ELEVATORS AND FIRE ALARMSYSTEM INTERFACES
CANADIAN FIRE ALARM ASSOCIATION
2011 ONTARIO ANNUAL TECHNICAL SEMINAR
RANDAL BROWN & ASSOCIATES LTD. 1© 2011
PRESENTED BYPRESENTED BY
SIMON CROSBY, CET, CFPSRANDAL BROWN & ASSOCIATES LTD.
416-492-5886 [email protected]
RANDAL BROWN & ASSOCIATES LTD. 2© 2011
CODES & STANDARDSNEW CONSTRUCTION
RANDAL BROWN & ASSOCIATES LTD. 3© 2011
ONTARIO CODES & STANDARDS
• FIRE ALARM SYSTEM / ELEVATOR• FIRE ALARM SYSTEM / ELEVATORINTERFACE REQUIREMENTS:
2006 ONTARIO BUILDING CODE– 2006 ONTARIO BUILDING CODE
– CSA-B44-07, SAFETY CODE FOR ELEVATORSAND ESCALATORSAND ESCALATORS
– TSSA CODE ADOPTION DOCUMENT
NOTE: CONFLICTS EXIST BETWEEN THE OBC & CSA-B44
RANDAL BROWN & ASSOCIATES LTD. 4© 2011
ONTARIO BUILDING CODEONTARIO BUILDING CODE
RANDAL BROWN & ASSOCIATES LTD. 5© 2011
2006 ONTARIO BUILDING CODE
• ARTICLE 3 2 6 4 EMERGENCY OPERATION• ARTICLE 3.2.6.4, EMERGENCY OPERATIONOF ELEVATORS
APPLICABLE IN HIGH BUILDINGS– APPLICABLE IN HIGH BUILDINGS
– AUTOMATIC ELEVATOR RECALL FORELEVATORS SERVING STOREYS ABOVE THEELEVATORS SERVING STOREYS ABOVE THEFIRST STOREY IN UNSPRINKLERED BUILDINGS
RANDAL BROWN & ASSOCIATES LTD. 6© 2011
2006 ONTARIO BUILDING CODE
• ARTICLE 3 2 6 4 (CONT’D)• ARTICLE 3.2.6.4 (CONT D)– AUTOMATIC RECALL INITIATED BY:
• SMOKE DETECTORS CONNECTED TO THE• SMOKE DETECTORS, CONNECTED TO THEBUILDING’S FIRE ALARM SYSTEM, LOCATED INEACH ELEVATOR LOBBY ON EACH STOREY, OR
• THE BUILDING FIRE ALARM SYSTEM
RANDAL BROWN & ASSOCIATES LTD. 7© 2011
2006 ONTARIO BUILDING CODE
• ARTICLE 3 2 4 10 FIRE DETECTORS• ARTICLE 3.2.4.10, FIRE DETECTORS– FIRE DETECTORS REQUIRED IN ELEVATOR
SHAFTSSHAFTS
NOTE: NEW REQUIREMENT FOR SMOKE DETECTORS INNOTE: NEW REQUIREMENT FOR SMOKE DETECTORS INELEVATOR MACHINE ROOMS IN THE 2010 NBCC
RANDAL BROWN & ASSOCIATES LTD. 8© 2011
2006 ONTARIO BUILDING CODE
• ARTICLE 3 2 4 14 ELEVATOR EMERGENCY• ARTICLE 3.2.4.14, ELEVATOR EMERGENCYRETURN
FOR ELEVATORS EQUIPPED WITH AUTOMATIC– FOR ELEVATORS EQUIPPED WITH AUTOMATICRECALL, SMOKE DETECTION REQUIRED AT THERECALL LEVEL ELEVATOR LOBBYRECALL LEVEL ELEVATOR LOBBY
– WHEN ACTUATED, RETURNS ELEVATORS TOTHE ALTERNATE RECALL LEVELTHE ALTERNATE RECALL LEVEL
– WAIVED WHEN THE RECALL LEVEL ISSPRINKLERED
RANDAL BROWN & ASSOCIATES LTD. 9© 2011
CSA-B44-07CSA B44 07
RANDAL BROWN & ASSOCIATES LTD. 10© 2011
CSA-B44-07
• HARMONIZED STANDARD WITH US BUT• HARMONIZED STANDARD WITH US, BUTSTILL CONTAINS CANADA SPECIFIC RULES
A O• APPLIED IN ONTARIO THROUGH THETSSA CODE ADOPTION DOCUMENT– ELEVATING DEVICES CODE ADOPTION
DOCUMENT – AMENDMENT 225/07 R03A– AMENDS ELEVATOR RECALL REQUIREMENTS
• IN THE STANDARD NBCC = OBC
RANDAL BROWN & ASSOCIATES LTD. 11© 2011
CSA-B44-07
• SECTION 2 27 3 FIREFIGHTER’S• SECTION 2.27.3, FIREFIGHTER SEMERGENCY OPERATION
FIREFIGHTERS’ EMERGENCY OPERATION– FIREFIGHTERS’ EMERGENCY OPERATIONAPPLIED TO ALL ELEVATORS, EXCEPT
• WHERE THE HOISTWAY IS NOT REQUIRED TO BE• WHERE THE HOISTWAY IS NOT REQUIRED TO BEFIRE RATED,
• WHERE THE RISE DOES NOT EXCEED 2000 MM, AND
• WHERE THE HOISTWAY DOES NOT PENETRATE AFLOOR
RANDAL BROWN & ASSOCIATES LTD. 12
FLOOR.
