Electrical Utilitas

256
Powerline Review Center, Inc. Saturday, June 9, 2012

Transcript of Electrical Utilitas

Page 1: Electrical Utilitas

Powerline Review Center, Inc.

Saturday, June 9, 2012

Page 2: Electrical Utilitas

ELECTRICAL SYSTEM DESIGNFOR

HIGH RISE BUILDING

Powerline Review Center, Inc.

Saturday, June 9, 2012

Page 3: Electrical Utilitas

Saturday, June 9, 2012

Page 4: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

Saturday, June 9, 2012

Page 5: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

High – rise buildings normally refer to occupancy for:

Saturday, June 9, 2012

Page 6: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

• general offices

High – rise buildings normally refer to occupancy for:

Saturday, June 9, 2012

Page 7: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

• commercial establishments

• general offices

High – rise buildings normally refer to occupancy for:

Saturday, June 9, 2012

Page 8: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

• hotels / condominiums or their combinations. The definitions as to number of floors and areas vary from one party to another.

• commercial establishments

• general offices

High – rise buildings normally refer to occupancy for:

Saturday, June 9, 2012

Page 9: Electrical Utilitas

ELECTRICAL SYSTEM DESIGN for HIGH-RISE BUILDING

These buildings distinctively differ from industrial buildings for manufacturing with regards to electric utilization equipment installed and the number of floors. The latter are mostly single or two-storey structure due to operational requirements and constraints. Exceptions are the taller silos for stockpiling of materials or finished products.

• hotels / condominiums or their combinations. The definitions as to number of floors and areas vary from one party to another.

• commercial establishments

• general offices

High – rise buildings normally refer to occupancy for:

Saturday, June 9, 2012

Page 10: Electrical Utilitas

Saturday, June 9, 2012

Page 11: Electrical Utilitas

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

Saturday, June 9, 2012

Page 12: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

Saturday, June 9, 2012

Page 13: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 14: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 15: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 16: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•air-conditioning for temperature control2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 17: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 18: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 19: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 20: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•elevators and escalators3. Transport System

•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 21: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 22: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

4. Water Pumps

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 23: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•potable and non-potable water supply4. Water Pumps

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 24: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•water sprinkle (fire suppression)•potable and non-potable water supply

4. Water Pumps

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 25: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•pumps / drainage•water sprinkle (fire suppression)•potable and non-potable water supply

4. Water Pumps

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 26: Electrical Utilitas

1. General Lighting & Power

1 – HIGH RISE BUILDING POWER SUPPLY REQUIREMENTS:

•sewage ejectors

•pumps / drainage•water sprinkle (fire suppression)•potable and non-potable water supply

4. Water Pumps

•conveyors, dumbwaiters, others•elevators and escalators

3. Transport System•heaters for humidity control•blowers and fans ventilation•air-conditioning for temperature control

2. Heating, Ventilation & Air-conditioning (HVAC) System

• power for appliances and office machines

• light for general illumination, seeing tasks, decorative features, hallways and stairways, others

Saturday, June 9, 2012

Page 27: Electrical Utilitas

Saturday, June 9, 2012

Page 28: Electrical Utilitas

5. Communication System

Saturday, June 9, 2012

Page 29: Electrical Utilitas

5. Communication System• PABX telephone system

Saturday, June 9, 2012

Page 30: Electrical Utilitas

5. Communication System

• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 31: Electrical Utilitas

5. Communication System

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 32: Electrical Utilitas

5. Communication System

• entrance and exit for pedestrians6. Automatic Doors

• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 33: Electrical Utilitas

5. Communication System

• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 34: Electrical Utilitas

5. Communication System

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 35: Electrical Utilitas

5. Communication System

• CPU and peripherals7. Central Computer System

• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 36: Electrical Utilitas

5. Communication System

• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 37: Electrical Utilitas

5. Communication System

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 38: Electrical Utilitas

5. Communication System

• intrusion and hold-up control system8. Auxiliaries

• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 39: Electrical Utilitas

5. Communication System

• fire suppression and alarm system• intrusion and hold-up control system

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 40: Electrical Utilitas

5. Communication System

• background music and paging• fire suppression and alarm system• intrusion and hold-up control system

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 41: Electrical Utilitas

5. Communication System

• sound reinforcement and video facilities• background music and paging• fire suppression and alarm system• intrusion and hold-up control system

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 42: Electrical Utilitas

5. Communication System

• noise masking and acoustics, others• sound reinforcement and video facilities• background music and paging• fire suppression and alarm system• intrusion and hold-up control system

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 43: Electrical Utilitas

5. Communication System

Note: The latter items could be integrated into the building automation system as may be provided in the design.

• noise masking and acoustics, others• sound reinforcement and video facilities• background music and paging• fire suppression and alarm system• intrusion and hold-up control system

8. Auxiliaries• Terminals• CPU and peripherals

7. Central Computer System• garage and freight• entrance and exit for pedestrians

6. Automatic Doors• Intercom • PABX telephone system

Saturday, June 9, 2012

Page 44: Electrical Utilitas

Saturday, June 9, 2012

Page 45: Electrical Utilitas

2 – HIGH-RISE BUILDING SYSTEM COMPONENTS

Saturday, June 9, 2012

Page 46: Electrical Utilitas

2 – HIGH-RISE BUILDING SYSTEM COMPONENTS

A high-rise building electrical system is composed of hundreds of components, designed and assembled into a safe, functional power-delivery system. In figure 2.1 shows a typical building electrical system riser diagram, where the building’s electrical system is connected to the utility system. Here, it is a pad-mounted transformer, but in other cases it might be a bank of transformers mounted overhead on a utility pole (for a demand less than 1,000 kVA).

Saturday, June 9, 2012

Page 47: Electrical Utilitas

2 – HIGH-RISE BUILDING SYSTEM COMPONENTS

A high-rise building electrical system is composed of hundreds of components, designed and assembled into a safe, functional power-delivery system. In figure 2.1 shows a typical building electrical system riser diagram, where the building’s electrical system is connected to the utility system. Here, it is a pad-mounted transformer, but in other cases it might be a bank of transformers mounted overhead on a utility pole (for a demand less than 1,000 kVA).

The underground service connects the utility system to building’s main distribution panel (MDP). Located within the MDP is the main building over-current device, or main disconnect, as well as individual over-current devices for the system components connected to the MDP. The MDP may also contain provisions for utility metering, as well as instrumentation for the measurement of system voltage and current.

Saturday, June 9, 2012

Page 48: Electrical Utilitas

Saturday, June 9, 2012

Page 49: Electrical Utilitas

The main disconnect device can be either a circuit breaker or a fused switch. This main device often contains special circuitry for sensing low-level faults (i.e. ground faults for more than 1,000 Amp main), which otherwise might escape detection. The MDP might be thought of as the electrical nerve center of the building. It is normally located near building exterior wall and as close as possible to the utility transformer to minimize the cost of main service feeders.

Saturday, June 9, 2012

Page 50: Electrical Utilitas

The main disconnect device can be either a circuit breaker or a fused switch. This main device often contains special circuitry for sensing low-level faults (i.e. ground faults for more than 1,000 Amp main), which otherwise might escape detection. The MDP might be thought of as the electrical nerve center of the building. It is normally located near building exterior wall and as close as possible to the utility transformer to minimize the cost of main service feeders.

Thus, all components of the system must be chosen carefully based on design requirements and must function safely, under normal operating conditions and also under abnormal conditions, such as short circuits.

Saturday, June 9, 2012

Page 51: Electrical Utilitas

Saturday, June 9, 2012

Page 52: Electrical Utilitas

Saturday, June 9, 2012

Page 53: Electrical Utilitas

Saturday, June 9, 2012

Page 54: Electrical Utilitas

3 – POWER SUPPLY SYSTEM

Saturday, June 9, 2012

Page 55: Electrical Utilitas

3 – POWER SUPPLY SYSTEM

The franchise utility power company serves at nominal level of 230/115-volt, single- or three-phase, two-, three or four wires depending on the type of load and as long as it does not exceed 1,000 kVA. For extremely large service entrance current, multiple conductors may be used. Likewise, multiple protective/disconnect devices not exceeding six (6) may be connected in parallel for the service entrance (as stated by P.E.C.).

