EARTH LEAKAGE CIRCUIT BREAKER B People Electric Appliance serves for people. ISO14001 OHSAS18001 ISO9001

Transcript of EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can...

Page 1: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

EARTH LEAKAGECIRCUIT BREAKER

B

People Electric Appliance serves for people.

• ISO14001 OHSAS18001ISO9001

Page 2: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

DZ47LE EARTH LEAKAGE CIRCUIT BREAKER

APPLICATION

DZ47LE earth leakage circuit breaker is used for the protection against electrical leakage in t hecircuit of 50Hz or 60Hz, rated voltage single-phase 240V, 3-phase 415V, rat ed cu rrent up t o 60AWhen somebody gets an electirc shock or the residual current of the circuit exceeds the fixevalue, the ELCB can cut off the power within the time of 0.1s automatically protec ting thepersonal safety and preventing the equipement from the fault re sulted fro m the resi dual current.With this function, the ELCB can protect the circuit against overload and short circu it or can beused for the unfrequent switchover of the circuit under normal conditions. It conforms to IEC61009 standard.

SPECIFICATIONS

RatedVoltage(V) Pole No Rated current

(A)

Leakage action

current(mA)

Leakagedead

current(mA)

Leakageactiontime(s)

220V

380V

1P

2,3,4P

30

100

1~10

15~32

40~60

15

50

0.1

a.TH35-7.5 rail is used for the product installation.b.Outline and installation dimensions(see the figure and the table)

Type

DZ47LE-60/1N

DZ47LE-60/2

DZ47LE-60/3

DZ47LE-60/3N

DZ47LE-60/4

Dimensions

A B C D E

46

64

91

100

118

70

70

70

70

70

40

40

40

40

40

45

45

45

45

45

94

94

94

94

94

MAIN TECHNICAL DATA

Single-poledouble line

Double-poledouble line

Triple-poletriple line

Triple-polefour line

Four-polefour line

DZ47LEC45LE

1 / 2

DZ47LEC45LE

2 / 2

DZ47LEC45LE

3 / 3

DZ47LEC45LE

3 / 4

DZ47LEC45LE

4 / 4

DZ47LE 1P

EARTH LEAKAGE CIRCUIT BREAKER

DZ47LE 2P

DZ47LE 3P

DZ47LE 4P

• B-01

Page 3: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

RDX2LE-100 EARTH LEAKGE CIRCUIT BREAKER

RDX65LE EARTH LEAKGE CIRCUIT BREAKER

SPECIFICATIONS

APPLICATION

RDX65LE is used for the protection against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 230V, 3 phase 400V, rated current up to 60A.Whe n so mebody gets an electric shock or the residual current of the circ uit exceeds the fixed value, the ELCB can cut off the power within the time of 0.1s automatically to protect the personal safety and preventthe equipment from the fault resulted by the residual current. With this funtion, the ELCB canprotect the circuit against overload and short circuit or can be used for the unfrequent switchoverof the circuit under normal conditions. It conforms to IEC61009.

Number of PolesRated voltageRated current

Rated Operating Current(mA)Rated non-operation (I n)

Tripping Curve

1P+N, 2P+N, 3P+N, 4P+N240/415V

6A 10A 16A 20A 25A 32A 40A 50A 63A30mA 100mA 300mA

0.5I nC,D

RDX65LE 1P

RDX65LE 2P

APPLICATION

SPECIFICATIONS

RDX2LE-100 is suitable for the circuit of 50Hz, rated voltage 230/400V, and rated current upto 100A.It has the earth leakage, overload & short circuit protect function. It can al so add over voltageprotect function. It is mainly used in buiding illumination and electrical distribution system.

Number of PolesRated Current(A)Rated Residual Operating Current(I n)(mA)Rated Residual Non-operation Current(I no)(mA)Rated Voltage(V)Residual Current Off-timeShort Circuit Capacity(Icu)EnduranceTripping CurvePortection Degree

1P+N,2P+N,3P+N,4P+N40,50,63,80,100

30,50,100,200,3000.5I n

AC 230/4000.1S

3000A4000

C,DIP20

OVERALL AND MOUNTING DIMENSIONS(UNIT:MM)