© 2011
CSA-B44-07
• SECTION 2 27 3 (CONT’D)• SECTION 2.27.3 (CONT D)– PHASE I EMERGENCY RECALL OPERATION
• KEY OPERATED AND FIRE DETECTION INITIATED• KEY OPERATED AND FIRE DETECTION INITIATEDRECALL REQUIRED INDEPENDENT OF OBC REQUIREMENTS
• REQUIREMENTS AMENDED BY THE CAD
RANDAL BROWN & ASSOCIATES LTD. 13© 2011
CSA-B44-07
• SECTION 2 27 3 2 2 PHASE I EMERGENCY• SECTION 2.27.3.2.2, PHASE I EMERGENCYRECALL OPERATION BY FIRE ALARMINITIATING DEVICESINITIATING DEVICES– SMOKE OR FIRE DETECTORS INSTALLED TO
INITIATE AUTOMATIC RECALL:INITIATE AUTOMATIC RECALL:• AT EACH FLOOR SERVED BY THE ELEVATOR, AND
• IN THE ASSOCIATED ELEVATOR MACHINE ROOM, IN THE ASSOCIATED ELEVATOR MACHINE ROOM, CONTROL SPACE, OR CONTROL ROOM
– FIRE DETECTORS (FIRE ALARM INITIATING
RANDAL BROWN & ASSOCIATES LTD. 14
(DEVICES) = SMOKE OR HEAT DETECTORS
© 2011
CSA-B44-07
• SECTION 2 27 3 2 2 (CONT’D)• SECTION 2.27.3.2.2 (CONT D)– ELEVATOR RECALL CAN BE EITHER DIRECTLY
TO OR THROUGH THE FIRE ALARM SYSTEMTO, OR THROUGH THE FIRE ALARM SYSTEMTO, THE ELEVATOR CONTROLLER(S)
– FIRE DETECTORS INSTALLED TO THE OBC– FIRE DETECTORS INSTALLED TO THE OBC– FIRE DETECTORS OUTSIDE THE MACHINE
ROOM, CONTROL SPACE, OR CONTROL ROOMROOM, CONTROL SPACE, OR CONTROL ROOMNOT REQUIRED IF THE FLOOR AREA ISEQUIPPED WITH AN ELECTRICALLY
RANDAL BROWN & ASSOCIATES LTD. 15
SUPERVISED SPRINKLER SYSTEM© 2011
CSA-B44-07
• SECTION 2 27 3 2 2 (CONT’D)• SECTION 2.27.3.2.2 (CONT D)– WHERE A FIRE ALARM SYSTEM INITIATES
RECALL MANUAL STATIONS ARE NOT TORECALL, MANUAL STATIONS ARE NOT TOINITIATE DESIGNATED OR ALTERNATE LEVELRECALL
RANDAL BROWN & ASSOCIATES LTD. 16© 2011
CSA-B44-07
• SECTION 2 27 3 2 3 PHASE I EMERGENCY• SECTION 2.27.3.2.3, PHASE I EMERGENCYRECALL OPERATION
ACTIVATION OF A FIRE DETECTOR OTHER– ACTIVATION OF A FIRE DETECTOR, OTHERTHAN ON THE DESIGNATED RECALL LEVEL
• ALL ELEVATORS SERVING THE FLOOR OF• ALL ELEVATORS SERVING THE FLOOR OFINITIATION, AND ANY ASSOCIATED ELEVATORS, TORETURN NONSTOP TO THE DESIGNATED LEVEL
RANDAL BROWN & ASSOCIATES LTD. 17© 2011
CSA-B44-07
• SECTION 2 27 3 2 3 (CONT’D)• SECTION 2.27.3.2.3 (CONT D)– ACTIVATION OF A MACHINE ROOM, CONTROL
SPACE OR CONTROL ROOM FIRE DETECTORSPACE, OR CONTROL ROOM FIRE DETECTOR• ALL ELEVATORS SERVED BY THE MACHINE ROOM,
CONTROL ROOM, OR CONTROL SPACE RETURNNONSTOP TO THE DESIGNATED LEVEL
• IF MACHINE ROOM, CONTROL ROOM, OR CONTROLSPACE LOCATED ON THE DESIGNATED LEVEL ALLSPACE LOCATED ON THE DESIGNATED LEVEL, ALLELEVATORS TO RETURN NONSTOP TO THEALTERNATE LEVEL