Saturday, June 9, 2012

Page 56: Electrical Utilitas

3 – POWER SUPPLY SYSTEM

The franchise utility power company serves at nominal level of 230/115-volt, single- or three-phase, two-, three or four wires depending on the type of load and as long as it does not exceed 1,000 kVA. For extremely large service entrance current, multiple conductors may be used. Likewise, multiple protective/disconnect devices not exceeding six (6) may be connected in parallel for the service entrance (as stated by P.E.C.). For establishment of greater than 1,000 kVA load, as most commercial and industrial consumers, the power company requires a load center unit sub-station and serves power at primary line distribution level of 13.8 or 34.5k Volts or whatever potential level available in the vicinity.

Saturday, June 9, 2012

Page 57: Electrical Utilitas

3 – POWER SUPPLY SYSTEM

The franchise utility power company serves at nominal level of 230/115-volt, single- or three-phase, two-, three or four wires depending on the type of load and as long as it does not exceed 1,000 kVA. For extremely large service entrance current, multiple conductors may be used. Likewise, multiple protective/disconnect devices not exceeding six (6) may be connected in parallel for the service entrance (as stated by P.E.C.).

The size of the load center depends on the proposed connected load and allowances for future growth of the establishment; its configuration, on the other hand, depends on the requirements and available facilities of the utility company.

For establishment of greater than 1,000 kVA load, as most commercial and industrial consumers, the power company requires a load center unit sub-station and serves power at primary line distribution level of 13.8 or 34.5k Volts or whatever potential level available in the vicinity.

Saturday, June 9, 2012

Page 58: Electrical Utilitas

Saturday, June 9, 2012

Page 59: Electrical Utilitas

The major components of the load center are:

Saturday, June 9, 2012

Page 60: Electrical Utilitas

The major components of the load center are:

(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 61: Electrical Utilitas

The major components of the load center are:

(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 62: Electrical Utilitas

The major components of the load center are:

(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 63: Electrical Utilitas

The major components of the load center are:

(4) Metering equipment(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 64: Electrical Utilitas

The major components of the load center are:

3.1 – Utilizing Voltage

(4) Metering equipment(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 65: Electrical Utilitas

The major components of the load center are:

Usually in large installations with private load centers, the practice is to use 208/120-volt for general lighting and power, and 460-volt for motors. This appears to be the more economical and practical arrangements.

3.1 – Utilizing Voltage

(4) Metering equipment(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 66: Electrical Utilitas

The major components of the load center are:

Usually in large installations with private load centers, the practice is to use 208/120-volt for general lighting and power, and 460-volt for motors. This appears to be the more economical and practical arrangements.

3.1 – Utilizing Voltage

Three-phase electric motors are normally dual-voltage, i.e. 460/230 volts and using the higher 460-volt rating will result in half-as-much ampere draw, hence smaller wires, lower circuit breaker rating (although higher voltage) and smaller starter unit.

(4) Metering equipment(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 67: Electrical Utilitas

The major components of the load center are:

Usually in large installations with private load centers, the practice is to use 208/120-volt for general lighting and power, and 460-volt for motors. This appears to be the more economical and practical arrangements.

3.1 – Utilizing Voltage

For lighting and appliances, 460-volt line can likewise be used but availability of fixtures for such potential may not be easily procured, i.e. 265-volt ballasts for fluorescent and convenience outlet with built-in unit t r a n s f o r m e r s o f 5 0 t o 1 0 0 V A , 4 6 0 - 2 3 0 / 1 1 5 - v o l t ratings.

Three-phase electric motors are normally dual-voltage, i.e. 460/230 volts and using the higher 460-volt rating will result in half-as-much ampere draw, hence smaller wires, lower circuit breaker rating (although higher voltage) and smaller starter unit.

(4) Metering equipment(3) Low-voltage switchgear; secondary side(2) Power transformer section(1) High-voltage switchgear; primary side

Saturday, June 9, 2012

Page 68: Electrical Utilitas

Saturday, June 9, 2012

Page 69: Electrical Utilitas

For total load of 1,000 kVA or less, the power supply is 208/120-volt or 230/115-volt only. In some cases, and for temporary construction power, the power company would serve 460-volt for use of construction equipment, subject to their requirements, rules and regulations.

Saturday, June 9, 2012

Page 70: Electrical Utilitas

For total load of 1,000 kVA or less, the power supply is 208/120-volt or 230/115-volt only. In some cases, and for temporary construction power, the power company would serve 460-volt for use of construction equipment, subject to their requirements, rules and regulations.

3.2 – Configuration of Load Centers

Saturday, June 9, 2012

Page 71: Electrical Utilitas

For total load of 1,000 kVA or less, the power supply is 208/120-volt or 230/115-volt only. In some cases, and for temporary construction power, the power company would serve 460-volt for use of construction equipment, subject to their requirements, rules and regulations.

Should the customer enterprise be required to provide its own load center unit substation, several options are available, again subject to approval of the power utility company.

3.2 – Configuration of Load Centers

Saturday, June 9, 2012

Page 72: Electrical Utilitas

Saturday, June 9, 2012

Page 73: Electrical Utilitas

OPTION – 1 : High-voltage supply line from power company transformed to utilization voltage of 208/120-volt for general lighting and power, and 460-volt for motors using two separate power transformers as shown in fig. 3.2(a).

Saturday, June 9, 2012

Page 74: Electrical Utilitas

OPTION – 1 : High-voltage supply line from power company transformed to utilization voltage of 208/120-volt for general lighting and power, and 460-volt for motors using two separate power transformers as shown in fig. 3.2(a).

Saturday, June 9, 2012

Page 75: Electrical Utilitas

Saturday, June 9, 2012

Page 76: Electrical Utilitas

OPTION – 2 : High-voltage supply line from power company transformed to 460-volts; general lighting and power fed by the 460-volt line

through a unit dry-type transformer, 460-208 / 120-volt, as shown in fig. 3.2(b).

Saturday, June 9, 2012

Page 77: Electrical Utilitas

OPTION – 2 : High-voltage supply line from power company transformed to 460-volts; general lighting and power fed by the 460-volt line

through a unit dry-type transformer, 460-208 / 120-volt, as shown in fig. 3.2(b).

Saturday, June 9, 2012

Page 78: Electrical Utilitas

Saturday, June 9, 2012

Page 79: Electrical Utilitas

OPTION – 3 : Similar to Option – 2 “except” several units of smaller units of smaller dry-type transformers are distributed in the areas or floors for general lighting and power system; these unit transformers are fed by 460-volt line or lines from the load center as shown in fig 3.2 (c).

Saturday, June 9, 2012

Page 80: Electrical Utilitas

OPTION – 3 : Similar to Option – 2 “except” several units of smaller units of smaller dry-type transformers are distributed in the areas or floors for general lighting and power system; these unit transformers are fed by 460-volt line or lines from the load center as shown in fig 3.2 (c).

Saturday, June 9, 2012

Page 81: Electrical Utilitas

Saturday, June 9, 2012

Page 82: Electrical Utilitas

Any of these configurations will serve the purpose of transforming the incoming high-voltage line from the utility company to acceptable utilization equipment level. The final choice of the desired system is normally dictated by costs and equipment availability. Power transformers are either dry-type or oil-immersed.

Saturday, June 9, 2012

Page 83: Electrical Utilitas

Any of these configurations will serve the purpose of transforming the incoming high-voltage line from the utility company to acceptable utilization equipment level. The final choice of the desired system is normally dictated by costs and equipment availability. Power transformers are either dry-type or oil-immersed. The common disadvantage of all of the above load center configurations is its inflexibility. In cases of breakdown of any of the main components, i.e. high or low-voltage switchgear mains, or the transformer itself will result in total system shut-down.

Saturday, June 9, 2012

Page 84: Electrical Utilitas

Any of these configurations will serve the purpose of transforming the incoming high-voltage line from the utility company to acceptable utilization equipment level. The final choice of the desired system is normally dictated by costs and equipment availability. Power transformers are either dry-type or oil-immersed.

