Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

22
Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001

Transcript of Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Page 1: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Dynasonics

California Building Code

UL Damper Requirements

2007 vs. 2001

Page 2: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

2007-CBC 2007-CBC Big Changes Big Changes• IBC / CBC Brief History

• UL Damper Requirements (2007-CBC)

• Smoke Control – Overview of Required Locations

• Q&A – as we go

Agenda

Page 3: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

International Building CodeDevelopment History

19941994: ICBO, BOCA, & SBCCI form the International Code Council (ICC) to create a single national model single national model building codebuilding code.

19971997: 1st Edition of the International Building Code (IBC) NFPA & ICC Split over consensus process

20032003: 3rd Edition of IBC – Widely Adopted

20062006: 4th Edition of IBC – Current Edition

Page 4: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

IBC Adoption - Nationwide

IBC - 47 states + Washington, D.C.

IRC - 45 states + Washington, D.C.

IFC - 41 states + Washington, D.C.

State or Local AdoptionState or Local Adoption

Page 5: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

California Building CodeRecent History

19971997: Final UBC Cycle (1997-CBC)

20002000: Readopted 1997-UBC (2001-CBC)

20032003: NFPA-5000 adopted in split vote Never published due to recall of Gov. Davis

20052005: Rescinded NFPA-5000 & adopted IBC

20062006: 2006-IBC modified to meet California requirements

20072007: 2007-CBC Published July 1, 2007

January 1, 2008: 2007-CBC Enforcement Statewide2007-CBC Enforcement Statewide

Page 6: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

UBC vs. IBCOverview

2001-CBC2001-CBC Progressive Sprinklers + Compartmentalization Balanced & ComplementaryBalanced & Complementary

2006-IBC 2006-IBC Chapter 7 Based on BOCA Extensive Sprinkler Tradeoffs

Singular Focus on Sprinklers Height & Area

Fire Resistive Construction

Smoke Control

2007-CBC2007-CBC* Amended to ~ 2001-CBC Eliminated numerous tradeoffs

Sprinklers + Compartmentalization Height & Area

Fire Resistive Construction

+ Smoke Control in High-Rise

* CSFM modifications DON’T apply to:Group B, F, M, S, & U, except as required in Section 111.

Page 7: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

2007-CBC2007-CBC

Organized by Barrier Type

Fire Walls Fire Barriers Shaft Enclosures Fire Partitions Smoke Barriers ... Ducts & Air Transfer Openings ...

Chapter 7 New Layout

2001-CBC2001-CBC

Organized by Systems

Structural Members Projections Joint Systems ... Protection of Openings ...

Page 8: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

2007-CBC2007-CBC

By Barrier Type – Many Trade-offs

716.3.2 Smoke DampersSmoke DampersUL-555SClass-2, 250°F (min)

716.3.1 Fire DampersFire DampersUL-555

1-1/2 Hour (Assemblies < 3hr)

3 Hour (Assemblies ≥ 3hr)

716.6.2.1 Ceiling Radiation DampersCeiling Radiation DampersUL-555C

2001-CBC2001-CBC

Concise – Few Trade-offs

713.10 Smoke DampersSmoke DampersUL-555SClass-2, 250°F (min)

713.11 Fire DampersFire DampersUL-5551-1/2 Hour (Assemblies <

3hr)3 Hour (Assemblies ≥

3hr)

710.3 Ceiling Radiation DampersCeiling Radiation DampersNot Specified

UL Dampers Ratings

Page 9: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Walls located on lot lines or that segregate areas into separate buildings. Fire walls run from exterior wall to exterior wall, from foundation to or through the roof, and are self supporting during a fire.

All Buildings Fire Dampers OnlyFire Dampers OnlyNO EXCEPTIONS

No penetrations are allowed on lot lines. (705.11)

One of the few allowable penetrations to fire walls is between an anchoring building and a covered mall. (402.7.3)

Fire Walls – 716.5.12007 Damper Requirements

Page 10: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Fire Barriers – 716.5.2 2007 Damper Requirements

Shaft enclosures, exit enclosures, exit passageways, horizontal exits, incidental use areas, occupancy separations, and exterior walls

CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.

