Electrical Circuit Protection
-
Upload
saman-sri-ananda-rajapaksa -
Category
Documents
-
view
244 -
download
5
Transcript of Electrical Circuit Protection
-
7/28/2019 Electrical Circuit Protection
1/59
Electrical Circuit Protection
By
Saman Rajapakse Assistant Manager-Technical Training
Rotax Ltd
-
7/28/2019 Electrical Circuit Protection
2/59
Electrical circuit protection
Circuit Breakers
Over Current andShort Circuit
Protection
Earth FaultProtection
Miniature Circuit
Breakers (MCB)
Air circuit breaker
(ACB)
RESIDUAL CURRENTCIRCUIT
BREAKER(RCCB)
Earth Fault Relay
(EFR )
Molded case circuitbreaker (MCCB)
Earth leakage relayELR
Surge protectiondevices
-
7/28/2019 Electrical Circuit Protection
3/59
Protection Types ( )
Over Current( )
Short Circuit ( )
Earth Leakage( )
-
7/28/2019 Electrical Circuit Protection
4/59
Circuit protection devices
A circuit protection device has three maincomponents ( )
Sensing to sense the line current, leakage currentetc( )
Measure - to measure the current and decideweather the same is above/below the set point( /
)
Action - to trip the circuit if the current is abovethe set point
( )
-
7/28/2019 Electrical Circuit Protection
5/59
Over Current and Short Circuit
Miniature Circuit Breaker (MCB)( )
Molded Case Circuit Breaker (MCCB)( )
Air Circuit Breaker (ACB)( )
-
7/28/2019 Electrical Circuit Protection
6/59
Earth Leakage
Residual Current Circuit Breaker (RCCB) ( )
Earth Leakage Relay( )
Earth Fault Relay( )
-
7/28/2019 Electrical Circuit Protection
7/59
Miniature Circuit Breakers (MCBs)
Comply with IEC 60947-2 or IEC 60898
Fixed Thermal / Magnetic Releases ( , /
)
Rated Current up to 125 Amps ( 125 )
Breaking Capacity ( ) up to 10 kA (IEC 60898) or 15 kA (IEC 60947-2)
Up to 4 Pole ( ) Versions
Tripping Characteristic Curves ( ) - B/C/D
Specifications
-
7/28/2019 Electrical Circuit Protection
8/59
Miniature circuit breakers (continued )
Specifications . . .IEC 60947-2
Low voltage switch gear and control gear circuitbreakers
IEC 60898
Circuit breakers for over current protection for household and similar installations
-
7/28/2019 Electrical Circuit Protection
9/59
Miniature circuit breakers (continued)
Specifications
Thermal over load ( )
Bi metal construction ( )
Inverse time characteristics ( )
Magnetic short circuit ( )
Main circuit current excites the coil of an electromagnet ( )
-
7/28/2019 Electrical Circuit Protection
10/59
Miniature circuit breakers(continued)
Specifications .
Preferred current ratings ( )
6, 10, 16, 20, 25, 32, 40, 50, 63,80, 100, 125 amperes
Some mcb current rating can be identified by its togglecolour (
)
Eg; F&G AUSTRIA6(green),10(red),25(yellow),40(black),63(orange)
-
7/28/2019 Electrical Circuit Protection
11/59
Miniature circuit breakers(continued)
Specifications .
Breaking capasity ( )to 10ka as per IEC60898
Suitable for domestic and medium size commercial applications( / )
Breaking capasity above 10 ka as per IEC 60947-2
Suitable for large commercial applications ( )
-
7/28/2019 Electrical Circuit Protection
12/59
Miniature circuit breaker
Magnetic short circuit release
Bi metallic thermalrelease
Arcchute
toggle
contacts
-
7/28/2019 Electrical Circuit Protection
13/59
Miniature circuit breakers (continued)
Specifications .
