electrical-engineering-portal.com http://electrical-engineering-portal.com/hvmvlv-transformer-protection-schemes? utm_source=Technical+Articles&utm_campaign=9006167881- RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-9006167881- 319127325&mc_cid=9006167881&mc_eid=62e44fb4ff Google+ HV/MV/LV Transformer Protection Schemes HV/MV/LV Transformer Protection Schemes Transformer protection // Transformer protection should take into account the power, voltage, vector group and the importance of the unit within a particular system. Depending on these factors, the transformers can be assigned to one of the two groups: MV/LV transformers HV/MV/LV transformers and autotransformers MV/LV transformers The protection of these units should include overcurrent protection for both the MV and LV windings, plus devices such as overpressure protection (e.g. Buchholz surge), and thermal protection, as indicated in Figure 1 below. Typical ratios for inter- busbar MV/LV transformers at substations are 33/11, 34.5/13.2 and 13.2/4.16 kV.

description

electrical mvmvlv transformer protection

Transcript of Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

Page 1: Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

electrical-engineering-portal.comhttp://electrical-engineering-portal.com/hvmvlv-transformer-protection-schemes?utm_source=Technical+Articles&utm_campaign=9006167881-RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-9006167881-319127325&mc_cid=9006167881&mc_eid=62e44fb4ff

Google+

HV/MV/LV Transformer Protection Schemes

HV/MV/LV Transformer Protection Schemes

Transformer protection //

Transformer protection should take into account the power, voltage, vector group and the importance of the unitwithin a particular system. Depending on these factors, the transformers can be assigned to one of the two groups:

MV/LV transformers

HV/MV/LV transformers and autotransformers

MV/LV transformers

The protection of these units should include overcurrent protection for both the MV and LV windings, plus devices suchas overpressure protection (e.g. Buchholz surge), and thermal protection, as indicated in Figure 1 below. Typical ratiosfor inter- busbar MV/LV transformers at substations are 33/11, 34.5/13.2 and 13.2/4.16 kV.

Page 2: Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

Figure 1 – Protection scheme for MV/LV transformer

Go back to Transformer Groups ↑

Page 3: Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

HV/MV/LV transformers and autotransformers

In addition to the protection listed for the MV/LV transformers, the protection for transformers in this group shouldinclude overall differential protection, which is essential because of its reliability and high speed of operation. In thiscase, shown in Figure 2, since the transformer has three windings, a three terminal type of differential protection isrequired.

The diagram also includes the differential busbar protection, which is usually installed on large transformers connectedto HV busbars. As the transformer has an LV winding, overcurrent protection for this winding has been included aswell.

Typical ratios for HV/MV transformers are: 132/33, 145/ 11, 132/11, 115/34.5 and 115/13.2 kV.

Page 4: Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

Figure 3 – Protection schematic for an HV/MV/LV transformer

It is common to use autotransformers where large powers are involved and the voltage ratio is around 2:1. Typicalratios for autotransformers are 275/132 kV and 230/115 kV.

The protection schemes for autotransformers are very similar to those for HV/MV/LV transformers sinceautotransformers can be treated as three winding units for protection purposes.

Page 5: Electrical Engineering Portal.com HVMVLV Transformer Protection Schemes

The protection for this type of transformer is essentially the same as that quoted in the previous paragraph, taking intoaccount the modifications to the overcurrent relay connections (see Figure 2).

Go back to Transformer Groups ↑

Reference // Protection of Electricity Distribution Networks – Juan M. Gers and Edward J. Holmes