3.3 – Load Center Flexibility & Reliability

The common disadvantage of all of the above load center configurations is its inflexibility. In cases of breakdown of any of the main components, i.e. high or low-voltage switchgear mains, or the transformer itself will result in total system shut-down.

Saturday, June 9, 2012

Page 85: Electrical Utilitas

Any of these configurations will serve the purpose of transforming the incoming high-voltage line from the utility company to acceptable utilization equipment level. The final choice of the desired system is normally dictated by costs and equipment availability. Power transformers are either dry-type or oil-immersed.

While a “fail-safe” system could not be adopted due to its prohibitive cost, still some degree of flexibility and reliability of the system can be reasonably reached.

3.3 – Load Center Flexibility & Reliability

The common disadvantage of all of the above load center configurations is its inflexibility. In cases of breakdown of any of the main components, i.e. high or low-voltage switchgear mains, or the transformer itself will result in total system shut-down.

Saturday, June 9, 2012

Page 86: Electrical Utilitas

Any of these configurations will serve the purpose of transforming the incoming high-voltage line from the utility company to acceptable utilization equipment level. The final choice of the desired system is normally dictated by costs and equipment availability. Power transformers are either dry-type or oil-immersed.

While a “fail-safe” system could not be adopted due to its prohibitive cost, still some degree of flexibility and reliability of the system can be reasonably reached.

3.3 – Load Center Flexibility & Reliability

The load center can be split into two (2) equal or identical units to serve the likewise equally, as far as practicable, divided electrical loads. In cases of failure of any of the major components of either unit, the remaining half is still operational. System selectivity can be attained, either on the primary or secondary sides or both, by using “tie-breaker”.

The common disadvantage of all of the above load center configurations is its inflexibility. In cases of breakdown of any of the main components, i.e. high or low-voltage switchgear mains, or the transformer itself will result in total system shut-down.

Saturday, June 9, 2012

Page 87: Electrical Utilitas

Saturday, June 9, 2012

Page 88: Electrical Utilitas

Properly coordinated interlocking system should be provided between the tie and main breakers to prevent accidents.

Saturday, June 9, 2012

Page 89: Electrical Utilitas

Properly coordinated interlocking system should be provided between the tie and main breakers to prevent accidents.

The load centers described in the proceeding paragraph will be served on two (2) separate ends and thus termed “double-ended” unit. Customarily, the power company serves this type of load center from two (2) separate distribution feeder lines to further enhance the system’s selectivity. Figure 3.3 shows the one line diagram of a typical “double-ended” system as adopted from Option 3. The same can be done for both Option 1 and 2.

Saturday, June 9, 2012

Page 90: Electrical Utilitas

Saturday, June 9, 2012

Page 91: Electrical Utilitas

Saturday, June 9, 2012

Page 92: Electrical Utilitas

Saturday, June 9, 2012

Page 93: Electrical Utilitas

Note: The interlock, mechanical/electrical, will prevent putting “ON” the tie-breaker until either of the main breaker is “OFF”; metering CT’s and PT’s are to be installed in both the high-voltage incoming lines 1 and 2.

Saturday, June 9, 2012

Page 94: Electrical Utilitas

Note: The interlock, mechanical/electrical, will prevent putting “ON” the tie-breaker until either of the main breaker is “OFF”; metering CT’s and PT’s are to be installed in both the high-voltage incoming lines 1 and 2.

4 – EMERGENCY POWER SYSTEM

Saturday, June 9, 2012

Page 95: Electrical Utilitas

Note: The interlock, mechanical/electrical, will prevent putting “ON” the tie-breaker until either of the main breaker is “OFF”; metering CT’s and PT’s are to be installed in both the high-voltage incoming lines 1 and 2.

The power requirements of the building can be sufficiently supplied by the power company at acceptable level, continuity and characteristics. There are, however, instances when the power may be interrupted due to the system fault or deficiencies, some of which are inherent in the power transmission and distribution. Longer interruptions will greatly inconvenience the building occupants and may even be dangerous to life and limbs. Losses in terms of unproductive man-hours and business opportunity may also substantial.

4 – EMERGENCY POWER SYSTEM

Saturday, June 9, 2012

Page 96: Electrical Utilitas

Note: The interlock, mechanical/electrical, will prevent putting “ON” the tie-breaker until either of the main breaker is “OFF”; metering CT’s and PT’s are to be installed in both the high-voltage incoming lines 1 and 2.

The power requirements of the building can be sufficiently supplied by the power company at acceptable level, continuity and characteristics. There are, however, instances when the power may be interrupted due to the system fault or deficiencies, some of which are inherent in the power transmission and distribution. Longer interruptions will greatly inconvenience the building occupants and may even be dangerous to life and limbs. Losses in terms of unproductive man-hours and business opportunity may also substantial.

4 – EMERGENCY POWER SYSTEM

The suggested solution, other than the self-contained battery-powered emergency lights, is a stand-by diesel engine-generator set or sets. It is not economically sound, and probably poor engineering practice, to provide 100% back-up or stand-by power because of the tremendous costs of the generator set or sets to be used in relatively short time of main power interruptions.

Saturday, June 9, 2012

Page 97: Electrical Utilitas

Saturday, June 9, 2012

Page 98: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

Saturday, June 9, 2012

Page 99: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes

Saturday, June 9, 2012

Page 100: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes• Counter areas for public transactions

Saturday, June 9, 2012

Page 101: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes

• Water pumps and fire pumps• Counter areas for public transactions

Saturday, June 9, 2012

Page 102: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes

• One or two elevators to be used by physically handicapped• Water pumps and fire pumps• Counter areas for public transactions

Saturday, June 9, 2012

Page 103: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes

• Computer system• One or two elevators to be used by physically handicapped• Water pumps and fire pumps• Counter areas for public transactions

Saturday, June 9, 2012

Page 104: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

• Stairways’ and hallways’ lighting for safety purposes

• Rooms or suites of top executives• Computer system• One or two elevators to be used by physically handicapped• Water pumps and fire pumps• Counter areas for public transactions

Saturday, June 9, 2012

Page 105: Electrical Utilitas

The more essential loads of the building are to be supplied with emergency power in cases of main power failure. Normally, these are the following:

Power transfer to stand-by generator can be done manually by double-throw transfer-switch or automatically by automatic-transfer-switch (ATS). For the latter, it is necessary that the feeder/s or line/s serving the essential loads should not include the non-essential facilities. Separate emergency lines and panel boards will be provided exclusively for the purpose. A typical one-line diagram is shown in fig. 4.1 as adopted from fig. 3.3.

• Stairways’ and hallways’ lighting for safety purposes

• Rooms or suites of top executives• Computer system• One or two elevators to be used by physically handicapped• Water pumps and fire pumps• Counter areas for public transactions

Saturday, June 9, 2012

Page 106: Electrical Utilitas

Saturday, June 9, 2012

Page 107: Electrical Utilitas

Saturday, June 9, 2012

Page 108: Electrical Utilitas

Saturday, June 9, 2012

Page 109: Electrical Utilitas

The system operates as follows:

Saturday, June 9, 2012

Page 110: Electrical Utilitas

The system operates as follows:

• When main power voltage dips to 70 to 80% of nominal value, the ATS automatically starts the generator and build- up same to its rated output voltage; after 20 seconds of such power condition, the ATS automatically transfer the emergency feeder mains to generator;

Saturday, June 9, 2012

Page 111: Electrical Utilitas

The system operates as follows:

• When main power is restored to its rated level, the ATS instantly transfer the load back to the main power feeder; after 1 or 2 minutes of main power stabilized conditions, the generator set automatically stops;

• When main power voltage dips to 70 to 80% of nominal value, the ATS automatically starts the generator and build- up same to its rated output voltage; after 20 seconds of such power condition, the ATS automatically transfer the emergency feeder mains to generator;

Saturday, June 9, 2012

Page 112: Electrical Utilitas

The system operates as follows:

• The ATS could also be programmed to automatically “exercise” or operate the generator at no-load for 15-minute, twice-a-week periods in order to keep the set and auxiliaries in good running conditions.

