Effective January 2019 Supersedes October 2018 Rev. 7 Instruction Manual IM01005010E Innovative Technology® SPD Products The I.T. Protector® I.T. Protector Family of Products Contents e g a P 1 Introduction ............................................................................. 3 1.1 Scope......................................................................... 3 1.2 I.T. Protector Catalog Numbering System................. 3 1.3 Safety Precautions..................................................... 4 2 Installation............................................................................... 5 2.1 Before Installation ...................................................... 5 2.2 Wire Requirement ...................................................... 6 2.3 Overcurrent Protective Device Requirement ............. 6 2.4 Conduit Installation Guidelines .................................. 7 2.5 Mounting the SPD...................................................... 7 2.6 Disconnecting the ATN Filter ....................................11 2.7 Wiring SPD to Electrical System ..............................12 2.8 Form C Relay Contacts ........................................... 16 2.9 Power Up and System Checkout............................. 17

Transcript of Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements...

Page 1: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

Effective January 2019Supersedes October 2018 Rev. 7Instruction Manual IM01005010E

Innovative Technology® SPD ProductsThe I.T. Protector®

moc.notaE.www :tisiv noitamrofni erom roF 9002/8 etaD evitceffE

Contents egaP

1 Introduction ............................................................................. 31.1 Scope......................................................................... 31.2 I.T. Protector Catalog Numbering System................. 31.3 Safety Precautions..................................................... 4

2 Installation............................................................................... 52.1 Before Installation ...................................................... 52.2 Wire Requirement...................................................... 62.3 Overcurrent Protective Device Requirement ............. 62.4 Conduit Installation Guidelines .................................. 72.5 Mounting the SPD...................................................... 72.6 Disconnecting the ATN Filter....................................112.7 Wiring SPD to Electrical System ..............................122.8 Form C Relay Contacts ........................................... 162.9 Power Up and System Checkout............................. 17

Innovative Technology® SPD Products The I.T. Protector®

Installation

Instruction Manual: IM01005010ERev. 5 – August 2009

I.T. Protector Family of Products

moc.notaE.www :tisiv noitamrofni erom roF 9002/8 etaD evitceffE

Contents egaP

1 Introduction ............................................................................. 31.1 Scope......................................................................... 31.2 I.T. Protector Catalog Numbering System................. 31.3 Safety Precautions..................................................... 4

2 Installation............................................................................... 52.1 Before Installation ...................................................... 52.2 Wire Requirement...................................................... 62.3 Overcurrent Protective Device Requirement ............. 62.4 Conduit Installation Guidelines .................................. 72.5 Mounting the SPD...................................................... 72.6 Disconnecting the ATN Filter....................................112.7 Wiring SPD to Electrical System ..............................122.8 Form C Relay Contacts ........................................... 162.9 Power Up and System Checkout............................. 17

Innovative Technology® SPD Products The I.T. Protector®

Installation

Instruction Manual: IM01005010ERev. 5 – August 2009

I.T. Protector Family of Products

Page 2: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

2

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR ii egaP

Notice: Product improvements and enhancements are continuous; therefore the specifications and information contained in this document may change without notice.

Eaton shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.

No part of this document may be reproduced for publication, or translated to another language without the prior written consent of Eaton.

Innovative Technology® is a registered trademark of Eaton. All other trademarks, trade names, service marks and logos referenced herein belong to their respective owners.

Page 3: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

3

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

E01050010MInoitallatsnI rotcetorP .T.I

1 egaP 9002/8 – 5 .veR

1 INTRODUCTION

1.1 Scope This installation manual contains the information necessary to install Eaton Corporation’s line of I.T. Protector Surge Protective Devices (SPDs) for the following electrical system wiring configurations:

• Single Phase (1P)• Split Phase (1S)• 3 Phase Wye (Star) (3Y)• 3 Phase High-Leg Delta (3D)• 3 Phase No Neutral (NN)

1.2 I.T. Protector Catalog Numbering System

Before connecting the SPD to the electrical system, locate the label attached to the SPD that contains the unit’s Catalog Number, and then use the diagram below to verify that the SPD matches the electrical system’s voltage and wiring configuration.

