Transtech Electronic Controls Pty Ltd ABN 21 070 629 499 Perth - Melbourne Perth Tel: (08) 9302-2044 Melbourne Tel: (03) 9330-3624 [email protected] Electronic Transient Surge Protection From Mains Power Supply to Low Volts & Communications Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH TRANSTECH ELECTRONIC CONTROLS www.transtech.com.au

Transcript of Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech...

Page 1: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: (03) 9330-3624 [email protected]

Electronic Transient Surge Protection From

Mains Power Supply to Low Volts & Communications

Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH

TRA

NST

ECH

ELE

CTR

ON

IC C

ON

TRO

LS

ww

w.tr

anst

ech.

com

.au

Page 2: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

FIG 1 FIG 2 FIG 3 FIG 4 FIG 5

AS 1768 IEEE C62 compliant MODELS VOLTAGE Nominal

(Vrms)Maximum (Vrms)

PEAK DISCHARGE CURRENT

Per Mode 8/20usec (kA)

MAX “LET-THRU” VOLTAGE

Volts/Modes

INDICATION Visual/Remote FIGURE No DIMENSIONS

in mm

kA W H DLow Cost DIN 1 PH (Cat A) TLP-8-1P/120V 120 / 150 8.5 390 / 2 N / N Ref HO 12.5 75 53

TLP-8-1P/240V 240 / 275 8.5 600 / 2 N / N Ref HO 12.5 75 53

High Spec DIN 1 PH (Cat C) TLP-40-1P 240 / 275 40 <600 / 3 Y / Y FIG 1 80 110 85

TLP-80-1P 240 / 275 80 <600 / 3 Y / Y FIG 1 80 110 85

TLP-120-1P 240 / 275 120 <600 / 3 Y / Y FIG 1 80 110 85

High Spec DIN 3 PH (Cat C) TLP-P40-3DRI 240 / 275 40 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75

Compact series DIN profile TLP-P80-3DRI 240 / 275 80 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75

Remote status/Indication capable TLP-P120-3DRI 240 / 275 120 <810 / 3 Y / Y + FIG9 FIG 1 105 120 75

High E-N Fault DIN 3 PH (Cat C) TLP-80-3P/NEM 415 / 475 80 <810 / 3 Y / Y + NEM FIG 3 150 110 85

With unique N to E monitoring feature = NEM TLP-120-3P/NEM 415 / 475 120 <810 / 3 Y / Y + NEM FIG 3 150 110 85

TLP-160-3P/NEM 415 / 475 160 <810 / 3 Y / Y + NEM FIG 3 150 110 85

TLP-200-3P/NEM 415 / 475 200 <810 / 3 Y / Y + NEM FIG 3 150 110 85

Compact Series DIN PROFILE (Cat A or B) TLP-150-3P/CAT B 415 / 475 40 <710 / 3 Y / Y FIG 4 150 110 85

No neutral required for this model TLP-415P-E-DIN 415 / 475 40 <810 / 1 Y / N FIG 4 43 110 85

FIG 6 FIG 7 FIG 8 FIG 9 FIG 10

AS 1768, IEEE C62 compliant MODELS VOLTAGE Nominal

(Vrms)/Maximum (Vrms)

PEAK DISCHARGE CURRENT

With 8/20usec (kA)

MAX “LET-THRU” VOLTAGE

Volts/Modes

INDICATION Visual/Remote FIGURE No DIMENSIONS

in mm

kA W H DIndustrial (Cat B) TLP-GPO-10A 240/275 20 710 / 2 N / N 1 x 10A GPO ith 2mtr lead

Integral 20Amp series filter TLP-SF20SL-120V (DIN style) 120 / 275 48 385 / 3 Y / N FIG 6 23 115 85

Integral 20Amp series filter TLP-SF20SL-240V (DIN style) 240 / 275 48 600 / 3 Y / N FIG 6 23 115 85

Integral 20Amp series filter + Relay TLP-SF20RI-120 240 / 275 48 600 / 3 Y / Y FIG 8 23 115 85

Integral 20Amp series filter + Relay TLP-SF20RI-240 240 / 275 48 600 / 3 Y / Y FIG 8 23 115 85

Integral 40Amp series filter TLP-SF40T-P120 185 / 210 48 810 / 3 Y / N FIG 10 95 115 85

Integral 40Amp series filter TLP-SF40T-P240 255/275 48 810 / 3 Y / N FIG 10 95 115 85

Series OR Parallel Cat B TLP-SP20SL 30V 30 / 40 54 600 / 3 Y/ N FIG 7 23 115 85

Up to 20 amps series connected TLP-SP20SL 50V 50 / 60 72 690 / 3 Y / N FIG 7 23 115 85

unlimited in parallell connected TLP-SP20SL 150V 150 / 170 72 690 / 3 Y / N FIG 7 23 115 85

TLP-SP20SL 275V 240 / 275 72 690 / 3 Y/ N FIG 7 23 115 85

FIG 11 FIG 12 FIG 13 FIG 14 FIG 15

AS 1768, IEEE C62 compliant MODELS VOLTAGE Nominal

(Vrms)Maximum (Vrms)

PEAK DISCHARGE CURRENT

With 8/20usec (kA)

MAX “LET-THRU” VOLTAGE

Volts/Modes

INDICATION Visual/Remote FIGURE No DIMENSIONS

in mm

kA W H DSignals (either Analog or Digital) TLP-15L TO TLP-60L 15 / 18 - 60 / 70 8 18 / 3 N / N FIG 14 17.5 75 65.5

transmitters or switches TLP-SL62-xxD (2 ch 6.2mm wide) 15 / 18 - 60 / 70 8 21 / 3 N / N FIG 13 6.2 90 100

TLP-SL62-xxD (2 ch 6.2mm wide) 16 / 18 - 60 / 70 8 43 / 3 N / N FIG 13 6.2 90 100

* Other voltages TLP-SL62-xxD (2 ch 6.2mm wide) 17 / 18 - 60 / 70 8 75 / 3 N / N FIG 13 6.2 90 100

upon request TLP-SL62-xxD (2 ch 6.2mm wide) 18 / 18 - 60 / 70 8 90 / 3 N / N FIG 13 6.2 90 100Protects 24v loop M20 entry TLP-48HM/M20 24 / 48 10 28 / 3 N / N FIG 15 - 172 25 hexProtects 24v loop NPT entry TLP-48HM/NPT 24 / 48 10 28 / 3 N / N FIG 15 - 172 25 hexProtects 24v supply as well as loop M20 entry TLP-48HM-4W/M24 24 / 48 10 28 / 3 N / N FIG 15 - 172 25 hexProtects 230v supply as well as loop M20 entry TLP-48HM-4W/M240 240/24/48 10 28 / 3 N / N FIG 15 - 172 25 hex

Bus Protectors TLP-RS232 ±15 / ±18 400W PPPD 19 / 2 N / N FIG 14 17.5 75 65.5* Other types upon request TLP-RS485 ±12 / ±15 Vdc 400W PPPD 19 / 2 N / N FIG 14 17.5 75 65.5

TLP-RS485/MB ±12 / ±15 Vdc 400W PPPD 19 / 2 N / N FIG 14 17.5 75 65.5

TLP-RS485/PB ±12 / ±15 Vdc 400W PPPD 19 / 2 N / N .FIG 14 17.5 75 65.5

TLP-DNET 24 / 31 400W PPPD 19 / 2 N / N FIG 14 30 75 65.5

TLP-48/RJ45H-4 24 / 31 400W PPPD 19 / 2 N / N FIG 12 25 85 55

Coaxial RF Protectors TLP-N/FF 70V 20 700 / 1kV/Ms N / N FIG 11 TNC FEM/FEM Bulkhead* Other types upon request TLP-F/MF 90V 20 700 / 1Kv/Ms N / N FIG 11 F FEM/MALE

TLP-F/FF 90V 20 701 / 1Kv/Ms N / N FIG 11 F FEM/FEM

Notes and Standards: AS 1768-2005, IEC61643-1, BS 6651-1992, IEEE C62. 41-1991, BS 2914-1972 Compliance: N2909

TransTech Electronic Controls Pty LtdPerth H.O Design/ManufacturingContact: Dale Tunbridge or John King or Mark Van Schalm (Melbourne)MOB: 0439 911-883 or 0419-502-660 or 0409 697-156Unit 2 / 48 Dellamarta RoadWANGARA W.A. 6065

[email protected] or [email protected] or [email protected]\\server\i\Shared\Price Lists & data sheets\Transtech\Flyers\TLP_Listing.xlsx

TLP Transient Lightning Protection

CAT C, 20kV AND 20 kA - use TLP-80-3P, TLP-120-3P, TLP-160-3P

CAT B & A, 6kV @ 20 Amps.

CAT B, 6kV and 3kA - use TLP-8-1P/240 OR TLP-150-3P/CATB,

MAINS PROTECTORS

SERIES FILTERS UP TO 40 AMPS

Process - Industrial - Mining - Commercial - Government - Factories - Research

Perth - Melbourne - Sydney - Brisbane - Adelaide

LOW VOLTAGE PROTECTORS, INSTRUMENTATION AND COMMUNICATIONS (Cat A & B)

This is a TLP overview - contact sales for the full range of TLP protectors

Page 3: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transient Protection Presentation

- 10 – I:\Shared\Price Lists & data sheets\Transtech\Application Notes\TLP Presentation_new.docx TRANSTECH

5. Transient Standards Categories and Definitions.

According to AS 1768:2005 the installation of transient over-voltage protectors can be broken down into five (5) categories. Such categories are shown below from highest risk (E) to lowest risk (A): CAT E 6kV / 70kA CAT D 6kV / 30kA CAT C 6kV / 15 - 20kA CAT B 6kV / 3kA CAT A 6kV / 500Amp

The Point of entry to “very exposed or critically important site. Example: Telecom tower on hill.