4P3P2P1P

10881

5427

3P+N 4P 1083P 81

2P 54

81 45

7044 16

35 27

L

7.5

RDX2LE-100 2P+N

RDX2LE-100 3P+N

EARTH LEAKGE CIRCUIT BREAKER

• B-02

Page 4: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

DZ47LE EARTH LEAKAGE CIRCUIT BREAKER

APPLICATION

SPECIFICATIONS

DZ65LE EARTH LEAKAGE CIRCUIT BREAKER

APPLICATION

SPECIFICATIONS

Rated voltage

Rated current

Pole

Rated operating current (mA)

Rated non-operating (I N)

Tripping curve

240/415V

6A 10A 16A 20A 25A 32A 40A 50A 63A

1P 2P 3P 4P

30mA 50mA 100mA 300mA

0.5I n

C type D type

This products provide a high level of protection against earth leakage faults by the RCD in addition to the overcurrent and short-circuit protection offered by the MCB. This products are suitable for the protection of circuits with the highest safety requirements(i.e.eletctric apparatus in rooms with high humidity, socket circuits, rooms with bath bubs of shower etc.)

Rated voltage

Rated current

Pole

Rated operating current (mA)

Rated non-operating (I N)

Tripping curve

Type

230/400V

6A 10A 16A 20A 25A 32A 40A 50A 63A

1P+N 2P 3P 4P

30mA 50mA 100mA 300mA

0.5I N

C type D type

Electronic

This products provide a high level of protection against earth leakage faults by the RCD in addition to the overcurrent and short-circuit protection offered by the MCB.

This products are suitable for the protection of circuits with higher safety requirements (i.e.electric apparatus in rooms with high humidity, socket c ircuits, ro oms with bath bubs orshower etc.)

EARTH LEAKAGE CIRCUIT BREAKER

• B-03

Page 5: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

APPLICATIONS

DXM3L(DZ30L)RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION

APPLICATION

DXM3L(DZ30L) leakage protective breaker, DXM3L(DZ30L) (phase wire+neutral wire+leakage

+overload voltage) protective breaker is used in the single phase residence circuit of AC.50Hz/ 60Hz ,

rat ed voltage 220V, used as electron shock protection. It can protect civil electron circuit from

over load and short-circuit. This produc t has advantages of small volume, high breaking capacity

zero, and live wires are cutted off at the same time, also protecting person fro m electric shock

when the livewire connected opposite.

This product conforms to IEC61009, Gb6829, GB/16917 .

PC60NL EARTH LEAKAGE CIRCUIT BREAKER

PC60NL

DXM3L(DZ30L)

EARTH LEAKAGE CIRCUIT BREAKER

Test Monthly

The PC60NL RCCB incorporates a residual curren t ope rated electromagnetic release which

operates without any auxiliary source of supply to open a circuit automatically in the case of an

earth leakage fault between phase and earth greater than or equal to I n.

The PC60NL combined with MCB & RCCB Provides:

1. protection against indirect contact

2. complementary protection against direct contact

3. protection for the installation against insulation faults

PS250LE RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

SPECIFICATIONS

PS250LE RCBO is suitable for the circuit of 50/60Hz, rated volta ge 230/400V,and rated current up to 100A. It has the earth leakage, overload, short circuit protect function. It can also ad d over voltage protect function. It is mainly used in building illumination and electrical distribution system.

Number of Pole

Rated Current(A)

Rated Residual Operating Current(I n)(mA)

Rated Residual Non-operation Current(I n)(mA)

Rated Voltage(V)

Residual Current Off-time

Short Circuit Capacity(Icu)

Endurance

Tripping Type

Protection Degree

1P+N,2P,3P+N,4P

40,50,63,80,100

30,50,100,200,300

0.5I n

AC 230/400

0.1S

3000A

4000

C,D

IP20

PS250LE 2P

PS250LE 4P

• B-04

Page 6: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

ADVANTAGE

Earth leakage Circuit Breaker With Overcurrent ProtectionElectronic typeCompact structure, small volume, (two modules in width)With short circuit, overload and residual current protectionAction function has nothing to do with main circuit voltageWith midline cut-off functions, it is safer and more reliable.With double functional connection terminals, it has strong connection ability.With contact state indicator, it is easy to recognize the contact situation.Different handle colors are used to indicate different rated current.High breaking capacity:10KAWith wide range of rated current, it can be used as family main switchUnited accessories seriesType can provent the error tripping caused by electric equipment

SPECIFICATIONS

MOUNTING DIMENSION

Pole No.