Model

PT = Protector

PT SDX 160 3Y101 _

Configuration & Voltage Ranges (Vac)

1P101 = Single-Phase – 100, 110, 120, 1271P201 = Single-Phase – 200, 208, 220, 230, 240, 2771S101 = Split-Phase – 100/200, 110/220, 120/240, 127/2543Y101 = Three-Phase WYE (Star) – 100/175, 110/190, 120/208, 127/2203Y201 = Three-Phase WYE (Star) – 220/380, 230/400, 240/415, 277/4803Y300 = Three-Phase WYE (Star) – 305/525, 347/6003D101 = Three-Phase High Leg Delta - 120/240NN201 = Three-Phase Delta – 200, 208, 220, 230, 240NN400 = Three-Phase Delta – 380, 400, 415, 440, 480NN501 = Three-Phase Delta – 525, 600

CIrcuit Design

X= Standard SuppressionE = Active Tracking Network (ATN)

Sine Wave Tracking,

Options

In this example, Catalog Number PTX160-3Y101-SDIdentifies a Protector with the following features and ratings:

• Standard Suppression Circuitry• Surge Current Rating of 160 kA• Three-Phase WYE configuration• Voltage Range of 100/175 to 127/220 Vac• S.M.A.R.T. Surge Counter

* Note: the PEM and PEM-E Options have been discontinued.

120160240300400

Per Phase Peak Surge Current (kA)

048 = 48065 = 65 080 = 80

C = Circuit Breaker

Blank = None

CD = Circuit Breaker Disconnect

Options*

SD = S.M.A.R.T Surge Counter

Blank = None

SS = Stainless Steel Enclosure

UL1283 7th Edition

_

2 W

# of Wires

2 W3 W4 W+G4 W+G4 W+G4 W+G3 W+G3 W+G3 W+G

Page 4: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

4

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

IM01005010E I.T. Protector Installation

Page 2 Rev. 5 – 8/2009

1.3 Safety Precautions A licensed/qualified electrician must complete all instructions and measurements described in this instruction in accordance with the U.S. National Electrical Code, state and local codes, or other applicable country codes. The U.S. National Electrical Code and state and local requirements (or other applicable country codes) supersede this instruction.

Read and understand all instructions before beginning the installation.

WARNING! The use of the word WARNING in this manual denotes a potential hazard associated with the use of this equipment. It calls attention to a procedure, practice, or condition, or the like, which if not correctly performed or adhered to, could result in personal injury or death.

CAUTION The use of the word CAUTION in this manual denotes a potential hazard associated with the use of this equipment. It calls attention to a procedure, practice, condition, or the like, which if not correctly performed or adhered to, could result in damage to the equipment.

WARNING! SHOCK HAZARDS:

IMPROPER INSTALLATION CAN CAUSE DEATH, INJURY AND/OR EQUIPMENT DAMAGE. Follow all warnings and cautions. Completely read and understand the information in this document before attempting to install or operate this equipment.

IMPROPER WIRING COULD CAUSE DEATH, INJURY, AND/OR EQUIPMENT DAMAGE.Only licensed/qualified electricians who are trained in the installation and service of electrical devices are to service this equipment.

USE APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC FLASH PROTECTION.

DURING NORMAL OPERATION, HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT.

Page 5: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

5

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

E01050010MI noitallatsnI rotcetorP .T.I

3 egaP 9002/8 – 5 .veR

2 INSTALLATION

2.1 Before Installation Perform or plan the following before installing the SPD:

1. Refer to Section 1.2 and verify that the correct SPD model is being installed.

WARNING! SHOCK HAZARD: When working inside the SPD as described in any of the following steps, be sure to follow all safe work practices to avoid an electrical shock hazard.

2. For systems with a Neutral wire, there must be a Neutral to Ground/Earth bond present at the SPD. Note that the SPD may be damaged if not connected to ground.

3. Measure the voltage between Neutral and Ground. If this voltage is greater than 5 Vac, then a problem may exist in the electrical system. The SPD can still be installed under this condition, but a licensed electrician should be consulted to correct the problem.

4. The Active Tracking Network (ATN) filter, which is contained in all PTE models, will need to be disconnected if the SPD is being connected to an electrical panel feeding medical patient care equipment, or containing a ground fault circuit interrupting (GFCI) main breaker. Disconnect the ATN filter per Section 2.6.

5. The SPD can be mounted in any position. If necessary, the cover may be rotated 180 degrees to improve readability of the label (not applicable to Circuit Breaker models (with a “C” or “CD” suffix) or models with a hinged cover). When removing the cover, be careful not to damage the indicator light circuit board or wiring attached to the cover.

6. Isolated Ground: The SPD’s ground wire is internally bonded to its housing. If the electrical system utilizes an isolated ground, then the SPD’s housing must be isolated from ground using insulated conduit fittings, and its ground wire must be connected to the system’s isolated ground bus. When making this connection, always follow national, state, and local wiring codes.

