Patrick E. Montero, SRS IIPhilippine Council for Industry, Energy, and Emerging Technology Research and Development (PCIEERD)Department of Science and Technology (DOST
![Page 2: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/2.jpg)
Outline
• Objectives and scope of the topic
• Definition of terms
• Guiding principles
• Methods of measurement
• Energy saving opportunities
![Page 3: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/3.jpg)
Objectives
• To determine the efficiency of electric motors by loss estimation method under operating conditions in the plant where the motor is installed and running or available as spare.
• To simplify instrumentation so that the test can be conducted with portable instruments and facilities available with plant engineers and energy auditors.
• To identify energy saving opportunities in electric motors.
![Page 4: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/4.jpg)
Scope
• The topic deals with the commonly used electric motor in the industry which is the induction motor. These motors and driven equipments account for more than 90% of energy consumption in the industrial motor driven systems.
• The methods that will be presented in this topic can be also used for efficiency testing of squirrel cage and slip ring induction motors.
![Page 5: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/5.jpg)
Definition of TermsSymbol Description Units
E Energy kWh
P Power Watts (W) or kilowatts (kW)
t Time duration Seconds
T Temperature °C
Pfe Core losses W
Pfw Friction and windage losses W
Pk Constant losses W
Pcu-st Stator copper loss W
Pcu-rot Rotor copper loss W
PS Stray losses W
PT Total losses W
Pmech Mechanical power W
V Terminal voltage V
I Current I
Cos θ Power factor Per unit
f Frequency Hertz (Hz)
p Number of poles - -
N Speed RPM
Ns Synchronous speed RPM
s slip Per unit
R Average D.C. resistance Ω
η Efficiency %
![Page 6: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/6.jpg)
What is an electric motor?
• A machine that converts electricity to mechanical work.
![Page 7: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/7.jpg)
Electric Motor Principle
DC Motor Schematic Diagram
AC Motor Schematic Diagram
![Page 8: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/8.jpg)
Types of Electric Motors
• AC Electric Motors
Asynchronous Synchronous
Inductance
BrushlessHysteresisSine Wave Reluctance Stepper
PM Wound Field
PM Wound Field
PM Hybrid Var. Reluc.
![Page 9: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/9.jpg)
Types of Electric Motors
• DC Electric Motors
Homopolar Commutator
Permanent Magnet Wound Field
Compound Shunt Series
Universal
![Page 10: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/10.jpg)
Electric Motor Parts
Shaft Slinger
Rotor
Frame
Rotor Laminations
Shaft
Wound StatorInsulation
Fan
Bearing
Conduit Box
Nameplate
![Page 11: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/11.jpg)
Facts About Electric Motors
Most electric motors are designed to run at 50% to 100% of rated load. Maximum efficiency is usually near 75% of rated load.
A motor’s efficiency tends to decrease dramatically below about 50% load.
![Page 12: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/12.jpg)
Facts About Electric Motors
Motor Part-Load Efficiency (as a Function of % Full-Load Efficiency)
Source: U.S. Department of Energy
![Page 13: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/13.jpg)
Facts About Electric Motors
Motor Power Factor (as a Function of % Full-Load Amperage)
Source: U.S. Department of Energy
![Page 14: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/14.jpg)
Guiding Principles
![Page 15: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/15.jpg)
Planning the Audit• METHOD – 1
– When a motor is not coupled mechanically to any load, but available as spare/newly purchased. In this case, motor efficiency at full load can be estimated.
– Motor nameplate rating of full load speed and full load output are assumed to be correct.
– Measurements are done on the motor at no load conditions.
![Page 16: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/16.jpg)
Planning the Audit
• METHOD - 2
– When a motor is installed and coupled to driven equipment, say a pump, compressor etc.
– In addition to the measurements at no load, measurements are also required to be done at the actual operation of the motor on load.
– In this method, actual speed and power input is measured at load condition and output is estimated from power input and measured losses.
![Page 17: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/17.jpg)
Pre-Audit Requirements
1. Conditions when it is not recommended to conduct the audit:
a) If the voltage is fluctuating by more than 5%
b) If the difference among phase voltages is more than 15V.
c) Frequency is below 48.5 hertz or fluctuating.
2. Ensure that the motors to be tested are in working condition
![Page 18: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/18.jpg)
Pre-Audit Requirements
3. Nameplate information of the motor is required for the tests. Ensure that the nameplate information is clearly visible.
