Edwards Fire Alarm Equipment

download Edwards Fire Alarm Equipment

of 45

description

Fire Alarm

Transcript of Edwards Fire Alarm Equipment

  • drawing on the best

    89024-0010T Issue 1

    mhopeLogo Stamp

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 1 of 6

    Intelligent 4D Multisensor DetectorSIGA-IPHS

    OverviewPeople detect danger by relating many observations to one another and comparing them to familiar patterns. The simultaneous use of multiple senses allow humans to filter out situations which are not dangerous. The ability to detect danger depends largely on intelligence and knowledge from past experience. GE Security 4D detectors provide both.

    The SIGA-IPHS Intelligent 4D Multisensor Detector gathers analog information from each of its three fire sensing elements (ioniza-tion, photoelectric, and heat) and converts it into digital signals. The detectors on-board microprocessor measures and analyzes these signals separately with respect to a fourth element - Time. We call this technology 4D. It compares the information to historical read-ings, time patterns and several known fire characteristics to make an alarm decision. Digital filters remove signal patterns that are not typical of fires. Unwanted alarms are virtually eliminated.

    Standard FeaturesIntegrates three sensing technologies Processes and analyzes information from each sensor (ion/pho-to/heat) separately using dynamic filters then applies a sophisti-cated algorithm for optimum detection accuracy.

    Non-volatile memory Permanently stores serial number, type of device, and job num-ber. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, time of last alarm1 and analog signal patterns for each sensing element just before last alarm.

    Automatic device mapping Each detector transmits wiring information regarding its location with respect to other devices on the circuit. Detectors installed in the wrong location during cleaning are automatically reported to the loop controller.

    Electronic addressing Permanently stores programmable address; there are no switches or dials to set. Addresses are downloaded from a PC, or the SIGA-PRO Signature Program/Service Tool.

    Environmental compensation Each sensing element self-compensates for changes in the detectors installed environment to maintain the sensitivity set-ting and prevent unwanted alarms. The detector reports when it cannot compensate any further.

    Integral microprocessor Intelligent detector All decisions are made at the detector allowing lower com-munication speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring prop-erties; twisted or shielded wire is not required.

    Wide 0.67 3.70%/ft. sensitivity range window Program the detector to operate at any one of five sensitivity settings within the window.

    Pre-alarm Detector stores one of 20 pre-alarm sensitivity values to alert local personnel prior to the sensor reaching a full evacuation sensitivity. Sensitivity values can be set in 5% increments.1

    MEA

    Application Notes Available

    CHINAS

    Life Safety SystemsIntelligent Initiating Devices

    Note: Some features described here may not be supported by all control systems. Check your control panels Installation and Opera-tion Guide for details.

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 2 of 6

    into stand-alone mode. The circuit acts like a conventional alarm receiving circuit. Each detector on the circuit continues to collect and analyze information from its surroundings. The detector alarms if the preset smoke obscuration level is reached or ambient temper-ature increases by 65oF (35oC). If the detector is mounted to a relay base, the relay operates. Similarly, if it is mounted to an audible base, the on-board horn sounds.

    Fast Stable Communication - On-board intelligence means less information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when it has something new to report. This provides very fast control panel response time and allows a lower baud rate (speed) to be used for communication on the circuit.

    Environmental Compensation - Detection sensitivity for the SIGA-IPHS is virtually independent of its installed environment and its physical condition. Environmental compensation means each sens-ing element adapts to long-term changes caused by dirt, humidity, temperature, aging etc. It even compensates for small amounts of normal ambient smoke. Approximately six times every hour, the detector adjusts and updates the sensitivity (% obscuration) and ambient temperature baselines for each sensing element. Signature Series environmental compenstion is so reliable that it meets NFPA72 field sensitivity testing requirements without the need for external meters.

    Sensitivity Range - The SIGA-IPHS has a sensitivity range or win-dow of 0.67 - 3.70% obscuration per foot. The installer selects the detectors ALARM sensitivity level. Five settings ranging from the least sensitive at 3.5% obscuration/ft to the most sensitive at 1.0% obscuration/ft are available.

    Pre-Alarm - Pre-alarm warnings may alert local staff to a possible fire condition allowing them to investigate before entering into a full alarm condition which requires building evacuation. The 4D mul-tisensors wide sensitivity range permits the use of early warning pre-alarm values. The pre-alarm value can be set by the user in 5% increments, allowing up to 20 pre-alarm settings.

    Automatic Day/Night Sensitivity Selection - Signature Series detectors may be programmed for different sensitivities during day and night periods. This allows the detector to be more sensitive dur-ing unoccupied periods when lower ambient background conditions are expected.

    Stability - The 4D detectors sensitivity remains stable in wind ve-locities up to 500 ft/min (2.53 m/sec). Ambient temperature has very little affect on the detector. The detector may be installed in rooms with ambient temperatures up to 100oF (38oC).

    Status LEDs - Twin LEDs are visible from any direction. A flashing GREEN LED shows normal system polling from the loop controller. A flashing RED LED means the detector is in alarm state. Both LEDs on steady shows alarm state - stand-alone mode. Normal GREEN LED activity is not distracting to building occupants, but can be quickly spotted by a maintenance technician.

    Electronic Addressing - The loop controller electronically addresses each detector, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each detector has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the circuit and assigns a soft address to that devices serial number. If desired, detectors can be addressed using the SIGA-PRO Signature Program/Service Tool.

    Identification of dirty or defective detector Self-diagnostic and sensitivity check provides a dirty detector signal.

    Automatic day/night sensitivity adjustment Makes detector more sensitive during inactive nighttime periods.

    Stand-alone operation The detector makes decisions and inputs an alarm even if the loop controller fails. The detector reverts to an intelligent con-ventional detector when polling interrogation stops.

    Stable design Sensitivity remains stable with air velocity up to 500 ft/min (2.53m/sec) making it suitable for direct insertion in low velocity duct applications.

    Designed for high ambient temperature operation Install in ambient temperatures up to 100 F (38 C).

    Twin status LEDs Flashing GREEN shows normal; flashing RED shows alarm state; steady RED and steady GREEN show alarm state in stand alone mode, visible from any direction.

    Standard, relay, fault isolator, and audible mounting bases Four mounting bases provide clamp terminals, allow room side wiring and include an optional tamper-resist feature.

    Designed to ISO 9001 standards Manufactured to strict international quality standards for high-est reliability.

    Signature Series OverviewThe microprocessor in each detector provides four additional ben-efits - Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication.

    Self-diagnostics and History Log - Each Signature Series detec-tor constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in the detectors non-volatile memory. This information is accessible for review any time at the control panel, PC, or by using the SIGA-PRO Signature Program/Service Tool.

    Automatic Device Mapping - The loop controller learns where each devices serial number address is installed relative to other devices on the circuit. This mapping feature provides supervision of each devices installed location to prevent a detector from being reinstalled (after cleaning etc.) in a different location from where it was originally. The history log for the detector remains relevant and intact regardless of its new location.

    The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or as-built drawing information showing wire branches (T-taps), device types and their address are stored on disk for printing hard copy. This takes the mystery out of the installation. The preparation of as-built drawings is fast and efficient.

    Stand-alone Operation - A decentralized alarm decision by the detector is guaranteed. On-board intelligence permits the detector to operate in stand-alone mode. If loop controller CPU communica-tions fail for more than four seconds, all devices on that circuit go

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 3 of 6

    Installation

    ApplicationWith intelligent 4D multisensor detectors, unwanted alarms go down to nearly zero and the detection of all types of fire increases to nearly 100%. The European standard DIN EN 54 part 9 describes six standard test fires used to rate the sensitivity of heat, ionization, and photoelectric smoke detectors. No single sensing element is equally suitable for all test fires.

    The table below shows that the 4D detector is suited for all applica-tions. Normal detector spacing guidelines should be followed.

    SIGA-IPHS detectors are compatible only with GE Securitys Signa-ture Loop Controller.

    Test Fire SIGA-IS Ion SIGA-PS Photo

    SIGA-HRS and SIGA-HFS Rate-of-Rise/ Fixed Temp.

    SIGA-PHS Photo Heat 3D

    SIGA-IPHS Ion/Photo/Heat 4D

    Open Wood optimum unsuitable optimum very suitable optimumWood Pyrolysis suitable optimum unsuitable optimum optimumSmouldering Cotton very suitable optimum unsuitable optimum optimumPoly Urethane Foam very suitable very suitable suitable very suitable optimumn-Heptane optimum very suitable very suitable optimum optimumLiquid Fire without Smoke unsuitable unsuitable optimum very suitable very suitable

    Depending on the type of fire expected in a protected space, the designer usually chooses from three types of sensor technology. Ionization sensors respond well to fast, flaming fires. Photoelectric sensors respond well to smoldering fires, and heat sensors are used as backup or in environmentally poor atmospheres for smoke detection. Agency requirements demand that ionization sensors respond to smoldering fires and that photoelectric sensors respond to flaming fires. This makes single element sensors more prone to false alarms and slow to respond to fires that are difficult for them

    to detect. Only when ALL three fire sensing elements Ionization, Photoelectric and Heat are suitably combined into one detector can ALL types of fires be effectively detected while virtually elimi-nating false alarms.