7. When a NEMA 4X enclosure is used, plan on installing weatherproof (corrosion resistant) conduit and fittings to maintain the enclosure’s 4X rating.

8. Plan to install the SPD as close as possible to the electrical panel. Long lead lengths and sharp bends between the SPD and the electrical panel will degrade the performance of the SPD.

9. Refer to Table 2-1 and determine the wiring size requirements of the SPD model being installed. For example, a Standard PTX160 includes #10 AWG wires that are internally connected to the SPD, while a Standard PTX300 requires that the customer supply wire in the range of #10–1/0 AWG.

10. If necessary, install an overcurrent protective device between the SPD and electrical system per national, state, and local electrical codes as described in Section 2.3.

Page 6: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

6

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 4 egaP

2.2 Wire Requirement

For SPDs that are not supplied with wire, the customer must provide wires of the appropriate size and color as specified in Table 2-1 below. These wires are used to connect the SPD to the electrical system as described in Section 2.7.

Table 2-1. Wire Requirement

PTE and PTX Standard Models Wire Size Range

048 / 065 / 080 / 120 / 160 #10 AWG (6mm2)Stranded Wire Included

240 / 300 / 400 #10–1/0 AWG (6–50 mm2)Wire Not Included

Wire Size Range PTE and PTX Circuit Breaker / Circuit Breaker

Disconnect ModelsCircuit Breaker /

Circuit Breaker Disconnect Models (C & CD suffix)

048 / 065 / 080 / 120 / 160 / 240 / 300 / 400

#10–1/0 AWG (6–50 mm2)

Wire Not Included

Wire Colors: Neutral = White or Gray Ground = Green or Green w/Yellow Stripe Phases A, B, and C = Black

2.3 Overcurrent Protective Device Requirement

For Type 2 SPD models that are not supplied with a Circuit Breaker or Circuit Breaker disconnect(without a “C” or “CD” suffix), a customer supplied 30 ampere singe-throw circuit breaker must be installed, normally located inside the electrical panel in close proximity to the SPD’s wire-entry point.

For Type 1 SPD models that are supplied with a Circuit Breaker or Circuit Breaker disconnect (with a “C” or “CD” suffix), these models contain an internal Circuit Breaker to protect against short circuit fault conditions within the device.

Refer to Section 2.7 for wiring details.

a Factory prewired 18 inches of 10 AWG wire for units with no C or CD suffix.

b Factory prewired 36 inches of 10 AWG wires for Stainless Steel units with no C or CD suffix

a,b

Page 7: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

7

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

I.T. Protector Installation IM01005010E

Rev. 5 – 8/2009 Page 5

2.4 Conduit Installation Guidelines

The following guidelines should be followed when installing conduit between the SPD and electrical panel:

• Avoid using 90° elbows and keep the conduit run as short and straight as possible. See Figure 2-1.

• If the electrical system utilizes an isolated ground, then the SPD’s housing must be isolated from ground using insulated conduit fittings.

• When applicable, use weatherproof (corrosion resistant) conduit and fittings to maintain the enclosure’s NEMA 4 or 4X rating.

• If the SPD enclosure does not already have a hole for installing conduit, punch or drill a hole of the appropriate size to accommodate the size of conduit being installed.

CAUTION: Choose a hole location that will provide the minimum connecting wire length, while also not disturbing or damaging any components inside the SPD.

Be cautious to capture and remove all metal shavings during the drilling process to avoid possible short circuits.

Figure 2-1. Conduit Installation Guidelines

2.5 Mounting the SPD Select a location where the SPD will be mounted based on the internal configuration of the electrical panel and the physical surroundings outside the panel. Choose a mounting location that provides the shortest possible wire length to the overcurrent protective device (when used) and then to the electrical panel’s bus bar.

Once a location has been determined, mount the SPD to the nearby supporting surface using the SPD’s mounting feet and suitable fasteners. Mounting feet and hole dimensions of each SPD model are shown in Figures 2-2 thru 2-6.

Tip: SPD models that are light in weight can be mounted directly on the electrical panel using only a chase nipple and conduit nuts.