CAT E – very high risk The point of entry to an exposed rural site. Example: Pump station a Country Area

The point of entry to a site in the City or built up area. Example: Most common building or site

Within a building immediately after the point of entry or Main Board. Example: Sub-boards.

Within a building and fed from a sub-board being CAT B location. Example: GPO,s

C B B

C B A A

Page 4: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 220VAC rms Maximum Working voltage 275VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 800V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 80kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or Neutral Disconnected the relay de-energizes. LED’s (2) Power On / Unit Healthy, (LED ON = healthy)

GENERAL SPECIFICATION Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel(Powder coated) Dimensions 80 (H) x 80 (H) x 115 (L) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-80-1P is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-80-1P is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. The TLP-80-1P offers a DIN style housing to suit most MCB profiles. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xx 1P. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Neutral to Earth Monitor ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2003 NOTE: This device must be installed by a Qualified Electrician

MODEL :- TLP-80-1P Transtech Lightning Protector - 240V Single Phase, 3 Modes

For CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-80-1P new.docx 05/02/2011

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1

NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

REMOTE RELAY OUT

TLP-80-1P

SINGLE PHASE TRANSIENT PROTECTOR

L1 N E

3 2 1Remote Alarm

1 = N/O | 2 = COMM | 3 = N/CModel No

TRANSTECH

UNITHEALTHY

(Replace if OFF)

POWERON

CAT CV = 240VIn = 40kA

Imax = 120kA

80(W) x 80(H) x 115(L)

Page 5: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 220VAC rms Maximum Working voltage 275VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 800V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 120kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or Neutral Disconnected the relay de-energizes. LED’s (2) Power On / Unit Healthy, (LED ON = healthy)

GENERAL SPECIFICATION Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel(Powder coated) Dimensions 80 (H) x 80 (H) x 115 (L) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-120-1P is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-120-1P is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. The TLP-120-1P offers a DIN style housing to suit most MCB profiles. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP 1P. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Neutral to Earth Monitor ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed motherboard ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2003 NOTE: This device must be installed by a Qualified Electrician

MODEL :- TLP-120-1P Transtech Lightning Protector - 240V Single Phase, 3 Modes

For CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-120-1P new.docx 05/02/2011

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1

NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

REMOTE RELAY OUT

TLP-120-1P

SINGLE PHASE TRANSIENT PROTECTOR

L1 N E

3 2 1Remote Alarm

1 = N/O | 2 = COMM | 3 = N/CModel No

TRANSTECH

UNITHEALTHY

(Replace if OFF)

POWERON

CAT CV = 240VIn = 40kA

Imax = 120kA

80(W) x 80(H) x 115(L)

Page 6: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts Less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains In 36kA Imax 80kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss disconnected the relay de-energizes. LED’s (dual colour) L1, L2, L3, (LED ON = healthy) (LED AMBR = replace)

GENERAL SPECIFICATION Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red / Amber LED’s Housing Material Mild Steel(Powder coated) Dimensions 105 (W) x 120 (H) x 75 (D) Weight 700 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-P80-3DRI is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-P80-3DRI is a true 3 mode (L-L / L-N / N-E) parallel connected surge protection device offering protection for all 3 phases, it also introduces a unique feature, by being connected to a TLP-DSI which will indicate the status of each phase remotely. The TLP-P80-3DRI is powered by all 3 phases and does not lose indication until all 3 phases have failed. This is a distinct advantage over units where indicators are powered from a single phase. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xx-3P. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Internally protected – automatic reset ♦ Local status indication by dual colour LED’s ♦ Remote panel indicator ♦ Alarm status indication via in-built c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and AS/NZS

1768:2003 NOTE: This device must be installed by a Qualified Electrician

MODEL :- TLP-P80-3DRI Transtech Lightning Protector - 415V Three Phase, 3 Mode

For CAT C

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-P80-3DRI new.docx 30 Jan 2010

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

TLP-P80-3DRI

SUPPLY SIDE LOAD SIDE

CONNECTION DIAGRAM

3PH + E SURGE PROTECTION

FUSE/MCB PROTECTION

N E

TRANSTECH

E E

L2

L1

L2

L1

RELAY OUT

LED’s L1 -L2-L3RED = OKAMBER = DECREASEDOFF = REPLACE TLP

L1L1 L1

N

L3

N

L3

REMOTE IND OUT

Page 7: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts Less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 80kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or Neutral & Earth both disconnected the relay de-energizes. LED’s (4) L1, L2, L3, N-E (LED ON = healthy) GENERAL SPECIFICATION

Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel(Powder coated) Dimensions 155 (W) x 105(D) x 85 (H) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-80-3P/NEM is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-80-3P/NEM is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. The TLP-80-3P/NEM now offers a Neutral to Earth protection monitoring circuit (NEMON) which until now has not been available. The NEMON circuit ensures that all 3 modes of protection are active and offers a fully monitored and reliable protection device. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xx-3P/NEM. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Neutral to Earth Monitor ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and AS/NZS

1768:2003 NOTE: This device must be installed by a Qualified Electrician

MODEL :- TLP-80-3P/NEM Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral to Earth Monitoring

For CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-80-3P_NEM new.docx 30 Jan 2010

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1L2L3NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

TLP-80-3P/NEM

THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR

L1 N EL3L2

RELAY OUT1 = N/O2 = COMM3 = N/C

1 2 3

REMOTE RELAY OUT

155(W) x 105(D) x 85(H)

Page 8: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts Less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains In 43kA (10 Impulses) Imax 130kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss disconnected the relay de-energizes. LED’s (dual colour) L1, L2, L3, (LED RED = healthy) (LED AMBER = replace)

GENERAL SPECIFICATION Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red / Amber LED’s Housing Material Mild Steel(Powder coated) Dimensions 105 (W) x 120 (H) x 75 (D) Weight 700 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-P130-3DRI is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-P130-3DRI is a true 3 mode (L-L / L-N / N-E) parallel connected surge protection device offering protection for all 3 phases, it also introduces a unique feature, by being connected to a TLP-DSI which will indicate the status of each phase remotely. The TLP-P130-3DRI is powered by all 3 phases and does not lose indication until all 3 phases have failed. This is a distinct advantage over units where indicators are powered from a single phase. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xx-3P. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Internally protected – automatic reset ♦ Local status indication by dual colour LED’s ♦ Remote panel indicator ♦ Alarm status indication via in-built c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and AS/NZS

1768:2003 NOTE: This device must be installed by a Qualified Electrician

MODEL :- TLP-P130-3DRI Transtech Lightning Protector - 415V Three Phase, 3 Mode

For CAT C

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-P130-3DRI new.docx 24 April 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

TLP-P130-3DRI

SUPPLY SIDE LOAD SIDE

CONNECTION DIAGRAM

3PH + E SURGE PROTECTION

FUSE/MCB PROTECTION

N E

TRANSTECH

E E

L2

L1

L2

L1

RELAY OUT

LED’s L1 -L2-L3RED = OKAMBER = DECREASEDOFF = REPLACE TLP

L1L1 L1

N

L3

N

L3

REMOTE IND OUT

Page 9: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 120kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or Neutral & Earth both disconnected the relay de-energizes. LED’s (4) L1, L2, L3, N-E (LED ON = healthy) GENERAL SPECIFICATION

Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel (Powder coated) Dimensions 155 (W) x 105 (D) x 85 (H) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP 120-3P/NEM is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP120-3P/NEM is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. The TLP-120-3P/NEM now offers a Neutral to Earth protection monitoring circuit (NEMON) which until now has not been available. The NEMON circuit ensures that all 3 modes of protection are active and offers a fully monitored and reliable protection device. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP 3P/NEM. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Neutral to Earth Monitor ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2003 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-120-3P/NEM Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral Earth Monitoring

CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-120-3P_NEM new.docx 12 January 2010

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1L2L3NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

TLP-120-3P/NEM

THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR

L1 N EL3L2

RELAY OUT1 = N/O2 = COMM3 = N/C

1 2 3

REMOTE RELAY OUT

155(W) x 105(D) x 85(H)

Page 10: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 160kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or MOV failed the relay de-energizes. LED’s (4) L1, L2, L3, N-E (LED ON = healthy) GENERAL SPECIFICATION

Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel (Powder coated) Dimensions 155 (W) x 105 (H) x 85 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP 160-3P is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP160-3P is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2003 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-160-3P Transtech Lightning Protector - 415V Three Phase, 3 Mode

CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-160-3P new.docx 27 June 2011

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1L2L3NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

TLP-120-3P

THREE PHASE TRANSIENT PROTECTOR

L1 N EL3L2

RELAY OUT1 = N/O2 = COMM3 = N/C

3 2 1

REMOTE RELAY OUT

Page 11: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 160kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or Neutral & Earth both disconnected the relay de-energizes. LED’s (4) L1, L2, L3, N-E (LED ON = healthy) GENERAL SPECIFICATION

Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel (Powder coated) Dimensions 155 (W) x 105 (D) x 85 (H) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP 160-3P/NEM is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP160-3P/NEM is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. The TLP-160-3P/NEM now offers a Neutral to Earth protection monitoring circuit (NEMON) which until now has not been available. The NEMON circuit ensures that all 3 modes of protection are active and offers a fully monitored and reliable protection device. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP 3P/NEM. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Neutral to Earth Monitor ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2003 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-160-3P/NEM Transtech Lightning Protector - 415V Three Phase, 3 Mode with Neutral Earth Monitoring

CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-160-3P_NEM new.docx 12 January 2010

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1L2L3NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

TLP-160-3P/NEM

THREE PHASE TRANSIENT PROTECTOR WITH NEUTRAL/EARTH MONITOR

L1 N EL3L2

RELAY OUT1 = N/O2 = COMM3 = N/C

1 2 3

REMOTE RELAY OUT

155(W) x 105(D) x 85(H)

Page 12: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 415VAC rms Minimum Working voltage 328VAC rms Maximum Working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts less than 810V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 240kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output Phase loss or MOV failed the relay de-energizes. LED’s (4) L1, L2, L3, (LED ON = healthy) GENERAL SPECIFICATION

Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Red LED’s Housing Material Mild Steel (Powder coated) Dimensions 155 (W) x 105 (H) x 85 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP 240-3P is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP 240-3P is a true 3 mode parallel connected protection device offering 3 levels of kA rating in all 3 modes. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Internally protected – automatic reset ♦ Local status indication by LED’s ♦ Remote status indication c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-240-3P Transtech Lightning Protector - 415V Three Phase, 3 Mode

CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-240-3P new.docx 27 June 2011

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

L1L2L3NE

SUPPLY LOAD

CONNECTION (CABLES 16sq/mm AS SHORT AS POSSIBLE)

TLP-240-3P

THREE PHASE TRANSIENT PROTECTOR

L1 N EL3L2

RELAY OUT1 = N/O2 = COMM3 = N/C

3 2 1

REMOTE RELAY OUT

Page 13: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal working voltage 415VAC rms Minimum working voltage 328VAC rms Maximum working voltage 476VAC rms Working Freq. 40 - 60Hz Peak let thru volts <800V Maximum mains current Unlimited (parallel connected)

Must be fuse protected over 100A Mains Category AS/NZS 1768 Cat B In (Crest current) 60kA (8/20uS) Imax (Max discharge current) 150kA (8/20uS) Response time Less than 25nS Surge Reset Automatic SPECIAL FEATURES LED Indication LED’s ON = TLP healthy LED OFF = TLP repair Relay Output Changeover volt-free

GENERAL SPECIFICATION Operating Temp -40 to +70 Deg C Terminals 16mm2 solid max / 10mm2 flex max Remote Terminals N/A Indicators Green LED’s Housing Material Aluminium (Powder coated) Dimensions 95.5(W) x 72(H) x 108(L) Weight 700 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-150-3M/CAT B is a lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The mains borne transient voltages may occur as a result of lightning strikes or the switching of large inductive / capacitive loads. The TLP-150-3M/CAT B is a parallel device for Cat B applications and should be installed as close as possible to the supply being protected. It is recommended that connecting cables be kept shorter than 300mm. The TLP-150-3M/CAT B is a true 3 mode protection device with an Imax rating of 150kA for Cat B applications. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP 150-3M. FEATURES ♦ Low “let thru” voltage ♦ Designed and manufactured to ISO 9001 ♦ Certified for BER Projects ♦ Internally protected – automatic reset ♦ LED status indication for power loss or fault ♦ Designed to pass IEC 616431-1:2005 and AS/NZS

1768:2003 ♦ Long lifetime, fully lacquered PCB’s ♦ CE Marking / C-tick N 2909 ♦ Full 3 mode protection ♦ DIN 43880 compliant

MODEL: TLP-150-3M/CAT B Transtech Lightning Protector - 415V Three Phase, 3 Mode

I:/Docs/word/DataSheets/TLP-150-3M/CATB 14th October 2009

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

TLP-XXX-3M/CATB

SUPPLY SIDE

LOAD SIDE

L1L2L3NE

L1L2L3NE

CONNECTION DIAGRAM

3PH 415V PROTECTION CAT BFU

SE

/MC

B

PR

OTE

CTI

ON

L1 ENL3L2

Page 14: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE PAGE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-DSI.doc Confidential Page 1 March 12, 2013

d

DATA SHEET Subject to change without notice

TECHNICAL DATA The TLP-DSI is powered directly from the Remote Indicator (RI) output of Transtech TLP any High Energy TLP unit which incorporates the unique Remote Indicator circuitry. Status LEDs 3 x RED

GENERAL SPECIFICATION Operating Temp. -25 to 70 degrees C Connection 3 way 2.5mm2 plug-off Housing Material ABS. Dimensions 48 x 48 x 60 mm Weight 25gm nominal Mounting Through panel mount

GENERAL DESCRIPTION The TLP-DSI is a self-powered remotely mounting status indicator which mirrors the status LEDs on Transtech’s High Energy TLP’s which have a unique remote Indicator (RI) output fitted. The LEDs of the TLP-DSI match their respective status LED on the monitored TLP unit. A unique circuit design means that only 3 wires are required to display the status of any one of the monitored TLP LEDs. The length of the 3 core cable between the TLP-xxx and its TLP-DSI should be no more than a maximum of 5 meters. FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Small size 48mm x 48mm panel mount unit ♦ 3 bright, easy to read LEDs ♦ Status LEDs match those of the TLP LEDs ♦ Easy to connect - only 3 wires ♦ Plug-off terminals ♦ No setup required.

MODEL TLP-DSI Direct Status Indicator

L1

NE

LOAD

CONNECTION

REMOTE RELAY OUT

TLP-40-3P

THREE PHASE TRANSIENT PROTECTOR

N E

3 2 1Remote Alarm

1 = N/O | 2 = COMM | 3 = N/CModel No

TRANSTECH

UNITHEALTHY

(Replace if OFF)

POWERON

CAT CV = 240VIn = 40kA

Imax = 120kA

REMOTE STATUS OUT

3 core cable 0.5 sqmmMax 5 mtr

TLP-DSITRANST ECH

L1 L2 L3

L2L3

Page 15: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE PAGE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-PSI.docx Confidential Page 1 March 7, 2013

d

DATA SHEET Subject to change without notice

TECHNICAL DATA Power Supply: 120, 220/240 +/- 15% VA Rating : Typically 1.3VA Status LEDs: Power BLUE Healthy RED Fault YELLOW Output: Relay volt free contact

GENERAL SPECIFICATION Operating Temp. -25 to +70 degrees C Power Terminals Plug in 1.5mm2

Sense Terminals Plug in 1.5mm2

Relay Output Term. Plug off 2.5mm2 Indicators Blue, Red, Yellow LEDs Housing Material ABS Dimensions 48 x 48 x 60 Weight 50gm nominal Mounting Through panel mount

GENERAL DESCRIPTION The TLP-PSI is a 48mm x 48mm AC powered, status indicator which may be connected to any TLP product which incorporates a status output relay. The TLP-PSI can be mounted in a convenient location at some distance from the associated transient protection device. The TLP-PSI uses a transformer isolated 24V DC to monitor the TLP status (fault) relay, it has three status LEDs;

BLUE = Power OK RED = Healthy YELLOW = Faulty (replace)

FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Small size 48mm x 48mm panel mount unit ♦ 3 bright, easy to read LEDs ♦ Easy to connect ♦ Plug-off terminals ♦ Boxed (shrouded) AC connector ♦ No setup required.

MODEL TLP-PSI Powered Remote Status Indictaor

L1

NE

SUPPLY LOAD

REMOTE RELAY OUT

TLP-40-3P

THREE PHASE TRANSIENT PROTECTOR

N E

3 2 1Remote Alarm

1 = N/O | 2 = COMM | 3 = N/CModel No

TRANSTECH

UNITHEALTHY

(Replace if OFF)

POWERON

CAT CV = 240VIn = 40kA

Imax = 120kA

TLP-PSI/240VTRANST ECH

REMOTE RELAY OUT NeutralLine

Supply120Vac or 240Vac

L1 L2 L3

L2L3

Page 16: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-415p e.din new.docx Confidential August 24, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working voltage

415V Max. working volts 480V RMS Working Freq. 40 - 60 Hz Peak let thru volts 710V Protection Modes Phase -Earth ONLY Surge Rating 20kA, Mass Surge Material 60kA 8/20uSecs Meets Surge Ratings to AS/NZS 1768-1991 IEEE C 62.41, UL 1449 Earth Leakage Approx 500uA Operating Current N/A in parallel

GENERAL SPECIFICATION Operating Temp -20 to 70 Deg C Storage Temp -55 to 75 Deg C Humidity 0 - 90% RH Indication 3 Neon indicators Terminals Self opening 0.5 - 10mm 20 - 6 AWG Housing Material KRILEN / AL cover Mounting Style DIN or G rail Dimensions 112mm x 75mm x 45mm Weight 195 grams

L1 L2 L3

EARTH

GENERAL DESCRIPTION The TLP-415P/E-DIN series is a lightning and power transient arrester which provide voltage surge limitation to power electrical devices connected to the mains power supply. The TLP-415P/E-DIN provides effective protection by clamping the over voltage to a safe level. Three (3) indicators show if the TLP-415P/E-DIN is “healthy” and providing protection. Should one(1) indicator go off replacement should be done as soon as possible if ALL three indicators are off the device must be replaced IMMEDIATELY. The TLP-415P/E-DIN must always be installed on the load side of a fuse or MCB. The TLP-415P/E-DIN can be mounted directly on to “G” or “DIN” rails (DIN 46277-1 and 46277-3) BENEFITS:- ♦ Low “let thru” voltage ♦ Protection between 3 Phases – Earth ♦ Fast snap on DIN rail mounting ♦ 26kA discharge capacity per line ♦ Location Category B to AS 1768 ♦ CE / C-tick marking ♦

*** CAUTION *** ♦ Ensure that the Earth is appropriately terminated at

all times. Ensure that the all Phases are at 0V potential before removing the unit for service.

