circuits

LVbLV VV

IVSSb -1

where

neutraltolineVV --

currentlineII -

HVbHV VV

bLV

bbLV

V

SI

bHV

bbHV

V

SI

Page 27: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

27

b

bLV

bLV

bLVbLV

S

V

I

VZ

2)(

b

bHV

bHV

bHVbHV

S

V

I

VZ

2)(

*

pupu

b

pu IVS

SS

cospupu

b

pu IVS

PP

sinpupu

b

pu IVS

QQ

Page 28: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

28

Transformation Between Bases

Ab VV 1Ab SS 1

1

1

b

Lpu

Z

ZZ

1

2

11

b

bb

S

VZ

And second

Bb VV 2Bb SS 2

2

2

b

Lpu

Z

ZZ

2

2

22

b

bb

S

VZ

Page 29: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

29

Transformation Between Bases

2

2

2

1

2

1

2

11

21

2

b

b

b

b

b

b

L

b

b

L

pu

pu

V

S

S

V

Z

Z

Z

Z

Z

Z

Z

Z

1

2

2

2

112

b

b

b

bpupu

S

S

V

VZZ

“1” – old

“2” - new

oldb

newb

newb

oldb

oldpunewpuS

S

V

VZZ

,

,

2

,

,

,,

Page 30: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

30

Transformation Between Bases

Generally per-unit values given to another base can be

converted to new base by the equations:

2

11___2___ ),,(),,(

base

basebaseonpubaseonpu

S

SSQPSQP

2

11___2___

base

basebaseonpubaseonpu

V

VVV

1

2

2

2

2

11___2___

)(

)(),,(),,(

basebase

basebasebaseonpubaseonpu

SV

SVZXRZXR

When performing calculations in a power system, every

per-unit value must be converted to the same base.

Page 31: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

31

Per-unit System for Single Phase Transformer

Consider the equivalent circuit of transformer referred to

LV side and HV side shown below:

LVV HVV LVV HVV

SS jXR

1N 2N

22 a

Xj

a

R SS

Referred to LV side Referred to HV side

Define 12

1 N

N

V

Va

HV

LV

S

Page 32: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

32

Per-unit System for Single Phase Transformer

Choose

ratedLVb VV ,1

ratedb SS

Compute

112

1bb

LV

HVb V

aV

V

VV

b

bb

S

VZ

2

11

b

bb

S

VZ

2

22

2

2

1

2

1

2

2

2

1

2

1

)1

(

a

Va

V

V

V

Z

Z

b

b

b

b

b

b

Page 33: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

33

Per-unit System for Single Phase Transformer

Per-unit impedances are

1

1..

b

SSup

Z

jXRZ

12

1

22

2

22

2..

b

SS

b

SS

b

SS

upZ

jXR

a

Za

jX

a

R

Z

a

jX

a

R

Z

2..1.. upup ZZ

Page 34: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

34

Voltage Regulation

%100-

-

--

loadfull

loadfullloadno

V

VVVR

Voltage regulation is defined as

%100,

,,

-

-

--

loadfullpu

loadfullpuloadnopu

V

VVVR

In per-unit system

Vfull-load: Desired load voltage at full load. It may be equal to, above, or

below rated voltage. Vno-load: The no load voltage when the primary voltage is the desired

voltage in order the secondary voltage be at its desired value

at full load.

Page 35: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

35

Example

A single-phase transformer rated 200-kVA, 200/400-V, and

10% short circuit reactance. Compute the voltage

regulation when the transformer is fully loaded at unity

power factor and rated voltage 400-V.

PVSV1.0j

loadS

VVb 4002

kVASb 200

puS puload 01,

pujX puS 1.0,

SX

Page 36: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

36

Rated voltage

puV puS 00.1,

pu

jj

XIVV

o

puSpupuSpuP

7.5001.1

1.011.000.100.1

,,,

puV

SI

puS

puload

puload 00.100.1

00.1**

,

,

,

Page 37: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

37

puVV o

puPloadnopu 7.5001.1,, -

puVV puSloadfullpu 00.1,, -

Secondary side

Voltage regulation

%1.0%1000.1

0.1001.1

%100,

,,

-

-

-

--

loadfullpu

loadfullpuloadnopu

V

VVVR

Page 38: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

38

Select Vbase in generator circuit and Sb=100MVA, compute the

per unit equivalent circuit.