![Page 19: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/19.jpg)
Pre-Audit Requirements
4. Any Variable Frequency drive, voltage controller or soft starter installed at the motor need to be disconnected from the line during measurements.
5. While conducting no load test, ensure that the motor is completely decoupled from the load.
6. If the motor has been in operation prior to no load test, stop the motor, decouple the load and keep the motor idle condition till the motor cools to ambient temperature.
![Page 20: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/20.jpg)
Methods of Measurement
• The measurement of following parameters is required for efficiency testing of motor:
1. Power Input (Pi)2. Current (I)3. Voltage (V)4. Frequency (f)5. Speed (N)6. Stator Resistance (Ω)7. Ambient Temperature (°C)
![Page 21: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/21.jpg)
Methods of Measurement
• Power Input (Pi) can be measured by using a calibrated energy meter or power analyzer.
![Page 22: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/22.jpg)
Methods of MeasurementPower input (Pi) for NO LOAD TEST using two (2) wattmeter method
3-Φ Motor
W1
W2
Contactor
A
B
C
Total Power = W1 + W2
![Page 23: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/23.jpg)
Methods of Measurement
• No Load Test Equivalent Circuit
3-Φ Motor
IC
VBC
IA
VAB
W1
W2
Contactor
A
B
C
Total Power = W1 + W2
![Page 24: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/24.jpg)
Methods of Measurement
• Voltage (V) can be measured on all the three (3) phases by using a voltmeter or power analyzer.
Vph = VL
FOR DELTA CONNECTION: FOR WYE CONNECTION:
Vph = VL/√3
![Page 25: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/25.jpg)
Methods of Measurement
Example:An existing motor is identified as a 40-hp, 1800 rpm unit with an open drip-proof enclosure. The motor is 12-years old and has not been rewound.
The following measurements was obtained:
Vab = 467 V
Vbc = 473 V
Vca = 469 V
Ia = 36 A
Ib = 38 A
Ic = 37 A
PFa = 0.75 A
PFb = 0.78 A
PFc = 0.76 A
Determine the Power input.
![Page 26: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/26.jpg)
Methods of Measurement
Example (Continuation):
Solution:V = (467+473+469)/3 = 469.7 V
I = (36+38+37)/3 = 37 A
PF = (0.75+0.78+0.76)/3 = 0.763
Pi = 469.7 x 37 x 0.763 x √3 / 1000
Pi = 22.9 kW
![Page 27: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/27.jpg)
Methods of Measurement
• Current (I) can be measured on all the three (3) phases by using a clamp-on ammeter or power analyzer.
FOR DELTA CONNECTION: FOR WYE CONNECTION:
Iph = ILIph = IL/√3
![Page 28: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/28.jpg)
Methods of Measurement
• Speed (N) - slip is measured from synchronous speed (Ns) and Operating Speed (NL) as given below:
SL = Ns - NL
Ns
Ns = 120 x f
p
SLIP CALCULATION SYNCHRONOUS SPEED
SFL = Ns - NFL
Ns
![Page 29: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/29.jpg)
Methods of Measurement
• Speed can be measured by using a contact or non-contact tachometer.
Non – Contact Type
Contact Type
![Page 30: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/30.jpg)
Methods of Measurement
• Resistance TestA1
B1 C1
A1 B1 C1
A2 B2 C2
WYE Connected Winding Connection at Motor Terminal Box
Rph = 0.5 x Rave
Where Rave is the average value of line-to-line resistance to phase resistance obtained.
![Page 31: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/31.jpg)
Methods of Measurement
• Resistance Test
A1 B1 C1
B2 C2 A2
A1 B2
A2
C1 C2
B1
DELTA Connected Winding Connection at Motor Terminal Box
Rph = 1.5 x Rave
Where Rave is the average value of line-to-line resistance to phase resistance obtained is designated as Rave
![Page 32: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/32.jpg)
Methods of Measurement
• The resistance measured should be corrected to the operating/full load temperature by using the following relationship.
