[DOCUMENT TITLE] 1 ELECTRICITY INSPECTION AND AUDIT MANUAL

Transcript of ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ......

Page 1: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

[DOCUMENT TITLE]

1

ELECTRICITY INSPECTION AND AUDIT MANUAL

Page 2: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

2

TABLE OF CONTENTS

1 INTRODUCTION ................................................................................................................................. 4

2 THE MANUAL ...................................................................................................................................... 4

2.1 OBJECTIVE .................................................................................................................................. 5

2.2 POWER TO CONDUCT INSPECTION .................................................................................... 5

3 TECHNICAL AUDIT OVERVIEW ..................................................................................................... 5

3.1 Types of Audits ........................................................................................................................... 5

3.1.1 Compliance Audit .............................................................................................................. 5

3.1.2 LICENSING AUDIT ............................................................................................................. 6

3.1.3 ACCIDENTS/INCIDENTS INVESTIGATIONS ................................................................ 6

3.1.4 CONSUMER COMPLAINT INVESTIGATION ................................................................. 6

3.1.5 ENVIRONMENTAL IMPACT ASSESSMENT REVIEWS ................................................ 6

3.2 AUDIT PHASES ........................................................................................................................... 7

3.2.1 PRE-AUDIT PREPERATIONS ............................................................................................. 7

3.2.2 CONDUCTING THE AUDIT .............................................................................................. 8

3.2.3 AUDIT REPORT ................................................................................................................... 8

4 AUDIT METHODOLOGY................................................................................................................... 8

4.1 COMPLIANCE AUDITS ............................................................................................................. 8

4.1.1 SYSTEMS AUDITS ............................................................................................................... 9

4.1.2 SITE INSPECTIONS .......................................................................................................... 13

LIST OF APPENDICES ............................................................................................................................. 14

APPENDIX 1: PRE-LICENSING SITE INSPECTION CHECKLIST ...................................................... 15

APPENDIX 2: LARGE HYDROPOWER STATION INSPECTION CHECKLIST ................................ 18

APPENDIX 3: SMALL HYDROPOWER STATION INSPECTION CHECKLIST ................................ 24

APPENDIX 4: SUBSTATION INSPECTION CHECKLIST (VOLTAGE ABOVE 33kV) ..................... 30

Page 3: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

3

APPENDIX 5: DISTRIBUTION SUBSTATION INSPECTION CHECKLIST (VOLTAGE BELOW

33kV) 35

APPENDIX 6: THERMAL POWER STATION INSPECTION CHECKLIST ......................................... 39

APPENDIX 7: Environmental Inspection checklist on Hydropower projects, ............................. 43

Page 4: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

4

1 INTRODUCTION

The Energy and Water Utilities Regulatory Authority (EWURA, here in after referred

to the Authority) is a statutory body established by the Energy and Water Utilities

Regulatory Authority Act, Cap 414 of the Laws of Tanzania to regulate the energy

sector through the establishment and enforcement of technical and performance

standards encompassing quality, safety and reliability of supply of energy and water.

The Electricity Technical Audit Manual activities shall be anchored on the systematic

efforts to carry out infrastructure and pre-licensing inspection in electricity

generation, transmission and distribution facilities. The Manual will be useful for the

Authority's Inspectors as well as for Licensees.

Among the Authority’s objectives are to provide better regulation that promotes

economic and technical efficiency in all aspects of the energy sector through an

implementation of an incentive-based regulation, performance benchmarking and

enforcement of standards and regulations. The focus shall be on improvement of

supply quality and reliability, promotion of security of supply and increased access

to electricity services in Tanzania. The manual therefore shall be used for compliance

audit and sites inspections. Also, the checklists attached to this Manual will be used

by EWURA as well as Licensee for inspection purposes. The licensee will give

commitments as to when the defects found during Auditing and Sites inspection as

well as be free to give suggestions and comments for better improvements on

inspected facilities will be cleared.

The Manual is divided into four sections: Section 1 gives some background

information to audits and inspections, while Section 2 introduces the manual. Section

3 gives an overview of technical audits inspections to be conducted and Section 4

outlines the audit methodology. Checklists are provided in Appendices 1, 2, 3, 4,5 &

6.

2 THE MANUAL

Technical audits are key element in the process of ensuring that licensed entities are

adhering to stipulated standards and guidelines.

Page 5: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

5

2.1 OBJECTIVE

The manual is intended to provide guidance to the Authority and Licensees on how

technical audits and infrastructure inspections of different categories are to be

conducted. It clearly stipulates the responsibilities of the regulator and the licensee,

during and after the inspection audits. The manual therefore aims at ensuring

effective and efficient inspection audit practices to accomplish the fore-going goals.

2.2 POWER TO CONDUCT INSPECTION

This manual is made pursuant to Sections 31 of the Electricity Act, Cap 131, which

requires the Authority to monitor and assess compliance of licensees to governing

laws, rules and guidelines through inspections. The Authority has the power of

monitoring technical and safety standards (refer to Section 45, (b), (viii) of the

Electricity Act, Cap 131).

3 TECHNICAL AUDIT OVERVIEW

3.1 Types of Audits

The following audit and inspection activities shall be conducted by EWURA or

authorized entities:

3.1.1 compliance audits;

3.1.2 licensing audits;

3.1.3 accident/incident investigations;

3.1.4 consumer complaint investigations; and

3.1.5 Environmental impact assessment review

3.1.1 Compliance Audit

Compliance audits shall involve establishing whether the licensee is complying with

the stipulated licence conditions, standards, rules and regulations. Standards

enforcement shall be anchored on the following:

a) power quality and reliability ;

b) electricity safety code;

c) quality of consumer service;

d) the grid code and distribution code; and

e) electrical wiring and installations standards

The Authority shall monitor performance of servicee providers or licensees with

regard to prescribed performance benchmarks. Compliance audits shall generally

be conducted once every year, or as shall otherwise be deemed necessary.