MODEL :-TLP-415P/E-DIN Transtech Lightning Protector (no Neutral) - CAT B

L x H x W = 112mm x 75mm x 45mm

Page 17: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: (03) 9330-3624 [email protected]

Electronic Transient Surge Protection 20 AMP Series Filter 23mm WIDE

Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH

TRA

NST

ECH

ELE

CTR

ON

IC C

ON

TRO

LS

ww

w.tr

anst

ech.

com

.au

UNIQUE FEATURES: Slimmest 20Amp Model available 3rd Party Tested to IEC 61643-1:2005 (PASSED) High Fault Rating 54kA Mass Metal Hosuing Front LED Australian Designed and Manufactured Over 15,000 Installed Australia Wide

Model: TLP-SF20-SL-240V

Model: TLP-SP20-SL-240V

Page 18: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE PAGE Page 1 of 2 ISSUE A / Rev C I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SF20SL-240V revc.docx Confidential Page 1 November 2, 2011

d

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working voltage

240V RMS Max. Working volts 275V RMS Working Freq. 40 - 60 Hz Peak let thru volts 710 V (typical 1 pulse) Protection Modes Ph-N, Ph-E, N-E Surge Rating;- Imax (max discharge current)42kA (8/20msec) @ 75% Iin (crest current) 24kA Meets Surge Ratings to AS/NZS 1768:2003 IEEE C 62.41, UL 1449 Tested & Pass to IEC 61643.1:2005 Surge Filter Inductor Type Common Mode 20A choke Capacitors X and Y Cut-off Frequency Less than 1kHz (-3dB loss) Attenuation (60dB) 5MHz Earth Leakage Approx. 500uA Operating Current 3mA nominal Loss Less than 2Watts Continuous Current 20 Amps GENERAL SPECIFICATION Operating Temp -35 to 70 Deg C Storage Temp -55 to 90 Deg C Humidity 0 - 90% RH Terminals Self opening 0.5 – 4sq mm Housing Material MS cover/ ABS base Mounting Style DIN or G rail Dimensions (LxHxW) 112mm x 75mm x 23.5mm nom. Weight 175 grams

GENERAL DESCRIPTION The TLP-SF20SL series are lightning and power surge transient arrestors with surge filtering. These provide voltage limitation and filtering of transients for sensitive electronic devices connected to the mains power supply. The TLP-SF20SL provides effective protection via a three stage circuit. The input stage limits the over-voltage excursion, the second stage series surge filter restricts the rate of rise of voltage (dV/dt) of any transient over-voltage and the final stage clamps the output voltage to a safe level. The TLP-SF20SL must always be installed on the load side of a fuse rated at 20 amps or less. The TLP-SF20SL can be mounted directly on to “G” or “DIN” rails (DIN 46277-1 and 46277-3) BENEFITS:- ♦ Slim 23mm wide metal housing. ♦ Low “let thru” voltage ♦ Series inductor to control rate of voltage

rise ♦ Protection between all lines ♦ System Healthy Indicator - LED ♦ Fast snap on DIN rail mounting ♦ 24kA discharge capacity per line ♦ For location Cat B to AS 1768:2003 ♦ Tested & Passed to IEC 61643-1:2005 ♦ Designed to IEEE C 62.41 (UL1449) ♦ Designed and manufactured in Australia to

ISO 9001

MODEL :-TLP-SF20SL-240V Transtech Lightning Protector/Surge Filter - 20Amp for 240Vac

L x H x W = 112mm x 75mm x 23.5mm nom.

INPUT POWER

UNIT HEALTHY LED

L N E

L N E

TLP-SF20SL

SYSTEM HEALTHY

OUTPUT POWERCLEAN

CB / FUSE

TLP-SF

RCD DEVICE

LOAD

LINE

Page 19: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE PAGE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SF20RI-240.doc Confidential Page 1 8/9/2012

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working voltage

220 - 250V RMS Max. working volts 275V RMS Working Freq. 40 - 60 Hz Peak let thru volts 710V (single pulse) Protection Modes Ph-N, Ph-E, N-E Surge Rating: Imass 108kA Imax 72kA Iin 48kA Operating Burden Approx 7mA Meets Surge Ratings to AS/NZS 1768:2003 IEEE C 62.41:2005UL 1449 Filter Inductor Type Common Mode 20A choke Capacitors X and Y Attenuation (60dB) 5MHz Earth Leakage Approx 500uA Operating Current 20 Amps Maximum Current 22 Amps Other Features Relay Output Form C 5A continuous

(Relay fails to safe position) Relay Terminals Plug-in 0.5 – 2.5mm

GENERAL SPECIFICATION Operating Temp -35 to 70 Deg C Storage Temp -55 to 75 Deg C Humidity 0 - 90% RH Terminals Self opening 0.5 – 4 sq mm Housing Material Mild Steel – DIN clip feet Mounting Style DIN rail Dimensions (HxWxD) 120mm x 52mm x 80mm Weight 195 grams

GENERAL DESCRIPTION The TLP-SF20RI series is a series of lightning and power transient arrestors with filtering + LED and relay output which provides voltage surge limitation and filtering to sensitive electronic devices connected to the mains power supply and rated up to 20 amps. The TLP-SF20RI provides effective protection by clamping the over voltage and via the series filter reducing the rate of rise of the clamped voltage to a safe level. If a fault occurs within the TLP-SF20RI the “healthy LED will extinguish and the relay will de-energize). The TLP-SF20RI must always be installed on the load side of a protective device rated at 20 amps or less. The TLP-SF20RI can be mounted directly on to “DIN” rails (DIN 46277-1) BENEFITS:- ♦ Low “let thru” voltage ♦ Series filter to control rate of voltage rise ♦ Protection between all lines (diff & common

mode) ♦ Power “ON” indication ♦ Unit “HEALTHY” indication (with relay) ♦ Fast snap on DIN rail mounting ♦ Designed for MEN Systems ♦ Location Category B to AS 1768:2005 ♦ Tested to IEEE C 62.41:2005 & compliant) ♦ Designed and manufactured to ISO 9001 ♦ CE / C-tick marking

MODEL :-TLP-SF20RI-240V Transtech Lightning Protector/Filter - 20Amp for 240Vac with Relay

INPUT

OUTPUT

N/O COM N/C

Fault

Power

TLP-SF20RI-240SERIES FILTER SURGE PROTECTOR

INPUT SUPPLYL N E

L N EOUTPUT CLEAN SUPPLY

ALARM OUTPUT

RELAY

TRANSTECH

Page 20: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET

TECHNICAL DATA Voltage rating Normal working voltage

240V DC/AC Max. Working volts 275V DC/AC Working Freq. DC - 60 Hz Rated Current 20 Amps for series connect Unlimited for parallel connect Peak let thru volts 900 V Protection Modes Ph-N, Ph-E, N-E Surge Rating;- Ph-N, 24kA, 8/20μS Ph-E, 24kA, 8/20μS N-E, 24kA, 8/20μS Imax 72kA Earth Leakage Approx 500uA Continuous Current 20 Amps (see above re series/parallel) Meets Surge Ratings to AS/NZS 1768:2003 IEEE C 62.41, UL 1449 IEC 61643.1:2005 GENERAL SPECIFICATION

Operating Temp -35 to 70 Deg C Storage Temp -55 to 90 Deg C Humidity 0 - 90% RH Terminals Self opening 0.5 – 4sq mm Housing Material M/Steel cover / ABS base Mounting Style DIN or G Rail Dimensions (LxHxW) 112mm x 75mm x 23.5mm Weight 175 grams

GENERAL DESCRIPTION The TLP-SP20SL range is either a series or parallel connected lightning and power transient arrestor. The range provides voltage surge limitation for sensitive electronic devices connected to the mains power supply. The TLP-SP20SL must always be installed on the load side of a fuse rated at 20 amps or less. The TLP-SP20SL can be mounted directly on to “G” or “DIN” rails (DIN 46277-1 and 46277-3) BENEFITS:- ♦ Slim 23mm wide metal housing. ♦ Low “let thru” voltage ♦ Protection between all lines ♦ System Healthy Indicator ♦ Fast snap on DIN rail mounting ♦ 24kA discharge capacity per line ♦ For location Cat B to AS 1768:2003 ♦ Tested to IEC 61643-1:2005 ♦ Tested to IEEE C 62.41 (UL1449) ♦ Designed and manufactured in Australia to

ISO 9001

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

MODEL :-TLP-SP20SL-275 Transtech SERIES/PARALLEL Lightning Protector - 20Amp for 275V

PAGE 1 / 1 ISSUE A REV B

INPUT POWER

UNIT HEALTHY LED

L N E

L N E

TLP-SP20SL

SYSTEM HEALTHY

OUTPUT TO LOAD

MAX 20amps

INPUT POWER

UNIT HEALTHY LED

L N E

L N E

TLP-SP20SL

SYSTEM HEALTHY

OUTPUT TO LOAD

UNLIMITED amps

SERIES PARALLEL

FUSESMax 20amps

FUSESMax 20amps

CONNECTION SCHEDULE

Page 21: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: (03) 9330-3624 [email protected]