    When 4D multisensor detectors are installed, a fire alarm system does not have to be altered when the application or the type of expected fire changes. The guesswork is removed. The SIGA-IPHS 4D detector is suited for all fire detection applications.

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 4 of 6

    Typical WiringThe detector mounting bases accept #18 AWG (0.75mm2), #16 AWG (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm2) wire sizes.

    Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

    Standard Detector Base, SIGA-SB, SIGA-SB4

    Term Description 1 Not Used 2 DATA IN/OUT (+) 3 Not Used 4 DATA IN (-) 4 Remote LED (-) 5 Remote LED (+) 6 Not Used 7 DATA OUT (-)

    Term Description 1 Not Used 2 DATA IN/OUT (+) 3 DATA IN (-) 4 Not Used 5 Not Used 6 DATA OUT (-) 7 Not Used

    NOYES NO

    JUNCTION BOX

    TERMINAL STRIP

    FROMPREVIOUS

    DEVICE

    TONEXT

    DEVICE

    TOT-TAPPEDDEVICEPROPER METHOD

    FOR T-TAPS

    Isolator Detector Base, SIGA-IB, SIGA-IB4Isolator Detector Base, SIGA-IB, SIGA-IB4

    Relay Detector Base, SIGA-RB, SIGA-RB4

    Term Description 1 Normally-Open 2 DATA IN/OUT (+) 3 Common 4 DATA IN (-) 5 Not Used 6 Normally-Closed 7 DATA OUT (-)

    CONTACT RATING 1.0 Amp @ 30 VDC

    (Pilot Duty)

    SIG+ SIG-DATA-OUT

    DATA-IN

    DATA+IN/OUT

    24 Vdc inFrom power supply or

    previous base

    Data inFrom Signature controller or

    previous device

    24 Vdc outTo next base or EOL relay

    Data outTo next Signature device+

    -+

    -

    Volume setting

    Default = High volumeCut for low volume

    Tone setting

    Default = Temporal patternCut for steady tone

    +-

    +-

    To configure output volumeor tone, cut the circuit board

    as shown.

    Audible Detector Base, SIGA-AB4G

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 5 of 6

    SIGA-IB Isolator Base

    SIGA-LED Remote LED

    SIGA-RB Relay Base

    SIGA-SB Standard Base

    SIGA-AB4G Audible Base

    AccessoriesAll detector mounting bases have wiring terminals that are acces-sible from the room-side after mounting the base to the electrical box. The bases mount to North American 1-gang boxes and to 3 inch or 4 inch octagon boxes, 1 inches (38 mm) deep. They also mount to European BESA and 1-gang boxes with 60.3 mm fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to North American 4 inch sq. electrical boxes in addition to the above boxes. They include the SIGA-TS4 Trim Skirt which is used to cover the mounting ears on the base. The SIGA-AB4G mounts to a 4 sqare box only.

    Standard Base SIGA-SB, SIGA-SB4 - This is the basic mounting base for GE Security Signature Series detectors. The SIGA-LED Remote LED is supported by the Standard Base.

    Relay Base SIGA-RB, SIGA-RB4 - This base includes a relay. Nor-mally open or closed operation is selected during installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relays posi-tion is supervised to avoid accidentally jarring it out of position. The SIGA-RB can be operated as a control relay if programmed to do so at the control panel (EST3 V. 2 only). The relay base does not support the SIGA-LED Remote LED.

    Audible Base SIGA-AB4G - This base is designed for use where local-ized or group alarm signaling is required. When the detector senses an alarm condition, the audible base emits a local alarm signal. The optional SIGA-CRR Polarity Reversal Relay can be used for sounding

    to other audible bases on the same 24 Vdc circuit.

    Relay and Audible Bases operate as follows:

    - at system power-up or reset, the relay is de-energized.

    - when a detector is installed in the base with the power on, the relay energizes for four seconds, then de-energizes.

    - when a detector is removed from a base with the power on, the relay is de-energized.

    - when the detector enters the alarm state, the relay is energized.

    Isolator Base SIGA-IB, SIGA-IB4 - This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate. The isolator base does not support the SIGA-LED Remote LED.

    The isolator operates as follows:

    - a short on the line causes all isolators to open within 23 msec

    - at 10 msec intervals, beginning on one side of the Class A circuit nearest the loop controller, the isolators close to provide the next isolator down the line with power

    - when the isolator next to the short closes, it reopens within 10 msec.

    The process repeats beginning on the other side of the loop control-ler.

    Remote LED SIGA-LED - The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base only. It features a North American size 1-gang plastic faceplate with a white finish and red alarm LED.

    SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be ordered separately to use with the other bases to help hide surface imperfections not covered by the smaller bases. Use black model (SIGA-TSB) with SIGA-IPHSB.

    Testing & MaintenanceEach detector automatically identifies when it is dirty or defective and causes a dirty detector message. The detectors sensitiv-ity measurement can also be transmitted to the loop controller. A sensitivity report can be printed to satisfy NFPA sensitivity measure-ments which must be conducted at the end of the first year and every two years thereafter.

    The user friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors may be turned off temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used.

    Scheduled maintenance (Regular or Selected) for proper detector operation should be planned to meet the requirements of the Au-thority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

    Warnings and CautionsThis detector will not operate without electrical power. As fires fre-quently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist.

    This detector will NOT sense fires that start in areas where smoke or heat cannot reach the detector. Smoke or heat from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector to alarm it.

    The heat sensor in this device only provides a source of information to supplement the information provided by the ionization and pho-toelectric smoke sensors. The heat sensor by itself does NOT protect life against fire and smoke.

  • Data Sheet 85001-0245 Issue 7Not to be used for installation purposes. Page 6 of 6

    U.S.T 888-378-2329F 866-503-3996

    CanadaT 519 376 2430F 519 376 7258

    AsiaT 852 2907 8108F 852 2142 5063

    AustraliaT 61 3 9259 4700F 61 3 9259 4799

    EuropeT 32 2 725 11 20F 32 2 721 86 13

    Latin AmericaT 305 593 4301F 305 593 4300

    www.gesecurity.com

    2006 General Electric CompanyAll Rights Reserved

    Ordering InformationCatalog Number

    Description Ship Wt. lbs (kg)

    SIGA-IPHS Intelligent 4D Multisensor Detector - UL/ULC Listed 0.5 (.23)SIGA-IPHSB Intelligent 4D Multisensor Detector (Black) - UL/ULC Listed

    AccessoriesSIGA-SB Detector Mounting Base

    0.2 (.09)SIGA-SB4 4 inch Detector Mounting Base c/w SIGA-TS4 Trim SkirtSIGA-RB Detector Mounting Base w/RelaySIGA-RB4 4 inch Detector Mounting Base w/Relay c/w SIGA-TS4 Trim SkirtSIGA-IB Detector Mounting Base w/Fault IsolatorSIGA-IB4 4 inch Detector Mounting Base w/Fault Isolator c/w SIGA-TS4 Trim Skirt

    0.2 (.09)SIGA-LED Remote Alarm LED SIGA-AB4G Audible (Sounder) Base 0.3 (0.15)SIGA-TS4 Trim Skirt (supplied with 4 inch bases)

    0.1 (.04)SIGA-TSB Trim Skirt - Black (use with black detector)SIGA-TS Trim Skirt - (optional for non-4 bases)

    SpecificationsAgency Listings UL, ULC, CSFM, MEAIon Sensor (unipolar) 0.135C Americium 241Photo Sensor Light Scattering PrincipleHeat Sensor Alarms at 65F (35C) above ambientStorage and Operating Environment

    Air Velocity Range: 0 to 500 ft/min (0 to 2.53 m/s) Operating Temperature: 32F to 100F (0C to 38C) Storage Temperature: -4F to 140F (-20Cto 60C) Humidity: 0 to 93% RH, Non-condensing Altitude: 6,000 ft. (1828m) above sea level maximum

    Sensitivity Range ULI/ULC - 0.67% to 3.70% obscuration/foot User Selected Alarm Sensitivity Settings

    Most Sensitive: 1.0%/ft. More Sensitive: 2.0%/ft. Normal: 2.5%/ft. Less Sensitive: 3.0%/ft Least Sensitive: 3.5%/ft.

    Pre-alarm Sensitivity 5% increments, allowing up to 20 pre-alarm settingsOperating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)Operating Current Quiescent: 45A @ 19 V Alarm: 45A @ 19 V Emergency Stand-alone

    Alarm Mode: 18mA Pulse Current: 100A (100 msec)Construction & Finish High-Impact Engineering Polymer - White or BlackCompatible Mounting Bases

    SIGA-SB Standard Base, SIGA-RB Relay Base, SIGA-IB Isolator Base, SIGA-AB4, AB4G Audible Bases

    LED Operation On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm Both LEDs - Glow steady when in alarm (stand-alone) Compatible Remote Red LED (model SIGA-LED) Flashes when in alarm

    Compatibility Use With Signature Loop ControllerAddress Requirements Uses one Device AddressUL Listed Spacing 30 ft.