Page 6: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

6

3.1.2 LICENSING AUDIT

Licensing Audit shall involve undertaking site visits to appreciate the physical

aspects relating to the projects technical and financial assessment of licence

applications. Technical assessments shall generally be conducted with regard to the

following:

a) verification of information given in the licensee application and other issues in

accordance with the site verification checklist;

b) establishment of the applicant’s technical expertise;

c) establishment of premises for the proposed activity and status of project

implementation; and

d) Compliance with Technical, Health, Safety and Environmental issues.

Prior to undertaking a site visit, the Inspector assigned shall make the necessary

arrangement for the visit with the Utility's Designated Officer. The Inspector shall

obtain answers of the items described in Appendix I of the checklists of this

manual, and will comment on all abnormalities.

3.1.3 ACCIDENTS/INCIDENTS INVESTIGATIONS

Accident/Incident investigations shall be conducted following receipt of a verbal or

written incident/accident report. EWURA may make use of investigation report

carried out by other relevant authorities as a reference to its main investigation

report.

3.1.4 CONSUMER COMPLAINT INVESTIGATION

Consumer complaints that require an investigation shall be conducted in

collaboration with appropriate personnel from the utility company who is conversant

with the matter.

3.1.5 ENVIRONMENTAL IMPACT ASSESSMENT REVIEWS

Electricity infrastructure shall be inspected to verify whether they comply with

Environmental requirements as per“ The Environmental Impact Assessment and

Audit Regulations 2005 “ and “Environmental Management Act , 2004 “ .

EWURA recognizes issued certificate by a National Environment Management

Council (NEMC), and therefore findings of the inspections on environmental issues of

a particular site / project will be documented either in the form of an environmental

project brief (for small projects with minimal environmental impacts or an

environmental project statement (for big projects with significant environmental

impacts assessments). Appropriate measures will be taken against those who will not

Page 7: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

7

comply with environmental issues. Furthermore, EWURA’s Inspector will fill in

Appendix 7 by providing comments when is on site , such that although he has seen

the NEMC Certificate from the project developer, he/she has to verify some

important environmental aspects , just for self satisfaction that some one who did the

EIA study report he did not forget anything.

3.2 AUDIT PHASES

The following phases shall be followed;

a) Pre-audit preparations (Audit initiation);

b) Conducting the Audit; and

c) Audit report

3.2.1 PRE-AUDIT PREPERATIONS

At the beginning of every year, or within 30 days after the work plans have been

developed, general audit introduction and notification letters with indicative dates

shall be sent to utilities that will be audited.

Prior to carrying out an audit, the Inspector responsible shall satisfy himself beyond

doubt that he/she is conversant with the following:

a) this Manual;

b) the facilities to be audited;

c) relevant provisions of prescribed standards;

d) provisions of the relevant licence; and

e) the Electricity Act, EWURA Act, and any other relevant legislation including

the Environmental Management Act.

The Inspector shall also endeavour to familiarize himself with relevant internal

policies of the licensee to be audited.

At least seven (7) working days prior to the intended date of commencement of the

audit, the Inspector responsible for carrying out the inspection shall ensure that

written communication is sent to the appropriate Licensee's office (Regional office,

Divisional office and/or the corporate office, as the case may be) of the Utility to be

audited. Furthermore, the Inspector shall also endeavour to inform the relevant

utility's personnel verbally within the 7 days notice period. Written communication

shall cover the following:

a) audit participants;

b) the objective and period for the audit;

c) the time and date of the opening meeting;

d) the number of auditors in the audit team and the date and length of their visit;

Page 8: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

8

e) the audit coordinator whom the Utility may contact for clarifications with

regard to the notification letter; and

f) Utility's records that will be reviewed during the audit.

In the event that non-compliance is established at a particular facility, the preferred

course of action shall be a notice for remedial measures and/or sanction by the

Authority.

3.2.2 CONDUCTING THE AUDIT

Unless otherwise required, all audits shall begin with communications with the Head

Office of the Utility. Copy of the communications shall be sent to the respective area

to be audited. At any given time, audit shall be conducted in the presence of senior

member of management in-charge or representative of the area to be audited. The

absence of any Utility's Senior Officers or Representative during an audit exercise

will be considered and recorded as a non compliance.

3.2.3 AUDIT REPORT

Following the completion of an audit, the Inspector shall conduct an exit meeting to

conclude the audit. The completed audit checklist signed by the inspector in-charge

shall also be signed by the utility's authorised representative, and a copy left with the

utility staff for record and follow-up action. The final report shall be submitted to the

utility within a period not exceeding 30 days from date of completion of the audit.

The Utility shall submit a detailed action plan on non-complied matters within a

prescribed period, failure to which the Authority will take appropriate action.

4 AUDIT METHODOLOGY

Audit methodology discussed herewith relates to compliance with standard

operating procedures of the energy utilities companies. There will be two sections

for Auditing, one is compliance audit and the second is site inspection Audit. These

are discussed in detail in sections 4.1 and 4.2 below :

4.1 COMPLIANCE AUDITS

Compliance audits shall comprise of systems audits and site inspections. System

Audit referred to checking compliance to quality and reliability of supply, safety,

maintenance, planning, performance monitoring, and demand side management and

compliance to the Electricity Act, 2008. The Audit shall also verify the information

previous provided by the utility company. Site Inspection will be done to oversee

and identify the actual electricity facilities conditions on site as well as recording all

findings for the utility company to rectify. The site inspection shall involve the items

Page 9: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

9

indicated in a checklists attached to this manual (No.1 to 6 ) which shall be signed by

both parties after inspection.