Standards

Rated Current

Rated eakage Current I n

Rated Voltage(Ue)

Tripping Time

Sensitivity

Type

Breaking Capacity Icn

Tripping Characteristic

Grade of Protection

Service Life

Terminal Connection

Shell width

2 P

IEC61009(EN61009)GB16917.1

Type C 6,10,13,16,20,25,32,40AType D 6,10,13,16,20A

30,100mA

230V;50Hz

G Minimum 10ms for prolonging

AC type

3

10KA

C,D

IP40

Electric:no less than 4000 timesMachanic:no less than 20000 times

Wire 1-25 square micronBus-bar row thickness 0.8-2mm

Din Rail 35mm(Two modulus in width)

5.5 30.5 4.5

44

9.5

45

60

1P+N

80

35

1 N

2 N

RDX6LE-63 EARTH LEAKAGE CIRCUIT BREAKER

RDX6LE-63

RDX6LE-63

EARTH LEAKAGE CIRCUIT BREAKER

RDX6LE-63

• B-05

Page 7: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

APPLICATION

PID RESIDUAL CURRENT CIRCUIT BREAKER

SPECIFICATIONS

OVERALL AND MOUNTING DIMENSIONS(Unit:mm)

NORMAL OPERATION AND MOUNTING REQUIREMENT

PID RCCB is in conformity with the standard of IEC61008. The RCC B ca n cu t of f the faul tcircuit immediately on the occasion of shock hazard or earth leakage of trunk ine. Thu s, it is suitable to avoid the shock hazard and fire caused by earth leakage.

The RCCB is m ainly suit able for useing in varieties of plants and enterprises, buildings,constructions. It can be used in circuits up to 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use in DC pulse system.

Number of PoleRated Current(A)Rated Residual Operating Current(I n)(mA)

Rated Voltage(V)

Residual Operating Current Scope

Residual Current Off-timeShort Circuit Capacity(Icu)Endurance

Protection Degree

1P+N,3P+N16,20,25,40,50,63

30,100,300,500AC 230/240AC400/415

0.5I n~1I n0.3S

6000A4000IP20

Circumstance temperature-5 ~+40 ,average temperature not exceeding 35 . Altitude above sea level less than 2000m. Humidity not exceeding 50% at 40 and not exceeding 90% at 25 . Installation class or . Pollution class . Installation method DIN Rail mounting type. The external magnetism shall not be more than 5 times of terrestrial one. Product shall be installed vertically at the place where there shall be no severe impact or

vibration. The product is switched on when the handle is at upper position.

74.5

35.5

36

65 85

N

O.OFF

N

65 85

N

O.OFF

72

PID 2P

RESIDUAL CURRENT CIRCUIT BREAKER

PID 4P

• B-06

Page 8: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

PID-N RESIDUAL CURRENT CIRCUIT BREAKER

WIRING DIAGRAM

CONSTRUCTION AND FEATURE

TECHNICAL DATA

Provides protection against earth fault/leakage current and function of isolation High short-circuit current withstand capacity

Applicable to terminal and pin/fork type busbar connection Contact position indication

Equipped with finger protected connection terminals Fire resistant plastic parts endures abnormal heating and strong impact

Automatically disconnect the circuit when earth fault/ leakage current occurs and exceeds the rated sensitivity.

Independent of power supply and line voltage, and free from external interference, voltage fluctuation.

Rated conditional residual short-circuit Current I c: 6000A Tripping duration: instantaneous tripping 0.1s Residual tripping current range: 0.5I n~1I n Electro-mechanical endurance: 4000 cycles

Connection terminal: Screw terminal Pillar terminal with clamp

2 Connection capacity: Rigid conductor 25mm

Fastening torque: 2.0Nm Installation: On symmetrical DIN rail 35mm

Mode: electro-magnetic type, electronic type

Pole No.: 2, 4

Rated making and breaking capacity: 630A

Rated current(A): 25, 40, 63 Rated voltage: 230/400V AC Rated frequency: 50/60Hz

Residual current characteristics: A, AC

Rated residual operating current I n(mA):

Rated residual non-operating current I no: 0.5I n Rated conditional short-circuit current Inc: 6000A

Panel mounting

10, 30, 100, 300, 500

PID-N 2P

RESIDUAL CURRENT CIRCUIT BREAKER

•••••••••

••••••• •

•••••

PID-N 4P

•••••••••

••••••• •

•••••

• B-07

Page 9: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

Design according toTripping time

Rated voltageRated tripping currentSensitivityRated shortCircuit strength

Maximum back-up fuse forShort circuit protectionMaximum back-up fuse forOveload protectionResistance to climatic conditionsDegree of protectionEndurance electrical comp. mech comp.