    Signature Series is a Trademark of GE Security.

  • Data Sheet 85001-0241 Issue 6Not to be used for installation purposes. Page 1 of 4

    Life Safety SystemsIntelligent Input/Output

    Input ModulesSIGA-CT1, SIGA-CT2 & SIGA-MCT2

    OverviewThe SIGA-CT1 Single Input Module and SIGA-CT2/SIGA-MCT2 Dual Input Modules are intelligent analog addressable devices used to connect one or two Class B normally-open Alarm, Supervisory, or Monitor type dry contact Initiating Device Circuits (IDC).

    The actual function of these modules is determined by the personality code selected by the installer. This code is downloaded to the module from the Signature loop controller during system configuration.

    The input modules gather analog information from the initiating devices connected to them and convert it into digital signals. The modules on-board microprocessor analyzes the signal and decides whether or not to input an alarm.

    The SIGA-CT1 and SIGA-CT2 mount to standard North American 1-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module.

    The SIGA-MCT2 is part of the UIO family of plug-in Signature Series modules. It functions identically to the SIGA-CT2, but takes advan-tage of the modular flexibility and easy installation that character-izes all UIO modules. Two- and six-module UIO motherboards are available. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in GE Security enclosures.

    Standard FeaturesMultiple applications Including Alarm, Alarm with delayed latching (retard) for water-flow applications, Supervisory, and Monitor. The installer selects one of four personality codes to be downloaded to the module through the loop controller.

    Plug-in (UIO) or standard 1-gang mount UIO versions allow quick installation where multiple modules are required. The 1-gang mount version is ideal for remote locations that require a single module.

    Automatic device mapping Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop.

    Electronic addressing Programmable addresses are downloaded from the loop control-ler, a PC, or the SIGA-PRO Signature Program/Service Tool. There are no switches or dials to set.

    Non-volatile memory Permanently stores serial number, type of device, and job number.

    Stand-alone operation The module makes decisions and inputs an alarm from initiating devices connected to it even if the loop controllers polling interro-gation stops. (Function availability dependent upon control panel.)

    Ground fault detection by address Detects ground faults right down to the device level.

    SIGA-CT1/2

    SIGA-MCT2

    MEAApplication Notes

    Available

    CHINAS

  • Data Sheet 85001-0241 Issue 6Not to be used for installation purposes. Page 2 of 4

    InstallationSIGA-CT1 and SIGA-CT2: modules mount to North American 2 inch(64 mm) deep 1-gang boxes and 1 inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

    ApplicationThe duty performed by the SIGA-CT1 and SIGA-CT2/MCT2 is de-termined by their sub-type code or Personality Code. The code is selected by the installer depending upon the desired application and is downloaded from the loop controller.

    One personality code can be assigned to the SIGA-CT1. Two person-ality codes can be assigned to the SIGA-CT2/MCT2. Codes 1, 2, 3 and 4 can be mixed on SIGA-CT2/MCT2 modules only. For example, personality code 1 can be assigned to the first address (circuit A) and code 4 can be assigned to the second address (circuit B).

    NORMALLY-OPEN ALARM - LATCHING (Personality Code 1) - As-sign to one or both circuits. Configures either circuit A or B or both for Class B normally open dry contact initiating devices such as Pull Stations, Heat Detectors, etc. An ALARM signal is sent to the loop controller when the input contact is closed. The alarm condition is latched at the module.

    NORMALLY-OPEN ALARM - DELAYED LATCHING (Personality Code 2) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally-open dry contact initiating devices such as Waterflow Alarm Switches. An ALARM signal is sent to the loop controller when the input contact is closed for approximately 16 seconds. The alarm condition is latched at the module.

    NORMALLY-OPEN ACTIVE - NON-LATCHING (Personality Code 3) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally-open dry contact monitoring input such as from Fans, Dampers, Doors, etc. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is not latched at the module.

    NORMALLY-OPEN ACTIVE - LATCHING (Personality Code 4) - Assign to one or both circuits. Configures either circuit A or B or both for Class B normally open dry contact monitoring input such as from Supervisory and Tamper Switches. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condi-tion is latched at the module.

    FIREALAR

    M

    MODULE

    Compatible electrical box

    Wall plate, white(1-gang)

    SIGA-MCT2: mount the UIO motherboard inside a suitable GE Secu-rity enclosure with screws and washers provided. Plug the SIGA-MCT2 into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard (see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

    Signature Series OverviewThe Signature Series intelligent analog-addressable system from GE Security is an entire family of multi-sensor detectors and mount-ing bases, multiple-function input and output modules, network and non-network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microprocessor in each Signature device provides four addi-tional benefits Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication.

    Self-diagnostics and History Log Each Signature Series device constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This informa-tion is accessible for review any time at the control panel, PC, or using the SIGA-PRO Signature Program/Service Tool.

    Automatic Device Mapping The Signature Data Controller (SDC) learns where each devices serial number address is installed rela-tive to other devices on the circuit. The SDC keeps a map of all Sig-nature Series devices connected to it. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or as-built drawing information showing branch wiring (T-taps), device types and their address are stored on disk for printing hard copy.

    #6 Flat washers

    6-32Self-tappingscrews

    UIO Motherboard

    Plug-in (UIO)Module

    Captivescrews

    Cabinet or electrical enclosure

    Electronic Addressing - The loop controller electronically addresses each module, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a soft address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool.

    GE Security recommends that this module be installed according to latest recognized edition of national and local fire alarm codes.

  • Data Sheet 85001-0241 Issue 6Not to be used for installation purposes. Page 3 of 4

    Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), and #14AWG (1.50mm2), and #12 AWG (2.50mm2) wire sizes.

    Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

    Warnings & CautionsThis module will not operate without electrical power. As fires fre-quently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

    CompatibilityThe Signature Series modules are compatible only with GE Securi-tys Signature Loop Controller.

    SIGA-CT1

    UL/ULC Listed47K EOL

    1 2 4

    1 2 3 4

    4321

    4321

    TB14

    TB15Green LED (Normal)

    SIGA-MCT2

    SIGA-UIO(R) series motherboard

    No connections required forSIGA-MCT2

    Other modules may requireconnections.

    No connections or jumper settingsrequired for SIGA-MCT2.

    UL/ULC Listed47K EOL

    Red LED (Active)

    1 2 3 4

    CATNO.

    SIGA-M

    CT2

    4733

    8735

    1EDWARDSSYSTEMSTECHNOLO

    GY

    Data In

    3

    TB7

    SignatureDataCircuit

    Data Out

    4321

    Typical NO Initiating Device

    Input 2 Input 1

    5

    SIGA-MCT2

    SIGA-CT2

    Initiating (Slave) Device Circuit Wire SpecificationsMaximum Allowable Wire Resistance 50 ohms (25 ohms per wire) per Circuit

    Maximum Allowable Wire Capacitance 0.1F per Circuit

    For Design Reference: Wire Size Maximum Distance to EOLR

    #18 AWG (0.75 mm)

    4,000 ft (1,219 m)#16 AWG (1.00 mm)

    #14 AWG (1.50 mm)

    #12 AWG (1.50 mm)

    NOTES

    1 Maximum 25 Ohm resistance per wire.

    2 Maximum #12 AWG (2.5 mm ) wire; Minimum #18 AWG (0.75 mm2).

    3 Refer to Signature controller installation sheet for wiring specifications.

    4 Maximum 10 Vdc @ 350 A

    5 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.

    6 All wiring is supervised and power-limited.

    7 These modules will not support 2-wire smoke detectors.

  • Data Sheet 85001-0241 Issue 6Not to be used for installation purposes. Page 4 of 4

    U.S.T 888-378-2329F 866-503-3996

    CanadaT 519 376 2430F 519 376 7258

    AsiaT 852 2907 8108F 852 2142 5063

    AustraliaT 61 3 9259 4700F 61 3 9259 4799

    EuropeT 32 2 725 11 20F 32 2 721 86 13

    Latin AmericaT 305 593 4301F 305 593 4300

    www.gesecurity.com

    2006 General Electric CompanyAll Rights Reserved

    SpecificationsCatalog Number SIGA-CT1 SIGA-CT2 SIGA-MCT2Description Single Input Module Dual Input Module

    Type Code 48 (factory set) Four sub-types (personality

    codes) are available

    49 (factory set) Four sub-types (personality codes) are available

    Address Requirements Uses One Module Ad-dress

    Uses Two Module Addresses

    Operating Current Standby = 250A; Activated = 400A

    Standby = 396A; Activated = 680A

    Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)

    Construction High Impact Engineering Polymer

    Mounting North American 2 inch (64 mm) deep one-gang boxes and 1 inch (38 mm) deep 4 inch square

    boxes with one-gang covers and SIGA-MP mounting plates

    UIO2R/6R/6 Mother-board

    Storage and Operating Environment

    Operating Temperature: 32F to 120F (0C to 49C) Storage Temperature: -4F to 140F (-20C to 60C); Humidity: 0 to 93% RH

    LED Operation On-board Green LED - Flashes when polled; On-board Red LED - Flashes when in alarm/active Both LEDs - Glow steady when in alarm (stand-alone)

    Compatibility Use with Signature Loop Controller

    Agency Listings UL, ULC, MEA, CSFM

    Ordering InformationCatalog Number

    Description Ship Wt. lbs (kg)

    SIGA-CT1 Single Input Module UL/ULC Listed 0.4 (0.15)SIGA-CT2 Dual Input Module UL/ULC Listed 0.4 (0.15)SIGA-MCT2 Dual Input Plug-in (UIO) Module UL, ULC Listed 0.1 (0.05)

    Related Equipment27193-11 Surface Mount Box - Red, 1-gang 1.0 (0.6)27193-16 Surface Mount Box - White, 1-gang 1.0 (0.6)SIGA-UIO2R Universal Input-Output Module Board w/Riser Inputs

    Two Module Positions0.32 (0.15)

    SIGA-UIO6R Universal Input-Output Module Board w/Riser Inputs Six Module Positions

    0.62 (0.28)

    SIGA-UIO6 Universal Input-Output Module Board Six Module Positions 0.56 (0.25)MFC-A Multifunction Fire Cabinet Red, supports Signature Module

    Mounting Plates7.0 (3.1)

    SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)

    Signature Series is a Trademark of GE Security.