4.1.1 SYSTEMS AUDITS

Systems audits shall encompass the following:

4.1.1.1 quality and reliability of supply;

4.1.1.2 safety;

4.1.1.3 maintenance;

4.1.1.4 planning;

4.1.1.5 performance monitoring ;and

4.1.1.6 demand side management

4.1.1.1 QUALITY AND RELIABILITY OF SUPPLY

In establishing the adequacy of internal systems with regard to quality and

reliability of supply, the audit criteria shall comprise the establishment of

adherence to provisions of quality and reliability standard.

The following aspects shall be examined:

1. Power quality:

a) Does the Utility monitor and control voltage within required limits?

b) Does the Utility determine and set operating voltage limits which will

ensure adequate post-contingency voltage?

c) Does the Utility determine, set and monitor reactive reserve requirements

such that post-contingency voltage is adequate? The reactive reserve

requirement may be expressed by pre-contingency voltage limits.

2. Prudent utility practice:

a) Does the Utility determine the needed amount and location of operating

reserves, implements generator commitment and dispatch schedules?

b) Does the Utility monitor the levels of real and reactive reserves to ensure

they are adequate and takes action when they are not?

c) Does the Utility monitor and take action against transmission congestion?

Page 10: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

10

3. Emergency preparedness:

a) Does the Utility prepare and maintain emergency operating procedures,

which describe the responsibilities and actions to be taken by plant

personnel during system emergencies

b) When emergencies appear imminent, does the Utility seek regulatory

relief from those regulatory requirements that reduce output?

c) Does the emergency operating procedures address the following system

disturbances and the facility’s response to these disturbances on :

(i) low Frequency System Instability;

(ii) high Frequency;

(iii) low Voltage;

(iv) low System Reserve Margins;

(v) low VARs; and

(vi) loss of normal communications.

d) Does the Utility have a procedure and an authority to shed load when an

emergency is declared without any management approval?

e) Does the Utility have site specific emergency preparedness procedures?

f) Does the site emergency response plan address the following?

i. how to report emergencies;

ii. notification of appropriate site personnel;

iii. notification of outside parties; both organizational as well as

civil;

iv. the location and staffing of a “command” centre;

v. individual roles and responsibilities;

vi. egress procedures and assembly points;

vii. all clear and re-entry procedures;

viii. isolation and shut-down of vital processes and work areas;

ix. chemical spills clean-up and mitigation procedures;

x. search and rescue procedures;

xi. control of visitors and contractors;

xii. emergency telephone numbers;

xiii. off-site emergencies;

xiv. communications with the general public and media; and

xv. radiation sources.

g) Does the Utility have at least one means of communication during

emergencies?

h) Does the Utility perform real-time contingency studies to ensure

system is being operated in a manner that will allow it to recover

from any N-1 contingency within sixty minutes?

4. Load Management

Page 11: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

11

a) Does the Utility implement generator dispatch schedules to ensure that

load and generation are balanced?

b) Does the Utility maintain approved scheduled generation outages?

c) Does the Utility maintain approved scheduled transmission outages?

d) Does the Utility have a policy on load shedding?

4.1.1.2 SAFETY

In auditing safety systems requirements, the Inspector shall seek answers to the

following questions:

1. Personal protective Equipment (PPE);

Does the Utility have a procedure to provide required Personal Protective

Equipment (PPE) to its employees?

2. Does the Utility have a procedure for prompt communication of information

gained from an accident/incident investigation throughout the utility and to

the relevant statutory bodies?

3. Does the Utility have a procedure that requires general safety

inspections/technical audits to be conducted at its sites at regular (at least

quarterly) intervals?

4. Permit systems

a) Does the Utility have adequate senior authorized personnel at the site?

b) Does the Utility have a procedure that is used to identify the requirements

for site-specific permits and special work practices (WPs) for work

associated with: confined spaces, Energy sources, hazardous materials,

flammable atmospheres, hot work, Excavation?

c) Does the Utility keep copies of issued permits kept on file in accordance

with regulatory requirements and good practices?

5. Does the Utility have a procedure for orienting and educating employees on

relevant rules prior to starting new or different work assignments?

6. Does the Utility have a procedure to allocate the appropriate signs and colour-

coding to be used to reinforce rules and work processes?

7. Does the Utility have a procedure for analyzing the site's significant operations

to identify hazards and risks associated with them?

Page 12: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

12

8. Does the Utility have a procedure to ensure all new employees receive a

general orientation to the site's safety program?

9. Does the Utility have a formal refresher process for the competency training

program which ensures employees receive update training for vital skills at

least every three years?

10. Does the Utility keep accurate records of who received safety management

training?

11. Does the Utility have a procedure for collecting and providing feedback to

employees regarding their safety concerns?

12. Does the Utility have a policy on safety, health, environment and quality?

4.1.1.3 MAINTENANCE

Maintenance systems shall be audited with regard to preventive and breakdown

maintenance. The following criteria shall be used:

1. Does the Utility have an annual maintenance schedule?

2. Does the Utility adhere to the annual maintenance schedule?

3. Does the Utility have a system to evaluate the effectiveness of the annual

maintenance schedule?

