ELEC0047 - Power system dynamics, control and stability Long-term voltage instability: dynamic aspects Thierry Van Cutsem [email protected] www.montefiore.ulg.ac.be/~vct December 2017 1 / 25

Transcript of ELEC0047 - Power system dynamics, control and stability...

Page 1: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects

Thierry Van [email protected] www.montefiore.ulg.ac.be/~vct

December 2017

1 / 25

Page 2: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects

Table of contents

Instability mechanisms of a Load Tap Changer (LTC)

Dynamic simulations of a 5-bus system

Dynamic simulations of a larger test system

please refer to the separate slides “Voltage stability of the Nordic test system”

Countermeasures against voltage instability

2 / 25

Page 3: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Instability mechanisms of a Load Tap Changer (LTC)

A simple model

We assume for simplicity that:the transformer is ideal :

V = r V2

the Load Tap Changer (LTC) adjusts r to have V2 = V o2

if V2 < V o2 then r is decreased

if V2 > V o2 then r is increased

the voltage dead-band is neglected

the load behaves as a constant admittance with unity power factor :

P = G V 22 = G

(V

r

)2

Q = 0

3 / 25

Page 4: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Small-disturbance stability (of an operating point)

P = G(V o2 )

2 = P o

V

PP o

load with voltage V2

restored to V o2 by LTC

C

load for various valuesof r changed by LTC

P = G(Vr )2

U

S

small disturbance = ∆r = small increase of r

equilibrium point S is stable:

∆r > 0 ⇒ ∆P < 0 ⇒ ∆V2 < 0 ⇒ the LTC decreases r∆r < 0 ⇒ ∆P > 0 ⇒ ∆V2 > 0 ⇒ the LTC increases r

equilibrium point U is unstable:

∆r > 0 ⇒ ∆P > 0 ⇒ ∆V2 > 0 ⇒ the LTC further increases r∆r < 0 ⇒ ∆P < 0 ⇒ ∆V2 < 0 ⇒ the LTC further decreases r 4 / 25

Page 5: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

As the “demand” G increases, the stable and unstable operating pointsconverge, coalesce and disappear at point C

point C is a bifurcation point : a point where, for a small variation of one orseveral parameter(s), the qualitative behaviour of the dynamics changes withrespect to :

the number of equilibrium pointsor the number of limit cyclesor the stability of equilibrium points or limits cycles, etc.

this particular bifurcation is called a saddle-node bifurcation

the saddle-node bifurcation point is also the maximum load power pointbecause the equilbrium characteristics of the load is a constant power, underthe effect of the LTC.

5 / 25

Page 6: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Instability due to a large disturbance(outage of transmission lines or generators)

P = G(V o2 )

2 = P o

V

P

disturbance

P o

load with voltage V2

restored to V o2 by LTC

C

load for various valuesof r changed by LTC

P = G(Vr )2

pre-disturbanceoperating point

the LTC attempts to restore V2 → V o2 and, hence, P → G (V o

2 )2 = Po

the disturbance causes the maximum load power to become smaller than Po

successive operating points shown with dots : in its attempt to restore V2 theLTC depresses the transmission voltage V

after crossing the critical point C, the tap changes produce reverse effects.

6 / 25

Page 7: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Dynamic simulations of a 5-bus system

System

Load center:

equivalent induction motor

static load with exponential model P = Po(V /V o)1.5 Q = Qo(V /V o)2.5

LTC controlling voltage of static load. Tap delays = 20 + k.10 s

fed by:

external system (represented by Thevenin equivalent) through long line

local synchronous generator equipped with AVR and OEL

7 / 25

Page 8: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Model of overexcitation limiter

inverse-time characteristic: the smaller the field winding overload, the longer thedelay before the field current is decreased to its limit (2.825 pu)

8 / 25

Page 9: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 1. Disturbance

At t = 1 s, tripping of one circuit of the line

9 / 25

Page 10: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 1. Time responses

10 / 25

Page 11: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 2. Disturbance

same as Case 1 but exponential load increased to 1500 MW

11 / 25

Page 12: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 2. Time responses

12 / 25

Page 13: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 2. Comments

field current of local generator limited by OEL at t ' 70 s

from there on, the LTC fails restoring the distribution voltage; on thecontrary, it has reverse effect on this voltage

the transmission voltage drops under the effect of the LTC and the OEL

the short-term dynamics of the generator, its regulators, etc. respond in astable way

there is a pseudo-stabilization when the LTC reaches its limit. Thispseudo-equilibrium is not viable:

voltage is really low (in a real system, protections could trigger furthertrippings, with cascading effects)any attempt to increase the demand will result in opposite effect.