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page 1 of 6

    EST Fire & Life SafetyIntelligent Input/Output

    GESecurity

    OverviewThe Control Relay Module and the Polarity Reversal Relay Module are part of the Signature Series system. They are intelligent analog addressable devices available in either plug-in (UIO) versions, or standard 1-gang mount versions.

    The SIGA-CR/MCR Control Relay Module provides a Form C dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon com-mand from the loop controller, the SIGA-CR/MCR relay activates the normally open or normally-closed contact.

    The SIGA-CRR/MCRR Polarity Reversal Relay Module provides a Form C dry relay contact to power and activate a series of SIGA-AB4G Audible Sounder Bases. Upon command from the Signature loop controller, the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop.

    Standard-mount versions (SIGA-CR and SIGA-CRR) are installed to standard North American 1-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module.

    Plug-in uIO versions (SIGA-MCR and SIGA-MCRR) are part of the UIO family of plug-in Signature Series modules. They function identically to the standard mount versions, but take advantage of the modular exibility and easy installation that characterizes all UIO modules. Two- and six-module UIO motherboards are available. All wiring connections are made to terminal blocks on the mother-board. UIO assemblies may be mounted in GE Security enclosures.

    Control Relay ModulesSIGA-CR, SIGA-MCR, SIGA-CRR, SIGA-MCRR

    Standard FeaturesProvides one no/nc contact (SIGA-CR/MCR)Form C dry relay contact can be used to control external appli-ances such as door closers, fans, dampers etc.

    Allows group operation of sounder basesThe SIGA-CRR/MCRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop.

    Plug-in (uIO) or standard 1-gang mountUIO versions allow quick installation where multiple modules are required. The 1-gang mount version is ideal for remote locations that require a single module.

    Automatic device mappingSignature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop.

    Electronic addressingProgrammable addresses are downloaded from the loop con-troller, a PC, or the SIGA-PRO Signature Program/Service Tool; there are no switches or dials to set.

    Intelligent device with microprocessorAll decisions are made at the module to allow lower communica-tion speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties; twisted or shielded wire is not required.

    Ground fault detection by addressDetects ground faults right down to the device level.

    SIGA-CR

    SIGA-MCR

    MEA

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page 2 of 6

    InstallationSIGA-CR and SIGA-CRR: modules mount to North American 2 inch (64 mm) deep 1-gang boxes and 1 inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

    FIREALAR

    M

    MODULE

    Compatible electrical box

    Wall plate, white(1-gang)

    SIGA-MCR and SIGA-MCRR: mount the UIO motherboard inside a suitable GE Security enclosure with screws and washers provided. Plug the module into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard (see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.

    #6 Flat washers

    6-32Self-tappingscrews

    UIO Motherboard

    Plug-in (UIO)Module

    Captivescrews

    Cabinet or electrical enclosure

    Electronic Addressing - The loop controller electronically addresses each module, saving valuable time during system commissioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a soft address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool.

    GE Security recommends that this module be installed according to latest recognized edition of national and local fire alarm codes.

    ApplicationThe operation of Signature Series control relays is determined by their sub-type code or Personality Code.

    Personality Code 8: CONTROL RELAY (SIGA-CR/MCR) - Dry Contact Output. This setting configures the module to provide one Form C DRY RELAY CONTACT to control Door Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @ 24 Vdc; 0.5 amp @ 120 Vac (or 220 Vac for non-UL applications). Personality Code 8 is assigned at the fac-tory. No user configuration is required.

    Personality Code 8: POLARITY REvERSAL RELAY MODuLE (SIGA-CRR/MCRR). This setting configures the module to reverse the polarity of its 24 Vdc output. Contact rating is 2.0 amp @ 24 Vdc (pilot duty). Personality Code 8 is assigned at the factory. No user configuration is required.

    CompatibilityThe Signature Series modules are compatible only with GE Securi-tys Signature Loop Controller.

    Warnings & CautionsThis module will not operate without electrical power. As fires fre-quently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

    Testing & MaintenanceThe modules automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance pro-gram shows the current state of each module and other pertinent messages. Single modules may be turned off (deactivated) tempo-rarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page 3 of 6

    SIGA-CR Control Relay

    Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.5mm2) wire sizes.

    Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

    4321

    4321

    TB14

    TB15Green LED (Normal)

    Red LED (Active)

    TB7

    4321

    1

    Data Out

    Data In

    CAT

    NO

    .M

    CR

    4733

    8735

    8

    2

    1 2 3 4

    3

    4

    Normally Open Normally ClosedCommon

    1 2 3 4

    No connections required forMCR. Other modules mayrequire connections.

    No connections required forMCR. Other modules mayrequire connections.

    SIGA-MCR Control Relay

    Notes

    1 RefertoSignatureLoopControllerInstallationSheetforwiringspecifications.

    2 NFPA72requiresthattheSIGA-CR/SIGA-MCRbeinstalledinthesameroomasthedeviceitiscontrol-ling.Thisrequirementmaynotapplyinallmarkets.CheckwithyourlocalAHJfordetails.

    3 TheSIGA-UIO6RandtheSIGA-UIO2RdonotcomewithTB14.

    4 TheSIGA-UIO6doesnotcomewithTB8throughTB13.

    5 Supervisedandpower-limited.

    6 Ifthesourceisnonpower-limited,maintainaspaceof1/4inchfrompower-limitedwiringoruseFPL,FPLP,FPLR,oranequivalentinaccordancewiththeNationalElectricalCode.

    7) Maximum#12AWG(2.5mm2)wire.Min.#18(0.75mm2).

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page of 6

    AB4GAudible Base

    AB4GAudible Base

    Optional CRfor disabling/disconnectingsounder base

    21

    1

    AB4GAudible Base

    +

    -

    +

    +

    -

    CR

    -+Signature

    Controller DATA

    CRR

    Listed 24 VDCNominal Power

    Supply

    CT1

    6254A-003EOL Relay

    2

    3 3

    2 2

    2

    3

    33

    3

    2

    1

    SIGA-CRR

    Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.50mm2) wire sizes.

    Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

    Data Out

    or

    4321

    4321

    TB14

    TB15Green LED (Normal)

    Green LED (Normal)

    Red LED (Active)

    Red LED (Active)CAT

    NO

    .

    CAT

    NO

    .

    MC

    RR

    4733

    8736

    0

    MC

    RR

    4733

    8735

    9

    5

    1 12 23 34 4

    7

    8

    6 6

    No connections required forMCRR. Other modules mayrequire connections.

    No connections required forMCRR. Other modules mayrequire connections.

    No connections required for MCRR. Othermodules may require connections.

    1 2 3 4

    UIO(R) series motherboard

    MCRR

    Optional MCRRor MCR fordisabling/disconnectingan audible base.

    4

    8

    3

    7

    2 1

    CT11

    23

    4

    1011

    98

    76

    5

    AudibleBases

    6254A-003EOL Relayrequired forsupevision

    SignatureDataCircuit

    UL/ULC Listed24 Vdc powersupply

    1 2 3 4

    For normal operation

    For General FireAlarm Operation

    TB7

    Data Out

    Data In

    4321

    17

    SignatureDataCircuit

    DAT

    A (+

    ) IN

    /OU

    T

    DAT

    A (-

    ) IN

    DAT

    A (-

    ) OU

    T

    SIG

    +

    SIG

    -

    SIGA-MCRR

    SIGA-CRR SchematicPower In Power Out

    Polarity reverseswhen activated.

    SIGA-CRR Schematic SIGA-MCRR Schematic

    Notes 1 Refer to the Signature controller installation sheet for

    wiring.

    2 One Pair of Wires (24 Vdc power).

    3 One Pair of Wires (Signature Data).

    4 Single Wire (24 Vdc power).

    5 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.