Suppr ession Cir cuit Status1 LED per phase, nor m ally on - OK

Avoid sharp bends in wiring and longer than necessary wire lengths

Keep wire lengths as short and straight as possible

Suppr ession Cir cuit Status1 LED per phase, nor mally on - OK

Page 8: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

8

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

IM01005010E I.T. Protector Installation

Page 6 Rev. 5 – 8/2009

Figure 2-2. PTE048, 065, 080 / Models 1P101, 1S101, 3Y101, 3D101 PTX048, 065, 080 / All Models

6.00(152.4)

6.75(171.5)

7.50(190.5)

2.00(50.8)

4.30(109.2)

6.00(152.4)

4.30(109.2)

1.25(31.8)

1.48(37.6)

WeldedHub, Id

MountingFoot

MountingHole

Ø0.75(Ø19.1)

Ø0.31(Ø7.9)

Weight:PTX & <240V PTE = 7 lb>240V PTE = 12 lb

Dimensions: Inches (mm)

Figure 2-3. PTE048, 065, 080 / Models 1P201, 3Y201, 3Y300, NN201, NN400, NN501 PTX/PTE120, 160 / All Models

8.75(222.3)

9.50(241.3)

4.00(101.6)

5.25(133.4)

MountingFoot

MountingHole

Ø0.31(Ø7.9)

7.35(186.7)

Weight:<240V PTE048, 065, 080 = 7 lb>240V PTE048, 065, 080 = 12 lbPTX/PTE160 = 12 lb

Dimensions: Inches (mm)

Page 9: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

9

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

I.T. Protector Installation IM01005010E

Rev. 5 – 8/2009 Page 7

Figure 2-4. PTX/PTE240, 300, 400 / All Models

7.00(177.8)

MountingFoot

Ø 0.31(Ø 8)

Mounting Hole

6.00(152.4)9.38

(238.3)

10.75(273.1)

11.50(292.1)

Weight:PTX/PTE300 = 30 lbPTX/PTE400 = 32 lb

Dimensions: Inches (mm)

Figure 2-5. Circuit Breaker (C) & Circuit Breaker Disconnect (CD) Options for 48, 65, 80, 120, 160 240 or 300 kA Models

Page 10: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

10

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 8 egaP

Figure 2-6. Circuit Breaker Disconnect (C and CD) Option for 400 kA Models

Dimensions: Inches (mm)

2.6 Disconnecting the ATN Filter

The ATN filter, which is part of all PTE models, should be disconnected if the SPD is connected to an electrical panel feeding medical patient care equipment, or containing a ground fault circuit interrupting (GFCI) main breaker. The ATN filter provides enhanced Neutral to Ground/Earth protection that may cause nuisance tripping of breakers that are part of the above-mentioned applications.

Note: The following procedures disable only the ATN filter. Other protection circuits are not affected.

WARNING! SHOCK HAZARD: When disconnecting the ATN filter, be sure to de-energize the electrical system and follow safe work practices to avoid an electrical shock hazard.

For Standard PTE Models (without a “C” or “CD” suffix): Open or remove cover on SPD, being careful not to strain the wires or damage the circuit board attached to the cover. Look into the enclosure and locate a green/yellow loop of wire protruding from the encapsulation. Use a wire-cutting tool to cut this wire in the center of the loop. Cap off the ends of each wire using UL listed wire nuts. Close or reinstall cover.

For Circuit Breaker / Circuit Breaker Disconnect PTE Models (with a “C” or “CD” suffix): Open or remove cover on SPD, being careful not to strain the wires or damage the circuit board attached to the cover. Next to the Circuit Breaker mounting panel, locate a green/yellow loop of wire. Use a wire-cutting tool to cut this wire in the center of the loop. Cap off the ends of each wire using UL listed wire nuts. Close or reinstall cover.

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 8 egaP

Figure 2-7. Flushmntplate3A PTE/X units 40, 65, 80 kA

7.75

10.6

0

4.350.70

0.65

0.70

1.18

2.77

2.80

1.75

0.75

0.70

0.135

0.275

6.32

R0.14(4 PL)

Ø0.22 (4 PL)

R0.25 (4 PL)

1.25 5.25 1.25

1.83

1.001.00

NOTES:

1. Pieces are to be stamped from 14 AWG cold rolled steel stock.

2. Blank sizes will vary slightly depending on the exact thickness of thesteel used.

3. Blanks are to be drilled as indicated and bent according to the drawing.

4. There shall be a total of 2 brackets included per plate, accompanied by(4) 8/32" pan-head phillips screws which shall be packaged together andlabeled as "ZPLATE-3A".