4. Does the Utility have a system to monitor equipment condition at regular

intervals?

5. Does the Utility have general guidelines on equipment restoration following a

breakdown?

4.1.1.4 PLANNING

System planning shall be audited with regard to network expansion and

reinforcement plans. Planning principles shall be evaluated using the following

criteria:

1. Does the Utility conduct regular least cost transmission and generation

planning?

2. Does the Utility maintain system expansion plans based on thorough load

forecasting studies?

3. Does the Utility have a system to identify areas requiring reinforcement?

4. Does the Utility carry out periodic load flow studies?

Page 13: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

13

4.1.1.5 PERFORMANCE MONITORING

Performance monitoring systems shall be monitored with regard to the following:

1. Does the Utility have a system to analyze their performance in terms of

prescribed Key Performance Indicators?

2. Does the Utility set internal performance benchmarks for key performance

indicators?

4.1.1.6 DEMAND SIDE MANAGEMENT

Demand Side Management (DSM) efforts shall be monitored with regard to the

following:

1. Does the Utility have a DSM program?

2. Does the Utility have Educational program to educate its customers?

3. Does the Utility have Metering targets for its unmetered customers?

4. Does the Utility have meters at all its bulk supply points?

5. Does the Utility enforces power factor improvements requirements for its

industrial customers?

4.1.2 SITE INSPECTIONS

Site inspections shall be undertaken to verify regulatory information submitted by

the Utility to the Authority. Prior to conducting site visits, the Officers assigned shall

satisfy themselves that the report has all the necessary sections and information

(including detailed site maps) for decision making.

Page 14: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

14

LIST OF APPENDICES

1. Appendix 1 : Pre licensing Site Inspection Checklist

2. Appendix 2 : Large Hydropower(>10MW ) station Checklist

3. Appendix 3: Small Hydropower (<10MW) Station Inspection Checklist

4. Appendix 4 : Substation Inspection Checklist (Voltage above 33kV )

5. Appendix 5 : Distribution Substation Inspection Checklist (Voltage below 33kV )

6. Appendix 6 : Thermal power station Inspection checklist

7. Appendix 7 : Environmental Inspection checklist on Hydropower plants,

Transmission and Distribution lines

Page 15: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

15

APPENDIX 1: PRE-LICENSING SITE INSPECTION CHECKLIST

NAME OF LICENSEE

PLANT NAME

REGION/TOWN

DATE

INSTALLED CAPACITY

( MVA/MW )

AVAILABLE CAPACITY (MVA/MW )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

CAPACITY(MW)

AVAILABLE

CAPACITY

(MW)

Page 16: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

16

PHYSICAL SITE VERIFICATION CHECKLIST

Applicant:……………………………………………………………………………………..

Application Reference:……………………Date:………………………………………...

License Details:…………………………… MW Location:………………………………

Date of Site Visit: …………………………………………………………………………...

1. LOCATION

Site description (size, boundaries, neighbourhood): ……………………..........

Land acquisition (leased or acquired?):……….....………………………............

Interference to other human activities: ……………………………………...........

Interference to other infrastructure (power line, water or gas systems, road diversions or

blockage etc)……………………………………………

Availability to utilities/services/access road, power/water/gas

supply:…………………………………………………………………………...........

2. PLANT LAYOUT

Suitability to personnel/equipment movement?:………………………….........

Suitability to emergency response (exits and signs, fire extinguishers, passage ways

etc):……………………………………………………………................................

Functional interfaces (e.g. various connections for power, water, fuel, drainage etc) including

metering where applicable:……………………..............................................

Location of key equipment relative to their functions (engines, generators, transformers,

auxiliary facilities etc):………………………..................................................

3. ELECTRICAL LAYOUT

Single line diagram:........ ...………………………………………………….........

Metering points:………………………………………………………………..........

Page 17: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

17

4. MAIN EQUIPMENT DESCRIPTION

Equipment Type/ID Capacity No Units Other Specification

Engine/Turbine

E1=

E2=

E3=

Generator G1=

G2=

G3=

Transformer Type/ID Size Voltages

Any other comments.............................................................................

Name of EWURA’s Inspector: .................................................................................

Signature..................................................................................................................

Date.........................................................................................................................

I acknowledge the contents of the above document as has been served upon me by the above

named EWURA official

Name of Licensee Official: ………………………………………………………………....

Job Title: ……………………………………………………………………………………....

Signature: ……………………………………………………………………………………..

Date: …………………………………………………………………………………………..

Page 18: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

18

APPENDIX 2: LARGE HYDROPOWER STATION INSPECTION CHECKLIST

NAME OF LICENSEE

PLANT NAME

REGION/TOWN

DATE

INSTALLED CAPACITY ( MVA/MW )

AVAILABLE CAPACITY (MVA/MW )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

CAPACITY(MW)

AVAILABLE

CAPACITY

(MW)