    6 The SIGA-UIO6 does not come with TB8 through TB13.

    7 Supervised and power-limited.

    8 If the source is nonpower-limited, maintain a space of 1/4 inch from power-limited wiring or use FPL, FPLP, FPLR, or an equivalent in accordance with the National Electrical Code.

    9 Maximum #12 AWG (2.5 mm ) wire; Minimum #18 AWG (0.75 mm ).

    10 End-of-Line Relay must monitor and report power sup-ply trouble to control panel.

    11 Class B Data wiring may be T-tapped.

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page 5 of 6

    Specifications

    Ordering Information

    Catalog Number SIGA-CR SIGA-MCR SIGA-CRR SIGA-MCRR

    Description Control Relay Polarity Reversal Relay

    Type Code Personality Code 8 (Factory Set) Personality Code 8 (Factory Set)

    Address Requirements Uses 1 Module Address

    Operating Current Standby = 100A Activated = 100A

    Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)

    Relay Type and Rating Form C 24 VDC = 2 amps (pilot duty) 120 Vac = 0.5 amps 220 Vac (non-UL) = 0.5 amps

    Mounting North American 2 inch (64 mm) deep 1-gang boxes and 1 inch (38 mm) deep 4 inch square boxes with

    1-gang covers and SIGA-MP mounting plates

    Plugs into UIO2R, UIO6R or UIO6 Motherboards

    North American 2 inch (64 mm) deep 1-gang boxes and 1 inch (38 mm) deep 4 inch square boxes with

    1-gang covers and SIGA-MP mounting plates

    Plugs into UIO2R, UIO6R or UIO6 Motherboards

    Construction & Finish High Impact Engineering Polymer

    Storage and Operating Environment

    Operating Temperature: 32F to 120F (0C to 49C) Storage Temperature: -4F to 140F (-20C to 60C) Humidity: 0 to 93% RH

    LED Operation On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm/active

    Compatibility Use With: Signature Loop Controller

    Agency Listings UL, ULC, CSFM, MEA

    Catalog Number Description Ship Weight - lbs (kg)

    SIGA-CR Control Relay Module (Standard Mount) 0.4 (0.15)

    SIGA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)

    SIGA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)

    SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)

    Related Equipment

    27193-11 Surface Mount Box - Red, 1-gang 1 (0.6)

    27193-16 Surface Mount Box - White, 1-gang 1 (0.6)

    SIGA-UIO2R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)

    SIGA-UIO6R Universal Input-Output Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)

    SIGA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)

    SIGA-AB4G Audible (Sounder) Detector Base 0.3 (0.15)

    Accessories

    MFC-A Multifunction Fire Cabinet - Red, supports Signature Module Mounting Plates 7.0 (3.1)

    SIGA-MB4 Transponder Mounting Bracket (allows for mounting two 1-gang modules in a 2-gang box) 0.4 (0.15)

    SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)

    SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)

    SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)

  • Data Sheet 85001-0239 Issue 7.2Not to be used for installation purposes. Page 6 of 6

    U.S.T 888-378-2329F 866-503-3996

    CanadaT 519 376 2430F 519 376 7258

    AsiaT 852 2907 8108F 852 2142 5063

    AustraliaT 61 3 9259 4700F 61 3 9259 4799

    EuropeT 32 2 725 11 20F 32 2 721 86 13

    Latin AmericaT 305 593 4301F 305 593 4300

    www.gesecurity.com/est

    2006 General Electric CompanyAll Rights Reserved

    GESecurity

    Signature Series OverviewThe Signature Series intelligent analog-addressable system from GE Security is an entire family of multi-sensor detectors and mounting bases, multiple-function input and out-put modules, network and non-network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microprocessor in each Signature device provides four additional benefits Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Com-munication.

    Self-diagnostics and History Log Each Signature Series device constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This information is accessible for review any time at the control panel, PC, or using the SIGA-PRO Signature Program/Service Tool. The information stored in device memory includes:

    Device serial number, address, and type

    Time and date of last alarm

    Most recent trouble code logged by the detector 32 possible trouble codes may be used to diagnose faults.

    Automatic Device Mapping The Signature Data Controller (SDC) learns where each devices serial number address is installed relative to other devices on the circuit. The SDC keeps a map of all Signature Series devices connected to it . The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or as-built drawing informa-tion showing branch wiring (T-taps), device types and their address are stored on disk for printing hard copy. This takes the mystery out of the installation. The preparation of as-built drawings is fast and efficient.

    Device mapping allows the Signature Data Controller to discover:

    Unexpected additional device addresses

    Missing device addresses

    Changes to the wiring in the circuit.

    Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the SDC during system configura-tion and are indicated during device mapping.

    Standalone Operation A decentralized alarm decision by the device is guaranteed. On-board intelligence permits the device to operate in standalone (degrade) mode. If Signature loop controller CPU communications fail for more than four seconds, all devices on that circuit go into standalone mode. The circuit acts like a conventional alarm receiving circuit. Each Signature device on the circuit continues to collect and analyze information from its slave devices. When connected to a panel utilizing standalone operation, modules with their personality set as alarm devices (IDC) will alarm should their slave alarm-initiating device activate.

    Signature Series is a Trademark of GE Security.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 1 of 8

    Life Safety SystemsFire Suppression

    OverviewThe SIGA-REL is an analog addressable module that communi-cates directly with the fire alarm panel Signature loop controller. The SIGA-REL controls sprinkler, pre-action and deluge systems, and may also be used to release extinguishing agents such as CO2, Halon, or foam. The module is easily configured in the field and of-fers a wide range of options that ensure dependable service, while preventing the unnecessary release of extinguishing agent.

    In addition to being an intelligent network component, the SIGA-REL interfaces with a number of conventional devices. These provide manual actuation of abort, release, and service disconnect func-tions. Together with the SIGA-REL, they comprise a complete fire suppression package. There is no need for a separate releasing panel because the SIGA-REL takes full advantage of the existing control panel communications infrastructure. This ensures low-cost installations with all the benefits of Signature Series analog initia-tion and control.

    Seven on-board circuits provide added flexibility. Each SIGA-REL hosts:

    Two supervised Class B release circuitsTwo supervised Class B pre-release NACsOne supervised Class B manual release input circuit (latching)One supervised Class B abort circuit for normally-open abort switch (non-latching)One first alarm output relay (Form C contact)

    The SIGA-REL also includes a series of built-in timers that determine the duration of abort routines and release sequences. These timers are easily configured in the field and provide a highly flexible range of options.

    Standard FeaturesIdeal for sprinkler, pre-action and deluge systems Suitable a wide range of sprinkler applications and extinguishing agents such as CO2 and Halon.

    Built-in timers Selectable durations for abort, manual, and automatic delays.

    Four abort modes Field-configurable abort routines determine how the timers operate when the abort function is initiated.

    Supervised circuitry you can rely on Two Class B release circuits and two pre-release circuits pro-vided.

    Manual operation keeps ultimate control in plain view The SIGA-REL features a manual release input circuit as well as a manual abort input circuit.

    Fully automated response leaves nothing to chance This modules Form C relay is ideal for room preparation rou-tines.

    Unprecedented compatibility The SIGA-REL is compatible with any solenoid that is both UL-listed and FM-approved.

    Automatic device mapping simplifies installation Signature modules transmit directly to the loop controller their circuit locations with respect to other Signature devices on the wire loop.

    Patented

    Releasing ModuleSIGA-REL

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page of 8

    Understanding the SIGA-REL

    The SIGA-REL Releasing Module is a network component that pro-vides control for fire suppression routines. It fulfils much the same purpose as a standalone releasing panel, but supports Signature Series detectors as an integral part of the suppression system. The SIGA-REL is easy to set up and accepts programming via the control panels SDU Rules Editor.

    The diagram below represents typical application of the SIGA-REL. The explanations that follow summarize each element of the module.

    Signature loop controller

    MRA

    M

    Fire alarm control panel

    Release Circuit 2

    RELA-EOL Release Circuit 1

    M

    SD

    RELA-EOLSD

    M

    SD

    A

    MR

    Signature Series smoke detectors

    Signature Series modules

    Horn circuit

    Strobe circuit

    Service Disconnect Station

    Manual Abort Station

    Manual Release Station

    First Alarm Output Relay

    Releasing Module

    Release Circuits. The SIGA-REL includes two supervised release circuits, each of which provides fire suppression control to different areas of a protected space. The releasing circuits actuate solenoids on the suppression agent tanks according to pre-de-fined release routines. These solenoids release the agent into the protected area. Both circuits operate together.

    First Alarm Relay. This on-board relay provides a Form C con-tact that activates at the first alarm input or manual release. The relay is typically used for room preparation such as controlling fans and dampers in advance of the release of suppression agent.

    Pre-release. Pre-release circuits are used to provide power to notification appliances located within the protected are. Two supervised pre-release circuits are provided: one (steady) for visual notification appliances, and one (pulsed) for audible notifica-tion appliances. The pre-release circuits activate with the start of the automatic delay timer.

