EACO News Magazine2010 September
2010-09: Topics
• DVM Plus IIIup compatibility• New control devices
– MIM-B16– MIM-B17– MIM-B18
• How to change option code with MR-CH01
The next EACO News Magazine will be released 01 October ‘10
Compatibility table: DVM Plus III vs DVM Plus IIIup (1)
Outdoor Unit Indoor Units
Before:
DVM Plus III
CurrentDVM Plus IIIIndoor units
After:
DVM Plus IIIup
NewWall Mounted with EEV included
(NS~HHXEA)
Compatible
Not compatible
Compatibility table: DVM Plus III vs DVM Plus IIIup (2)
• So it’s not allowed to make a module system with a mix of DVM Plus III and DVM Plus IIIup outdoor units
• For our Digital Solution Devices there is a free compatibility between old and new outdoor units
BeforeDVM Plus III
AfterDVM Plus IIIup
Module SystemDVM Plus III + DVM Plus
IIIup
NO!
5
• Opto-isolated Interface with pulse-type watt hour meters for electricity billing system
• Max. 8 watt hour meters per interface module• Total 8 WHM interface module per DMS1/DMS2• Pulse coefficient setting: 1Wh/pulse ~ 1000Wh/pulse • Pulse width setting: 20ms~400ms in 1ms intervals• Interval between pulses: minimum 3ms
• No support of pulse coefficient with decimal points• Power data storage in non-volatile memory ( 8 channels)• Data recovery from power failure• Current time setting and display• Configuration information display on LCD• Error display (communication, out-of-range pulse width..)
MIM-B16: WHM interface module (1)
Pulse signal
Max. 8 watt hour meters
6
MIM-B16: WHM interface module (2)
MIM-B16
Max. 8 MIM-B16’sP
ower
Sup
ply
Pow
er s
uppl
y
DMS2
RS485 Comm.
Power supply
Pulse signal
Power boxPower box
7
MIM-B17: BACnet Gateway (1)
• Interface for BACnet management system• Max. 256 indoor units/ERVs support with max. 16 interface modules• Lower physical layer : RS485• Upper physical layer : BACnet/IP
Control Monitoring
On/Off control On/Off state In/out contact state
Operation mode Operation mode Emergency Stop
Temperature setting Set/Room temperature Error code
Fan speed/direction Fan speed/direction
ERV operation mode ERV operation mode
ERV fan speed ERV fan speed
Filter alarm reset Filter alarm
User control restriction User control restriction
Operation mode lock Thermo Off/On
Set temperature limit Power distribution
Emergency stop Operation mode lock
Output contact control Set temperature limit
8
MIM-B17: BACnet Gateway (2)
Ethernet
BACnet BMS
Interface module
RS485
Max
. 16
9
MIM-B18: LonWorks Gateway (1)
• Interface for Lon-Connection to LonWorks management system• Max. 128 indoor units/ERVs support• Communication : RS485 to LonWorks• Upper physical layer : FTT-10A• Combinational use of LonWorks and S-NET3/S-NET mini
Control Monitoring
On/Off control On/Off state In/out contact state
Operation mode Operation mode Emergency Stop
Temperature setting Set/Room temperature Error code
Fan speed/direction Fan speed/direction
ERV operation mode ERV operation mode
ERV fan speed ERV fan speed
Filter alarm reset Filter alarm
User control restriction User control restriction
Operation mode lock Thermo Off/On
Set temperature limit Power distribution
Emergency stop Operation mode lock
Output contact control Set temperature limit
10
MIM-B18: LonWorks Gateway (2)
FTT-10A
LonWorksBMS
Interface module
RS485
Max
. 16
Ethernet
S-NET3 S-NET mini
How to change option code with MR-CH01 (1)
1. Remove one battery from the wireless remote controller.
2. Press the Temp ▲▼ buttons together and put the battery back to enter the
option code setting mode.
3. Set two digits of the option code respectively. And press “Mode” to change to
the next two digits.
4. Press the On/Off power button to change the option code.
11
Initial display
24-bit option code setting
How to change option code with MR-CH01 (2)
12
24-bit option code setting
Example : 027402 – 14221A – 200001 - 300000
4. Then “OFF timer” is displayed
5. Set the next 10 digits
6. Press “On/Off” to set the new option code
※ 20 digits (blue) except the page digits must be set
1. Set the two digits using the Temp ▲▼ buttons
2. Press “Mode” to move to the next two digits. Indicator moves to the next operation mode ◀
icon
3. Press “Mode” to move to the third option code page