No; of poles (e.g; single, two, three, three pole +N, four)
when No; of poles increases toggles are interconnected by abridging bar ( )
Three pole +N version no over load/short circuit protection for
neutral ( )
Four pole version overload/short circuit protection for threephases +neutral ( )
-
7/28/2019 Electrical Circuit Protection
14/59
Miniature circuit breakers
1 pole 1p& n2 pole
3 pole
3p & n4 pole
-
7/28/2019 Electrical Circuit Protection
15/59
Miniature circuit breakers (continued)
Specifications . Tripping characteristics
Type B 3-5 times rated current and suitable for lighting loads( )
Type C 5-10 times rated current and suitable for motor loads( )
Type D 10-20 times rated current and suitable for x-ray units,welding plants ( / )
-
7/28/2019 Electrical Circuit Protection
16/59
Miniature circuit breakers
B curve
C curve
D curve
Thermalregion
Magneticregion
-
7/28/2019 Electrical Circuit Protection
17/59
MINIATURE CIRCUIT BREAKER
MAKE & MODEL
THERMAL CURVETYPE C
BREAKINGCAPASITYIN AMPS
RATEDCURRENT IN
AMPS
RATEDVOLTAGE
RELEVENTSTANDARD
-
7/28/2019 Electrical Circuit Protection
18/59
Molded case circuit breakers Breaking Capacity up to 100 Ka
Utilization category ( )type A or type B
Front/rear connections ( /
Isolation marking
( )-
-
7/28/2019 Electrical Circuit Protection
19/59
Molded case circuit breaker
Thermal Release sense the over load condition ( )
Magnetic release sense the short circuit condition (
)
Rated Current up to 2500 Amps
Breaking Capacity up to 100 kA
Rated insulation voltage ( ) (U i) 690 v ac
Rated impulse withstand voltage ( )(Uimp) 8000 volts
-
7/28/2019 Electrical Circuit Protection
20/59
Molded case circuit breakers (continued)
Specifications Thermal/magnetic releasesFixed thermal/magnetic
Adjustable thermal(.63-1 times of ratedcurrent)/fixed magnetic
Fixed thermal/ adjustable magnetic(6-12 times of rated current)
Adjustable thermal/magnetic
0.63
0.8
1.0
-
7/28/2019 Electrical Circuit Protection
21/59
Molded case circuit breaker
Thermalregion
Magneticregion
Thermaladjustment(.63-1 of In)
Magnetic adjustment
(5-10 times of In)
-
7/28/2019 Electrical Circuit Protection
22/59
Molded case circuit breaker (continued)
Specifications Rated current expressed as frame size/thermalrelease current
Frame size ratings ( AF )100,125,160,250,400,630,800,1250,1600,2000amperes
Thermal release current ratings ( AT )10,15,20,30,40,50,60,75,100,125,160,250,400,630,800,1000,1250,1600,2000 amps
-
7/28/2019 Electrical Circuit Protection
23/59
Molded case circuit breaker (continued )
Specifications Breaking capacity expressed as two values
Rated ultimate short circuit breaking capacity(I cu ) up to 100 Ka at 400 volts ac
Rated service short circuit breaking capacity
(I cs ) up to 75 kA at 400 volts ac
Ics =% of Icu (eg; 25,50,75,100 %)
-
7/28/2019 Electrical Circuit Protection
24/59
Molded case circuit breakers(continued)
Specifications Utilization category type A designed for current discriminationonly
Utilization category type B ,designed for current and timediscrimination
Short time withstand current ( Icw) available for only type B mccb
-
7/28/2019 Electrical Circuit Protection
25/59
Molded case circuit breakers (continued)
Specifications . Type of connections
Front connected (most popular type)
Rear connected (for bus bars)
Plug in ( special applications)
-
7/28/2019 Electrical Circuit Protection
26/59
Molded case circuit breakers (continued)
Specifications Externally mounted accessories
Handles panel /breaker mounted
Motor operator
Mechanical interlocks
Extended bars for terminals
Inter pole barriers
-
7/28/2019 Electrical Circuit Protection
27/59
Molded case circuit breaker (continued)
Motor operator
Thermal o / l and s/crelease
Extended bars
-
7/28/2019 Electrical Circuit Protection
28/59
Molded case circuit breakers (continued)
Specifications .
Internally mounted accessories
Shunt trip coil
Under voltage trip coil
Auxiliary switches
Alarm switch
-
7/28/2019 Electrical Circuit Protection
29/59
MOLDED CASE CIRCUIT BREAKERS (INTERNALLYMOUNTED ACCESSORIES)
-
7/28/2019 Electrical Circuit Protection
30/59
-
7/28/2019 Electrical Circuit Protection
31/59
-
7/28/2019 Electrical Circuit Protection
32/59
-
7/28/2019 Electrical Circuit Protection
33/59
Air circuit breakers (continued)
Specifications , Rated current -800,1250,1600,2000,2500,3200,4000,5000,6300 amps
Over current release (OCR) for general feeder protection andgenerator protection
Rated current of OCR 200,400,800,1250,1600,2000,2500,3200amps
-
7/28/2019 Electrical Circuit Protection
34/59
Position switchterminal
Close/openCounter
ON OFF indicator
Over current release (OCR)
OFF button
Breaker Fixingbolt
Key-lock location
Draw-out position padlock
Control circuit terminal
Auxiliary switch terminal
Draw-out chassis
Spring charge indicator
Spring charging handle
Close
button
Draw-out handleinsertion hole
Draw-out positionindicator
Air circuit breaker
-
7/28/2019 Electrical Circuit Protection
35/59
Main circuit terminal
Draw-out maincontactFixed contact
Moving contact
Measurement CT
Power CT
Draw-out arm
Control circuitterminal
Charging motor
Closing coil
Closing spring
Arc chamber
Operating mechanism
Mold cover
air circuit breaker (internal structure)
-
7/28/2019 Electrical Circuit Protection
36/59
Air circuit breakers (continued )
Specifications .