    Manual Release. The manual release circuit is used to acti-vate the suppression system by means of a connected normally-open release station. This initiates the manual release sequence according to a pre-defined routine. The manual release circuit is supervised and latching. Input from this circuit is processed at the module communication with the control panel is not necessary.

    Abort. The abort circuit is used to prevent the release of agent into the protected area after the release sequence has begun, but before the automatic delay timer expires. A connected normally-open release station provides manual control over this circuit. The abort circuit is supervised and non-latching.

    Service Disconnect. The service disconnect switch is used to temporarily disable the fire suppression system. There is no dedicated circuit for this switch. Instead, it is installed on both release circuits between the SIGA-REL and the RELA-EOL end-of-line relay. Opening the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel.

    Data. The Signature data circuit provides an input and an output to the data loop that communicates with the Signature loop controller at the control panel. The SIGA-REL resides on the same data loop as the Signature Series detectors that initiate the automatic release sequence. This close association offers the most reliable performance and ensures compliance with prevail-ing life safety codes.

    Power. The SIGA-REL requires 24 Vdc (power limited). See the specification table for details.

    ApplicationUnderstanding fire suppression

    Fire suppression today is an important part of a growing number of life safety installations. With an ever-increasing reliance on mis-sion-critical computer systems and record high capital investment in high-tech production facilities, businesses large and small are looking for a means of protecting their investments and ensuring a fire wont cripple their operations.

    While fire detection remains the first line of defense against the risks of fire to people, building owners are looking to fire suppres-sion as a means of protecting their property and assets.

    But its a well known fact that fire suppression is a double-edged sword: water can snuff out a mission-critical computer system as easily as it can a fire. Alternatives to water, including carbon dioxide and other extinguishing agents can endanger lives, while the release of even the most inert extinguishing agents can disrupt operations and cost millions of dollars in down-time and lost pro-duction.

    A primary goal of any fire suppression system is to prevent the re-lease of extinguishing agent unless it is absolutely necessary. There is no margin for error. But no matter what measures are taken to prevent the unwanted release of extinguishing agent, the fact remains that no suppression system is any better than the detec-tors it relies on for input. The foundation of an effective suppression system, therefore, rests firmly on the quality and reliability of its smoke detectors.

    Signature Series detectors form an integral part of the suppres-sion system built around the SIGA-REL releasing module. These detectors provide unsurpassed reliability and immunity from false alarms. The SIGA-REL is engineered to the same exacting standards of quality and performance. With a robust set of features designed to eliminate any unwanted release of extinguishing agent, the SIGA-REL provides all the benefits of a dedicated releasing panel without the extra expense, and equally important, all the proven advantages of the Signature Series family of products.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 3 of 8

    OperationThe SIGA-REL has several built-in safeguards to prevent the un-wanted release of extinguishing agent. All release sequences are subject to configurable delay timers that provide the opportunity for an occupant of the area to manually abort the release se-quence. If no abort signal is received before the delay timer expires, the suppression agent is released.

    The SIGA-REL includes three delay timers: one for manual release sequences (up to 30 seconds); one for automatic release sequences (up to 50 seconds); and one for abort sequences (10 seconds).

    Normal State

    In its normal operating state the SIGA-REL supervises both of its release circuits and both of its pre-release NAC circuits for faults. Should a short or open occur on any of these circuits, a Trouble condition is reported to the control panel.

    A trouble condition on any of these circuits may prevent the opera-tion of that circuit, but it wont inhibit the operation of any other fault-free circuit.

    Manual Release Sequence

    The operation of a manual release station initiates the manual release sequence. The diagram below outlines the manual release sequence.

    Manual release activated

    Agent release

    System reset (manually at the control panel)

    Release circuits

    First alarm relay

    Time Line (see details below)

    Manual delay timer

    Pre-release circuits

    Selectable manualdelay time

    (0 to 30 seconds)

    Note: A manual release sequence cannot be aborted.

    Manual Release Time Line

    An active manual release station disables automatic operation and the abort function and simultaneously activates the:

    Manual delay timer Pre-release circuit Pre-release strobe circuit (steady On) Pre-release horn circuit (60 pulses per minute)

    Ten seconds before the expiration of the manual delay timer, the pre-release horn changes from 60 pulses per minute to steady On.

    The manual delay timer expires and the release circuits activate.

    A manual reset at the fire alarm control panel deactivates the release solenoids and the Releasing Module returns to the normal state.

    Automatic Release Sequence

    The automatic release sequence requires an AND group (cross zone) or a matrix group (counting zone). AND groups and matrix groups require fire alarm signals from designated Signature Series devices. These logic groups are programmable through a laptop computer and the System Definition Utility (SDU).

    Note: EST2 systems do not support matrix groups. See Program-ming the SIGA-REL for AND group rules. To create AND groups and matrix groups, see the System Programming Manual and the SDU Online Help for your system.

    The diagram below outlines the automatic release sequence.

    First alarm

    Active signal from AND group (e.g.: Second alarm)

    Agent release

    System reset

    Release circuits

    Pre-release circuits

    First alarm relay

    Automatic delay timer

    Time Line (see details below)

    Selectable automaticdelay time

    (10 to 50 seconds)

    Automatic Release Time Line

    A detector signals the first alarm. This event simultaneously acti-vates the:

    First alarm relay Pre-release strobe circuit (steady On) Pre-release horn circuit (15 pulses per minute)

    A detector in the protected area signals a second alarm and meets the AND group conditions.* The automatic delay timer then starts its countdown and the pre-release horn circuit changes to 60 pulses per minute.

    * AND group and matrix group conditions depend on programming.

    10 seconds before the automatic delay timer expires, the pre-re-lease (horn) circuit changes to steady On.

    The automatic delay timer expires and the release circuits activate.

    A manual reset at the fire alarm control panel deactivates the release solenoids and the Releasing Module returns to the normal state.

    Note: Misapplication of the SIGA-REL can have serious conse-quences. Descriptions provided here are for information only, are subject to change, and should not be used as a guide to field installation of equipment. Always consult the SIGA-REL installation manual when setting up or configuring this component.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 4 of 8

    Abort SequencesThe SIGA-REL provides four abort modes. Aborts do not terminate the release of fire sup-pression agents. They merely offer a limited extension of the automatic timer delay period.

    CompatibilitySprinkler systemsThe SIGA-REL works with two types of sprinkler systems: deluge and pre-action. The primary difference between both systems is the type of sprinkler head (or nozzle) that terminates the pipes. Table1-1 outlines the Factory Mutual Research Corporation (FMRC) require-ments for deluge and pre-action systems.

    FM approval requirements for deluge and pre-action sprinkler systems

    Standby operation 90 hours

    Alarm operation 10 minutes

    NFPA style Class A (Style D or E) or Class A (Style 2, 5, 6, or 7)

    FMRC documentation FMRC Approval Guide (Volume 1)

    Deluge sprinkler systemsIn Deluge sprinkler systems, open-valve sprinkler heads terminate pipes connected to a water supply controlled by a single valve. When the system detects a fire it automatically opens the valve to allow the waterflow through all of the sprinkler heads. Deluge sprinklers are useful for applications that require the simultaneous discharge of water through every sprinkler.

    The following fire detection systems meet FRMC requirements for deluge systems:

    Wet pilot sprinkler line Dry pilot sprinkler line Hydraulic rate-of-rise Pneumatic rate-of-rise Electric

    Pre-action sprinkler systemsIn Pre-action sprinkler systems, closed-valve sprinkler heads termi-nate pipes connected directly to a water supply. The water sup-ply is usually in the same area as the sprinklers and the pipes are supervised for air pressure. Pre-action sprinklers are useful where it is important to prevent the accidental discharge of water.

    Abort Mode 3Industrial Risk Insurers (IRI) Mode: To be recognized as valid, the abort must be active when the second alarm is received. When the abort switch is restored, the release will occur with the expiration of the abort delay timer (set for 10 sec).

    Abort Mode 4 International applications: If the abort is initiated before the auto-matic time delay expires, it will prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer will reset and commence time from t = 0. The release will occur with the expiration of the timer setting minus 10 seconds.

    The following fire detection systems meet FRMC requirements for pre-action systems:

    Hydraulic rate-of-rise Pneumatic rate-of-rise Electric

    Automatic fire extinguishing systemsAutomatic fire extinguishing systems automatically detect and extinguish fires. They require no manual input because detectors automatically activate releasing solenoids or sprinkler valves. The table below provides a list of the fire suppression agents and the applicable NFPA documents.

    Fire suppression agents and NFPA documentation

    Agent NFPA documentation

    Low-expansion foam NFPA 11

    Medium- and high-expansion foam NFPA 11A

    CO2 NFPA 12

    Sprinklers NFPA 13

    Water spray NFPA 15

    Foam-water NFPA 16

    Dry chemicals NFPA 17

    The table below outlines the FMRC requirements for automatic fire extinguishing systems.

    FM approval requirements for automatic fire extinguishing systems

    Standby operation 24 hours

    Alarm operation 10 minutes

    NFPA style B or D

    FMRC documentation FMRC Approval Guide (Volume 1)

    Warning! Improper applications of fire suppression agents can lead to property dam-age, injury, or loss of life. Consult the applicable NFPA documents and the authority having jurisdiction (AHJ) for more information.

