EKAS 2.19.30Flexible cords and plugs to 250 V
UEE31307 Certificate III in Refrigeration and Air Conditioning
Stage 2A Units: UEENEEPOO2B
Chris Hungerford4/21/23
Flexible cordsFlexible cords
Light Duty
Ordinary Duty
Heavy Duty
2.19.30.A
How is a flexible cord How is a flexible cord different from other cables?different from other cables?
• The conductors in a flexible cord are made up of many more strands of finer wire than an ordinary cable (0.3mm). This allows the cord to flex without breaking the conductors.
• The maximum cross-sectional area (CSA) of a conductor in a flexible cord is 4mm2.
• Finally, the maximum number of insulated conductors (or cores) in a single cord is five.
2.19.30.A
Maximum length of flexible cordsMaximum length of flexible cords
2.19.30.A
Maximum current rating of flexible cordsMaximum current rating of flexible cords
NOTES:1 Where a flexible cord is wound on a drum, multiply current-carrying capacity by the appropriate factor, as follows:Number of layers: 1 2 3 4Derating factor: 0.76 0.58 0.47 0.40
2 Flexible cords having tinsel conductors with a nominal cross-sectional area of 0.5 mm2 have a current carrying capacity of 0.5 A.
3 The current-carrying capacity is based on a cable maximum conductor operating temperature of 60°C in order to limit the surface temperatures for the expected use of such cables. Where flexible cords are used as fixed wiring, the current ratings are given in Tables 4 to 15 and 17. (Refer to Clause 3.3.2).
4 To determine the three-phase voltage drop, refer to the appropriate value in Table 46, Table 47 or Table 48. To determine the single-phase voltage drop, multiply the three-phase value by 1.155.
2.19.30.A
An electrical cable is identified by its: 1. Conductor material e.g. copper or
aluminium2. Conductor size e.g. 1.5mm² CSA3. Insulation material e.g. rubber, glass, PVC4. Number of cable cores e.g. 7/0.50 – i.e. 7
strands of 0.50mm circular diameter 5. Voltage grading e.g. 0.6 / 1 KV; 250V /
440V6. Sheathing7. Protection
Electrical cables 3 Core & Earth Circular
Steel Wire Armoured SWASteel Wire Armoured SWA
Strand Conductor
2.19.30.A
Ratings of cables
• Voltage rating, all cables have a maximum operating voltage. This is directly related to the type and thickness of the insulation material.
• Temperature rating, table 3.2 AS 3000: 2007.• Cables are NOT rated in Current Carrying Capacity.
A cable's current carrying capacity is determined buy how it is installed as per AS/NZS 3008.1.1 (Australian).
2.19.30.A
Selecting a cord• Current carrying capacity of the cable.
• Operating conditions;– temperature– voltage– installation factors such as in direct sunlight,
mechanical protection, & thermal installation.
• Number of conductors.
2.19.30.A
Plugs and socketsPlugs and sockets• There are many types of plug tops, the most
common being the 10A three-pin plug.
2.19.30.A
2.19.30.A
2.19.30.A
2.19.30.A
International Protection Numbers2.19.30.A
3.7.2.8 Flexible cordsJoints shall not be made in flexible cords.Exceptions: Joint in flexible cords may be made -(a) Where used as installation wiring(b) By means of suitable cable couplers
Any flexible cord shall be installed so that undue stress on its connections due to a pull on the cord is alleviated by a pillar, post, grip, tortuous path, or other effective means.
Knotting of the flexible cord shall not be acceptable for this purpose.
AS/NZS-3000:2007 SAA Wiring Rules
2.19.30.C
2.19.30.C
Accessories• All accessories must be suitable and as
per Australian standards .
• All accessories must be suitable for the application.
• Wide variety of accessories can be accessed via suppliers catalogues.
2.19.30.C
A=Excellent B=Good C=Fair D=Poor
2.19.30.C
AS/NZS-3000:2007, SAA Wiring Rules
3.7 ELECTRICAL CONNECTIONS3.7.1 GeneralConnections between conductors and between conductors and other electrical equipment shall provide electrical continuity and adequate mechanical strength.
•Solder less lugs•Crimps•Compression terminals•Soldered connections
2.19.30.C
3.7.2.2 Preparation for connectionThe insulation on a conductor shall not be removed any further than is necessary to make the connection.
For connections between insulated conductors the connection shall be insulated to provide a degree of insulation not inferior to that of the conductors.
Any damaged insulation shall be reinstated.