Problem

G

100j

20 kV 22kV/220kV

80MVA

14%

220kV/20kV

50MVA

10%

50MVA

0.8 PF

lagging

Page 39: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Residential Distribution Transformers

Single phase transformers are commonly used in residential distribution systems. Most distribution

systems are 4 wire, with a multi-grounded, common neutral.

39

Page 40: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Three-Phase Transformers

Page 41: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

41

Per-unit System for Three Phase Circuits

LVLbLV VV ,

IVSSSb 33 13 --

3/)(lineLneutraltoline VVV --

Lcurrentline III -

HVLbHV VV ,

LLb IVS 3

bHVbHVbLVbLVb IVIVS 33

Page 42: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

42

Per-unit System for Three Phase Circuits

b

bLV

b

bLVbLV

LV

LV

bLVS

V

S

VV

I

VZ

2)(3

3

b

bHVbHV

S

VZ

2)(

**

3

3

3pupu

bb

LL

b

pu IVIV

IV

S

SS

bLV

bbLV

V

SI

3

bHV

bbHV

V

SI

3

Page 43: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

43

Three 25-kVA, 34500/277-V transformers connected in D-

Y. Short-circuit test on high voltage side:

Determine the per-unit equivalent circuit of the

transformer.

Per-unit System for Three Phase Transformer

VV SCLine 2010,

AI SCLine 26.1,

WP SC 912,3

Page 44: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

44

Using Y-connection equivalent circuit

Per-unit System for Three Phase Transformer

3

34500277

SS jXR

VASb 250003

2010SCV

26.1SCI

00.92126.1

47.1160SCZ

VVSC 47.11603

2010

Page 45: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

45

Per-unit System for Three Phase Transformer

-- 86.90048.191921 2222

SSCS RZX

WP 3043

912 48.191

26.1

30422

SC

SI

PR

86.90048.191 jZSC

VASb 25000 VV HVb 58.199183

34500,

99.1586925000

58.19918 2

,HVbZ

pujj

Z YpuSC 0568.0012.099.15869

86.90048.191,,

Page 46: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

46

Using D-connection equivalent circuit

Per-unit System for Three Phase Transformer

34500 277

D,SCZ

VASb 250002010SCV

3

26.1SCI

D 79.2764727.0

2010,SCZ

VVSC 2010 AISC 727.03

26.1

Page 47: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

47

Per-unit System for Three Phase Transformer

-- DDD 30.270418.57579.2764 222

,

2

,, SSCS RZX

WP 3043

912 D 18.575

727.0

30422,

SC

SI

PR

86.90048.191 jZSC

VASb 25000 VV HVb 34500,

4761025000

345002

,HVbZ

pujj

Z puSC 0568.0012.047610

30.170418.575,,

D

Page 48: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Transformer Efficiency

lossout

out

in

out

P P

P

P

P

powerInput

powerOutput

θ IVP SSout cos

100

cos

cos

CCuSS

SS

P P θ IV

θ IV

Page 49: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Load Tap Changing Transformers

• LTC transformers have tap ratios that can be varied to regulate bus voltages.

• The typical range of variation is 10% from the nominal values, usually in 33 discrete steps (0.0625% per step).

• Because tap changing is a mechanical process, LTC transformers usually have a 30 second dead-band to avoid repeated changes to minimize wear and tear.

• Unbalanced tap positions can cause “circulating VARs;” that is, reactive power flowing from one winding to the next in a three phase transformer.

49

Page 50: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Phase Shifting Transformers

• Phase shifting transformers are used to control the phase angle across the transformer.

• Since power flow through the transformer depends upon phase angle, this allows the transformer to regulate the power flow through the transformer.

• Phase shifters can be used to prevent inadvertent "loop flow" and to prevent line overloads.

50

Page 51: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Phase Shifting Transformer Picture

230 kV 800 MVA Phase Shifting Transformer During factory testing

Source: Tom Ernst, Minnesota Power

Costs about $7 million, weighs about 1.2 million pounds

51

Page 52: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Power Transformers from China

Page 53: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current
Page 54: ELG4125: Lecture 2 Power Transformers - University of …rhabash/ELG4125LN22012.pdf · ELG4125: Lecture 2 Power Transformers The Ideal Transformer ... Transformer Exciting Current

Autotransformers

• Autotransformers are transformers in which the primary and secondary windings are coupled magnetically and electrically.

• This results in lower cost, and smaller size and weight.

• The key disadvantage is loss of electrical isolation between the voltage levels. This can be an important safety consideration when a is large. For example in stepping down 7160/240 V we do not ever want 7160 on the low side!

54