Page 19: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

19

A. TRANSFORMER (S) - Tick the appropriate item

Oil leaks Fire blast walls

No leaks

Has leaks

Fire Blast walls appropriately installed

No fire Blast walls

Transformer maintenance Oil spillage containment

Regular maintenance done

Inadequate-partial

maintenance

No maintenance –no records

Adequate bund wall in place

No Bund wall

Plinth condition

Concrete plinth in place

No concrete

Fire fighting facilities

Extinguishers available, adequate,

serviced and appropriate

Extinguishers inappropriate, not serviced

or inadequate

Not available

Ventilation – indoor s/s

Ventilation provided

No Ventilation

Transformer protection

Adequate protection in place

Inadequate or No protection GENERAL STATE OF REPAIR

Conditions of Turbine Condition of cooling water system

Turbine casing has no

leaks

Turbine casing leaking

All cooling water components in good

repair

Inadequate maintenance

Condition of excitation

System

Condition of drainage water system

Both AVRS working

Only one AVR working

Both AVRS not working

In good working condition

Not in good working condition

Not working Condition of governors Condition of penstock

Good working condition

Governor not in good

condition

Penstock leaking

Penstock not leaking

Page 20: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

20

Condition of lift/cranes

Lift and cranes working

and records available for

statutory inspection

Lift and cranes not working

Machine status indication lights

All indications working

Only some indications working

All indications not working

Equipment labels

Labelling available and in

good repair

Labelling not in good

repair or not there

Weed room

Good working condition

Poor condition or not working

Intake gates Trash rack

In good working condition

Poor condition or not

working

Good working condition

Not working

Spill way gates

Good working condition

Poor condition

Outfall cranes

Good working condition

Poor working condition or not working

SAFETY

Danger warning signs Competence of personnel

Appropriate notices or

signs in place

Inappropriate notices or

signs

No notices or signs

Plant manned by adequate (full

establishment )

Authorized personnel

Inadequate Authorized personnel

Fire and flood alarms Procedures for safe (emergency)

Shutdown

Available

Not available

Procedures available

Procedures not available

Page 21: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

21

First aid

facilities available

Only procedures available

Only facilities available

Procedures and facilities

unavailable

Fire fighting facilities

Extinguishers available, adequate,

serviced and appropriate

Extinguishers inappropriate, not

serviced or inadequate

Not available

PPE procedures

PPE available

PPE not available

Fire drills

Conducted

Not conducted

Emergency escape route

Escape route clearly

marked

Escape route faded and/or

not marked

Fire assembly point

Assembly point available

Assembly point not available

Plant security

Plant manned by adequate

(full

Established

PPE not available

Safety documents (permits )

Switching instructions, permit to work

and limitation of access properly issued

and kept on file

Permits not properly issued or not kept

on file

OPERATIONS AND MAINTENANCE

Operation logbook Means of communications

Available and in use

Inappropriate notices or signs

No notices or signs

Available

Unavailable

Black start procedure

Available and in use

Available but not in use

Not available

Work procedures

Available

Not available

Page 22: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

22

Equipment maintenance

Regular maintenance done

Inadequate partial maintenance

No maintenance –no records

Maintenance schedules (plan)

Available and adhered to

Available but not adhered to

Not available

Circuit breakers and isolators

Circuit breakers and isolators

adequate

Only circuit breakers installed

Only isolators installed

No circuit breakers and

isolators installed

Protective relays

In place ,regularly tested and in good

working condition

No test records

No relays

BATTERIES

Space around batteries Battery room floor

Space provided around

batteries

Adequate

Space inadequate

floor can contain electrolyte spillage

floor cannot contain electrolyte spillage

Battery enclosure

Battery enclosure

appropriate

Battery enclosure

inappropriate

Electrical (lighting) fixtures

Fixtures appropriately installed

Inappropriately installed

Ventilation

Ventilation available

Ventilation unavailable

Safety signs

Appropriate safety signs in place

Safety signs inappropriate or not there

Page 23: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

23

Battery racks

Battery racks properly

anchored & earthed

Battery racks not properly

anchored ( or earthed )

Battery maintenance

Maintenance records available

No records available Eye protection

Available

Not available

Any other comments..........................................................................

Name of EWURA’s Inspector: ..................................................................................

Signature.................................................................................................................

Date........................................................................................................................

I acknowledge the contents of the above document as has been served upon me by

the above named EWURA official

Name of Licensee Official: ………………………………………………………………........

Job Title: ……………………………………………………………………………………........

Signature: ………………………………………………………………………………….........

Date: ………………………………………………………………………………………..........

Page 24: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

24

APPENDIX 3: SMALL HYDROPOWER STATION INSPECTION CHECKLIST

NAME OF LICENSEE

SUBSTATION NAME

REGION/TOWN

DATE

INSTALLED CAPACITY

( MVA/MW )

AVAILABLE CAPACITY (MVA/MW)

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

CAPACITY(MW)

AVAILABLE

CAPACITY

(MW)