AS/NZS-3000:2007 SAA Wiring Rules
2.19.30.C
Insulation of conductors
Yes
• Electrical insulation tape
• Epoxy kits
• Heat shrink
No
• Masking tape
• packing tape
• sticky tape
• silicon mastic
2.19.30.C
Conductor colouringAS/NZS 3000 Table 3.4
Function Colour
Earth/bonding Green/yellow
Neutral BlackRed Brown, dark Blue, Grey, White, any colour other than green/yellow, green, black, yellow or light blue
ActiveLight blue
2.19.30.C
Terminations and connections
• Connections must not be soft soldered before compression terminations.
• Must be seated correctly.• Free of dirt and oxides.• Use a suitable lug or connector.• Insulated to the equivalent of the original
insulation.• Earth connection must be painted if
exposed to weather
2.19.30.C
3.7.2.6 Mechanical stressAll cables and conductors shall be installed so that there is no undue mechanical stress on any connection.
AS/NZS-3000:2007 SAA Wiring Rules
3.7.2.3.1 Loosening of connections
Connections shall be made so that no loosening is likely because of vibration, alteration of materials or temperature variations to which the connectionsare likely to be subjected in normal service.
2.19.30.C
The eight visual checks recommended are:1. Check for obvious damage or defects.2. Check that flexible cords are properly anchored3. Check for any damage to flexible cords.4. Check that maximum load warning labels are intact. 5. Check that any controls such as switches are in working order.6. Check that covers and guards are properly secured as intended.7. Check that any safety devices are in good working order.8. Check that vents or exhausts are unobstructed.
2.19.30.D
Earth Continuity Test
• Any Class I equipment with exposed metal parts must have its protective earth checked to ensure it is continuous from the earth pin of the plug to any exposed metal. The resistance must not be greater than 1Ω.
2.19.30.D
Instrument Low reading ohmmeter.
Earth Continuity
1
Earth Pin
To
Earth Socket
2.19.30.DInstrument Low reading ohmmeter.
What is the value of earth continuity?
Earth Continuity “Class 1”
1
Earth Pin
To
Exposed Metal
2.19.30.D
1
What is the value of earth continuity?
Instrument Low reading ohmmeter.
Insulation Resistance Test:
• All equipment must be tested to ensure the integrity of the insulation, no electricity must be allowed to escape from the conductors or the appliance.
2.19.30.D
Insulation Resistance “Class 1”
1M
Active & Neutral
To
Exposed Metal
Switch ON
2.19.30.D
1
MegohmmeterQ What is the value of insulation resistance?
Insulation Resistance “Class 2”
1M
Active & Neutral
To
Exposed Metal
Switch ON
2.19.30.D
1M1
MegohmmeterQ What is the value of insulation resistance?
Insulation Resistance “extension lead”
1M
Active & Neutral
To
Earth Pin
2.19.30.D
1M1
MegohmmeterQ What is the value of insulation resistance?
Polarity
low
Active Pin
To
Active Socket
2.19.30.D
1
Instrument Low reading ohmmeter.
What is the value of continuity?
Polarity
low
Neutral Pin
To
Neutral Socket
2.19.30.D
1M1
Instrument Low reading ohmmeter.
What is the value of continuity?
V1=?
V2=?
V3=?
240v
240v0v
240v
0v240v
0v
240v240v
0v
0v0v
What should the voltage be?
V1 240vV2 240vV3 0v
Is this correct?
Reversed polarity A-N
Is this correct?
Correct
Is this correct?
Reversed polarity A-E
Is this correct?
No Supply
2.19.30.D
Minimum records that should be completed and maintained
• A record of the inspection and test results. • A record of faulty electrical equipment (has it been repaired
or destroyed).
Date of inspection
Appliance Visual inspection
Earth continuity
Insulation resistance
M
Polarity = Correct
RCD test current
30 MA trip timeMilliseconds
0 180 Test butt
2/7/09 Refrigerator ( LG model R100020 Serial 1004039832)
O.K 0.3 75M N/A N/A N/A N/A
2/7/09 Safetypac (Clipsal mod 56B, serial 9987987)
o.K. 0.8 187M 22 18
2.19.30.D
2.19.30.D
Energising supply• Only after the visual inspections and safety testing as per
AS/NZS 3000:2007 has proven that the circuit is fit for purpose are you to energise the circuit.
• Remove only your Danger tag. If another worker has their danger tag on the isolated point then you can not energise.
• If clear: Energise the circuit.• Test for the correct and safe operation of the circuit, i.e.
rotation, system performance, current draw, voltage, etc.• Prepare all your safety and performance documentation.
2.19.30.D