• When main power is restored to its rated level, the ATS instantly transfer the load back to the main power feeder; after 1 or 2 minutes of main power stabilized conditions, the generator set automatically stops;

• When main power voltage dips to 70 to 80% of nominal value, the ATS automatically starts the generator and build- up same to its rated output voltage; after 20 seconds of such power condition, the ATS automatically transfer the emergency feeder mains to generator;

Saturday, June 9, 2012

Page 113: Electrical Utilitas

The system operates as follows:

Voltage level and time setting as mentioned may be adjusted to the desired level of the user, but instant transfer from main to stand-by power is not possible since it will require sometime for the generator voltage to build-up.

• The ATS could also be programmed to automatically “exercise” or operate the generator at no-load for 15-minute, twice-a-week periods in order to keep the set and auxiliaries in good running conditions.

• When main power is restored to its rated level, the ATS instantly transfer the load back to the main power feeder; after 1 or 2 minutes of main power stabilized conditions, the generator set automatically stops;

• When main power voltage dips to 70 to 80% of nominal value, the ATS automatically starts the generator and build- up same to its rated output voltage; after 20 seconds of such power condition, the ATS automatically transfer the emergency feeder mains to generator;

Saturday, June 9, 2012

Page 114: Electrical Utilitas

Saturday, June 9, 2012

Page 115: Electrical Utilitas

For uninterruptible power supply as may be required by computer

Saturday, June 9, 2012

Page 116: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It

Saturday, June 9, 2012

Page 117: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It is discussed in the succeeding paragraphs.

Saturday, June 9, 2012

Page 118: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It is discussed in the succeeding paragraphs.

Power Supply for Computer System

Saturday, June 9, 2012

Page 119: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It is discussed in the succeeding paragraphs.

Computer hardwares and operations requires controlled environment as to temperature, humidity and dust for satisfactory p e r f o r m a n c e . T h e s a m e i s t r u e f o r i t s e l e c t r i c p o w e r supply.

Power Supply for Computer System

Saturday, June 9, 2012

Page 120: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It is discussed in the succeeding paragraphs.

Computer hardwares and operations requires controlled environment as to temperature, humidity and dust for satisfactory p e r f o r m a n c e . T h e s a m e i s t r u e f o r i t s e l e c t r i c p o w e r supply.

Power Supply for Computer System

Power hits and dips which is normal occurrences in AC power system are sometimes beyond the tolerable limits of the computer. Some hardwares can not tolerate power disturbance of more than 1/5 of a cycle of the normal 60 Hz power. While specially designed automatic-voltage-regulators (AVR) may serve the purpose, the problem will be in the response time to correct the abnormalities, not to mention actual power interruptions.

Saturday, June 9, 2012

Page 121: Electrical Utilitas

For uninterruptible power supply as may be required by computer hardwares and the like, a different equipment configuration is necessary. It is discussed in the succeeding paragraphs.

Computer hardwares and operations requires controlled environment as to temperature, humidity and dust for satisfactory p e r f o r m a n c e . T h e s a m e i s t r u e f o r i t s e l e c t r i c p o w e r supply.

Power Supply for Computer System

On power interruptions, the time-lag for the emergency generator to build-up and supply power through the ATS is a way beyond the recovery time of the computer. Hence, the computer will shut-down, will have to be reset and re-started. If the computer is on a long-batch run schedules, it may be necessary to re-run the batch (viz. program) from the start. There is also the possible errors and damages to the computer hardwares and softwares which may prove very costly.

Power hits and dips which is normal occurrences in AC power system are sometimes beyond the tolerable limits of the computer. Some hardwares can not tolerate power disturbance of more than 1/5 of a cycle of the normal 60 Hz power. While specially designed automatic-voltage-regulators (AVR) may serve the purpose, the problem will be in the response time to correct the abnormalities, not to mention actual power interruptions.

Saturday, June 9, 2012

Page 122: Electrical Utilitas

Saturday, June 9, 2012

Page 123: Electrical Utilitas

The recommended conditioned power system for computer is the “uninterruptible power supply” system or UPS. In the country most UPS are static type. A typical block diagram is show in fig. 4.2.

Saturday, June 9, 2012

Page 124: Electrical Utilitas

The recommended conditioned power system for computer is the “uninterruptible power supply” system or UPS. In the country most UPS are static type. A typical block diagram is show in fig. 4.2.

Saturday, June 9, 2012

Page 125: Electrical Utilitas

Saturday, June 9, 2012

Page 126: Electrical Utilitas

The rectifier-charger, fed from emergency feeder thru “RCB” breaker, supplies the D-C bus. The battery is charged and at the same time supplies power to the inverter where D-C power is inverter to A-C output for the computer load. Charging of the battery is appropriately controlled.

Saturday, June 9, 2012

Page 127: Electrical Utilitas

The rectifier-charger, fed from emergency feeder thru “RCB” breaker, supplies the D-C bus. The battery is charged and at the same time supplies power to the inverter where D-C power is inverter to A-C output for the computer load. Charging of the battery is appropriately controlled. The output feeder line to the computer is protected by the inverter circuit breaker “ICB”.

Saturday, June 9, 2012

Page 128: Electrical Utilitas

The rectifier-charger, fed from emergency feeder thru “RCB” breaker, supplies the D-C bus. The battery is charged and at the same time supplies power to the inverter where D-C power is inverter to A-C output for the computer load. Charging of the battery is appropriately controlled.

In cases of power supply and system infirmities:

The output feeder line to the computer is protected by the inverter circuit breaker “ICB”.

Saturday, June 9, 2012

Page 129: Electrical Utilitas

The rectifier-charger, fed from emergency feeder thru “RCB” breaker, supplies the D-C bus. The battery is charged and at the same time supplies power to the inverter where D-C power is inverter to A-C output for the computer load. Charging of the battery is appropriately controlled.

• Hits and dips will not be reflected in the A-C output lines as this is absorbed in the rectifier / charger only; the UPS in effect, filters the power to the computer.

In cases of power supply and system infirmities:

The output feeder line to the computer is protected by the inverter circuit breaker “ICB”.

Saturday, June 9, 2012

Page 130: Electrical Utilitas

The rectifier-charger, fed from emergency feeder thru “RCB” breaker, supplies the D-C bus. The battery is charged and at the same time supplies power to the inverter where D-C power is inverter to A-C output for the computer load. Charging of the battery is appropriately controlled.

• When power is interrupted, the floating battery will supply D-C bus such that the inverter will not suffer any power stoppage; the battery bank is normally rated to supply power for 10 to 15 minutes, time enough to build-up and put on the line the emergency generator. The battery bank composed of 100 to 150 industrial type-heavy duty units, each with a rated terminal voltage of 2 to 2 ½ Volts for higher capacity units.

• Hits and dips will not be reflected in the A-C output lines as this is absorbed in the rectifier / charger only; the UPS in effect, filters the power to the computer.

In cases of power supply and system infirmities:

The output feeder line to the computer is protected by the inverter circuit breaker “ICB”.

Saturday, June 9, 2012

Page 131: Electrical Utilitas

Saturday, June 9, 2012

Page 132: Electrical Utilitas

There are several supplies of imported and locally manufactured UPS who can assists the users in selecting the configuration most suited to their respective purposes. Several options of Redundancy features are available to enhance the reliability of the system.

Saturday, June 9, 2012

Page 133: Electrical Utilitas

There are several supplies of imported and locally manufactured UPS who can assists the users in selecting the configuration most suited to their respective purposes. Several options of Redundancy features are available to enhance the reliability of the system.

A rotary type combination of an A-C motor-driven-alternator and stand-by diesel engine prime mover with “flywheel” is another configuration of a UPS system as shown in fig. 4.3, this is sometimes termed as “dynamic UPS” system. The flywheel stores and supplies the rotating power (i.e. kinetic energy) for the alternator before the stand-by prime mover assumes the A-C motor drive functions in cases of power failure. This is similar with the principle of rotating regulators in maintaining the speed of a D-C generator.