R2 =235 + T2
R1 235 + T1
R2 = unknown resistance at temperature T2
R1 = resistance measured at temperature T1
![Page 33: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/33.jpg)
Methods of Measurement
• Temperature for Insulation Classes - IEC
Thermal class of insulation
Reference temperature °C
A 75
B 95
F 115
H 130
*Ambient Temp reference is 25°C
![Page 34: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/34.jpg)
Methods of Measurement
• Ambient Air Temperature can be measured by using either mercury in glass thermometer, infrared thermometer or thermocouple with digital indicator
![Page 35: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/35.jpg)
Power Losses
Rotor
Frame
Wound Stator
Fan
Bearing
Core loss ( Pfe)
Windage loss (Pfw)
Friction loss (Pfw)
Stator loss (Pcu-s)
Copper loss (Pcu-rot)
Stray loss (Ps)
![Page 36: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/36.jpg)
Methods of Measurement
• Estimation of friction and windage losses by Variable Voltage Testing
Sample Plot of Power vs. voltage2 & voltage
Source: Bureau of Energy Efficiency, India
![Page 37: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/37.jpg)
Methods of Measurement
If Variable Voltage Testing is not possible, assuming friction & windage losses according to IEC standards is also reasonably correct.
For Drip proof motors ≈ 0.8% to 1.0% of motor rated output
For TEFC motors, friction & windage losses ≈ 1 to 1.5% of motor rated ouput
![Page 38: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/38.jpg)
Methods of Measurement
• Core losses estimation can be done by subtracting the friction & windage losses from constant losses times the square of rated voltage over the square of measured voltage as shown in the equation.
Pfe = Pk – Pfw xVrated
Vmeasured
2
![Page 39: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/39.jpg)
Methods of Measurement
• Stray loss estimation - IEC
![Page 40: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/40.jpg)
Methods of Measurement
• Stray loss estimation– Stray losses are very difficult to measure with any
accuracy under field conditions or even in a laboratory.
MOTOR RATING VS. STRAY LOSSES - IEEE
Motor Rating Stray Losses 1 – 125 HP 1.8 % of rated output125 – 500 HP 1.5 % 501 – 2499 HP 1.2 % 2500 and above 0.9 % Assumed values for Stray losses – IEEE Std 112 -1996
![Page 41: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/41.jpg)
METHOD 1 - Full Load Test
1. If the motor has been in operation prior to this test, stop the motor, decouple the load from the motor and keep the motor idle till it cools down to ambient temperature. Usually it takes about 2 hours.
η = Rated Motor Output
Rated Motor Output + Losses
![Page 42: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/42.jpg)
METHOD 1 - Full Load Test
2. Measure winding resistance (Rph) at cold conditions. Record the ambient temperature (Ta)
3. Apply voltage across the motor at no load and start the motor
4. Measure line voltage (Vnl), line current (Inl), and frequency (Hz). Otherwise, use the Direct power input (Pi) measurement if power meter is available.
![Page 43: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/43.jpg)
METHOD 1 - Full Load Test
5. Calculate the phase current (Iph)
6. Calculate stator copper loss at no load and subtract this from no load power to get constant losses as shown below.
No load stator Copper loss; Pcu-st = 3 x Iph-nl2 x Rph-nl
Constant loss; Pk = Pin – Pcu-st
![Page 44: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/44.jpg)
METHOD 1 - Full Load Test
7. Estimate friction & windage losses (Pfw) by using the IEC standards.
8. Estimate Core losses
Pfe = Pk – Pfw xVrated
Vmeasured
![Page 45: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/45.jpg)
METHOD 1 - Full Load Test
9. Calculate stator winding resistance at full load (i.e. temperature as defined in the class of insulation of IEC)
RT = Rph-a x(235 + TR)
(235 + Ta)
![Page 46: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/46.jpg)
METHOD 1 - Full Load Test
10.Estimate Stator copper losses at full load, assuming nameplate full load current and corrected stator resistance at full load.
Pcu-st-FL = 3 x Iph-FL2 x RT
![Page 47: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/47.jpg)
METHOD 1 - Full Load Test
11. Obtain stray losses as a % of input power from the IEC – data
![Page 48: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/48.jpg)
METHOD 1 - Full Load Test
12.Calculate full load slip (SFL) from the rated speed (NFL) and synchronous speed (NS) at the rated frequency
SFL = NS – NFL
NS
![Page 49: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/49.jpg)
METHOD 1 - Full Load Test
13. Calculate rotor input power from rotor output at full load
Power input to rotor, Pirot = Rotor output
(1 – SFL)
Note: Rotor output at full load is the nameplate output kW rating of the motor
![Page 50: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/50.jpg)
METHOD 1 - Full Load Test
14. Calculate rotor copper losses from full load slip and rotor input
Rotor copper loss, Pcu-rot = SFL x Pirot
15.Total losses at full load is sum of all the above losses
PT = Pfw + Pfe + Pcu-st-FL +Ps + Pcu-rot
![Page 51: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/51.jpg)
METHOD 1 - Full Load Test
16. Efficiency (η) at Full load is obtained from rated output and estimated total losses as:
η = Rated Motor Output
Rated Motor Output + Losses
![Page 52: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/52.jpg)
METHOD 2 - Operating Load Test
1. If the motor has been in operation prior to this test for more than one hour, it can be considered to be close to steady operating conditions. In this case, while testing, operation of the motor for 10 to 15 minutes is sufficient to attain steady operation
η = Motor input power - Losses
Motor input power
![Page 53: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/53.jpg)
METHOD 2 - Operating Load Test
2. If the motor and load were idle before the test, continuous operation of motor on load for at least 2 hours is recommended to attain steady state conditions.