Breaking capasity I cu up to 220 kA at 440 volts ac
Breaking capasity I cs up to 100 kA at 440 volts ac
-
7/28/2019 Electrical Circuit Protection
37/59
Horizontalterminal
Verticalterminals
Front connection
Air circuit breaker
(Main circuit terminals)
Rear connection
Up to 1600 amps asstandard
2000 amp and above asstandard
Specify when ordering
-
7/28/2019 Electrical Circuit Protection
38/59
Air circuit breakers (continued)
Specfications . Mounting type fixed or draw out
Fixed no maintenance possible
Draw out maintenance and inspection/replacement of contacts possible
Terminals -vertical (standard version) or horizontalor front connected
-
7/28/2019 Electrical Circuit Protection
39/59
Air circuit breakers (continued )
Specifications Spring charging operation manual or motor operator
Charging the closing spring
Closing the ACB
Opening the ACB
Mechanical interlocks
-
7/28/2019 Electrical Circuit Protection
40/59
Air circuit breaker (Mechanical
Interlock)Horizontal type Vertical typeStainless steel wire
Rod
-
7/28/2019 Electrical Circuit Protection
41/59
Residual Current Circuit Breakers (RCCBs)
Rated Current up to 100 Amps
Sensitivity 30/100/300 mA
Application Types A , AC and B
Tripping Delay Type S and G
Comply with IEC 61008 standard
Specifications
-
7/28/2019 Electrical Circuit Protection
42/59
Residual current circuit breakers (continued)
Specifications . Two types of technologies
Voltage dependent- electronic type-supply voltage dependent
Voltage independent- electro mechanical type- supply voltageindependent
-
7/28/2019 Electrical Circuit Protection
43/59
Residual current circuit breakers (continued)
VOLTAGE DEPENDENT RCCB VOLTAGE INDEPENDENT RCCB
ELECTRONICAMPLIFIER
POWER SUPPLY TOELECTRONICS
CORE BALANCE TRANSFORMER
-
7/28/2019 Electrical Circuit Protection
44/59
Residual current circuit breakers (continued)
Specifications .. Rated tripping (residual) current -10,30,100,300,500 Ma
Personal shock protection max; value
30mA
Fire protection max; value 300 mA
-
7/28/2019 Electrical Circuit Protection
45/59
Residual current circuit breakers (continued)
Specifications Type of residual current (sensitivity)
Type AC full wave ac residual current detection
Type A -full wave ac +pulsating dc residual currents
Type B -full wave ac +pulsating dc +pure dc residualcurrents
-
7/28/2019 Electrical Circuit Protection
46/59
Residual current circuit breakers (continued)
Specifications
Type of applications
Type AC - for domestic /commercial use
Type A - for computer network use
Type B - for variable speed drive circuit use
-
7/28/2019 Electrical Circuit Protection
47/59
Residual current circuit breakers (continued)
Specifications
Operating time category for rated residual current
Type G (instantaneous) - max; response time = 300Ms
Type) S (delayed)- min/max; response time= 130-500 mS
-
7/28/2019 Electrical Circuit Protection
48/59
Earth Leakage Relay
Sensitivity up to 30 Amps
Trip Time Delay up to 3 Secs
Zero Current Transformer Sensing
Specifications
-
7/28/2019 Electrical Circuit Protection
49/59
3-pole or 4-pole
Earth leakage relay (continued )
Zero currenttransformer
Earthleakage
relay
-
7/28/2019 Electrical Circuit Protection
50/59
Earth leakage relays (continued)
Specifications Sensitivity setting -30-750 mA,1- 30 amps
Time delay setting-inst; 50-500ms,1-3s leakage indicaters-10%-80%
Trip contact and 50% pre fault contact
Zero CT 40-120 mm inner dia; selectable
-
7/28/2019 Electrical Circuit Protection
51/59
Earth Fault Relay
Microprocessor based type
Low /high set earth fault setting
Adjustable Trip Time Delay for low/high setting
Sensing Using Current Transformers
C;T; Secondary current 5 amps
04 no current transformers required for a 3p & n system
Specifications
-
7/28/2019 Electrical Circuit Protection
52/59
Earth fault relay
-
7/28/2019 Electrical Circuit Protection
53/59
Surge protection devices
Different types of voltage surges
voltage Surges due to Direct lightning hits
Protected by lightning arresters/ finials
voltage surges due to Indirect lightning hits and switching
Protected by surge protection devices
-
7/28/2019 Electrical Circuit Protection
54/59
Surge protection devices
Surge protection devices
Two different technologies
Metal oxide varisters shows low resistance to high voltages
Gas discharge tube - discharges the high voltages to earththrough an air gap inside a glass envelope
-
7/28/2019 Electrical Circuit Protection
55/59
Surge protection devices
Metal oxide varisters
Type 1 (type B) -for out door use eg; over head distribution lines
Type 2 ( type B ) for incomer main distribution switchgear
Type 3 (type C) -for the protection of electrical appliances eg;
Type 4 (type D) for the protection of delicate electronicequipment
-
7/28/2019 Electrical Circuit Protection
56/59
surge protection levels
-
7/28/2019 Electrical Circuit Protection
57/59
-
7/28/2019 Electrical Circuit Protection
58/59
Thank You
-