Low Cost Surge Protection

Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH

TRA

NST

ECH

ELE

CTR

ON

IC C

ON

TRO

LS

ww

w.tr

anst

ech.

com

.au

Page 22: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 185VAC rms Maximum Working voltage 275AC rms Working Freq. 40 - 60Hz Peak let thru volts less than 1000V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 60kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output MOV failed the relay de-energizes. Indicator L1, L2, L3, flag type

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 35mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Green/Red mechanical flag Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 18 (W) x 60 (H) x 90 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-V60/275S is a “new series” PLUG-IN lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-V60/275S is a single mode parallel connected protection device offering 60kA single mode but for all three phases. see “1 Pole N/E” version Fig below. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Local status indication by mechanical flag ♦ Remote status indication by c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Available in 1P or 2P or 3P bases ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-V60/275/S Transtech Lightning Protector - 240V Plug-in Protectors CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275s.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3

CONNECTION DIAGRAM

FUS

E/M

CB

P

RO

TEC

TIO

N

TRANSTECH

TLP-V60

N/PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

L L

TRANSTECH

TLP-V60

PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

PE

L N

1 Pole N/E 3 Pole + E1 Pole N+E

NE

NE

Page 23: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 185VAC rms Maximum Working voltage 275AC rms Working Freq. 40 - 60Hz Peak let thru volts less than 1000V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 60kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output MOV failed the relay de-energizes. Indicator L1, L2, L3, flag type

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 35mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Green/Red mechanical flag Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 18 (W) x 60 (H) x 90 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-Vxx/275/S is a “new series” PLUG-IN lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-V60/275SM is the replacement plug-in module single mode parallel connected 60kA protection device. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Local status indication by mechanical flag ♦ Remote status indication by c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Available in 1P or 2P or 3P bases ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-V60/275/SM Transtech Lightning Protector - 240V Plug-in Protector Range CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275sm.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3

CONNECTION DIAGRAM

FUS

E/M

CB

P

RO

TEC

TIO

N

TRANSTECH

TLP-V60

N/PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

L L

TRANSTECH

TLP-V60

PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

PE

L N

1 Pole N/E 3 Pole + E1 Pole N+E

NE

NE

Page 24: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 185VAC rms Maximum Working voltage 275AC rms Working Freq. 40 - 60Hz Peak let thru volts less than 1000V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 100kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output MOV failed the relay de-energizes. Indicator Flag type

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 35mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Green/Red mechanical flag Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 36 (W) x 60 (H) x 90 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-V60/275S is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to a single phase distribution system. The TLP-V60/275S is a single mode parallel connected protection device offering 60kA single mode L-N and L-E(PE) (see middle Fig bottom left). For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Local status indication by mechanical flag ♦ Remote status indication by c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Available in 1P or 2P or 3P ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-DS60/275-2V Transtech Lightning Protector - 240V 1P+N E Protector 60kA CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-ds60-275-2vs.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3

CONNECTION DIAGRAM

FUSE

/MC

B PR

OTE

CTI

ON

TRANSTECH

TLP-V60

N/PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

L L

TRANSTECH

TLP-V60

PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

PE

L N

1 Pole N/E 3 Pole + E1 Pole N+E

NE

NE

Page 25: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms Minimum Working voltage 185VAC rms Maximum Working voltage 275AC rms Working Freq. 40 - 60Hz Peak let thru volts less than 1000V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 100kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output MOV failed the relay de-energizes. Indicator L1, L2, L3, flag type

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 35mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Green/Red mechanical flag Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 36 (W) x 60 (H) x 90 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-V100/275S is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-V100/275S is a single mode parallel connected protection device offering 60kA single mode. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Local status indication by mechanical flag ♦ Remote status indication by c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Available in 1P or 2P or 3P ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-V100/275 Transtech Lightning Protector - 240V 1P Protector 100kA CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v100-275.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3

CONNECTION DIAGRAM

FUS

E/M

CB

P

RO

TEC

TIO

N

1 Pole N+E

NE

NE

TRANSTECH

TLP-V100TRANSTECH

TLP-V100

L L

Page 26: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 240VAC rms L – E(PE) Minimum Working voltage 185VAC rms Maximum Working voltage 275AC rms Working Freq. 40 - 60Hz Peak let thru volts less than 1000V Maximum mains current Unlimited (parallel connected) Must be fuse protected over 100A Mains Imax 60kA (8/20uS) Response time Less than 25nS Relay Contacts SPCO (1 amp @240Vac) Surge Reset Automatic SPECIAL FEATURES Relay Output MOV failed the relay de-energizes. Indicator L1, L2, L3, flag type

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 35mm2 solid max / 10mm2 flex max Remote Terminals Plug in 2.5mm2 Indicators Green/Red mechanical flag Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 55 (W) x 60 (H) x 90 (D) Weight 850 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-DS60/275 3V is a “new series” lightning and transient protector which provides protection for electrical / electronic equipment connected to three phase distribution systems. The TLP-DS60/275 3V is a single mode parallel connected protection device offering 60kA single mode for Line 1,2,3 and Earth – see “3 Pole PE” version Fig below. For mains supply of greater than 100A adequate HRC fuse or MCB protection must be installed prior to the TLP-xxx- 3P FEATURES ♦ Designed and manufactured to ISO 9001 ♦ Local status indication by mechanical flag ♦ Remote status indication by c/o relay ♦ High Energy designed pcb’s ♦ CE Marking / C-tick N 2909 ♦ Available in 1P or 2P or 3P bases ♦ DIN 43880 compliant ♦ Designed to pass IEC 61643-1:2005 and

AS/NZS 1768:2005 NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-DS60/275/3V Transtech Lightning Protector – 3 x 240V Plug-in Protectors CAT C or less

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-v60-275s.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3

CONNECTION DIAGRAM

FUS

E/M

CB

P

RO

TEC

TIO

N

TRANSTECH

TLP-V60

N/PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

L L

TRANSTECH

TLP-V60

PE

L

TRANSTECH

TLP-V60TRANSTECH

TLP-V60

PE

L N

1 Pole N/E 3 Pole + E1 Pole N+E

NE

NE

Page 27: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Normal Working voltage 110 - 240VAC Minimum Working voltage - Maximum Working voltage 275AC Working Freq. 40 - 60Hz Peak let thru volts - Maximum mains current 100A Imax - Response time - Relay Contacts - Surge Reset Automatic SPECIAL FEATURES Relay Output - Indicator 2 digit LCD Battery 7.2V service life 1 year

GENERAL SPECIFICATION Operating Temp -40 to +80 Deg C Terminals 2.5mm Remote Terminals - Indicators 2 Digit LCD Housing Material Thermoplastic UL94-V-O Degree Protection IP-20 Dimensions (module) 18 (W) x 60 (H) x 90 (D) Weight 125 grams Mounting DIN 43880 Standard DIN Rail

GENERAL DESCRIPTION The TLP-LEC-A is a “new series” lightning and transient protector COUNTER with sensor for electrical / electronic equipment connected to three phase distribution systems. The TLP-LEC-A has a single current sensor for monitoring any one phase – if three phases require monitoring ins tall 3 TLP-LEC-A units. FEATURES ♦ Designed and manufactured to ISO 9001 ♦ CE Marking / C-tick N 2909 ♦ Available in 1P only ♦ DIN 43880 compliant NOTE: This device must be installed by a Qualified Electrician.

MODEL :- TLP-LEC-A Transtech Surge/ Lightning Counter

I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-lec-a.docx 01 Feb 2013

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE.

PAGE 1 / 1 ISSUE A / Rev A

CONNECTION DIAGRAM

SUPPLY SIDE LOAD SIDEL1L2L3

L1L2L3NE

NE

TRANSTECH

SUPPLYL N

SENSOR

TLP-LEC-A

99

Page 28: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044
Page 29: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: (03) 9330-3624 [email protected]

Electronic Transient Surge Protection

LOW VOLTAGE & BUS PROTECTORS – Cat B or A

Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH

TRA

NST

ECH

ELE

CTR

ON

IC C

ON

TRO

LS

ww

w.tr

anst

ech.

com

.au

NEW

Page 30: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL62-30D new.doc Confidential August 23, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating (per channel) Normal working volt 30V D.C. (peak AC) Max. working volts 37V D.C. (peak AC) Peak let thru volts 43.5V Current/Resistance rating (per channel) End to End resist. 6 ohms nominal Max Current 500 mA Discharge Current 2kA per mode or 4kA per

line (8/20usec) Response rating Response time: Under 10nsec

GENERAL SPECIFICATION Operating Temp -10 to 70 Deg C Storage Temp -40 to 105 Deg C Connections Self-opening 2.5mm/12AWG Housing Material Polyester PBT Mounting Style DIN Rail Dimensions 93.1(d) x 102.5(h) x 6.2(w) Weight 52 grams

GENERAL DESCRIPTION The TLP-SL62 series of lightning and transient arrestors are manufactured in a slim-line 6.2mm housing for those applications where a high packing factor is required. The units provide protection for electronic equipment connected to twisted pair control and communication signal lines. The TLP-SL62-30D has true three stage protection in all modes. FEATURES ♦ Dual channel unit ♦ Two independent channels ( common earth) ♦ 3 stage protection ♦ Low “let thru” voltage ♦ Protection between ALL lines ♦ Designed for 3kV impulse protection ♦ Fast snap on DIN rail mounting ♦ Fail to safe ♦ Field proven technology ♦ 4kA discharge capacity per channel ♦ Designed and manufactured to ISO 9001 ♦ 6.2mm Slim Profile ♦ 300mm uncommitted earthing cable ♦ CE marking / C-tick N2909