ICE61008 (EN 61008)undelayedmin.10 ms delaymin.40 ms delaywith selective disconnecting function230/400V; 50Hz10,30,100,300,500mAAC and pulsating DC10KA with 63A gL back-up fuse10KA with 80A gL(F7-80 and-863)6KA(rated current 63A) with 63A gL63A gL80A gL (F7-80 and-863)45A gL(F7-25 and-40A)40A gL(F7-80 A)according to IEC 61008built-in switch IP 40

4.000 operating cycles20.000 operating cycles

MECHANICAL

Frame sizeSocket sizeDevice widthMounting

Upper and lower terminalsTerminal protection

Terminal capacityBusbar thickness

45mm80mm35mm (2mod.), 70mm (4mod.)quick fastening with 2 lock-inPositions on DIN rail En50022open mouthed/lift terminalsfinger and hand touch safe,VBG 5, OVE-EN 6

21 --- 25mm0.8 - 2mm

PF7 RESIDUAL CURRENT DEVICE

APPLICATION

The RCD is in conformity with the standard of IEC61008, GB16916 and BS EN61008. The RCDcan cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunkline, thus, it is suitable to avoid the shock hazard and fire caused by earth leakage. The RCD is mainly suitable for using in variety of plants and ente rprises, buildings constructions,commerces, guesthouses and families. It can be used in circuits up to single phase 230V, three phases400V 50 to 60Hz. The RCD is not suitable for using on DC pulse system.

ELECTRICAL

PF7 2P

PF7 4P

RESIDUAL CURRENT DEVICE

DIMENSION (Units: mm)

•••••••••

•••••••••

•••••••••

•••••••••

• B-08

Page 10: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

PFIN RESIDUAL CURRENT DEVICE

PFIN Residual Current Device(RCD) is in conformity wit h th e st andar d of VDE 0664,CEE27 and BS4293. It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakageof trunk line. Thus, it is suitable to avoid the shock hazard and fire caused by earth leakage. PFIN ELCB is mainly suitable for var ieties of plants and enterprises, buildings, constructions, commerces,hotels and families. It can be used in circuits up to single phase 240V, three phases 415V, 50 or 60Hz.

TypeRated current In (A)

Rated operating current for earth leakage I n(A)Rated non-operating current for earth leakage I n(A)

Voltage Un(V)Pole

PNFIN2525

PNFIN4040

PNFIN6363

PNFIN100100

0.5I n0.03,0.1,0.3,0.5 0.1,0.3,0.5

240(220)V 415(380)V2 ,4

2In

I n0.2

2I n0.1

0.25A(or5I n)0.04

In=252001500

In=403002000

In=634003000

4000

Limited value of non-operating current forbalance load or unbalance load

In minimum value of rated making andbreaking capacity

Rated conditional short circuit current Inc(A)Endurance(times)

Operating time(second)

MAIN TECHNICAL DATA

PNFIN RESIDUAL CURRENT DEVICE

APPLICATION

PNFIN Residual Current Device(RCD) is in c onfor mity w ith th e stan dard of IEC61008,VDE 0664, CEE27 and BS4293. It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakageof trunk line. Thus, it is suitable to avoid the shock hazard and fire caused by earth leakage. PNFINRCD is mainly suitable for using in varieties of plants, enterprises, buildings, constructions,commerces, guesthouses and families. It can be used in circuits up to single phase 240V, three phases 415V, 50 or 60Hz.

SPECIFICATIONS

APPLICATION

MAIN TECHNICAL DATA

2In

I n0.2

2I n0.1

0.25A(or5I n)0.04

In=252001500

In=403002000

In=634003000

4000

Limited value of non-operating current forbalance load or unbalance load

In minimum value of rated making andbreaking capacity

Rated conditional short circuit current Inc(A)Endurance(times)

Operating time(second)

SPECIFICATIONType

Rated current In (A)Rated operating current for earth leakage I n(A)

Rated non-operating current for earth leakage I n(A)Voltage Un(V)

Pole

PFIN2525

PFIN4040

PFIN6363

PFIN100100

0.5I n0.03,0.1,0.3,0.5 0.1,0.3,0.5

240(220)V 415(380)V2 ,4

PNFIN 2P

PNFIN 4P

PFIN 2P

RESIDUAL CURRENT DEVICE

PF1-4P

• B-09

Page 11: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

Number of Pole

Rated Current (A)