5. Plate is to be properly prepared for painting, by degreasing andsandblasting all surfaces.

6. Plate and brackets are to be painted ANSI 61 GREY.

7. Bracket is to be bent at dashed lines, according to dimensions in theillustration.

Ø0.320WELD NUTS

(2 PL)

Ø0.140 (2 PL)

1.260

0.2500.380

0.3800.250

FLAT OF BRACKET0.580

0.447 1.28

10.4860.766

FINISHED BRACKET

0.580

0.766

0.183 0.127

Page 11: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

11

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 8 egaP

Figure 2-6. Circuit Breaker Disconnect (C and CD) Option for 400 kA Models

Dimensions: Inches (mm)

2.6 Disconnecting the ATN Filter

The ATN filter, which is part of all PTE models, should be disconnected if the SPD is connected to an electrical panel feeding medical patient care equipment, or containing a ground fault circuit interrupting (GFCI) main breaker. The ATN filter provides enhanced Neutral to Ground/Earth protection that may cause nuisance tripping of breakers that are part of the above-mentioned applications.

Note: The following procedures disable only the ATN filter. Other protection circuits are not affected.

WARNING! SHOCK HAZARD: When disconnecting the ATN filter, be sure to de-energize the electrical system and follow safe work practices to avoid an electrical shock hazard.

For Standard PTE Models (without a “C” or “CD” suffix): Open or remove cover on SPD, being careful not to strain the wires or damage the circuit board attached to the cover. Look into the enclosure and locate a green/yellow loop of wire protruding from the encapsulation. Use a wire-cutting tool to cut this wire in the center of the loop. Cap off the ends of each wire using UL listed wire nuts. Close or reinstall cover.

For Circuit Breaker / Circuit Breaker Disconnect PTE Models (with a “C” or “CD” suffix): Open or remove cover on SPD, being careful not to strain the wires or damage the circuit board attached to the cover. Next to the Circuit Breaker mounting panel, locate a green/yellow loop of wire. Use a wire-cutting tool to cut this wire in the center of the loop. Cap off the ends of each wire using UL listed wire nuts. Close or reinstall cover.

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 8 egaP

Figure 2-8. Flushmntplate8 PTE/X units 120 and 160 kA

1.78

8.38

0.70

3.78

7.25

0.651.25

R0.14

0.28

2.25

1.13

TOP OF LID

3.85

0.75

1.0010.75

0.70

0.14

R0.25 (4 PL)

6.31 2.00 0.70

2.56

FLAT OF BRACKET

0.08

FINISHED BRACKET

1.28

10.490.45

0.76

6

NOTES:1. Pieces are to be stamped from 14 AWG coldrolled steel stock.2. Blank sizes will vary slightly depending on theexact thickness of the steel used.3. Blanks are to be drilled as indicated and bentaccording to the drawing.4. There shall be a total of 2 brackets included perplate, accompanied by (4) 8/32" screws.5. Plate is to be properly prepared for painting, bydegreasing and sandblasting all surfaces.6. Plate is to be painted ANSI 61 GREY.7. Also reference ZPLATE-3A.8. Bracket is to be bent at dashed lines, accordingto dimensions in the illustration.9. Tolerance is +/- 0.01 unless otherwise specified.

0.58

0.25

0.13

0.766

0.58

1.260.25

0.380.38

Ø0.14 (2 PL)

Ø0.32WELD NUTS

(2 PL)

0.18

12.7

0

Ø0.22 (4 PL)

1.18"

R0.03

R0.03

Ø0.32WELD NUTS

(2 PL)

4 PL. ON PLATE2 PL. ON BRACKET

SAME DIMENSIONBUT CUT THROUGH

UP TO EDGE

Page 12: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

12

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

E01050010MI noitallatsnI rotcetorP .T.I

9 egaP 9002/8 – 5 .veR

2.7 Wiring SPD to Electrical System

WARNING! SHOCK HAZARD: When working inside the SPD, be sure to de-energize the electrical system and follow safe work practices to avoid an electrical shock hazard.

Important!

- Keep all connecting leads as short and straight as possible. Additionally, the conductors should be twisted together by approximately one turn every two inches for as much as the wire run as possible to achieve maximum SPD performance.

- For all Standard SPD models (without a “C” or “CD” suffix) the SPD must be connected to the electrical system through an external overcurrent protective device. Refer to Section 2.3 for details.

- Always connect the SPD to the load side of the main disconnect.

- If the system utilizes an isolated ground, then the SPD’s ground wire must be connected to the system’s isolated Ground bus.

1. Open or remove cover on SPD.

2. Do one of the following:

• For SPD models that are supplied with wire, identify the Neutral, Ground, and Phase wires. These wires are labeled and/or color coded as follows:

Neutral = White or Gray Ground = Green or Green w/Yellow Stripe Phase A, B, C = Black

Note that SPDs (models NN201, NN400, and NN501) that are connected to 3-Phase Delta (No Neutral) electrical systems do not contain a Neutral (WHT) wire.