    Abort Mode 1 (factory default) If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will continue to run while the abort is active. When the abort switch is restored, the release will occur with the expiration of the automatic delay timer or the abort delay timer, whichever occurs last.

    Abort Mode If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer will continue from the stop point and the release will occur with the expiration of the timer.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 5 of 8

    Compatible panels and devices Panels. The SIGA-REL is compatible with EST2 and EST3 fire alarm control panels. You may install the SIGA-REL in any of the following enclosures: 2-WB(X) series 2-CAB series 3-CAB series RACCR series MFC-A

    Note: Maintain a 1-inch (25.4 mm) minimum clearance all around the SIGA-REL. The clearance space must also comply with the National Electrical Code.

    Power supplies. The SIGA-REL is compatible with the following power supplies: 2-PPS(-220) 2-PPS/6A(-220) SIGA-APS(-220) 3-BPS/M 3-PPS/M BPS6*, BPS10*

    *Not compatible with FMRC sprinkler applications that require 90 hours of standby.

    Solenoid polarizing relays. Use the RELA-EOL with the SIGA-REL. For more information, see the RELA-EOL installation sheet.

    Abort stations. The SIGA-REL is only compatible with normally-open, momentary-action abort sta-tions. Abort stations must be listed with the appro-priate agencies in your area. See Listing agencies.

    Service disconnect stations. The SIGA-REL is only compatible with service disconnect stations that are normally-closed (minimum 2.0 Amps). Service dis-connect stations must be listed with the appropriate agencies in your area. See Listing agencies.

    Releasing solenoid valves. Releasing solenoid valves must be listed with the appropriate agencies in your area. See Listing agencies.

    Listing agencies. Listing agencies include: Factory Mutual Research Corporation (FMRC) Underwriters Laboratories, Inc. (UL) Underwriters Laboratories Canada (ULC)

    TB3 TB2

    TB6

    TB4 TB5

    TB1

    First alarm output

    In

    Out

    +_

    +_

    Release circuit 1

    +

    _24 Vdc in

    24 Vdc out

    Pre-release Circuit 2 (visual)(steady)

    Pre-release Circuit 1 (audible)(pulsed 15/60/Steady)

    Releasing Module

    +

    _

    1234

    RELA-EOL

    [5]

    +_ +_ +_ +_

    [5][8]

    1234

    RELA-EOL

    4321

    321321 4

    4321

    321 4 321 4

    [2]

    [6]

    [5]

    SignatureDataCircuit

    [2]

    [8]

    [8]

    [9]

    Manualrelease circuit

    [5]

    Abort circuit

    [5]

    [8]

    1234

    RELA-EOL

    1234

    RELA-EOL

    1234

    RELA-EOL

    [1][8][7]

    [2][1][8][7]

    Release circuit 2

    [6]

    [6]

    [6]

    [6]

    [1] Four RELA-EOLs per circuit, max.

    [2] Class B, 24 Vdc output

    [3] Class B, normally-open manual release station

    [4] Class B, normally-open abort station

    [5] Listed 47 k EOL resistor

    [6] Nvalve wiring is not supervised for wire-to-wireshorts. Run the connection to the valve inconduit within 20 feet of the RELA-EOL SolenoidPolarizing Relay.

    [7]

    [8] Supervised and power-limited.

    [9] P

    onpolarized valve. The releasing solenoid

    Polarity of circuit shown in supervisory state. Onalarm, polarity reverses.

    ower-limited when connected to a power-limited source. If nonpower-limited, maintain 1/4inch (6.4 mm) separation. Otherwise, use FPL,FPLR, or FPLP in accordance with the NationalElectric Code (NEC). Destroy power-limitedmarkings.

    10 Installations, which include other wiring, requireFPL, FPLR, FPLP, or equivalent NEC-approvedwiring for all power-limited wiring.

    Notes

    [3] [4]

    [5][8] [2]

    ServiceDisconnect Switch

    ServiceDisconnectSwitch

    Wiring

    Switch SettingsAbort mode and time delay settings are configured by means of dip switches on the module.

    Abort mode Mode SW1 SWDE FAULT 1 0 0 2 0 1 3 1 0 4 1 1

    Manual time delay (seconds) Delay SW3 SW4 0 0 0DE FAULT 10 0 1 20 1 0 30 1 1

    Automatic time delay (seconds) Delay SW5 SW6 SW7 10 0 0 0 20 0 0 1 30 0 1 0 40 0 1 1DE FAULT 50 1 0 0

    Abort time delay (seconds) Delay SW8 0 0DE FAULT 10 1

    DE FAULT Denotes default settings.

    Routines that determine how the abort function interacts with the timers.

    The length of time that the deluge is inhibited when the releasing function is manually initiated.

    The length of time that the deluge is inhibited when the releasing function is initiated by the control panel (i.e.: after receiving an alarm).

    The length of time that the deluge is inhibited when the abort function is restored (i.e.: cancelled).

    #6 Flat Washers

    #6-32 self-tapping screws

    MFC-A

    Releasing Module

    Mounting LED OperationLED Color Pattern FunctionDS1 Red Flashing Data (alarm conditions)*DS2 Green Flashing Data (normal conditions)*DS3 Red Steady AlarmDS4 Green Steady PowerDS5 Yellow Steady AbortDS6 Yellow Steady TroubleDS7 Red Steady Release Active*Note: During a loss of communications, the Releasing Module will go into a standby condition, which will cause DS1 and DS2 to change to a steady pattern during an alarm condition.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 6 of 8

    AccessoriesTypical application of SIGA-REL accessories (computer room)

    Signature loop controller

    Releasing Module(mounted in MFC-A cabinet)

    AbortStation

    ReleaseStation

    Fire alarm control panelSignature Series smoke detectors

    Signature Series smoke detectors

    Horn Strobe

    ServiceDisconnect

    ServiceDisconnect

    Raised floor

    Slab

    2 1Extinguishing agent storage cylinder

    Release circuit 1

    Release circuit 2

    Agent release nozzle

    Agentreleasenozzle

    RELA-EOL

    RELA-EOL

    Manual Release Station

    Second circuit maybe connected or left open

    To next device orend of line resistor

    Release Station (rear view)

    From releasing panel,module, or device

    The manual release station is a normally-open, dry contact signal initiating device. The 276A-REL is a single-action station that requires the user to pull the release handle to initiate the release of a fire sup-pression agent. The 278A-REL (shown) is a double-action station that requires the user to raise the upper door, then pull the release handle to initiate the release.

    Abort Station

    The abort station is a normally-open, non-latching device. It is used to prevent the release of agent into the protected area after the release sequence has begun.

    Service Disconnect Switch

    The service disconnect switch is used to temporarily disable the fire suppression system. One switch is installed on each of the two release circuits between the SIGA-REL and the RELA-EOL end-of-line relay. Opening the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel.

    End-of-Line Relay

    1

    2

    3

    4

    To nonpolarizedsolenoid valve

    End-of-line resistoror next relay

    From releasing panelor module

    Polarity shown for release active.

    (-)

    (+)

    (-)

    (+)

    (-)

    (+)

    End-of-Line Relay (rear view)

    The End-of-Line Relay facilitates the connection of a non-polarized releasing solenoid to a supervised, polarized releasing circuit. One relay is required per release solenoid.

    Module Enclosure The MFC-A cabinet is UL-listed for use with Signature modules. Shown here with plug-in style I/O modules, the MFC-A also meets UL requirements for spacing and clearance around the SIGA-REL Releasing Module. The cabinet features red epoxy finish with white FIRE markings.

  • Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 7 of 8

    Specifications Line Resistance

    Ordering Information

    Power riser

    Input voltage Supervisory current

    Riser input current Alarm

    24 Vdc (power limited) 25 mA, max. 4 amps maximum 170 mA min.; 4 A max.

    Release circuits

    Output rating Valves per circuit

    Max. supervisory current Nominal supervisory current

    Supervisory voltage End of line device

    2 A @ 24 Vdc (for each circuit) 4 valves, max. 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm EOL

    Pre-release alarm circuits

    Output rating Max. supervisory current

    Nominal supervisory current Supervisory voltage

    End of line device

    2 A @ 24 Vdc (for each circuit) 0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor

    Manual release input circuit

    Max. supervisory current Nominal supervisory current

    Supervisory voltage End of line device

    Circuit type Circuit capacitance

    0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor Class B N.O. latching 0.1 F, max

    Abort circuit

    Max. supervisory current Nominal supervisory current

    Supervisory voltage End of line device

    Circuit type Circuit capacitance

    0.4 mA (short circuit) 0.18 mA 26 Vdc, max. (open circuit) 47k Ohm resistor Class B N.O. non- latching 0.1 F, max

    First alarm output relay Contact rating

    3 A @ 24 Vdc (0.6 power factor) Form C

    Signature Data line

    Operating voltage Supervisory current

    Alarm current

    5.2 to 19.95 Vdc 1000 A 1000 A

    Environmental condiitions

    Operating temperature

    Storage temperature

    Humidity

    32 F to 120 F (0 C to 49 C) -4 F to 140 F (-20 C to 60 C) 0 to 93% Non-condensing

    Wiring Terminals Suitable for #18 to #12 AWG (2.5 mm to .75 mm)

    Type Code Factory SetAddressing Requirements Uses six module addresses

    Agency Listings UL, ULC, and FM

    Compatible Solenoids Must be both UL/ULC-listed and FM-approved

    Note: Output circuits are power-limited when the riser circuit is power-limited.

