  • Subject: Sources and Contributors To Short Circuit Current

    From: EEP - Electrical Engineering Portal ([email protected])

    To: [email protected];

    Date: Friday, March 15, 2013 7:02 PM

    Technical articles receive 15,903 electrical engineers worldwide. Email not displaying correctly?View it in your browser.

    Published on Mar 15, 2013 01:15 am by Edvard | Subscribe to Monthly Download Updates

    Recommended - Calculate Electrical Load & Consumption of PanelForward this article to your colleagues

    Print http://us.mg1.mail.yahoo.com/dc/launch?.gx=1&retry=1#mail

    1 of 4 3/19/2013 11:16 AM

  • Sources and Contributors To Short Circuit Current (photo by M. Diskovic)

    Flow Of Electrical Energy

    Every electrical system confines electric current flow to selected paths by surrounding the conductors withinsulators of various types. Short circuit current is the flow of electrical energy that results when theinsulation barrier fails and allows current to flow in a shorter path than the intended circuit.

    In normal operation, the impedances of the electrical appliance loads limit the current flow to relativelysmall values, but a short circuit path bypasses the normal current-limiting load impedance.

    The result is excessively high current values that are limited only by the limitations of the power sourceitself and by the small impedances of the conductive elements that still remain in the path between the powersource and the short circuit point.

    Short circuit calculations are used to determine how much current can flow at certain points in theelectrical system so that the electrical equipment can be selected to withstand and interrupt that magnitudeof fault current.

    In short circuit calculations, the contribution of current sources is first determined, and then the current-limiting effects of impedances in the system are considered in determining how much current can flow in aparticular system part.

    Print http://us.mg1.mail.yahoo.com/dc/launch?.gx=1&retry=1#mail

    2 of 4 3/19/2013 11:16 AM

  • There are three basic sources of short circuit currents:

    The electrical utility1.Motors2.On-site generators3.

    There are two types of motors that contribute short circuit current:

    Induction motors1.Synchronous motors2.

    Between these sources of short circuit current and the point of the short circuit, various impedances act tolimit (impede) the flow of current and thus reduce the actual amount of short circuit current available toflow into a short circuit.

    Naturally, the value of these impedances is different at every point within an electrical system; therefore, themagnitudes of short circuit currents available to flow into a short circuit at different places within the electricalsystem vary as well.

    Several calculation methods are used to determine short circuit currents, and reasonably accurate resultscan be derived by system simplifications prior to actually performing the calculations.

    For example, it is common to ignore the impedance effect of cables except for locations where thecables are very long and represent a large part of the overall short circuit current path impedance.

    Accordingly, in the most common form of short circuit calculations, short circuit current is considered to beproduced by generators and motors, and its flow is considered to be impeded only by transformers andreactors.

    The Ability of the Electrical Utility System to Produce Short Circuit Current

    By definition, the source-fault capacity is the maximum out-put capability the utility can produce atsystem voltage.

    Generally, this value can be gotten from the electrical utility company by a simple request and is most oftengiven in amperes or kilovoltamperes.

    Suppose that the utility company electrical system interface data are given as:

    MVAsc = 2500 at 138 kilovolts (kV) with an X/R = 7 at the interface point

    For this system, the utility can deliver 2,500,000 kilovoltamperes (kVA) [138 kV(3)], or a total of 10,459symmetrical amperes (A) of short circuit current.

    The short circuit value from the electrical utility company will be added to by virtue of contributions fromthe on-site generator and motor loads within the plant or building electrical power system.

    That is, the short circuit value at the interface point with the electrical utility will be greater than just the valueof the utility contribution alone.

    Resource: EC&Ms Electrical Calculations Handbook John M. Paschal, Jr., P.E.

    Print http://us.mg1.mail.yahoo.com/dc/launch?.gx=1&retry=1#mail

    3 of 4 3/19/2013 11:16 AM

  • Jump to original technical article at EEP - Sources and Contributors To Short Circuit Current

    Category & Tags: Energy and Power, current flow, electrical utility, impedances, motors, short circuitcalculations, short circuit current, short-circuit

    Subscribe to Monthly Download Updates

    Recently published technical articles: What Is The Purpose Of Wind Farm Lighting?Defining Size and Location of Capacitor in Electrical System (2)Working Principle Of Thermal Motor Protection RelayAn Overview Of Short Circuit Current (part 3)Why Bats Are Insanely Attracted To Wind Turbines?Defining Size and Location of Capacitor in Electrical System (1)Transformer Routine Test Measurement of Voltage Ratio and Check of Phase DisplacementSuper Capacitors Different Then Others (part 2)An Overview Of Short Circuit Current (part 2)

    Share with your friends!

    Copyright 2013 EEP - Electrical Engineering Portal, All rights reserved.You're receiving this newsletter because you opted in at our website EEP forreceiving technical articles.Our mailing address is:EEP - Electrical Engineering PortalMurska 10Belgrade 11000Serbia

    Add us to your address book

    unsubscribe from this list | update subscription preferences

    Print http://us.mg1.mail.yahoo.com/dc/launch?.gx=1&retry=1#mail

    4 of 4 3/19/2013 11:16 AM