Rated Residual Operating Current (I n)(mA)

Rated Residual Non-operation Current (I no)(mA)

Residual Operating Current Scope

Residual Current Off-time

Short Circuit Capacity (Icu)

Endurance

Protection Degree

Rated Voltage (V)

2P,4P

16,20,25,32,40,50,63,80,100

10,30,100,300,500

0.5 I n

AC 230/240

AC 400/415

0.5I n~1I n

0.3S

3000A

4000

Ip20

PF360 RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

SPECIFICATION

The RCCB is in conformity with the standard of IEC61008. The RCCB can cut off the faultcircui t immediately on the occasion of shock hazard of ear th leakage of t runk line. Thus, it is suitableto avoid the shock hazard and fire caused by earth leakage. The RCCB is mainly suitable for useing in varieties of plants and enterprises, buildings constructions.It can be used in circuits up to 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use on DC pulse system.

OPERATION PRINCIPLE

OVERALL AND MOUNTING DIMENSIONS (UNIT: MM)

I >

1

2

3

4

I >

1

2

3 5 7 N

4 6 8 N

69

6844

6.3

90.4

90.4 71 46

7.5

3517.517.5

217.5

2

7017.517.5

2 17.5 17.5

90.4 71 46

17.52

7.5

PF362 2P

PF364 4P

RESIDUAL CURRENT CIRCUIT BREAKER

• B-10

Page 12: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

SensitivityHigh sensitiviy:10mA

30mA

Pole22

2222224444222224444422222444222222244444

Medium sensitivity:100mA

Low sensitivity:300mA

Low sensitivity:500mA

Terminal cover kit:(1 se = 2 covers)

For RCCBs2For RCCBs4For RCCBs2For RCCBs4

16 to 63A16 to 63A

80 to 100A80 to 100A

10 sets10 sets10 sets10 sets

PRCZ005PRCZ006PRCZ007PRCZ008

Current rating cat.ref.16A25A

16A25A40A63A80A

100A25A40A63A80A25A40A63A80A

100A25A40A63A80A

100A25A40A63A80A

100A25A40A63A80A

100A25A40A63A80A

100A25A40A63A80A

100A

PRC216BPRC225B

PRCD216BPRCD225BPRCD240BPRCD263BPRCD280BPRCD284BPRCD425BPRCD440BPRCC463BPRCD480BPRCE225BPRCE240BPRCE263BPRCE280BPRCE284BPRCE425BPRCE440BPRCE463BPRCE480BPRCE484BPRCF225BPRCF240BPRCF263BPRCF280BPRCF284BPRCF425BPRCF440BPRCF463BPRCF480BPRCF484BPRCG225BPRCG240BPRCG263BPRCG280BPRCG284BPRCG425BPRCG440BPRCG463BPRCG480BPRCG484B

DESCRIPTION

PR RESIDUAL CURRENT CIRCUIT BREAKER

EARTH FAULT INDICATOR

NUISANCE TRIPPING

To open a circuit automatically in case of an earth leakage fault between phase and earth and /or neutral greater or equal to 10mA, 30mA, 100mA, 300mA or 500mA. It is used in domestic,commercial and industrial installations.

Mechanical indicator appearing on the front face of the RCCB is to be differed between tr ippingand off position yellow-tripped.

All the RCCBs are protected against transient voltages (lightenin g, line disturbances)andtransient currents (from high capacitive circuits) DC sensitive RCCBs or time delay devices are available, please consult us you also have the possibiliy to install the following accessories:electrical cover kit, locking kit.

PRC 2P

PRC 4P

PRCC 2P

PRCC 4P

RESIDUAL CURRENT CIRCUIT BREAKER

• B-11

Page 13: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

45

5443.76.5

TH35

T

91

36 T

72

4464

12-6

672

90 45

I2/1 4/3 6/5N/N

Y1Y2

180

90L1L2L3NPE

1 3 5 N

M

AB

W1

2 4 6 N

T

PR101 RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

PR101 Series Earth Leakage Circuit Breakers apply to in AC circuit of frequency of 50 Hz, rated voltage up to 415V, rated current up to 80A. It is mainly use d as an indi rect con tactprotection fot human. It also can be used to preven t aga inst the f ire d anger caus ed b y ea rth faltcurrent ow ing to equipment insulation damage. When the protective measures of the electric shockare out of work, the RCCB whose rated residual operating current less than 30mA can serve as thesupplementary protection for in direct contact, but it can t be used as the sole direct contact protection.