3. Start the motor with load and bring it up to desired steady operating conditions.
![Page 54: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/54.jpg)
METHOD 2 - Operating Load Test
4. Measure line voltage (VL), line current (IL), and frequency (Hz). Otherwise, use the Direct power input (PiL) measurement if power meter is available.
5. Measure operating speed of motor, NL
6. Switch off the motor. Disconnect power supply. Measure DC resistance of the stator (Rph-L) winding immediately after switching off the motor.
![Page 55: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/55.jpg)
METHOD 2 - Operating Load Test
7. Decouple motor from the load and allow the motor to cool for at least 2 hours.
8. Repeat Steps 2 to 6 from Method 1 for no load calculation
![Page 56: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/56.jpg)
METHOD 2 - Operating Load Test
9. Calculate Stator copper losses at operating load,
10. Calculate Stray losses11. Calculate rotor input power
Pirot = PiL - Pcu-st-L – Pk – Ps-L
Pcu-st-L = 3 x Iph-L2 x Rph-L
![Page 57: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/57.jpg)
METHOD 2 - Operating Load Test
12. Calculate the slip (SL) from the operating speed (NL) and synchronous speed (NS) at the measured frequency
SL = NS – NL
NS
![Page 58: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/58.jpg)
METHOD 2 - Operating Load Test
13. Calculate rotor copper losses from slip and rotor input
Rotor copper loss, Pcu-rot = SL x Pirot
![Page 59: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/59.jpg)
METHOD 2 - Operating Load Test
14. Total losses at actual load is sum of all the above losses
PT = Pk + Pcu-st-L + Ps + Pcu-rot
![Page 60: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/60.jpg)
METHOD 2 - Operating Load Test
15. Efficiency is estimated from estimated output and measured input
η = PiL - PT
PiL
![Page 61: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/61.jpg)
Slip Method
![Page 62: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/62.jpg)
Slip Method
• The slip method for estimating motor load is recommended when only operating speed measurements are available. The synchronous speed of an induction motor depends on the frequency of the power supply and on the number of poles for which the motor is wound.
![Page 63: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/63.jpg)
Slip Method
Example: Slip Load CalculationGiven: Synchronous speed (Ns) in RPM = 1800
Nameplate full load speed (Nr) = 1750
Measured speed in RPM (Nm) = 1770
Nameplate rated horsepower (hp) = 25
Determine the actual output horsepower
Load =Ns - Nm
x 100 = 1800 - 1770
x 100 = 60%Ns - Nr 1800 - 1750
Actual output horsepower would be 60% x 25 hp = 15 hp
![Page 64: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/64.jpg)
Energy Saving Opportunities
• For every 1% increase in motor efficiency, there is about 5 kW power savings.
• Motors should be Properly size to the load for optimum efficiency. High efficiency motors offer of 4 - 5% higher efficiency than standard motors
![Page 65: Electric Motors.ppt](https://reader031.fdocuments.net/reader031/viewer/2022020920/548635fbb4af9f690d8b507b/html5/thumbnails/65.jpg)
Energy Saving Opportunities• Use energy-efficient motors where economical. • Use synchronous motors to improve power factor. • Check alignment. • Provide proper ventilation (For every 10 oC increase
in motor operating temperature over recommended peak, the motor life is estimated to be halved)
• Check for under-voltage and over-voltage conditions. • Balance the three-phase power supply. • (An imbalanced voltage can reduce 3 - 5% in motor
input power) • Demand efficiency restoration after motor rewinding. • (If rewinding is not done properly, the efficiency can
be reduced by 5 - 8%)