Saturday, June 9, 2012

Page 134: Electrical Utilitas

There are several supplies of imported and locally manufactured UPS who can assists the users in selecting the configuration most suited to their respective purposes. Several options of Redundancy features are available to enhance the reliability of the system.

• When the UPS itself fails, the static-transfer switch “SS” will automatically transfer the output to the by-pass line; the transfer is of the make-before-break operation that the A-C output will not detect the switch made; Manual transfer to the by-pass line can also be made thru the commercial circuit breaker “CCB”.

A rotary type combination of an A-C motor-driven-alternator and stand-by diesel engine prime mover with “flywheel” is another configuration of a UPS system as shown in fig. 4.3, this is sometimes termed as “dynamic UPS” system. The flywheel stores and supplies the rotating power (i.e. kinetic energy) for the alternator before the stand-by prime mover assumes the A-C motor drive functions in cases of power failure. This is similar with the principle of rotating regulators in maintaining the speed of a D-C generator.

Saturday, June 9, 2012

Page 135: Electrical Utilitas

Saturday, June 9, 2012

Page 136: Electrical Utilitas

Saturday, June 9, 2012

Page 137: Electrical Utilitas

Saturday, June 9, 2012

Page 138: Electrical Utilitas

5 – FEEDER : NUMBER & SIZES

Saturday, June 9, 2012

Page 139: Electrical Utilitas

5 – FEEDER : NUMBER & SIZES

Feeder line can either be bus way (bus bar trunking) or insulated conductors or combination of both. The former is more versatile, neat in appearance but decidedly more expensive Bus ways are very popular especially for high ampere capacity lines. It can carry up to 7,000 Amp as compared against wires of 540 Amp maximum per set.

Saturday, June 9, 2012

Page 140: Electrical Utilitas

5 – FEEDER : NUMBER & SIZES

Feeder line can either be bus way (bus bar trunking) or insulated conductors or combination of both. The former is more versatile, neat in appearance but decidedly more expensive Bus ways are very popular especially for high ampere capacity lines. It can carry up to 7,000 Amp as compared against wires of 540 Amp maximum per set.

Bus ways, however, should not be used in highly corrosive atmospheres as in battery rooms, in concealed locations, and where it may be subjected to serve mechanical injury as in hoist ways. For these cases, only insulated conductors in rigid steel conduit will suffice.

Saturday, June 9, 2012

Page 141: Electrical Utilitas

5 – FEEDER : NUMBER & SIZES

Feeder line can either be bus way (bus bar trunking) or insulated conductors or combination of both. The former is more versatile, neat in appearance but decidedly more expensive Bus ways are very popular especially for high ampere capacity lines. It can carry up to 7,000 Amp as compared against wires of 540 Amp maximum per set.

All feeder runs will terminate in the low-voltage switchgear and will be protected with appropriately rated circuit breakers or fuses. (see fig. 5.0)

Bus ways, however, should not be used in highly corrosive atmospheres as in battery rooms, in concealed locations, and where it may be subjected to serve mechanical injury as in hoist ways. For these cases, only insulated conductors in rigid steel conduit will suffice.

Saturday, June 9, 2012

Page 142: Electrical Utilitas

5 – FEEDER : NUMBER & SIZES

Feeder line can either be bus way (bus bar trunking) or insulated conductors or combination of both. The former is more versatile, neat in appearance but decidedly more expensive Bus ways are very popular especially for high ampere capacity lines. It can carry up to 7,000 Amp as compared against wires of 540 Amp maximum per set.

There is no limit placed in determining the number of feeders, its maximum load and hence its corresponding circuit protection. This is decided by the individual’s perception as regards to flexibility, functionality and economy.

All feeder runs will terminate in the low-voltage switchgear and will be protected with appropriately rated circuit breakers or fuses. (see fig. 5.0)

Bus ways, however, should not be used in highly corrosive atmospheres as in battery rooms, in concealed locations, and where it may be subjected to serve mechanical injury as in hoist ways. For these cases, only insulated conductors in rigid steel conduit will suffice.

Saturday, June 9, 2012

Page 143: Electrical Utilitas

Saturday, June 9, 2012

Page 144: Electrical Utilitas

Saturday, June 9, 2012

Page 145: Electrical Utilitas

Saturday, June 9, 2012

Page 146: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

Saturday, June 9, 2012

Page 147: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and ProtectionsFlexibility

Saturday, June 9, 2012

Page 148: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

Flexibility

Saturday, June 9, 2012

Page 149: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 150: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

Feeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 151: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

Feeder II - to serve Basement, 2nd, 4thFeeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 152: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

Feeder III - to serve 6th, 8th, 10th …Feeder II - to serve Basement, 2nd, 4thFeeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 153: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

and so forth; if the floor is sufficiently large, it may even be divided into zones and fed from different feeders.

Feeder III - to serve 6th, 8th, 10th …Feeder II - to serve Basement, 2nd, 4thFeeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 154: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

• The idea is to minimize areas affected by a single feeder breakdown;

and so forth; if the floor is sufficiently large, it may even be divided into zones and fed from different feeders.

Feeder III - to serve 6th, 8th, 10th …Feeder II - to serve Basement, 2nd, 4thFeeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 155: Electrical Utilitas

5.1 – Consideration in the Design of Feeders and Protections

• While a single feeder may sufficiently supply several areas or floors or loads, so the scope of it affects in cases of breakdown.

• The same principle could be adopted for air conditioning, elevators, pumps and other motor loads

• The idea is to minimize areas affected by a single feeder breakdown;

and so forth; if the floor is sufficiently large, it may even be divided into zones and fed from different feeders.

Feeder III - to serve 6th, 8th, 10th …Feeder II - to serve Basement, 2nd, 4thFeeder I - to serve Ground, 3rd, 5th floors

Flexibility

• For the general lighting and power system of a high-rise building, some designer distribute the loads among several feeders, example:

Saturday, June 9, 2012

Page 156: Electrical Utilitas

Saturday, June 9, 2012

Page 157: Electrical Utilitas

Conveniently Available Sizes of Bus ways or Conductors

Saturday, June 9, 2012

Page 158: Electrical Utilitas

Conveniently Available Sizes of Bus ways or Conductors

• While multiple bus ways or conductors can be used to meet desired current-carrying capacity of the line, there should be some limit to this multiplicity for practical purposes in handling and where building spaces are restricted.

Saturday, June 9, 2012

Page 159: Electrical Utilitas

Conveniently Available Sizes of Bus ways or Conductors

• While multiple bus ways or conductors can be used to meet desired current-carrying capacity of the line, there should be some limit to this multiplicity for practical purposes in handling and where building spaces are restricted.

for example, three or more sets of large sized conductors can not be conveniently terminated in a single receiving or originating lugs or breaker terminal.

Saturday, June 9, 2012

Page 160: Electrical Utilitas

Conveniently Available Sizes of Bus ways or Conductors

Minimized Number of Replacement Breakers in Stock to Reduce Inventory Carrying Costs

• While multiple bus ways or conductors can be used to meet desired current-carrying capacity of the line, there should be some limit to this multiplicity for practical purposes in handling and where building spaces are restricted.

for example, three or more sets of large sized conductors can not be conveniently terminated in a single receiving or originating lugs or breaker terminal.

Saturday, June 9, 2012

Page 161: Electrical Utilitas

Conveniently Available Sizes of Bus ways or Conductors

• A set of feeder breakers, say 10 units of 1,000 Amperes each, another set of 10 units of 500 amperes each and so forth will require lesser number of replacement units in stocks as compared against numerous feeders of substantially different sizes of breakers.

Minimized Number of Replacement Breakers in Stock to Reduce Inventory Carrying Costs

• While multiple bus ways or conductors can be used to meet desired current-carrying capacity of the line, there should be some limit to this multiplicity for practical purposes in handling and where building spaces are restricted.

for example, three or more sets of large sized conductors can not be conveniently terminated in a single receiving or originating lugs or breaker terminal.