MODEL :- TLP-SL62-30D Transtech Lightning Protector - Dual Channel

N2909

2

8

7

1

4

6

5

3

TLP-SL62-xxD

INPU

T 2

CLE

AN

OU

T 1

INPU

T 1

CLE

AN

OU

T 2

Transient Barrier

Earth

CAT BImax = 8kA

Voltage (Uc) = V

93mm x 102.5mm x6.2mm

Page 31: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL12-xx.docx Confidential November 6, 2012

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt 05,12,15,18,24,48V +/- Peak let thru volts 10,19,25,29,39,78V resp. Current/Resistance rating End to End resist. Less than 6 ohm Max Current 600 mA Surge Current Imax 2 kA/mode (8/20uS) Response rating Response time Under 10nsec

GENERAL SPECIFICATION GENERAL SPECIFICATION Operating Temp -10 to 60 Deg C Storage Temp -55 to 75 Deg C Terminals Self-opening 2.5mm/12AWG Housing Material KRILEN Mounting Style DIN Dimensions 110mm X 52mm X12mm Weight 60 grams

GENERAL DESCRIPTION The TLP-SL12-xx series is a very compact 12mm wide lightning and transient arrester providing protection for equipment connected to low voltage instrument loops by limiting the transient over-voltage to less than twice the normal working voltage. The TLP-SL12-xx series provides protection between all conductors, line to line and each line to earth. It is mounted on to “DIN” rail (46277-3) and offers screen termination via terminals and the earth via a 300 mm earth wire “tail”. FEATURES ♦ Low “let thru” voltage ♦ Protection between ALL lines ♦ Fast snap on DIN rail mounting ♦ Fail to safe status design ♦ Field proven technology ♦ Low line losses (volt drop) ♦ Designed and manufactured to ISO 9001 ♦ High stacking density ♦ C-Tick/ CE Compliant ♦ IEC 1000-4-2 & EN50082

MODEL :- TLP-SL12-xx Transtech Lightning Protector for Low Voltages 05V – 48V

TRANSTECH

INPUT LINE

TLP-

SL12

-xx

1 23 4

1 2

3 4

5 6

7 8

OUTPUT LINE

5 67 8

TRANSTECH

INPUT LINE

TLP-

SL12

-xx

1 23 4

1 2

3 4

5 6

7 8

OUTPUT LINE

5 67 8

CABLE - OUTPUT

CABLE - INPUT

CABLE - INPUT

CONNECTION SCHEDULE

SER

IES

CO

NN

ECTI

ON

PAR

ALL

ELC

ON

NEC

TIO

N

Page 32: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage Rating Current Loop: 22V – 48Vdc (black/black) Supply: 190-265Vac (blue/brown) Current/Impedance Rating End to End Impedance: N/A parallel connection Max Current: N/A parallel connection Discharge Power: Imax = 10kA (8-20uS wave) Response rating Response time: Less than 10nS EMC Compliance: EN50082 part 2 C-tick / CE compliant Field Bus: 31.25kbit/s

GENERAL SPECIFICATION Operating Temp: -20 to 60 Deg C Storeage Temp: -40 to 80 Deg C Humidity: 5% to 95% RH (Non-condensing) Termination wires: Flying Leads (250mm 1.0mm2) (colour coding) Blue & Brown for 240vac supply Black for 4-20mA signal Green / Yellow for earth Housing Material: ANSI 316 Stainless Steel Dielectric Strength: 25oC, 50 kHz, 19kV/mm Thread: a) 20mm ISO (M20 x 1.5) b) ½” NPT Weight: 185g Dimensions: 75mm (L) x 25mm Hex c/- 250mm coloured leads

GENERAL DESCRIPTION The TLP-48HM-4W-240 lightning/transient protector provides protection for field mounted transmitters or electronic devices mounted in exposed areas. The TLP-48HM-4W-240 consists of a high speed solid state switching network which protects all signal and supply lines and common earth. The front end protection per line has a gas discharge tube with a 10kA rating. The housing material is ANSI 316 stainless steel with a 23mm flat for assisting mechanical mounting. The unit is encapsulated in high temperature casting epoxy. This epoxy offers high impact resistance with excellent electrical properties and high temperature stability. The standard male thread is the common 20mm conduit entry (20mm ISO, M20 x 1.5), several other thread types are available upon request. The TLP-48HM-4W-240 is designed to be added to standard installations. Most field transmitters have two conduit entries, one is used to connect the data cable, the spare can be used for the TLP-48HM-4W-240 connection. Under most field installations no additional connection boxes are required. Should no spare entry be available then a simple conduit tee can be used as close as possible to the field device. The TLP-48HM-4W-240 connection is a simple parallel connection for BOTH supply and signal lines (see connection schedule). Care must be taken in the earthing of the green/yellow earth wire from the TLP-48HM-4W-240. This earth wire must be earthed to local general/structural metal work, all leads to be kept as short as possible at all times. FEATURES ♦ ESD Protection ♦ Low “let thru” voltage ♦ Protection between ALL lines (including 240vac supply) ♦ Field proven technology ♦ Simple field mounting ♦ Field Buss compatible (4-20mA loop only) ♦ Parallel Connection (No loop impedance) ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/CE compliant ♦ Meets AS/NZS 1768:2003 Class B ♦ Meets IEC 61643.1:2005 Class I & II ♦ Auto resetting ♦ High 10kA discharge

MODEL :- TLP-48HM-4W-240 Transtech Lightning Protector - Process Transmitter

Loop plus 240V Supply Protector

DESIGNED & MANUFACTURED by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE. I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-48HM-4W-240rev.doc 1st January 2009

PAGE 1 / 1 ISSUE C / Rev A

25mm Hex x 75mm c/- 250mm leads

Page 33: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-SL12-RS485MB.docx Confidential November 6, 2012

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt +/- 12V Peak let thru volts 19V @ 1p = 1A Peak let thru volts 24V @ 1p = 10A Current/Resistance rating End to End resist. Less than 0.6 ohms Max Current 1 Amp Discharge Power 400W PPPD @ (8/20uS) (Peak Pulse Power Discharge) Response rating Response time Under 10nsec

GENERAL SPECIFICATION GENERAL SPECIFICATION Capacitance @ 1mMz, 75pF Operating Temp -10 to 60 Deg C Storage Temp -55 to 75 Deg C Terminals Self-opening 2.5mm/12AWG Housing Material KRILEN Mounting Style DIN Dimensions 110mm X 52mm X12mm Weight 60 grams

GENERAL DESCRIPTION The TLP-SL12-RS 485MB is a very compact 12mm wide lightning and transient arrester providing protection for equipment connected to the Modbus RS 485 multi-point or party line bus by limiting the transient over-voltage to less than twice the normal working voltage. The TLP-SL12-RS 485MB provides protection between all conductors, line to line and each line to earth. It is mounted on to “DIN” rail (46277-3) and offers screen termination via terminals and the earth via a 300 mm earth wire “tail”. FEATURES ♦ Low “let thru” voltage ♦ Protection between ALL lines ♦ Fast snap on DIN rail mounting ♦ Fail to safe status design ♦ High speed switch technology to prevent

signal attenuation ♦ Low line losses (volt drop) ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/ CE Compliant ♦ IEC 1000-4-2 & EN50082

MODEL :- TLP-SL12-RS 485MB Transtech Lightning Protector - RS-485 (Modbus Compatible)

RS 485 STN

END

OF

LIN

E R

RS 485 STN RS 485 STN RS 485 STN

END

OF

LIN

E R

30 NODES

CONNECTION SCHEDULE

RS-485 BUSL1 +ve

Screen

L2 -ve

TRANSTECH

INPUT LINE

CLEAN LINE

TLP-

SL12

-RS4

85

1 23 4

5 67 8

TRANSTECH

INPUT LINE

CLEAN LINE

TLP-

SL12

-RS4

85

1 23 4

5 67 8

TRANSTECH

INPUT LINE

CLEAN LINE

TLP-

SL12

-RS4

85

1 23 4

5 67 8

TRANSTECH

INPUT LINE

CLEAN LINE

TLP-

SL12

-RS4

85

1 23 4

5 67 8

Page 34: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-DNET new.docx Confidential August 25, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage Rating Supply Normal Working voltage 24V D.C. Max. Working voltage 31V D.C. Varistors voltage 39V D.C. Surge current 1000A@(8/20uS) Current/Resistance Rating End to End resist. Less than 0.2R Max Current Thin cable = 4Amp Thick cable = 8 Amp Discharge Power 300W PPPD@ (8/20uS

(dissipation per line) Protection Protection modes CAN-H to CAN-L, CAN-H to Screen CAN-L to Screen, Screen to V-Screen to V+, V+ to V- Line Capacitance 15pF Breakdown Voltage 26.7V D.C. minimum Clamp voltage 43.0V D.C. maximum @ (8/20uS)

GENERAL SPECIFICATION Operating Temp -10 to 70 Deg C Storeage Temp -55 to 80 Deg C Terminals Self opening 2.5mm/12AWG Housing Material KRILEN Mounting Style DIN Dimensions 75mm X 45mm X 30mm Weight 120 grams