13 / 25

Page 14: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

A real incident with the same characteristics

Incident in Brittany (Western France), January 12, 1987

14 / 25

Page 15: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 2. Instability mechanism shown by PV curves

15 / 25

Page 16: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 3. Disturbance

same as Case 2 but local generation increased to 450 MW

16 / 25

Page 17: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 3. Time responses

17 / 25

Page 18: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 3. Comments

impact of LTC and OEL similar to Case 2

but under the effect of the long-term degradation of operating conditions, the(field-current limited) generator loses synchronism, which makes voltagesplunge

emergency actions have to be taken before reaching this “no-return” or“collapse” point

18 / 25

Page 19: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Case 3. Instability mechanism shown by PV curves

19 / 25

Page 20: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Countermeasures against voltage instability

Typical requirements for an adequate post-disturbance system response

Voltages remain above minimum values

at load buses: customer trouble, load models unreliable below ∼ 0.85 puat buses of limited generators: tripping by protection at ∼ 0.85 - 0.90 puat transmission buses: not easy to define an “unacceptable” value. . .

short-terms dynamics remains stable in spite of the sagging voltages

no motor stallingno loss of synchronism

power flows in transmission lines do not exceed the value monitored byprotections.

20 / 25

Page 21: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Series compensation

very effective way of reducing transmission impedances

but expensive, more complex protection of transmission line

and possibility of subsynchronous resonance (between network elements anddistributed masses of shafts in thermal plants)

used only in stretched systems with long transmission distances.

Shunt compensation by mechanically switched capacitors

cheapest solution

switching off shunt inductors equivalent to switching on shunt capacitors

preventive use:

maintain reactive power reserves on “fast reacting” devices (generators,synchronous condensers, static var compensators) to make them ready to facedisturbances

corrective use:

automatic switching of capacitors / reactors triggered by detection of lowvoltage

21 / 25

Page 22: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Static Var Compensators (SVC):

fast and smooth variation of shunt admittance

more expensive than mechanically switched capacitors

justified when speed of action is needed (short-term voltage instability)

also helps counteracting other instabilities: e.g. SVCs to improve transient(angle) instability in a long corridor.

Adjustment of generator active power productions (near load centers)

commitment of non-economical (“out of merit”) units for security reasons

generation rescheduling

start-up of fast units (e.g. gas turbines) located near loads

cost covered by transmission rights and/or electricity price

22 / 25

Page 23: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Adjustment of generator voltages

Generator voltages can be quickly increased to increase load voltages

this also increases the maximum power deliverable to loads

but variation limited by maximum voltage allowed at generator terminal

control of multiple generators must be coordinated.

Secondary voltage control:automatic, centralized, coordinated control of generator voltages to

keep voltages at predefined (“pilot”) buses near set-point values

share the reactive power reserves in proportion to generator capabilities

existing implementations (France, Italy):

can effectively respond to smooth load increasesare not fast enough to effectively react to equipment outages.

23 / 25

Page 24: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Emergency control of load tap changers

Avoid power restoration of voltage-sensitive loads by not restoring load voltages.

Techniques:

tap blocked on current position

tap moved in reverse direction to preserve transmission voltage

LTC voltage setpoint decreased

typical voltage decrease: 5 %equivalent to “partial load shedding”

Limitations:

too slow to correct important voltage drops

most often only a temporary relief: other load restoration processes may keepon depressing voltages.

24 / 25

Page 25: ELEC0047 - Power system dynamics, control and stability ...montefiore.ulg.ac.be/~vct/elec0047/volt_stab_LT_large_dist.pdf · ELEC0047 - Power system dynamics, control and stability

Long-term voltage instability: dynamic aspects Instability mechanisms of a Load Tap Changer

Undervoltage load shedding

“Last resort“ countermeasure

very effective: shedding need not be large to restore voltages to normal values

required to quickly correct large voltage drops

unlike load shedding against frequency collapse, location is important: actingfarther away from the best place requires to act more

amount and time of shedding are linked: there is a delay beyond which actinglater requires to act more.

25 / 25