Saturday, June 9, 2012

Page 162: Electrical Utilitas

Saturday, June 9, 2012

Page 163: Electrical Utilitas

Allowable Voltage Drops in the Conductors

Saturday, June 9, 2012

Page 164: Electrical Utilitas

Allowable Voltage Drops in the Conductors

• for branch circuits the allowable voltage drop not exceeding 3% at the farthest outlet of power, heating and lighting loads. While for both feeder and branch circuits to the farthest outlet the allowable voltage drop not exceeding 5% to provide reasonable efficiency of operation.

Saturday, June 9, 2012

Page 165: Electrical Utilitas

Allowable Voltage Drops in the Conductors

Note: The sizes of feeder and branch circuit wires are based on the connected load, allowances for future growth, demand factor and diversity factors. The following can be used as reference for this purpose:

• for branch circuits the allowable voltage drop not exceeding 3% at the farthest outlet of power, heating and lighting loads. While for both feeder and branch circuits to the farthest outlet the allowable voltage drop not exceeding 5% to provide reasonable efficiency of operation.

Saturday, June 9, 2012

Page 166: Electrical Utilitas

Allowable Voltage Drops in the Conductors

• branch circuit wires for lighting, heating, and similar loads should have a capacity of not less than 125% of the load supplied with over current protection not exceeding the capacity of the conductors or 150% of the rating of the load; it is considered good engineering practice if the capacity of the conductor is not less than 150% of the load supplied.

Note: The sizes of feeder and branch circuit wires are based on the connected load, allowances for future growth, demand factor and diversity factors. The following can be used as reference for this purpose:

• for branch circuits the allowable voltage drop not exceeding 3% at the farthest outlet of power, heating and lighting loads. While for both feeder and branch circuits to the farthest outlet the allowable voltage drop not exceeding 5% to provide reasonable efficiency of operation.

Saturday, June 9, 2012

Page 167: Electrical Utilitas

Allowable Voltage Drops in the Conductors

• for motors, owing to its starting current and occasional overload runs, the sizes shall be computed as follows.

• branch circuit wires for lighting, heating, and similar loads should have a capacity of not less than 125% of the load supplied with over current protection not exceeding the capacity of the conductors or 150% of the rating of the load; it is considered good engineering practice if the capacity of the conductor is not less than 150% of the load supplied.

Note: The sizes of feeder and branch circuit wires are based on the connected load, allowances for future growth, demand factor and diversity factors. The following can be used as reference for this purpose:

• for branch circuits the allowable voltage drop not exceeding 3% at the farthest outlet of power, heating and lighting loads. While for both feeder and branch circuits to the farthest outlet the allowable voltage drop not exceeding 5% to provide reasonable efficiency of operation.

Saturday, June 9, 2012

Page 168: Electrical Utilitas

Saturday, June 9, 2012

Page 169: Electrical Utilitas

Single motor load

Saturday, June 9, 2012

Page 170: Electrical Utilitas

Single motor load Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 171: Electrical Utilitas

Single motor load

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 172: Electrical Utilitas

Single motor load

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 173: Electrical Utilitas

Single motor load

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 174: Electrical Utilitas

Single motor load

• 250 to 300% for smaller motors, less than 7 ½ hp with full-voltage or across-the –line starters.

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 175: Electrical Utilitas

Single motor load

• 150 to 200% for bigger motors with reduce voltage, wye-delta or autotransformer starters.

• 250 to 300% for smaller motors, less than 7 ½ hp with full-voltage or across-the –line starters.

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 176: Electrical Utilitas

Single motor load

Example: A 150 hp, 3-phase 440-Volt squirrel cage induction motor with auto-transformer starter and full load ampere draw of 180 Amp.

• 150 to 200% for bigger motors with reduce voltage, wye-delta or autotransformer starters.

• 250 to 300% for smaller motors, less than 7 ½ hp with full-voltage or across-the –line starters.

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 177: Electrical Utilitas

Single motor load

Size of conductor = 125% of 180 A = 225 A

Example: A 150 hp, 3-phase 440-Volt squirrel cage induction motor with auto-transformer starter and full load ampere draw of 180 Amp.

• 150 to 200% for bigger motors with reduce voltage, wye-delta or autotransformer starters.

• 250 to 300% for smaller motors, less than 7 ½ hp with full-voltage or across-the –line starters.

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 178: Electrical Utilitas

Single motor load

Use: 3 - 125 mm² or 250 MCM THW Cu wire @ 225 Amp capacity in 65 mm ø or 2 ½ inch ø rigid metal conduit (RMC)

Size of conductor = 125% of 180 A = 225 A

Example: A 150 hp, 3-phase 440-Volt squirrel cage induction motor with auto-transformer starter and full load ampere draw of 180 Amp.

• 150 to 200% for bigger motors with reduce voltage, wye-delta or autotransformer starters.

• 250 to 300% for smaller motors, less than 7 ½ hp with full-voltage or across-the –line starters.

Approximately it will be:

Where the multiplier M% value depends on the type or class ofmotor as well as the starter or controller to be used,

Size of circuit breaker protection = M% times motor full-load ampere

Size of conductor = 125% of motor full-load ampere (FLA)

Saturday, June 9, 2012

Page 179: Electrical Utilitas

Saturday, June 9, 2012

Page 180: Electrical Utilitas

Size of circuit breaker = 150% of 180 A = 270 A

Saturday, June 9, 2012

Page 181: Electrical Utilitas

Size of circuit breaker = 150% of 180 A = 270 A Use: 300 AT, 400 AF, 3P, 500V circuit breaker

Saturday, June 9, 2012

Page 182: Electrical Utilitas

Size of circuit breaker = 150% of 180 A = 270 A

From the tables, it shows the approximate sizes of conductors and circuit protection for different sizes of electric motors. Note that the equivalent rating for safety switch is slightly higher than those of the circuit breaker.

Use: 300 AT, 400 AF, 3P, 500V circuit breaker

Saturday, June 9, 2012

Page 183: Electrical Utilitas

Size of circuit breaker = 150% of 180 A = 270 A

Group of motor and other loads

From the tables, it shows the approximate sizes of conductors and circuit protection for different sizes of electric motors. Note that the equivalent rating for safety switch is slightly higher than those of the circuit breaker.

Use: 300 AT, 400 AF, 3P, 500V circuit breaker

Saturday, June 9, 2012

Page 184: Electrical Utilitas

Size of circuit breaker = 150% of 180 A = 270 A

Example : Given a group of motors with their corresponding full-load ampere (FLA) and other loads being supplied by several feeders referring to fig. 5.1, provide the appropriate size of main feeder conductor and rating of circuit breaker for protection. Assume 3- phase, 460-volt, 60 Hz supply.

Group of motor and other loads

From the tables, it shows the approximate sizes of conductors and circuit protection for different sizes of electric motors. Note that the equivalent rating for safety switch is slightly higher than those of the circuit breaker.

Use: 300 AT, 400 AF, 3P, 500V circuit breaker

Saturday, June 9, 2012

Page 185: Electrical Utilitas

Saturday, June 9, 2012

Page 186: Electrical Utilitas

Saturday, June 9, 2012

Page 187: Electrical Utilitas

Saturday, June 9, 2012

Page 188: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

Saturday, June 9, 2012

Page 189: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 190: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 191: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

= 383 Amperes

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 192: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

Use: 3 - 400 mm² or 800 MCM THW Cu wires @ 485 AMP capacity in 100 mm ø or 5 inch ø rigid metal conduit (RMC)

= 383 Amperes

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 193: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

Note: 325 mm² (700 MCM) wire with 425 Amp capacity may be sufficient, but the next bigger wire is chosen to allow for future growth.

Use: 3 - 400 mm² or 800 MCM THW Cu wires @ 485 AMP capacity in 100 mm ø or 5 inch ø rigid metal conduit (RMC)

= 383 Amperes

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 194: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

Voltage drops should also be computed to determine the propriety of the selected size of conductors;

Note: 325 mm² (700 MCM) wire with 425 Amp capacity may be sufficient, but the next bigger wire is chosen to allow for future growth.

Use: 3 - 400 mm² or 800 MCM THW Cu wires @ 485 AMP capacity in 100 mm ø or 5 inch ø rigid metal conduit (RMC)

= 383 Amperes

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 195: Electrical Utilitas

Size of conductor = (125% full-load ampere of highest rated motor plus full load current of other loads) x demand factor

Where computed load exceeds the maximum available wire size, multiple or parallel runs can be used.