GENERAL DESCRIPTION The TLP-DNET lightning and transient arrestor provides protection for equipment connected to the DEVICENET INTERFACE NETWORK. The TLP-DNET provides very effective protection by limiting the transient overvoltage to less than twice the normal voltage on the supply and data lines. The TLP-DNET provides protection between all conductors, Power/data line to line and line to earth. The TLP-DNET can be mounted on DIN rail and the earth return in via a 5mm earth stud. FEATURES ♦ ESD Protection > 25kV ♦ Low “let thru” voltage ♦ Protection between ALL lines ♦ Fast snap on DIN mounting ♦ Fail to safe status design ♦ IEC 1000-4-2 & EN50082 ♦ Ultra low capacitance data line ♦ Field proven technology ♦ Low line losses (volt drop) ♦ Designed and manufactured to ISO 9001 ♦ High stacking density ♦ C-Tick / CE Compliant

MODEL :- TLP-DNET Transtech Lightning Protector - DeviceNet

NODES

CONNECTION SCHEDULE

CAN bus

TRANSTECH

1 2 3 4 5

BUS CONNECTION

SUPPLY/CONTROLLER

TLP-DNET

V1 L S H V+

X

1 2 3 4 5 V1 L S H V+

TRANSTECH

1 2 3 4 5

BUS CONNECTION

SUPPLY/CONTROLLER

TLP-DNET

V1 L S H V+

X

1 2 3 4 5 V1 L S H V+

TRANSTECH

1 2 3 4 5

BUS CONNECTION

SUPPLY/CONTROLLER

TLP-DNET

V1 L S H V+

X

1 2 3 4 5 V1 L S H V+

TRANSTECH

1 2 3 4 5

BUS CONNECTION

SUPPLY/CONTROLLER

TLP-DNET

V1 L S H V+

X

1 2 3 4 5 V1 L S H V+

DeviceNET STN

NODEPSU

DeviceNET STN

NODEPSU

DeviceNET STN

NODEPSU

DeviceNET STN

NODEPSU

BUS INPUT

CLEAN LINES

Page 35: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: (03) 9330-3624 [email protected]

Electronic Transient Surge Protection COMMUNICATIONS PROTECTORS

Also in Melbourne - Sydney – Brisbane – Adelaide TRANSTECH

TRA

NST

ECH

ELE

CTR

ON

IC C

ON

TRO

LS

ww

w.tr

anst

ech.

com

.au

Page 36: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

IMPORTED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-48_RJ45H4 new.docx Confidential August 25, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt 48Volts Nominal Current 1 Amp or less Clamping Volts 90Volts line to screen Impulse Clamping < 600Volts (1kV/us) Surge withstand Imax 0.3kA (8/20usec) Energy Level Less than 100 joules Characteristics Transmission Speed 100M bpss Insertion Loss < 3.0 dB at 100MHz Pins 1 – 2 and 3 - 6

GENERAL SPECIFICATION Insulation resistance > 10 Megohm Connections RJ45 Female / Female Operating Temp -10 to 70 Deg C Storage Temp -55 to 80 Deg C Mounting Style DIN Rail Female to Female Dimensions 85mm X 25mm X 40mm Weight 62 grams

GENERAL DESCRIPTION The TLP-48/RJ45H-4 lightning and transient arrestor provides protection for Ethernet, Twisted Pair Cat 5 ISDN and DSL Network Cables The TLP-48/RJ45H-4 provides very effective protection by limiting the transient over-voltage between the conductor s of Netowrk cable pairs and the screen The TLP-48/RJ45H-4 utilizes fast response gas filled arrestors and Transorbs to provide low let thru voltages for fast transient rise times. The use of low capacitance gas filled arrestors ensures reliable operation at high frequencies with low insertion losses. FEATURES ♦ Low “let thru” voltage ♦ Two Stage protection ♦ Protection between lines and screen ♦ Suitable for 10BaseT and 100BaseT ♦ Aluminium housing ♦ Field proven technology ♦ Low line losses ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/ CE Compliant ♦ Complies with IEC 616431L21-2005

MODEL:- TLP-48/RJ45H-4 Transtech Lightning Protector – Ethernet RJ45

Page 37: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-N_FF new.doc Confidential August 20, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt 70Volts Nominal Current 5 Amps or less Clamping Volts 90Volts line to screen Impulse Clamping < 600Volts (1kV/us) Surge withstand 20kA (8/20usec) Energy Level 400 joules RF Characteristics RF Power 50 Watts Insertion Loss < 0.2dB at 2GHz VSWR 1.07 : 1 @ 1GHz 1.10 : 1 @ 2GHz

GENERAL SPECIFICATION Capacitance < 1.5pF Insulation resistance > 10 Megohm Operating Temp -10 to 80 Deg C Storage Temp -55 to 80 Deg C Mounting Style Bulkhead/Type N Female to Female Dimensions 67mm X 25mm X25mm Weight 80 grams

GENERAL DESCRIPTION The TLP-N/FF lightning and transient arrestor provides protection for coaxial lines for radio transmitters, receivers or HF party line bus. The TLP-N/FF provides very effective protection by limiting the transient over-voltage between the inner conductor of the coaxial cable and the screen The TLP-N/FF utilizes fast response gas filled arrestors to provide low let thru voltages for fast transient rise times. The use of low capacitance gas filled arrestors ensures reliable operation at high frequencies with low insertion losses. FEATURES ♦ Low “let thru” voltage ♦ Protection between line and screen ♦ Bulkhead mounting with additional fixed

“bolt-thru” earth tag ♦ Field proven technology ♦ Low line losses ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/ CE Compliant ♦ IEC 1000-4-2 & EN50082 ♦ AS 1768-2003

MODEL:- TLP-N/FF Transtech Lightning Protector – Coax Bulkhead +Tag

12 mm25 mm

20 mm22 mm

56 mm

DIMENSIONS

TLP-N/FF

Page 38: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-F_FF new.doc Confidential August 20, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt 70Volts Nominal Current 5 Amps or less Clamping Volts 90Volts line to screen Impulse Clamping < 700Volts (1kV/us) Surge withstand 20kA (8/20usec) Energy Level 400 joules RF Characteristics RF Power 50 Watts Insertion Loss < 0.5dB at 2GHz VSWR < 1.3

GENERAL SPECIFICATION Capacitance < 1.5pF Insulation resistance > 10 Gigohm Operating Temp -10 to 80 Deg C Storage Temp -55 to 80 Deg C Mounting Style Type F Female to Female Dimensions 52mm X 25mm X25mm Weight 50 grams

GENERAL DESCRIPTION The TLP-F/FF lightning and transient arrestor provides protection for coaxial lines for radio transmitters, receivers or HF party line bus. The TLP-F/FF provides very effective protection by limiting the transient over-voltage between the inner conductor of the coaxial cable and the screen The TLP-F/FF utilizes fast response gas filled arrestors to provide low let thru voltages for fast transient rise times. The use of low capacitance gas filled arrestors ensures reliable operation at high frequencies with low insertion losses. FEATURES ♦ Low “let thru” voltage ♦ Protection between line and screen ♦ Field proven technology ♦ Low line losses ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/ CE Compliant ♦ IEC616431:21 ♦ IEC 1000-4-2 & EN50082 ♦ AS 1768-2003

MODEL:- TLP-F/FF Transtech Lightning Protector – Coax Type F Cables

TLP-F/FF

12 mm25 mm

21 mm22 mm

55 mm

DIMENSIONS

Page 39: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

DESIGNED & MANUFACTURED in AUSTRALIA by: Transtech Electronic Controls Pty Ltd Perth W.A. ABN: 21 070 629 499 Design changes may occur in the interests of product performance & development E&OE Page 1 of 1 ISSUE A / Rev A I:\Shared\Engineering Dept\DataSheets & Product Packet Labels\TLP-F_MF new.doc Confidential August 20, 2011

DATA SHEET Subject to change without notice

TECHNICAL DATA Voltage rating Normal working volt 70Volts Nominal Current 5 Amps or less Clamping Volts 90Volts line to screen Impulse Clamping < 700Volts (1kV/us/V) Surge withstand 20kA (8/20usec) Energy Level 400 joules RF Characteristics RF Power 50 Watts Insertion Loss < 0.5dB at 2GHz VSWR <1.3

GENERAL SPECIFICATION Capacitance < 1.5pF Insulation resistance > 10 Gigohm Operating Temp -10 to 80 Deg C Storage Temp -55 to 80 Deg C Mounting Style Type F Male to Female Dimensions 52mm X 25mm X25mm Weight 50 grams

GENERAL DESCRIPTION The TLP-F/MF lightning and transient arrestor provides protection for coaxial lines for radio transmitters, receivers or HF party line bus. The TLP-F/MF provides very effective protection by limiting the transient over-voltage between the inner conductor of the coaxial cable and the screen The TLP-F/MF utilizes fast response gas filled arrestors to provide low let thru voltages for fast transient rise times. The use of low capacitance gas filled arrestors ensures reliable operation at high frequencies with low insertion losses. FEATURES ♦ Low “let thru” voltage ♦ Protection between line and screen ♦ Field proven technology ♦ Low line losses ♦ Designed and manufactured to ISO 9001 ♦ C-Tick/ CE Compliant ♦ IEC616431:21 ♦ IEC 1000-4-2 & EN50082 ♦ AS 1768-2003

MODEL:- TLP-F/MF Transtech Lightning Protector – Coax Type F Cables

TLP-F/MF

12 mm25 mm

20 mm22 mm

56 mm

DIMENSIONS

Page 40: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\surge protection guide.docx Updated: 15/11/2011/

TransTech Electronic Controls Pty Ltd ABN 21 070 629 499

A GUIDE TO SPECIFYING

ELECTRONIC SURGE PROTECTION DEVICES

Preface: This document is meant as a guide to those involved in specifying, applying and/or approving electronic transient protection devices. It is by no means a definitive paper on the types of transient surge protection available nor in any way proposes to set out a particular manufacturer, type or technique. This guide does not address “structural lightning protection” other than to direct the reader to the Australian Standard AS NZS 1768:2005 and in particular to the proven techniques for effective structural lightning design and installation. Good structural protection and earthing/bonding is an essential part of minimizing possible effects from lightning transients. The most important consideration for any Engineer specifying electronic transient protection is the “let-thru” voltage as this is critical to the proper functioning of the electronic/electrical equipment it is intended to protect following a transient. The critical considerations in specifying electronic transient protectors are:

1. Be compatible with the system it is protecting 2. Survive transients and contain any fault condition arising 3. Have a low “let-thru” voltage for ALL conductor combinations 4. Not fail and leave the installation un-protected 5. Be correctly installed and maintained regularly.