PRODUCT FEATURES

1. PR101 Series Leakage Circuit Breakers are the protector for pure electromagnetic residual current operation.2. The operation function is unrelated to circuit voltage, but operation is reliable.3. It can be reliably operated on the loss of phase or neutral.4. The capacity of resisting electromagnetic interference is strong.

MAIN TECHNICAL DATA

Type Un(V) Hz Im

I mIncI m

InA

I nmA

I nomA I N 2I N 5I N

The maximum of break-time(s)

PR1012P 240

415

50,60

500A(In50A

10In)(In50A)

500A(In50A

10In)(In50A)

6000A

6000A

6,10,16,25,32,40,50,63

80

6,10,16,25,32,40,50,63

80

30

50

75

100

300

500

30

50

75

100

300

500

0.25A 500A

15

25

40

50

150

250

15

25

40

50

150

250

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.2

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

-

-

-

0.04

0.04

0.04

-

-

-

0.04

0.04

0.04

0.04

0.04

0.04

-

0.04

0.04

0.04

0.04

0.04

-

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

0.04

DIMENSIONS

PR101 2P

PR101 4P PR1014P

EARTH LEAKAGE CIRCUIT BREAKER

• B-12

Page 14: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

PBV-D RESIDUAL CURRENT CIRCUIT BERAKER

ELECTRICAL DATA

Design according toTripping time

Rated voltageRated tripping currentSensitivityRated shortCircuit strength

Maximum back-up fuse forShort circuit protectionMaximum back-up fuse forOverload protectitonResistance to climatic conditionsDegree of protectionEndurance electrical comp. mech comp

IEC 61008 (EN 61008)undelayedmin.10 ms delaymin.40 ms delaywith selective disconnecting function230/400V; 50Hz10,30,100,300,500mAAC and pulsating DC10KA with 63A gL back-up fuse10KA with 80A gL (F7-80 and -863)6KA(rated current 63A)with 63A gL63A gL80A gL(F7-80 and 863)45A gL(F7-25 and -40A)40A gL(F7-80 A)according to IEC 1008built-in switch IP 40

4.000 operating cycles20.000 operating cycles

MECHANICAL DATA

Frame sizeSocket sizeDevice widthMounting

Upper and lower terminalsTerminal protection

Terminal capacityBusbar thickness

45mm80mm35mm (2mod.), 70mm (4mod.)quick fastening with 2 lock-inPositions on DIN rail En50022open mouthed/lift terminalsfinger and hand touch safe,VBG 5, OVE-EN 61 --- 25mm20.8 - 2mm

PBV-D 2P

PBV-D 4P

RESIDUAL CURRENT CIRCUIT BREAKER

• B-13

Page 15: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

PG RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

PG RCCB, rated current is adjustable from 10A up to 60A. User can select suitable current for better protection against overload and short-circuit. The products comply with IEC61008.

SPECIFICATIONS

Number of PoleRated Voltage(V)Rated Current(A)

Leakage Motion Current(mA)Leakage Dead Current(mA)

2 4

250/44010,15,20,30,45,50,60A Adjustable

300,500150,250

300,500150,250

N 1

210

70

53

70 115

210

N 3 2 1

53

70

TG RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

TG RCCB, rated current is adjustable from 10A up to 60A. User can select suitable current for better protection against overload and short circuit.The products comply with IEC61008.

SPECIFICATIONS

Number of PoleRated Voltage(V)Rated Current(A)

Leakage Motion Current(mA)Leakage Dead Current(mA)

2 4

250/44010,15,20,30,45,50,60A Adjustable

300,500150,250

300,500150,250

PG230

TG430

PG430

TG230

RESIDUAL CURRENT CIRCUIT BREAKER

DIMENSION (Units: mm)

• B-14

Page 16: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

PL9 RESIDUAL CURRENT CIRCUIT BREAKER

APPLICATION

PL9 Residual Curren t De vice is i n con formi ty wi th the standard of IEC61008. It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk l ine. Thus, it is suitable to avoid the shock hazard and fire caused by earth leakage. PL9 RCD is mainly suitable for using in variet ies of plants, enterprises, buildings, constructions,commerces, guesthouses and families. It can be used in circuits up to 1phase 230V and 3 phases400V 50/60Hz.