• For SPD models that are NOT supplied with wire, obtain wire of the correct size and color (refer to Table 2-1 and connect one end of each wire to its designated ring or box terminal inside the SPD. Wire length should be kept as short as possible (18" maximum), but long enough to allow all necessary connections to be made inside the electrical panel.

3. Route the wires from the SPD (through conduit if used) into the electrical panel.

4. On Pages 13 thru 15, locate the wiring diagram of the electrical system to which the SPD is being connected. Perform the procedure associated that wiring diagram to connect the SPD to the electrical panel’s bus bars.

Page 13: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

13

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

IM01005010E I.T. Protector Installation

Page 10 Rev. 5 – 8/2009

• Single Phase (1P101, 1P201)

a. Connect the SPD’s Ground (GRN) wire directly to the electrical panel’s Ground bus bar.

b. Do one of the following:

• Neutral Connection – Connect the SPD’s Neutral (WHT) wire directly to the electrical panel’s Neutral bus bar.

• Phase B Line Connection – Connect the SPD’s Neutral (WHT) wire through an over-current protective device (refer to Section 2.3)* to the electrical panel’s Phase B voltage bus bar.

c. Connect the SPD’s Phase A (BLK) wire through an overcurrent protective device (refer to Section 2.3)* to the electrical panel’s Phase A voltage bus bar.

* Note: For Circuit Breaker or Circuit Breaker Disconnect SPD models (with a “C” or “CD” suffix), connect the SPD wires to the electrical panel according to National, State, and Local codes.

• Split Phase (1S101)

Important! Do not install SPD if the Neutral to Ground (Earth) bond is not present as the SPD may be damaged.

a. Connect the SPD’s Ground (GRN) wire directly to the electrical panel’s Ground bus bar.

b. Connect the SPD’s Neutral (WHT) wire directly to the electrical panel’s Neutral bus bar.

c. Connect the SPD’s Phase A (BLK) wire through an overcurrent protective device (refer to Section 2.3)* to the electrical panel’s Phase A voltage bus bar.

d. Repeat Step c to connect the SPD’s Phase B (BLK) wire to its associated bus bar.

* Note: For Circuit Breaker or Circuit Breaker Disconnect SPD models (with a “C” or “CD” suffix), connect the SPD wires to the electrical panel according to National, State, and Local codes.

PHASE A

GROUND

NETURAL or PHASE B

STANDARDMODEL

CUSTOMERSUPPLIED

OVERCURRENTPROTECTIVE

DEVICE

SPD

Neu

tral (

WH

T)

Pha

se A

(BLK

)

Gro

und

(GR

N)

Install an overcurrentprotective device ifconnected to Phase B,NOT neutral.

PHASE A

NEUTRAL

GROUND

PHASE B

STANDARDMODEL

Solid bond betweenGround/Earth andNeutral at serviceentrance or servingisolation transformer

SPD

Pha

se B

(BLK

)

Pha

se A

(BLK

)

Neu

tral (

WH

T)

Gro

und

(GR

N)

CUSTOMERSUPPLIED

OVERCURRENTPROTECTIVE

DEVICE

Page 14: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

14

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

I.T. Protector Installation IM01005010E

Rev. 5 – 8/2009 Page 11

• 3-Phase Wye (Star) (3Y101, 3Y201, 3Y300)

Important! Do not install SPD if the Neutral to Ground (Earth) bond is not present as the SPD may be damaged.

a. Connect the SPD’s Ground (GRN) wire directly to the electrical panel’s Ground bus bar.

b. Connect the SPD’s Neutral (WHT) wire directly to the electrical panel’s Neutral bus bar.

c. Connect the SPD’s Phase A (BLK) wire through an overcurrent protective device (refer to Section 2.3)* to the electrical panel’s Phase A voltage bus bar.

d. Repeat Step c to connect the SPD’s Phase B and C (BLK) wires to their associated bus bars.

* Note: For Circuit Breaker or Circuit Breaker Disconnect SPD models (with a “C” or “CD” suffix), connect the SPD wires to the electrical panel according to National, State, and Local codes.

• 3-Phase Delta (No Neutral) (NN201, NN400, NN501)

a. Connect the SPD’s Ground (GRN) wire directly to the electrical panel’s Ground bus bar.

b. Connect the SPD’s Phase A (BLK) wire through an overcurrent protective device (refer to Section 2.3)* to the electrical panel’s Phase A voltage bus bar.

c. Repeat Step b to connect the SPD’s Phase B and C (BLK) wires to their associated bus bars.