Voltage drops should also be computed to determine the propriety of the selected size of conductors;

Note: 325 mm² (700 MCM) wire with 425 Amp capacity may be sufficient, but the next bigger wire is chosen to allow for future growth.

Use: 3 - 400 mm² or 800 MCM THW Cu wires @ 485 AMP capacity in 100 mm ø or 5 inch ø rigid metal conduit (RMC)

= 383 Amperes

= [125% of 180 Amp + 27+14+65+27+27+ (75,000/ 3 x 460)] x 80% (assume an 80% demand factor refer to P.E.C. for the provision this item)

Saturday, June 9, 2012

Page 196: Electrical Utilitas

Saturday, June 9, 2012

Page 197: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus

Saturday, June 9, 2012

Page 198: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

Saturday, June 9, 2012

Page 199: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 200: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

= 443 Amperes= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 201: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

Use: 500 AT, 600 AF, 3P, 500V ACB

= 443 Amperes= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 202: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

The size of feeder conductor should be maintained through-out. It should not be reduced, say at point “x” regardless of the reduced current beyond the said point-of-tap. Such reduction in conductor size may be allowed if appropriately sized breaker is installed to serve as protection for the reduced line. The exception are for runs not exceeding 25 feet and within sight, provided that the reduce line capacity is not less than 1/3 of the main run capacity.

Use: 500 AT, 600 AF, 3P, 500V ACB

= 443 Amperes= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 203: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

6 – LOAD CENTER, PANEL BOARDS or SWITCHGEARS

The size of feeder conductor should be maintained through-out. It should not be reduced, say at point “x” regardless of the reduced current beyond the said point-of-tap. Such reduction in conductor size may be allowed if appropriately sized breaker is installed to serve as protection for the reduced line. The exception are for runs not exceeding 25 feet and within sight, provided that the reduce line capacity is not less than 1/3 of the main run capacity.

Use: 500 AT, 600 AF, 3P, 500V ACB

= 443 Amperes= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 204: Electrical Utilitas

Size of circuit breaker protection = (highest motor breaker rating plus full-load ampere of other loads) x demand factor

Ideally, load centers and panel boards should be located on the center of the loads to be served to save on wire runs and to minimize line voltage drops. However most of the time the designing architect, for aesthetic purposes, has the final decision on the matter.

6 – LOAD CENTER, PANEL BOARDS or SWITCHGEARS

The size of feeder conductor should be maintained through-out. It should not be reduced, say at point “x” regardless of the reduced current beyond the said point-of-tap. Such reduction in conductor size may be allowed if appropriately sized breaker is installed to serve as protection for the reduced line. The exception are for runs not exceeding 25 feet and within sight, provided that the reduce line capacity is not less than 1/3 of the main run capacity.

Use: 500 AT, 600 AF, 3P, 500V ACB

= 443 Amperes= [300A + 27 + 14 + 65 + 27+ 27+ (75,000/ 3 x 460)] x 80%

Saturday, June 9, 2012

Page 205: Electrical Utilitas

Saturday, June 9, 2012

Page 206: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

Saturday, June 9, 2012

Page 207: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 208: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 209: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

A panel board consists of a metal enclosure containing bus bars to which circuit breakers or fused switches are attached. The interior space of the housing provides sufficient physical space for safe installation of the circuit conductors to their respective over current devices (see fig. 6.1).

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 210: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

They are generally classified into two categories:

A panel board consists of a metal enclosure containing bus bars to which circuit breakers or fused switches are attached. The interior space of the housing provides sufficient physical space for safe installation of the circuit conductors to their respective over current devices (see fig. 6.1).

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 211: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

a) Lighting & appliance panels

They are generally classified into two categories:

A panel board consists of a metal enclosure containing bus bars to which circuit breakers or fused switches are attached. The interior space of the housing provides sufficient physical space for safe installation of the circuit conductors to their respective over current devices (see fig. 6.1).

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 212: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

b) Power distribution panelsa) Lighting & appliance panels

They are generally classified into two categories:

A panel board consists of a metal enclosure containing bus bars to which circuit breakers or fused switches are attached. The interior space of the housing provides sufficient physical space for safe installation of the circuit conductors to their respective over current devices (see fig. 6.1).

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 213: Electrical Utilitas

The electrical engineer should, however, strive to locate the panel boards at point where the farthest load to be served is within 30 meters. Otherwise, larger sized wires may be necessary to compensate for the voltage drop.

Panel board mounting of motor starter units may also be involved.b) Power distribution panelsa) Lighting & appliance panels

They are generally classified into two categories:

A panel board consists of a metal enclosure containing bus bars to which circuit breakers or fused switches are attached. The interior space of the housing provides sufficient physical space for safe installation of the circuit conductors to their respective over current devices (see fig. 6.1).

In general panel boards and switchgear are used as control protection points for groups of feeder or branch circuits serving the elctrical loads in building area, usually a floor or a section of the floor.

Panel boards, Switchboards & Switchgears

Saturday, June 9, 2012

Page 214: Electrical Utilitas

Saturday, June 9, 2012

Page 215: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

Saturday, June 9, 2012

Page 216: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2). There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 217: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

Main metal-enclosed switchgear for commercial, industrial, and public buildings is invariably located in the basement, and housed in a separate well-ventilated electrical switchgear rooms.

There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 218: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

Other types of metal-enclosed switchgear are:

Main metal-enclosed switchgear for commercial, industrial, and public buildings is invariably located in the basement, and housed in a separate well-ventilated electrical switchgear rooms.

There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 219: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

a) Metal-clad

Other types of metal-enclosed switchgear are:

Main metal-enclosed switchgear for commercial, industrial, and public buildings is invariably located in the basement, and housed in a separate well-ventilated electrical switchgear rooms.

There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 220: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

b) Compartmented (with one or more non-metallic partitions)a) Metal-clad

Other types of metal-enclosed switchgear are:

Main metal-enclosed switchgear for commercial, industrial, and public buildings is invariably located in the basement, and housed in a separate well-ventilated electrical switchgear rooms.

There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 221: Electrical Utilitas

A switchboard & switchgear, on the other hand are free standing assemblies of switches, fuses and circuit breakers, which serve as locations for larger over current devices, or as main distribution panels for an entire building. Switchboards are physically larger than panel boards, due to the size of the over current devices involved, and are design to provide the necessary space for installation of larger cables (see fig. 6.2).

c) Cubicle (with number of compartments less than that required for metal-clad or compartmented switchgear, usually having partition.

b) Compartmented (with one or more non-metallic partitions)a) Metal-clad

Other types of metal-enclosed switchgear are:

Main metal-enclosed switchgear for commercial, industrial, and public buildings is invariably located in the basement, and housed in a separate well-ventilated electrical switchgear rooms.

There is no clear distinction made between the terms “switchboard” and “switchgear”, although often high-voltage equipment (above 600 Volts) is referred to as switchgear. When molded case circuit breakers are utilized in a switchboard it is often known as building type switchboard.

Saturday, June 9, 2012

Page 222: Electrical Utilitas

Saturday, June 9, 2012

Page 223: Electrical Utilitas

Saturday, June 9, 2012

Page 224: Electrical Utilitas

Saturday, June 9, 2012

Page 225: Electrical Utilitas

Saturday, June 9, 2012

Page 226: Electrical Utilitas

Saturday, June 9, 2012

Page 227: Electrical Utilitas

7 – SUGGESTED STEPS in BUILDING WIRING DESIGN

Saturday, June 9, 2012

Page 228: Electrical Utilitas

7 – SUGGESTED STEPS in BUILDING WIRING DESIGN

Prepare an electrical load estimate based on areas of the building and other pertinent data; for office buildings, the P.E.C. has information on the estimated general illumination load, some other books can furnish data for other loads. An estimated load of 0.1 kilowatt per square meter of habitable area may be used to countercheck the estimated load.