1. Compatibility

The protector should not inhibit the systems normal operation if it operates 2. Survival & housing

Transients from a lightning strike (close proximity) can exceed 200,000 amps, however statistically the average transient is approx 10,000 amps. The IEC Standard uses 10,000 amps as the accepted “norm”, however AS1768 has adopted 70,000 amps therefore any protector at a point of entry should have a rating equal to or exceeding 70,000 amps to meet the current Australian Standard. It is recommended by the leading MOV suppliers that surge protectors incorporating such devices be constructed of metal as a safety precaution Clause 7.9.2 of IEC61643-1:2005 addresses this aspect.

3. Let-thru voltage The magnitude of the transient reaching the electronic/electrical equipment is critical and can cause anything from data-corruption to flash-over and arcing damage. The suitable protector should therefore offer a let-thru voltage less than the maximum voltage rating for the equipment (the current IEC states 2.5kV as the minimum insulation level). Transients occur between all conductors of a system – that is: Ph-N / Ph-E / N-E and in instrumentation and data-line circuits both Common Mode and Differential Mode. Protectors need to offer such levels of protection

4. Indication of failure In-line protectors such as used for 120/240vac sub-circuit, instrumentation and/or data-lines are inherently “self-revealing” upon a major transient as the circuit invariably goes open. In Main Board protection systems it is essential to have an indication to warn of failure or degradation of the protective devices, such indication should be both local visual and a relay output.

5. Installation The performance of transient protectors depends upon correct installation as they are required to manage high frequency waveforms, therefore the length and size of connecting cables must be considered, as a guide refer to AS4070:1992. As a rule of thumb the larger the cross section and the shorter the cable the better, 500mm of 6 sq mm cable is recommended as a minimum.

Page 41: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\surge protection guide.docx Updated: 15/11/2011/

TransTech Electronic Controls Pty Ltd ABN 21 070 629 499

SUGGESTED SPECIFICATION

1.1 Point-of-Entry Main & Sub Distribution Boards. Provide lightning/transient surge suppression to the mains supply of the main switchboard and each sub distribution board. Supply, install and connect a … insert Manufacturer(s)…., or similar product of equivalent function and quality to the satisfaction of the Engineer. Such rating to be no less than 70kA surge capacity according to IEC 61643.1 and are to include all 3 phases plus Neutral and offer true 3 mode protection. The installation shall be strictly in accordance with the Manufacturers recommendations. 1.2 Final Sub Circuits

Where indicated on power circuit schedules a series filter surge protector shall be fitted to protect individual circuits. The series filters shall be …. Insert manufacturer(s)…...or similar product equivalent in function, size and quality to the approval of the Engineer. Rating shall be no less than 24kA according to IEC 61643.1 and offer true 3 mode protection. The surge device shall be compatible with any RCD protection and protect against high frequency noise and transient surges in all modes (L-N, L-E, N-E). The series protectors shall be constructed to meet UL 1449 and be Third Party tested to IEC61643.1.

Where alternatives are offered the tenderer shall provide sufficient data to prove that the alternative complies with the specification. All transient/surge protection devices shall be mounted to protrude thru the distribution board escutcheon plate and shall have visible status indication. Where nominated such series surge filters shall have in addition an incorporated relay that monitors the health of the protection device and provides a volt-free changeover contact for monitoring by the Building Management System (BMS).

Page 42: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\fault rating design and fuse sizes.docx

TransTech Electronic Controls Pty Ltd ABN 21 070 629 499

SURGE CURRENT CAPACITY & FUSING

REF: AS/NZS 1768:2005

1. INTRODUCTION The committees of all International Standards, after years of research have decided that the average indirect lightning surge is only 10kA, Standards Australia, however, via AS1768:2005 Table F1 states 70kA as a maximum indirect lightning surge value, Transtech has therefore taken the decision to meet the higher level as detailed by Standards Australia and as a consequence the main board of the TLP range of Surge Protectors is designed to withstand multiple transient surges of 70kA and a single surge of 140kA. NOTE: The fault rating assigned to a Mains Surge Protector is not to be confused with the switchboard bus bar fault rating. A transient/lightning surge rating is based upon an 8/20micro second waveform therefore a duration of only 28 microseconds.

2. DESIGN OF TRANSTECH MAINS PROTECTORS

Transtech Electronic Controls Pty Ltd has been designing and manufacturing electronic transient/surge protectors since 1996 and has supplied some of Australia’s biggest Companies not to mention delivering over 15,000 pcs of its 20Amp single phase series filters to the BER Project Australia Wide.

Based upon the preceding information, Transtech Electronic Controls Pty Ltd designs its TLP Mains Surge Protectors with high quality 70micron copper board and accurately calculated track sizing designs. Surge protectors with ratings above 70kA simply offer extended lifetimes to users.

3. PROTECTING A TLP MAINS PROTECTOR Protection of a Mains Surge Protector is governed according to AS3000. It is a requirement to protect the circuit with either an HRC Fuse or a MCB, the HRC Fuse or MCB size is determined firstly by the Fault Rating of the Switchboard and secondly by the wire size supplying the TLP.

3.1.1. SWITCHBOARD FAULT RATING This refers to the bus bar fault level, therefore any protection device such as an HRC Fuse or a MCB must be in accordance with suppliers ratings and application advice (an example being Schneider Cascading & Enhanced Discrimination tables)

3.1.2. WIRE SIZE Transtech Electronic Controls Pty Ltd recommends the maximum size wire to connect a TLP Mains Protector – that is 16 mm2 therefore according to AS3000 Table B2 the HRC Fuse or MCB shall be 50 amps maximum.

3.1.3. PROTECTION SELECTION (amp rating) As per preceding comments, either an HRC Fuse or MCB is required to protect and provide isolation for the Mains Surge Protector. The factors to be considered in the selection of a suitable primary protection device are as per Clauses 3.1.1 and 3.1.2 above. The current rating of the HRC or MCB should be between 25 amps and 50 amps.

Page 43: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

I:\Shared\Price Lists & data sheets\Transtech\Application Notes\fault rating design and fuse sizes.docx

TransTech Electronic Controls Pty Ltd ABN 21 070 629 499

SUMMARY.

A. Transtech Electronic Controls Pty Ltd follows AS1768:2005 and all other relevant Standards in its

designs and meets them regarding surge fault ratings.

B. Transtech Electronic Controls Pty Ltd Mains Surge Protectors cover all Category’s E / D / C / B / A C. Transtech Electronic Controls Pty Ltd manufactures Mains Surge Protectors offering Surge Fault

ratings in excess of 70kA, these simply offer the user extended lifetime.

D. The fault ratings of the TLP Mains Surge Protectors should not be confused with switchboard bus bar fault ratings.

E. All Transtech Mains Surge Protectors type TLP’s have internal MOV protection fuses suitable to break 100Amps.

F. The fault rating of a TLP Mains Surge Protector is based upon a very short time of 28 microseconds, not to be confused with a typically 1sec rating as for switchboard Type Tests.

G. Transtech Electronic Controls Pty Ltd has been designing electronic surge protectors for over 16 years and accurately designs the circuit board layout in its TLP series to withstand a 70kA 8/20 microsecond surge.

H. PROTECTION TABLE:

TLP MODEL RECOMMENDED AMPS COMMENT DEVICE TLP-SF20SL-240V HRC 25 Single phase series filter TLP-40-xP HRC 40 TLP-80-xP HRC 50 TLP-120-xP MCB 50 MCB’s not tripped by transient TLP-160-xP MCB 50 MCB’s not tripped by transient TLP-200-xP MCB 50 MCB’s not tripped by transient TLP-240-xP MCB 50 MCB’s not tripped by transient

Page 44: Electronic Transient Surge Protection TRANSTECH ELECTRONIC … · 2018-08-21 · Transtech Electronic Controls Pty Ltd . ABN 21 070 629 499 . Perth - Melbourne . Perth Tel: (08) 9302-2044

Transtech Electronic Controls Pty Ltd ABN 21 070 629 499

Perth - Melbourne Perth Tel: (08) 9302-2044

Melbourne Tel: 0400 848-064 [email protected]

Also in Sydney – Brisbane – Adelaide

TRANSTECH

Transtech Electronic Controls Pty Ltd Australian Agent for:

HAZARDOUS AREA ENCLOSURES

HIGH SPEED SENSORS & TACHOS

ALARM ANNUCIATORS

ENCODERS AND TECHOS

HAZARDOUS AREA FLOW/TEMP/PRESSURE

PROXIMITY SENSORS & PE CELLS