* Note: For Circuit Breaker or Circuit Breaker Disconnect SPD models (with a “C” or “CD” suffix), connect the SPD wires to the electrical panel according to National, State, and Local codes.

PHASE A

GROUND

PHASE B

PHASE C

STANDARDMODEL

SPD

Phas

e C

(BLK

)P

hase

B (B

LK)

Pha

se A

(BLK

)

Gro

und

(GR

N)

CUSTOMERSUPPLIED

OVERCURRENTPROTECTIVE

DEVICE

PHASE A

NEUTRAL

GROUND

PHASE B

PHASE C

STANDARDMODEL

Solid bond betweenGround/Earth andNeutral at serviceentrance or servingisolation transformer

SPD

Pha

se C

(BLK

)Ph

ase

B (B

LK)

Phas

e A

(BLK

)

Neu

tral (

WH

T)G

roun

d (G

RN

)

CUSTOMERSUPPLIED

OVERCURRENTPROTECTIVE

DEVICE

Page 15: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

15

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 21 egaP

• 3-Phase Delta (High-Leg) (3D101)

Important! Do not install SPD if the Neutral to Ground (Earth) bond is not present as the SPD may be damaged.

a. Connect the SPD’s Ground (GRN) wire directly to the electrical panel’s Ground bus bar.

b. Connect the SPD’s Neutral (WHT) wire directly to the electrical panel’s Neutral bus bar.

c. Connect the SPD’s Phase A (BLK) wire through an overcurrent protective device (refer to Section 2.3)* to the electrical panel’s Phase A voltage bus bar.

d. Repeat Step c to connect the SPD’s Phase B and C (BLK) wires to their associated bus bars.

* Note: For Circuit Breaker or Circuit Breaker Disconnect SPD models (with a “C” or “CD” suffix), connect the SPD wires to the electrical panel according to National, State, and Local codes.

5. If the SPD’s Form C relay is to be used for remote alarm purposes, then proceed to Section 2.8 for detailed wiring information.

6. Recheck all connections, and then close or reinstall cover.

PHASE A

GROUND

NEUTRAL

PHASE B (High Leg)

PHASE C

STANDARDMODEL

Solid bond betweenGround/Earth andNeutral at serviceentrance or servingisolation transformer

SPD

Phas

e C

(BLK

)Ph

ase

B (B

LK)

Phas

e A

(BLK

)

Neu

tral (

WH

T)G

roun

d (G

RN

)

CUSTOMERSUPPLIED

OVERCURRENTPROTECTIVE

DEVICE

Page 16: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

16

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

E01050010MI noitallatsnI rotcetorP .T.I

31 egaP 9002/8 – 5 .veR

2.8 Form C Relay Contacts The SPD’s Form C relay (mounted on the cover) provides two sets of dry contacts labeled N/O (Normally Open), N/C (Normally Closed), and COM (Common). The label indicates the position of the contacts when the relay is energized.

The relay contacts are rated 125 Vac @ 0.5 A, or 30 Vdc @ 1 A (60 W or 125 VA).

The Form C relay contacts are “fail safe” and only change state when the relay is energized by all phase voltages being present. By connecting a remote alarm to these contacts, the alarm can be made to activate when the relay de-energizes as the result of losing at least one phase voltage.

Connect the SPD’s Form C relay contacts to a remote alarm device as follows:

WARNING! SHOCK HAZARD: When working inside the SPD, be sure to de-energize the electrical system and follow safe work practices to avoid an electrical shock hazard.

1. Open or remove cover on SPD, taking care not to damage the indicator light circuit board and wiring attached to the cover.

2. See Figure 2-9. Punch a hole through the cover’s overlay marked “Remote Alarm,” if provided, and install a watertight strain relief (e.g. Heyco 3208). If a side, top, or bottom location is required, or if no pre-drilled access point is provided, punch or drill a 0.5" (12.7 mm) diameter hole, centered at 1.125" (28.5 mm) from the lip of the box (cover opened/removed) in a location that will not interfere with the cover clamps or screws. And then install the watertight strain relief.

CAUTION: Be cautious to capture and remove all metal shavings during the drilling process to avoid possible short circuits.

Figure 2-9. Remote Alarm Access Point

Remote Alarm -Dry Contacts

Access Point

SPD

RemoteAlarm

AccessPoint

If a pre-drilled Access Pointis not provided, or if anotherlocation is desired, punch ordrill a 0.5" (12.7mm) hole asdescribed in Step 2 above.