Page 25: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

25

A. TRANSFORMER (S)

Tick Oil Leakages Tick Fire Blast Walls

No Leakages

Fire Blast Walls Appropriately

Installed

Has Leakages No Fire Blast Walls

Transformer Maintenance Oil Spillage Containment

Regular Maintenance Done Adequate Bund Wall In Place

Inadequate-Partial

Maintenance No Bund Wall

No Maintenance-No Records

Transformer Mounting/

Plinth Condition Fire Fighting Facilities

Concrete Plinth In Place

Extinguishers Available, Adequate,

Serviced And Appropriate

Not Concrete

Extinguishers Inappropriate, Not

Serviced Or Inadequate

Not Available

Ventilation - indoor s/s Transformer Protection

Ventilation Provided Adequate Protection In Place

No Ventilation Inadequate Or No Protection

B. GENERAL STATE OF REPAIR

Tick Condition Of Turbines Tick Condition Of Cooling System

Turbine Casing Has No Leaks

All Cooling Water Components

In Good Repair

Turbine Casing Leaking Inadequate Maintenance

Page 26: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

26

Condition Of Excitation System

Condition Of Drainage Water

System

Both AVRs Working In Good Working Condition

Only One AVR Working Not In Good Working Condition

Both AVRs Not Working Not Working

Condition of Governors Condition of Penstock

Good Working Condition Penstock Leaking

Governor Not In Good Condition Penstock Not Leaking

Condition of Lift/Cranes Machines Status Indication

Lights

Lifts And Cranes Working And

Records Available For Statutory

Inspection

All Indications Working

Lift And Cranes Not Working Only Some Indications Working

All Indications Not Working

Equipment Labels Weed Boom

Labelling Available And In Good

Repair

Good Working Condition

Labelling Not In Good Repair Or

Not There

Poor Condition Or Not Working

Intake Gates Trash Rack

In Good Working Condition Good Working Condition

Condition Poor Or Not Working Not Working

Page 27: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

27

C. SAFETY

Tick Fire Fighting Facilities Tick Danger/warning signs

Extinguishers Available,

Adequate, Serviced And

Appropriate Extinguishers

Appropriate Notices or Signs In

Place

Inappropriate, Not Serviced or

Inadequate

Inappropriate Notices or Signs

Not Available No Notices or Signs

Tick

Fire Alarm

Tick

Procedures For Safe

(Emergency) Shut Down

Available Procedures Available

Not Available Procedures Not Available

First Aid PPE

Procedures and facilities

Available

PPE available

Only Procedures available PPE Not available

Only Facilities available

Procedures and facilities

unavailable

Emergency Escape Route Plant Security

Escape route clearly marked Plant secured

Escape route faded and/or not

Marked

Plant not secured

Competency of Personnel Safety documents (Permits)

Plant manned by adequate (Full

Establishment)authorized

Personnel

Switching instructions, Permits to

Work and limitation of access

Properly issued and kept on File

Inadequate authorized Personnel Permits not properly issued or

not kept on File

Page 28: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

28

D. OPERATIONS AND MAINTENANCE

Operational Logbook Means Of Communication

Available and in use Available

Available but not in use Unavailable

Not Available

Black start Procedure Work Procedures

Available and understood Available

not available and/or not

understood

Not available

Equipment Maintenance Maintenance Schedules (Plan)

Regular maintenance done Available and adhered to

Inadequate-Partial Maintenance Available but not adhered to

No maintenance-no records Not available

Circuit Breakers And Isolators PROTECTIVE RELAYS

Circuit Breakers And Isolators

Adequate

In place, regularly tested and in

good working condition

Only circuit breakers installed No test records

Only isolators installed No Relays

No circuit breakers and isolators

installed

E. BATTERIES

Space around Batteries Battery room floor

Space provided around batteries

adequate

floor can contain electrolyte

spillage

Space inadequate floor cannot contain electrolyte

spillage

Battery enclosure Electrical (lighting) Fixtures

Page 29: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

29

Battery enclosure appropriate Fixtures appropriately installed

Battery enclosure inappropriate Inappropriately installed

Ventilation Safety Signs

Ventilation available appropriate safety signs in place

Ventilation unavailable safety signs inappropriate or not

there

Battery racks Battery Maintenance

Battery racks properly anchored

(&/or earthed)

maintenance records available

Battery racks not properly

anchored (or earthed)

no records available

Eye protection

Available

not available

Any Other Comments: ............................................................................

Name of EWURA’s Inspector: …………………………………………………..........................

Signature:………………………………………………………………………….........................

Date………………………………………………………………………………...........................

I acknowledge the contents of the above document as has been served upon me by

the above named EWURA Official

Name of Licensee Official:............................................................................................

Official:…..………………………………………………………............................................

Job Title:……………………………………………………………………….…………...............

Signature..………………………………………………………………………………….............

Date:……………………………………………………………..………...................................

Page 30: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

30

APPENDIX 4: SUBSTATION INSPECTION CHECKLIST (VOLTAGE ABOVE 33kV)

NAME OF LICENSEE

SUBSTATION NAME

REGION/TOWN

DATE

SUBSTATION CAPACITY ( MVA )

SUBSTATION MAXIMUM DEMAND (MVA )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

TRANSFORMERS

CAPACITY(MVA)

AVAILABLE

CAPACITY

(MVA)

REACTORS

(MVAr )

CAPACITORS

(MVAr)

Page 31: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

31

A.TRANSFORMER (S) - Tick the appropriate item

Oil leaks Fire blast walls

No leaks

Has leaks

Fire Blast walls appropriately installed

No fire Blast walls

Transformer maintenance Oil spillage containment

Regular maintenance

done

Inadequate-partial

maintenance

No maintenance –no

records

Adequate bund wall in place

No Bund wall

Transformer maintenance Fire fighting facilities

Plinth condition

Concrete plinth in place

No concrete

Extinguishers available, adequate,

serviced and appropriate

Extinguishers inappropriate, not serviced

or inadequate

Not available

Earthing

Properly done

Not properly done

Transformer protection

Adequate protection in place

Inadequate or No protection

B. SUBSTATION IN GENERAL

Equipment maintenance Protective relays

Regularly maintenance

done

Inadequate-partial

maintenance

No maintenance-no

records

In place and regularly tested

No test records

No relays

Drainage

Drainage is available

Not available

Substation lighting

Adequate lighting

Inadequate lighting

Page 32: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

32

Circuit breakers and

isolators

Substation Earthing and bonding

Circuit breakers and

isolators adequate

Only circuit breakers

installed

No circuit breakers and

isolators installed

Earthing installed, regularly tested and

all equipment bonded

No test records available

No Earthing

Substation

accessibility

Substation easily

accessible

Substation difficult to

access

Means of communication

All indications working

Only some indications working

All indications not working

Colour coding /phase

identification

Danger/warning signs

Phases have

appropriate color

coding or identification

Phase have

inappropriate color

coding or identification

Phases have no color

coding or means of

identification

Appropriate notices or signs in place

Inappropriate notices or signs

No notices or signs

First aid Safety document (permits)