RANDAL BROWN & ASSOCIATES LTD. 18© 2011
CSA-B44-07
• SECTION 2 27 3 2 3 (CONT’D)• SECTION 2.27.3.2.3 (CONT D)– ACTIVATION OF A HOISTWAY FIRE DETECTOR
• ALL ELEVATORS SERVED BY THE HOISTWAY TO• ALL ELEVATORS SERVED BY THE HOISTWAY TORETURN NONSTOP TO THE DESIGNATED LEVEL
• IF FIRE DETECTOR LOCATED AT OR BELOW THELOWEST RECALL LEVEL, ALL ELEVATORS TORETURN NONSTOP TO THE UPPER RECALL LEVEL
RANDAL BROWN & ASSOCIATES LTD. 19© 2011
CSA-B44-07
• SECTION 2 27 3 2 4 PHASE I EMERGENCY• SECTION 2.27.3.2.4, PHASE I EMERGENCYRECALL OPERATION TO ALTERNATELEVELLEVEL– ACTIVATION OF A FIRE DETECTOR ON THE
DESIGNATED RECALL LEVELDESIGNATED RECALL LEVEL• ALL ELEVATORS SERVING THE FLOOR OF
INITIATION, AND ANY ASSOCIATED ELEVATORS, TORETURN NONSTOP TO THE ALTERNATE LEVEL
RANDAL BROWN & ASSOCIATES LTD. 20© 2011
CSA-B44-07
• SECTION 2 27 3 2 5 RECALL LEVEL• SECTION 2.27.3.2.5, RECALL LEVEL– RECALL LEVEL FOR ELEVATOR RECALL
DETERMINED BY FIRST ACTIVATED FIREDETERMINED BY FIRST ACTIVATED FIREALARM INITIATING DEVICE
RANDAL BROWN & ASSOCIATES LTD. 21© 2011
CSA-B44-07
• SECTION 2 27 3 2 6 MACHINE ROOM • SECTION 2.27.3.2.6, MACHINE ROOM, CONTROL SPACE, CONTROL ROOM, ORHOISTWAY FIRE DETECTIONHOISTWAY FIRE DETECTION– IN ADDITION TO RECALL, ACTIVATION OF FIRE
DETECTION TO CAUSE IN CAR VISUAL SIGNALDETECTION TO CAUSE IN-CAR VISUAL SIGNALTO FLASH IN ELEVATORS WITH EQUIPMENT INAREA OF INITIATION
– TYPICALLY BY ELEVATOR CONTROLLER
– MAY REQUIRE SEPARATE INPUTS FROM THE
RANDAL BROWN & ASSOCIATES LTD. 22
MAY REQUIRE SEPARATE INPUTS FROM THEFIRE ALARM SYSTEM
© 2011
SUMMARYSUMMARY
RANDAL BROWN & ASSOCIATES LTD. 23© 2011
SUMMARY – OBC & CSA-B44
• SMOKE DETECTORS• SMOKE DETECTORS– ELEVATOR LOBBIES
E M R C– ELEVATOR MACHINE ROOMS, CONTROLSPACES, AND CONTROL ROOMS
NOTE: SMOKE DETECTORS IN ELEVATOR LOBBIES MAY BEOMITTED WITH AHJ APPROVAL IN BUILDINGS WITHELECTRICALLY SUPERVISED SPRINKLER SYSTEMS
RANDAL BROWN & ASSOCIATES LTD. 24© 2011
SUMMARY – OBC & CSA-B44
• FIRE DETECTORS (HEAT OR SMOKE• FIRE DETECTORS (HEAT OR SMOKEDETECTORS)
AS REQUIRED BY THE OBC– AS REQUIRED BY THE OBC– ELEVATOR SHAFTS
E P– ELEVATOR PITS
• MANUAL STATIONS– NOT TO INITIATE RECALL AS PER CSA-B44
RANDAL BROWN & ASSOCIATES LTD. 25© 2011
SUMMARY – OBC & CSA-B44
• FIRE ALARM / ELEVATOR INTERFACES• FIRE ALARM / ELEVATOR INTERFACES– DESIGNATED LEVEL RECALL
A L R– ALTERNATE LEVEL RECALL
– VISUAL SIGNAL FLASHM R C S • MACHINE ROOM, CONTROL SPACE, ANDCONTROL ROOM
• TOP OF SHAFTTOP OF SHAFT
• ELEVATOR PIT
RANDAL BROWN & ASSOCIATES LTD. 26© 2011
QUESTIONS?QUESTIONS?