Appropriate NEC ClassWire secured to SPDusing a WatertightStrain Relief

Wiring toAlarm Deviceand its powersource

Page 17: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

17

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

noitallatsnI rotcetorP .T.I E01050010MI

9002/8 – 5 .veR 41 egaP

3. Using a small flat-blade screwdriver, connect a customer supplied alarm device (and if required a power source) to the Form C relay’s COM and N/C or N/O terminals as necessary for proper device operation. Note that the relay terminals accept AWG #26 to #16 (0.16 to 0.5 mm2) wire. Be sure to follow applicable U.S. NEC Articles (or other applicable country codes). Also, follow rules of wiring class used when determining routing of alarm leads. To maintain NEMA 4 (IP66) rating, use appropriate cable and the supplied watertight strain relief.

In the example shown in Figure 2-10, the Form C relay will de-energize if one of the Phase voltages is lost, causing the alarm to activate.

4. Recheck all connections, and then close or reinstall cover.

Figure 2-10. Typical Alarm Wiring

N/C

N/O

COM

FORM C REL AYTERMINALS

(Located on IndicatorLight Circuit Board

Mounted on Cover of SPD)

Alarm Power Source(125 Vac @ 0.5A or30 Vdc @ 1A Max.)

ALARM• Low Power Indicator

Light or Horn• Computer Based

Control System• Alarm Annunciating

Circuit PLC

2.9 Power Up and System Checkout Apply system power and observe the following:

• The LED(s) visible through the SPD’s cover should glow. One LED should glow for each Phase voltage being monitored.

Tip: Should there be a significant difference in LED brightness, check the phase rotation of the electrical panel and ensure that the SPD’s Phase wires are connected to the correct phase. Slight differences in brightness DO NOT indicate a faulty LED, rather specification tolerance differences of the indicator circuit’s components. LED brightness symmetry and/or level do not indicate the SPD’s operational status.

• With all phase voltages present, the Form C relay should energize causing its contacts to move to their normal position.

Page 18: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

18

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

3.0 WarrantyEaton warrants these products for a period of 5 years from the date of delivery to the purchaser, 20 years if the product is properly regis-tered with Eaton, to be free from defects in both workmanship and materials. To register visit www.eaton.com/itvss and click the war-ranty registration icon. Eaton assumes no risk or liability for results of the use of the products purchased from it, including but without limiting the generality of the foregoing: (1) The use in combination with any electrical or electronic components, circuits, systems, assemblies, or any other materials or substances; (2) Unsuitability of any product for use in any circuit or assembly.

Purchaser’s rights under the warranty shall consist solely of requir-ing Eaton to repair, or at Eaton’s sole discretion, replace, free of charge, F.O.B. factory, and defective items received at said factory within said term determined by Eaton to be defective. The giving of or failure to give any advice or recommendations by Eaton shall not constitute any warranty by or impose any liability upon Eaton. The foregoing constitutes the sole and exclusive liability of Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED, IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY, FITNESS FOR PURPOSE SOLD, DESCRIPTION, QUALITY, PRODUCTIVENESS OR ANY OTHER MATTER.

In no event shall Eaton be liable for special or consequential dam-ages or for delay in performance of the warranty.

This warranty does not apply if the product has been misused, abused, altered, tampered with, or used in applications other than specified on the nameplate. At the end of the warranty period, Eaton shall be under no further warranty obligation expressed or implied.

The product covered by this warranty certificate can only be repaired or replaced by the factory. For help on troubleshooting the SPD, or for warranty information, call 1-800-809-2772, Option 4, sub-option 2. Repair or replacement units will be returned collect. If Eaton finds the return to be a manufacturer’s defect, the product will be returned prepaid.

Page 19: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

19

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

EATON www.eaton.com

Notes:

Page 20: Effective January 2019 Supersedes October 2018 Rev. 7 Innovative ...€¦ · Product improvements and enhancements are continuous; therefore the specifications and information contained

EatonElectrical Sector1000 Eaton Boulevard.Cleveland, OH 44122United States877-ETN-CARE (877-386-2273)Eaton.com

© 2019 EatonAll Rights ReservedPrinted in USAPublication No. IM01005010E / TBG000763January 2019

Eaton is a registered trademark of Eaton.

All other trademarks are property of their respective owners.

Instruction Manual IM01005010EEffective January 2019

Innovative Technology SPD ProductsThe I.T. Protector

Copyright © 2018 by Eaton, Moon Township, PA, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.

Specifications contained herein are subject to change without notice.

EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION IN THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF EATON, AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING CONTRACTUAL PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT.

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

The information, recommendations, descriptions and safety nota-tions in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be con-sulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.