Procedures and

facilities available

Only procedures

available

Only facilities available

Both procedures and

facilities not available

Switching instructions, permits to work

and limitation of access properly issued

and kept on file

Permits not properly issued

or not kept on file

PPE procedures

PPE available

PPE not available

Substation fencing

Substation fencing in good repair and

locked

Page 33: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

33

Operational logo book

Substation fencing not in good repair

Security of supply

Available and in use

Not available

Substation capacity firm

Capacity not firm

Substation grounds Equipment labels

Substation grounds

covered with high

resistivity material

No high resistivity

material

Labelling available in good repair

Labelling not in good repair or not there

Voltage regulation

Voltage within

allowable limits

Voltage outside

allowable limits

Substation house keeping

Orderly

Not orderly

C. BATTERIES

Space around batteries Battery room floor

Space provided around

batteries

Adequate

Space inadequate

floor can contain electrolyte spillage

floor cannot contain electrolyte spillage

Battery enclosure

Battery enclosure

appropriate

Battery enclosure

inappropriate

Electrical (lighting) fixtures

Fixtures appropriately installed

Inappropriately installed

Ventilation

Ventilation available

Ventilation unavailable

Safety signs

Appropriate safety signs in place

Safety signs inappropriate or not there

Page 34: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

34

Battery racks

Battery racks properly

anchored & earthed

Battery racks not

properly anchored ( or

earthed )

Battery maintenance

Maintenance records available

No records available

Eye protection

Available

Not available

Any other comments.............................................................................

Name of EWURA Inspector: .......................................................................................

Signature:.................................................................................................................

Date: .......................................................................................................................

I acknowledge the contents of the above document as has been served upon me by

the above named EWURA official

Name of Licensee Official: ………………………………………………………………..........

Job Title: ……………………………………………………………………………………..........

Signature: ……………………………………………………………………………………........

Date: ……………………………………........................................................................

Page 35: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

35

APPENDIX 5: DISTRIBUTION SUBSTATION INSPECTION CHECKLIST

(VOLTAGE BELOW 33kV)

NAME OF LICENSEE

SUBSTATION NAME

REGION/TOWN

DATE

SUBSTATION CAPACITY ( MVA )

SUBSTATION MAXIMUM DEMAND (MVA )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

TRANSFORMERS

CAPACITY(MVA)

AVAILABLE

CAPACITY

(MVA)

Page 36: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

36

A. TRANSFORMER (S)

Tick Oil Leakages Tick Fire Blast Walls

No Leakages

Fire Blast Walls Appropriately

Installed

Has Leakages No Fire Blast Walls

Transformer Maintenance Oil Spillage Containment

Regular Maintenance Done Adequate Bund Wall In Place

Inadequate-Partial

Maintenance No Bund Wall

No Maintenance-No Records

Transformer Mounting/

Plinth Condition Fire Fighting Facilities

Concrete Plinth In Place

Extinguishers Available, Adequate,

Serviced And Appropriate

Not Concrete

Extinguishers Inappropriate, Not

Serviced Or Inadequate

Not Available

Transformer Protection Ventilation – Indoor Substation

Adequate Protection In Place Ventilation Provided

Inadequate Or No Protection No Ventilation

B. SUBSTATION IN GENERAL

Tick Equipment Maintenance Tick Danger/Warning Signs

Regular Maintenance Done Appropriate Notices Or Signs In Place

Inadequate-Partial

Maintenance Inappropriate Notices Or Signs

No Maintenance-No Records No Notices Or Signs

Page 37: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

37

Substation Accessibility Substation Lighting

Substation Easily Accessible Adequate Lighting

Substation Difficult To Access Inadequate Lighting

Colour Coding/Phase

Identification Substation Earthing and Bonding

Phases Have Appropriate Color

Coding Or Identification

Earthing Installed, Regularly Tested

And

All Equipment Bonded

Phases Have Inappropriate

Color Coding Or Identification No Test Records Available

Phases Have No Color Coding

Or Means Of Identification

Earthing Installed but not all

equipment bonded.

No Earthing

PPE Security Of Supply

PPE Available Substation Capacity Firm

PPE Not Available Capacity Not Firm

Substation Fencing Safety Documents (Permits)

Substation Fencing In Good

Repair And Locked

Switching Instructions, Permits To

Work And Limitation Of Access

Properly Issued And Kept On File

Substation Fencing Not In Good

Repair

Permits Not Properly Issued Or Not

Kept On File

No Fencing

Voltage Regulation Substation Housekeeping

Voltages Within Allowable

Limits

Orderly

Voltages Outside Allowable

Limits

Not Orderly

Page 38: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

38

Any Other Comments:........................................................................

Name of EWURA’s Inspector: …………………………………………………….................

Signature: …………………………………………………………………………...................

Date: ………………………………………………………………………………...................

I acknowledge the contents of the above document as has been served upon me by

the above named EWURA Official

Name of Licensee Official: ..………………………………………………………................

Job Title: ..……………………………………………………………………….…………........

Signature: ..………………………………………………………………………………..........

Date: ..……………………………………………………………..…………………………......