    Power riserTotal riser

    current (Amps)

    Distance from SIGA-REL to power supply Wire resistance (Ohms per

    wire)#1 AWG .5 mm #14 AWG 1.5 mm

    4.0 29 ft 8.84 m 20 ft 6.10 m 0.0503.5 34 ft 10.36 m 23 ft 7.01 m 0.0573.0 39 ft 11.89 m 27 ft 8.23 m 0.0672.5 47 ft 14.33 m 32 ft 9.75 m 0.0802.0 59 ft 17.98 m 40 ft 12.19 m 0.1001.5 78 ft 23.77 m 53 ft 16.15 m 0.1331.0 118 ft 35.97 m 80 ft 24.38 m 0.200

    Pre-release and release circuits (per circuit)Total riser

    current (Amps)

    Distance from SIGA-REL to power supply Wire resistance (Ohms per

    wire)#1 AWG .5 mm #14 AWG 1.5 mm

    2.00 176 ft 53.64 m 120 ft 36.58 m 0.3001.75 202 ft 61.57 m 137 ft 41.76 m 0.3431.50 235 ft 71.63 m 160 ft 48.77 m 0.4001.25 282 ft 85.95 m 192 ft 58.52 m 0.4801.0 353 ft 107.59 m 240 ft 73.15 m 0.600

    0.50 706 ft 215.19 m 480 ft 146.30 m 1.200

    Model Description Ship Wt. lb (kg)SIGA-REL Analog addressable releasing module 0.52 (0.23)

    276A-RELManual releasing station (single-action). English markings, black text on yellow polycarbonate body.

    1.0 (0.45)

    278A-RELManual releasing station (double-action). English markings, black text on yellow polycarbonate body.

    1.0 (0.45)

    RELA-ABTManual Abort Station. English markings, black text on yellow polycarbonate body.

    1.0 (0.45)

    RELA-SRVService Disconnect Switch. English markings, white text on blue polycarbonate body.

    1.0 (0.45)

    RELA-EOLPolarized end-of-line relay. English markings on stainless steel cover.

    0.2 (0.1)

    MFC-A

    UL listed cabinet for mounting releasing modules, red with white FIRE. HWD: 8 x 14 x 3 (203mm x 356mm x 89mm)

    7.0 (3.1)

  • U.S.T 888-378-2329F 866-503-3996

    CanadaT 519 376 2430F 519 376 7258

    AsiaT 852 2907 8108F 852 2142 5063

    AustraliaT 61 3 9259 4700F 61 3 9259 4799

    EuropeT 32 2 725 11 20F 32 2 721 86 13

    Latin AmericaT 305 593 4301F 305 593 4300

    www.gesecurity.com

    2006 General Electric CompanyAll Rights Reserved

    Data Sheet 85001-0531 Issue 4Not to be used for installation purposes. Page 8 of 8

    Signature Series is a Trademark of GE Security.

  • Data Sheet 85001-0279 Issue 8Not to be used for installation purposes. Page 1 of 4

    GESecurity

    Data Sheet 85001-0279 Issue 8

    Manual Pull StationsSIGA-270, SIGA-270P, SIGA-278

    OverviewThe SIGA-270 and SIGA-278 series Manual Pull Stations are part of GE Securitys Signature Series system. The SIGA-270 Fire Alarm Manual Pull Stations feature our very familiar teardrop shape. They are made from die-cast zinc and fi nished with red epoxy pow-der-coat paint complemented by aluminum colored stripes and markings. With positive pull-lever operation, one pull on the station handle breaks the glass rod and turns in a positive alarm, ensuring protection plus fool-proof operation. Presignal models (SIGA-270P) are equipped with a general alarm (GA) keyswitch for applications where two stage operation is required. The up-front highly visible glass rod discourages tampering, but is not required for proper operation.

    GE Securitys double action single stage SIGA-278 station is a contemporary style manual station made from durable red colored lexan. To initiate an alarm, fi rst lift the upper door marked LIFT THEN PULL HANDLE, then pull the alarm handle.

    Standard FeaturesNote: Some features described here may not be supported by all control systems. Check your control panels Installation and Operation Guide for details.

    Traditional familiar appearance SIGA-270 models feature our familiar teardrop design with simple positive pull action and sturdy die-cast metal body.

    One stage (GA), two stage (pre-signal), and double action modelsSIGA-270 models are available for one or two stage alarm sys-tems. The single stage double action SIGA-278 features a rugged Lexan housing with keyed reset mechanism.

    MEA

    Patented

    SIGA-278

    Break glass operationAn up-front visible glass rod on the SIGA-270 discourages tam-pering.

    Intelligent device with integral microprocessorAll decisions are made at the station allowing lower communica-tion speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring properties; twisted or shielded wire is not required.

    ADA CompliantMeets ADA requirements for manual pull stations.

    Electronic Addressing with Non-volatile memoryPermanently stores programmable address, serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, and time and date of last alarm.

    Automatic device mappingEach station transmits wiring information to the loop controller regarding its location with respect to other devices on the circuit.

    Stand-alone operationThe station inputs an alarm even if the loop controllers polling interrogation stops.

    Diagnostic LEDsStatus LEDs; ashing GREEN shows normal polling; ashing RED shows alarm state.

    Designed for high ambient temperature operationInstall in ambient temperatures up to 120 F (49 C).

    EST Fire & Life SafetyIntelligent Initiating Devices

    SIGA-270 SERIES

  • Data Sheet 85001-0279 Issue 8Not to be used for installation purposes. Page 2 of 4

    Figure 4. Single Stage Systems

    Figure 5. Two Stage Systems

    ApplicationThe operating characteristics of the fire alarm stations are deter-mined by their sub-type code or Personality Code. NORMALLY-OPEN ALARM - LATCHING (Pesonality Code 1) is assigned by the factory; no user configuration is required. The device is configured for Class B IDC operation. An ALARM signal is sent to the loop con-troller when the stations pull lever is operated. The alarm condition is latched at the station.

    CompatibilitySignature Series manual stations are compatible only with GE Secu-ritys Signature Loop Controller.

    Warnings & CautionsThis device will not operate without electrical power. As fires fre-quently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist.

    Testing & MaintenanceTo test (or reset) the station simply open the station and operate the exposed switch. The SIGA-270 series are opened with a tool; the SIGA-278 requires the key which is supplied with that station.

    The stations automatic self-diagnosis identifies when it is defec-tive and causes a trouble message. The user-friendly maintenance program shows the current state of each Signature series device and other pertinent messages. Single devices may be deactivated temporarily, from the control panel. Availability of maintenance features is dependent on the fire alarm system used.

    Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Au-thority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards.

    Wiring Notes

    1 Refer to Signature Loop Controller manual for maximum wire distance.

    2. All wiring is power limited and supervised.

    Typical Wiring The fire alarm stations terminal block accepts #18 AWG (0.75mm2) to #12 AWG (2.5mm2) wire sizes. See Signature Loop Controller cata-log sheet for detailed wiring requirement specifications.

  • Data Sheet 85001-0279 Issue 8Not to be used for installation purposes. Page of 4

    Figure 2. SIGA-270, SIGC-270F, SIGC-270B installation

    Figure . SIGA-270P, SIGC-270PB installation

    InstallationSingle-stage Signature Series fire alarm manual pull stations mount to North American 2 inch (64 mm) deep 1-gang boxes.

    Two stage presignal (270P) models require 1 inch (38 mm) deep 4-inch square boxes with 1-gang, -inch raised covers. Openings must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model CI-52-C-49-1/2.

    All models include terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. GE Security recommends that these fire alarm stations be installed according to latest recognized edition of national and local fire alarm codes.

    Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system commission-ing. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a soft address to each serial number. If desired, the stations can be addressed using the SIGA-PRO Signature Program/Service Tool.

    Figure 1. SIGA-278 installation

    LIFT

    NORMAL

    Cover ReleaseScrew

    Comp atibleElectrical Boxwith -inch

    raised covers

    Glass RodRelease Lever

    ToggleSwitch

    BackPlate

    Do not useboxes with

    roundedopenings.

  • Data Sheet 85001-0279 Issue 8Not to be used for installation purposes. Page 4 of 4

    U.S.T 888-378-2329F 866-503-3996

    CanadaT 519 376 2430F 519 376 7258

    AsiaT 852 2907 8108F 852 2142 5063

    AustraliaT 61 3 9259 4700F 61 3 9259 4799

    EuropeT 32 2 725 11 20F 32 2 721 86 13

    Latin AmericaT 305 593 4301F 305 593 4300

    www.gesecurity.com/est

    2007 General Elec