SPECIFICATIONS

Number of Pole

Rated Current(A)

Rated Residual Operating Current(I n)(mA)

Rated Residual Non-operation Current(I n)(mA)

Rated Voltage(V)

Residual Current Off-time

Short Circuit Capacity(Icu)

Endurance

Protection Degree

2P,4P

40,50,60

30,100,300

0.5I n

AC 230/400

0.1S

3000A

4000

IP20

PL9 2P

PL9 4P

PDBR230 2P

PDBR430 4P

SPECIFICATIONS

Type

Poles

Rated voltage(V)

Rated current(A)

Leakage motion current(mA)

Leakage dead current(mA)

Accord with standand

PDBR230 PDBR430

250V/440V

5A-15A,10-30A,30-60AAdjustable

300mA

150mA

500mA

250mA

1000mA

500mA

NFC61450

2P 4P

RESIDUAL CURRENT CIRCUIT BREAKER

• B-15

Page 17: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

CBT 2P

CBT EARTH LEAKAGE CIRCUIT BREAKER

USAGE

CBT Residual Current Circuit Breaker without ov er curr ent prot ecti on c onforms to the

standard of GB16916.1, IEC61008, BS4293 etc. It is used in the circuits o f AC50~ 60Hz, single

phase 230V(220V), three phases 400V(380 V) i n in dus tri al & m ini ng ente rpri ses, comm erc ial

buildings and housing for protection of personal electric shock haz ard and electric equipment and

for unfrequent switchover of circuits under normal conditions.

INSTRUCTIONS

This RCCB is intended for installation within an enclosure in an ambient temperature between

-5 and 40 with an average value not exceeding 35 over a 24 hours period. It shou ld not be

installed at an altitude greater than 2000m above sea level, nor in an atmosphere subject to

excessive pollution by smoke, dust, chemical fumes, salt laden spray, prolonged periods of high

humidity or other abnormal conditions. See current product catalogues for a wide range of suitable

enclosure.

PL13 EARTH LEAKAGE PROTECTING DEVICE

Conforms with UL standard 943 CLASS A(GFCI and 498 receptacle). Protects against ground fault shock hazard from frayed wiring, damaged appliances, wherever

electrical contact might provide a path to ground through human body. Can be wired to provide 20 amp GFCI feed-through protection to other outlets on outlets on the

same circuit. Overload and neutral line error grounding protection. Trip thresholds of 4~6 milliamps. Unit trips within 0.025 seconds of fault detection. Operate within -35 ~66 environmental temperature. Protect against 10~450MHz voice interference. Made of high impact termoplastic to resist da mage fr om impa ct a nd f requ ent use. And with

unbreakable nylon wall plate. Back and side wiring terminals permit fast installation. Clearly marked line and load terminals. Incorporate dual bolt terminal and installation screws w hich accep t standard screw

driver blades. The voltage and frequency of the product can be designed as per customers different repuirements.

PL13-01

PL13-02

PL13-03

SPECIFICATION

EARTH LEAKAGE CIRCUIT BREAKER

• B-16

Page 18: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

GFCI RECEPTACLE

3 Grace Switch can control resistance and inductance load which meets residential useand commercial use for its reliability and unique performance. Switch Characteristics

Large head double-drive combination screws for quick wiring Back and side wire connection are easy to be installed Green grounding screw Choice of different color

GFCI, DuplexReceptacle With redReset Button and blueTest button 20A, 125VAC, 60Hz,With LED lightIndicator

PTG15-L-2ALPTG15-L-2DEPTG15-L-2BLPTG15-L-2GRPTG15-L-2IVPTG15-L-2WH

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

RED RESET/BUTTON TEST

PTG20-L

GFCI, DuplexReceptacle ButtonsMatch body face color20A, 125V AC, 60Hz,With LED lightIndicator

PTG20-L-1ALPTG20-L-1DEPTG20-L-1BLPTG20-L-1GRPTG20-L-1IVPTG20-L-1WH

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

PTG20-L-2ALPTG20-L-2DEPTG20-L-2BLPTG20-L-2GRPTG20-L-2IVPTG20-L-2WH

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

RED RESET/BUTTON TEST

GFCI, DuplexReceptacle With redReset Button and blueTest button 20A, 125VAC, 60Hz,With LED lightIndicator

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

PTG15-L

PTG20-L

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

RECEPTACLE

• B-17

Page 19: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

GFCI RECEPTACLE

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

GFCI, DuplexReceptacle With redReset Button and blueTest button 20A, 125VAC, 60Hz,

PTG15-2ALPTG15-2DEPTG15-2BLPTG15-2GRPTG15-2IVPTG15-2WH

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

RED RESET/BUTTON TEST

PTG15

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

DESCRIPTION ART.NO. BODY COLOR BUTTON COLOR

PTG20

PTG15-L

GFCI, DuplexReceptacle ButtonsMatch body face color20A, 125V AC, 60Hz.