Saturday, June 9, 2012

Page 229: Electrical Utilitas

7 – SUGGESTED STEPS in BUILDING WIRING DESIGN

Prepare an electrical load estimate based on areas of the building and other pertinent data; for office buildings, the P.E.C. has information on the estimated general illumination load, some other books can furnish data for other loads. An estimated load of 0.1 kilowatt per square meter of habitable area may be used to countercheck the estimated load.

Consult the local company as regards the point of service entrance, service voltage, metering equipment and other requirements for power connections; the same should be done for the telephone system.

Saturday, June 9, 2012

Page 230: Electrical Utilitas

7 – SUGGESTED STEPS in BUILDING WIRING DESIGN

Prepare an electrical load estimate based on areas of the building and other pertinent data; for office buildings, the P.E.C. has information on the estimated general illumination load, some other books can furnish data for other loads. An estimated load of 0.1 kilowatt per square meter of habitable area may be used to countercheck the estimated load.

Determine from other designers the exact electrical rating of all equipment, viz. HVAC, plumbing elevators and escalators, kitchen and others; the electrical designer may be asked for comparative characteristics of these equipment as regards the electrical supply.

Consult the local company as regards the point of service entrance, service voltage, metering equipment and other requirements for power connections; the same should be done for the telephone system.

Saturday, June 9, 2012

Page 231: Electrical Utilitas

Saturday, June 9, 2012

Page 232: Electrical Utilitas

Determine the location and estimated sizes of the different electric supply equipment such as load center, switchboards, electrical panel board, rooms or enclosures; this will enable the architect to allocate spaces for these equipment. This estimated space requirements could be checked and adjusted as may be necessary after the completion of the detailed plans.

Saturday, June 9, 2012

Page 233: Electrical Utilitas

Determine the location and estimated sizes of the different electric supply equipment such as load center, switchboards, electrical panel board, rooms or enclosures; this will enable the architect to allocate spaces for these equipment. This estimated space requirements could be checked and adjusted as may be necessary after the completion of the detailed plans.

Design the lighting system, using either the lumens or point-by-point methods, after due consultation with the architect and lighting designer as to the type of luminaires, ceiling and wall finished. For clarity of the plans, the lighting design which is mostly a reflection of the ceiling is separate from those of power layout showing the floor plans. A separate sets of plans may be prepared for auxiliaries, viz. fire alarm, hold-up and burglar, paging and background music, noise masking and the like.

Saturday, June 9, 2012

Page 234: Electrical Utilitas

Determine the location and estimated sizes of the different electric supply equipment such as load center, switchboards, electrical panel board, rooms or enclosures; this will enable the architect to allocate spaces for these equipment. This estimated space requirements could be checked and adjusted as may be necessary after the completion of the detailed plans.

Assign circuitry for all lighting and power system to appropriate panels including emergency lines, and compute panel loads.

Design the lighting system, using either the lumens or point-by-point methods, after due consultation with the architect and lighting designer as to the type of luminaires, ceiling and wall finished. For clarity of the plans, the lighting design which is mostly a reflection of the ceiling is separate from those of power layout showing the floor plans. A separate sets of plans may be prepared for auxiliaries, viz. fire alarm, hold-up and burglar, paging and background music, noise masking and the like.

Saturday, June 9, 2012

Page 235: Electrical Utilitas

Saturday, June 9, 2012

Page 236: Electrical Utilitas

Prepare riser or one line diagram to include main distribution panels, load centers, switchboards or switchgears and other service equipment. Compute feeder, sub-feeder sizes and all protective equipment ratings.

Saturday, June 9, 2012

Page 237: Electrical Utilitas

Check and coordinate with other trades, architectural structural, VAC, mechanical, plumbing, others to minimize conflicts in the work execution.

Prepare riser or one line diagram to include main distribution panels, load centers, switchboards or switchgears and other service equipment. Compute feeder, sub-feeder sizes and all protective equipment ratings.

Saturday, June 9, 2012

Page 238: Electrical Utilitas

Check and coordinate with other trades, architectural structural, VAC, mechanical, plumbing, others to minimize conflicts in the work execution.

Prepare riser or one line diagram to include main distribution panels, load centers, switchboards or switchgears and other service equipment. Compute feeder, sub-feeder sizes and all protective equipment ratings.

(the latter may belong to the project management team or the construction manager)

Saturday, June 9, 2012

Page 239: Electrical Utilitas

Saturday, June 9, 2012

Page 240: Electrical Utilitas

Saturday, June 9, 2012

Page 241: Electrical Utilitas

Saturday, June 9, 2012

Page 242: Electrical Utilitas

Table – 1: Typical Molded Case Circuit Breaker Frame Sizes, Trip

Saturday, June 9, 2012

Page 243: Electrical Utilitas

Table – 1: Typical Molded Case Circuit Breaker Frame Sizes, Trip Settings and Interrupting Rating

Saturday, June 9, 2012

Page 244: Electrical Utilitas

Table – 1: Typical Molded Case Circuit Breaker Frame Sizes, Trip Settings and Interrupting Rating

FRAME SIZE TRIP SETTING50 Amp 15 20 25 30 35 40 45 50100 Amp 15 20 25 30 35 40 45 50

60 70 80 90 100

250 Amp 70 80 90 100 110 125 150 175 200 225

400 Amp and 600 Amp 125 150 175 200 225 250 300 350 400 450 500 600

800 Amp and 1200 Amp 250 300 350 400 450 500 600 700 800 1000 1200

1600 Amp 400 450 500 600 700 800 1000 1200 1600

3000 Amp 2000 2500 30004000 Amp 40005000 Amp 50006000 Amp 6000

Saturday, June 9, 2012

Page 245: Electrical Utilitas

Saturday, June 9, 2012

Page 246: Electrical Utilitas

Typical Interrupting Rating (r.m.s. symmetrical Amperes)

Saturday, June 9, 2012

Page 247: Electrical Utilitas

Typical Interrupting Rating (r.m.s. symmetrical Amperes)

240 Volts 480 Volts10 kA18 kA22 kA

42 kA65 kA100 kA200 kA

14 kA

25 kA30 kA35 kA50 kA65 kA

150 kA

Saturday, June 9, 2012

Page 248: Electrical Utilitas

Saturday, June 9, 2012

Page 249: Electrical Utilitas

Standard Ampere Ratings for Low Voltage Fuses

Saturday, June 9, 2012

Page 250: Electrical Utilitas

Standard Ampere Ratings for Low Voltage Fuses

0 – 600 Amp 15 40 80 150 300 20 45 90 175 350 25 50 100 200 400 30 60 110 225 500 35 70 125 250 600

0 – 600 Amp 601 1200 2000 4500 650 1350 2500 5000 700 1500 3000 6000 800 1600 3500 1000 1800 4000

Saturday, June 9, 2012

Page 251: Electrical Utilitas

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012

Page 252: Electrical Utilitas

R e f e r e n c e s :

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012

Page 253: Electrical Utilitas

• Distribution Switchgear (Construction, Performance, Selection & Installation) By : R. W. Blower

R e f e r e n c e s :

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012

Page 254: Electrical Utilitas

• Distribution Switchgear (Construction, Performance, Selection & Installation) By : R. W. Blower

• Electrical Wiring Commercial – based from NEC (6th ed) By : R.L. Smith & S.L. Herman

R e f e r e n c e s :

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012

Page 255: Electrical Utilitas

• Distribution Switchgear (Construction, Performance, Selection & Installation) By : R. W. Blower

• Design & Analysis of Building Electrical Systems By : J.H. Mathews

• Electrical Wiring Commercial – based from NEC (6th ed) By : R.L. Smith & S.L. Herman

R e f e r e n c e s :

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012

Page 256: Electrical Utilitas

• Distribution Switchgear (Construction, Performance, Selection & Installation) By : R. W. Blower

• Philippine Electrical Code (part I & II) By : Institute of Integrated Electrical Engrs. Of the Phils. Inc.

• Design & Analysis of Building Electrical Systems By : J.H. Mathews

• Electrical Wiring Commercial – based from NEC (6th ed) By : R.L. Smith & S.L. Herman

R e f e r e n c e s :

Prepared by:ROMEO QUISTO, PEE#3004

Saturday, June 9, 2012