www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Conductor Inductance
(mH/km)
Current - Carrying Capacity at 30 C *
Short circuit current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max. (A)
in ground
Max.(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEBY 3 x (25-300) mm 6/10 kVN2XSEBY 3 x (25-300) mm 6/10 kVCu / XLPE / CTS / PVC / STA / PVC
Application :
For installation indoor, in ground direct burried, for power station and switchgear, if there is a risk that low mechanical damage may occur.
Special Features on Request
Fire Resistance Oil Resistance UV Resistance Flame Retardant Cat. A, B, C Flame Retardant Non Category Anti Termite Anti Rodent Low Smoke Zero Halogen
Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.Cross
SectionArea
OverallDiameter
CableWeight
approx. approx.
mm mm kg/km
Construction Data
25 43.0 2,767
35 46.0 3,279
50 48.5 3,799
70 52.5 4,687
95 56.5 5,753
120 60.0 6,690
150 63.5 7,761
185 67.5 9,091
240 73.0 11,235
300 78.0 13,326
Electrical Data
25 0.727 0.927 0.368 154 146 3.58 1.03
35 0.524 0.668 0.349 186 175 5.01 1.03
50 0.387 0.494 0.335 222 205 7.15 1.03
70 0.268 0.342 0.316 276 251 10.01 1.03
95 0.193 0.247 0.303 333 299 13.59 1.03
120 0.153 0.196 0.293 382 339 17.16 1.03
150 0.124 0.160 0.284 433 380 21.45 1.03
185 0.0991 0.128 0.277 493 427 26.46 1.37
240 0.0754 0.099 0.267 576 491 34.32 1.37
300 0.0601 0.080 0.261 654 550 42.90 1.37
Galvanized Steel TapeArmor
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)Standard Specification : IEC 60502-2
16833-0
2
Rev.
2.0
/ 2
009