PTG20-1ALPTG20-1DEPTG20-1BLPTG20-1GRPTG20-1IVPTG20-1WH

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

RED RESET/BUTTON TEST

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

PTG20-2ALPTG20-2DEPTG20-2BLPTG20-2GRPTG20-2IVPTG20-2WH

GFCI, DuplexReceptacle With redReset Button and blueTest button 20A, 125VAC, 60Hz,

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

ALMONDDEEP-ALMONDBLACKGRAYIVORYWHITE

PTG15-L-1ALPTG15-L-1DEPTG15-L-1BLPTG15-L-1GRPTG15-L-1IVPTG15-L-1WH

GFCI, DuplexReceptacle ButtonsMatch body face color15A, 125V AC, 60Hz.With LED lightindicator

PTG20

RECEPTACLE

• B-18

Page 20: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

DESCRIPTION ART. N0. COLOR

PTM-4 QUICKWIRE AND SIDE WIRED TOGGLE 15AMP 120V AC QUICK SWITCHES

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

PTM-4ALPTM-4DEPTM-4BLPTM-4GRPTM-4IVPTM-4WH

3-WayDecorativeSwitch WithGrounding ScrewQuick Wiring andSide Wiring

DESCRIPTION ART. N0. COLOR

PTM-3 QUICKWIRE AND SIDE WIRED TOGGLE 15AMP 120V AC QUICK SWITCHES

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

PTM-3ALPTM-3DEPTM-3BLPTM-3GRPTM-3IVPTM-3WH

Single-poleDecorative SwitchScrew QuickWiring and SideWiring

DESCRIPTION ART. N0. COLOR

PTM-2 QUICKWIRE AND SIDE WIRED TOGGLE 15AMP 120V AC QUICK SWITCHES

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

PTM-2ALPTM-2DEPTM-2BLPTM-2GRPTM-2IVPTM-2WH

3-Way ToggleSwitch WithGrounding ScrewQuick Wiring andSide Wiring

DESCRIPTION ART. N0. COLOR

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

PTM-1ALPTM-1DEPTM-1BLPTM-1GRPTM-1IVPTM-1WH

Single-pole ToggleSwitch WithGrounding ScrewQuick Wiring andSide Wiring

PTM-1 QUICKWIRE AND SIDE WIRED TOGGLE 15AMP 120V AC QUICK SWITCHES

GFCI RECEPTACLERECEPTACLE

• B-19

Page 21: EARTHLEAKAGE CIRCUIT BREAKERsite.iugaza.edu.ps/jtaha/files/2016/10/ELCB.pdf · value, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal

GFCI RECEPTACLE

RECEPTACLE CHARACTERISTICS

Additional assembly screw Side wire connection and 8 holes back quick wire connection Choice of different color Green grounding screw Large head double-drive combination screws for quick wiring

DESCRIPTION ART. N0. COLOR

PTMSR-15/1J

PTMSR-15/2J

Standard DuplexReceptacle 15A,125V ACWith 1J , forSelf-groundingClip

1 for Standard wire

PTMSR-15/1J-ALPTMSR-15/1-ALPTMSR-15/1JEDPTMSR-15/1EDPTMSR-15/1JBLPTMSR-15/1BLPTMSR-15/1JGRPTMSR-15/1GRPTMSR-15/1JIVPTMSR-15/1IVPTMSR-15/1JWHPTMSR-15/1WH

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

DESCRIPTION ART. N0. COLOR

Standard DuplexReceptacle 15A,125V ACWith 2J , forSelf-groundingClip

2 for Standard wire

PTMSR-15/2J-ALPTMSR-15/2-ALPTMSR-15/2JEDPTMSR-15/2EDPTMSR-15/2JBLPTMSR-15/2BLPTMSR-15/2JGRPTMSR-15/2GRPTMSR-15/2JIVPTMSR-15/2IVPTMSR-15/2JWHPTMSR-15/2WH

ALMONDDEEP-ALMONDBLACKGRAYIVORVWHITE

RECEPTACLE

• B-20