Page 39: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

39

APPENDIX 6: THERMAL POWER STATION INSPECTION CHECKLIST

NAME OF LICENSEE

PLANT NAME

REGION/TOWN

DATE

PLANT CAPACITY ( MVA )

PLANT MAXIMUM DEMAND (MVA )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

TRANSFORMERS

CAPACITY(MVA)

AVAILABLE

CAPACITY

(MVA)

Page 40: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

40

A. TRANSFORMER (S)

Tick Oil Leakages Tick Fire Blast Walls

No Leakages Fire Blast Walls Appropriately Installed

Has Leakages No Fire Blast Walls

Transformer

Maintenance

Oil Spillage Containment

Regular Maintenance Done Adequate Bund Wall In Place

Inadequate-Partial

Maintenance

No Bund Wall

No Maintenance Records

Transformer Mounting/

Plinth

Fire Fighting Facilities

Concrete Plinth In Place Extinguishers Available, Adequate, Serviced

And Appropriate

Not Concrete Extinguishers Inappropriate, Not Serviced

Or Inadequate

Not Available

Ventilation - indoor s/s Transformer Protection

Ventilation Provided Adequate Protection In Place

No Ventilation Inadequate Or No Protection

Page 41: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

41

B. SYSTEM AND GENERAL REQUIREMENTS

Tick Power House Condition Monitoring Tick Condition Of Cooling System

Power House Temperature Monitored Cooling System Adequate

Power House Temperature Not

Monitored

Cooling System Inadequate

System Adequacy Fuel Storage

System Adequate Fuel Storage Adequate

System Inadequate Fuel Storage Inadequate

Fire Fighting Facilities Danger/Warning Signs

Extinguishers available, adequate,

serviced and appropriate extinguishers

Appropriate notices or signs In

place

Inappropriate, Not Serviced Or

Inadequate

Inappropriate notices or signs

Not available No notices or signs

First Aid PPE

Procedures available PPE available

Only procedures available PPE Not available

Only facilities Available

Procedures and facilities unavailable

Plant Security Equipment Labels

Plant secured Labelling available and in good

Repair

Plant not secure Labelling not in good repair or not

there

Competency of Personnel Safety Procedures

Page 42: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

42

Plant manned ay adequate(Full

Establishment)authorized Personnel

Available

Inadequate authorized Personnel Not available

C. OPERATIONS AND MAINTENANCE

Operational Logbook Records Of Equipment Maintenance

Available and in use Records available

Available but not in use Records unavailable

Not available

Batteries Maintenance Schedules

Battery regularly maintained

and tested

Available and adhered to

Battery lacks maintenance Available but not adhered to

Not available

Circuit Breakers And Isolators Protective Relays

Circuit Breakers and Isolators

adequate

In Place, Regularly Tested And In Good

Working Condition

Only Circuit Breakers installed No test records

Only Isolators installed No Relays

No Circuit Breakers and

Isolators installed

Any Other Comments……………………………………………......................................

Name of EWURA Inspector: ……………………………………………………...........................

Signature: …………………………………………………………………………..........................

Date: ………………………………………………………………………………...........................

Page 43: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

43

I acknowledge the contents of the above document as has been served upon me by the

above named EWURA Official

Name of Licensee Official:.......………………………………………………………..................

Job Title: ..……………………………………………………………………….…………..............

Signature: ..…………………………………………………………………………………............

APPENDIX 7: Environmental Inspection checklist on Hydropower projects,

Transmission and Distribution line

1. Hydropower plants

NAME OF LICENSEE

PLANT NAME

REGION/TOWN

DATE

PLANT CAPACITY ( MVA )

PLANT MAXIMUM DEMAND (MVA )

NO. OF UNITS 1 2 3 4 5 6 7 8 9

INSTALLED

TRANSFORMERS

CAPACITY(MVA)

AVAILABLE

CAPACITY

(MVA)

Page 44: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

44

A Environmental Degradation Comments

Available Oil spillage from any

source to the soil and water

bodies

Waste water discharge into

water bodies e.g rivers

Efficiency use of water at site i.e.

water treatments and recycling

Dust prevention and dust

suppression at site

Measures put in place to

minimize noise and vibration

resulting from heavy equipment

or vehicle

B Catchment area of the project

Check whether the EIA study

report (if available on site) has

provided enough mitigations

and measures with regards to:

road accessibility

Any danger of ecosystem

exploitation and bio-

diversity losses

Water shed management

needs to protect

reservoir from silting

Agriculture activities and

practices that can have

an effect on vegetation

Page 45: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

45

and soils

Land use activities in the

catchment area that can

affect vegetation and

soils

Mining activities,

including quarrying and

their associated

environmental concerns.

C Reservoir Areas

Check whether EIA project

study report has been certified

by NEMC on all issues

concerned with Reservoir areas

and water bodies

D Dam, Spillway and Diversions

Check whether NEMC has

certified EIA study report (new

projects) on issues of dams,

spillway and diversions.

Page 46: ELECTRICITY INSPECTION AND AUDIT MANUAL - ENERGY · PDF file3 TECHNICAL AUDIT OVERVIEW ... SUBSTATION INSPECTION CHECKLIST ... is a statutory body established by the Energy and Water

46

Check whether the certified

EIA study report (for new

projects) by NEMC has

considered all issues concerned

with:

water conveyance

facilities ( e.g land use

changes, access

problems, etc ),

Power house

development and siting

(e.g design and layout

principles, access

problems e. t. c)

Contractors camp and

ancillary facilities ( if the

report has covered

pollution problems, land

use changes etc )

Did the certified project

study report by NEMC

considered issues of

water quality

downstream?

2 Transmission and

Distribution Lines

Check for availability of NEMC

certificate on transmission and

distribution lines construction

project.