EXCEPTIONS: 1. Tested per ASTM E119 without fire damper Doesn’t exempt the smoke damper.

2. The fire or smoke damper interferes with 909 smoke control system.

Non-CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group B, F, M, S, & U, except as required in Section 111. NO SMOKE DAMPERS REQUIRED

EXCEPTIONS: 1. Tested per ASTM E119 without fire damper.

2. The fire damper interferes 909 smoke control system.

3. In barriers rated ≤1 hour with minimum 26 ga fully ducted HVAC system in fully sprinklered buildings (other than group H).

Page 11: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Extending through one or more stories in a building, connecting vertical openings in successive floors, or floors and roof.

All Buildings Fire & Smoke DampersFire & Smoke Dampers

Fire Damper EXCEPTIONS: 1.122 inch subduct with continuous exhaust airflow.

1.2 Tested per ASTM E119 without fire damper.

1.3The fire damper interferes with 909 smoke control system.

1.4Parking garage shaft separated by 2-hour rated construction.

Smoke Damper EXCEPTIONS: 2.Kitchen, dryer, and bathroom exhaust in fully sprinklered group B or R occupancies with 22” subduct and continuously running fan per 909.11.

3.Parking garage shaft separated by 2-hour rated construction.

4.The smoke damper interferes with 909 mechanical smoke control system.

Shafts – 716.5.32007 Damper Requirements

Page 12: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Walls separating dwelling units or tenant spaces in covered malls, corridor walls, elevator lobby separations, and exterior walls.

CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111. NO EXCEPTIONS

Non-CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group B, F, M, S, & U, except as required in Section 111.

EXCEPTIONS: 1. Tenant separations or corridor walls in fully sprinklered buildings with ducts protected as through penetration per Section 712.

2. Tenant partitions in covered malls where walls do not extend to the underside of the floor or roof.

3. 26 ga duct < 100 in2 with no openings to corridor or adjacent rooms, AND

The opening is protected with a 12” x 16 ga sleeve with 1-1/2” x 1-1/2” x 16 ga retaining angles AND

The annular space between the wall and sleeve is filled with mineral wool bating on all sides.

Fire Partitions – 716.5.42007 Damper Requirements

Page 13: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Smoke Dampers are required for all fire-resistance rated corridors. Table 1017.1 defines fire-resistance rating by occupancy.

All CSFM regulated buildings require 1-hour rated corridors.

707.14.1 Elevator Lobbies Smoke dampers requirements = corridor requirement.

CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.

Fire Damper EXCEPTIONS: See Fire Partitions.

Smoke Damper EXCEPTIONS: 1. The smoke damper interferes with 909 mechanical smoke control system.

2. 0.019” thick duct and no openings to corridor serving the corridor.

Non-CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers

Group B, F, M, S, & U, except as required in Section 111. NO SMOKE DAMPERS IN SPRINKLERED BLDG

Same exceptions as SFM Regulated Buildings

Corridors – 716.5.4.12007 Damper Requirements

Page 14: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Bisects each floor of an underground building, bisects each patient floor of a hospital, hospital egress & areas of refuge.

All Buildings Smoke DampersSmoke Dampers

EXCEPTION: Openings in steel ducts limited to a single smoke compartment.

Smoke Barriers – 716.5.5 2007 Damper Requirements

Note: Fire damper requirements are not clearly spelled out, but it’s a safe bet that they should be included given the 1-hour fire resistance rating of all smoke barriers.

Page 15: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Smoke Partition – 710.72007 Damper Requirements

Smoke partitions are typically not fire-resistance rated and are constructed to limit the transfer of smoke.

Locations: Elevator Lobby Alternative (707.14.1)

CSFM Regulated Buildings Smoke DampersSmoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.

EXCEPTIONS: 1. The smoke damper interferes with 909 smoke control system.

2. 0.019” thick duct and no openings to corridor serving the corridor.

Non-CSFM Regulated Buildings Smoke DampersSmoke Dampers Group B, F, M, S, & U, except as required in Section 111. TRANSFER OPENINGS ONLY

EXCEPTIONS: 1. The smoke damper interferes with 909 smoke control system.

Page 16: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Ducts and air transfer openings that penetrate the ceiling membrane (NOT the floor or roof) of a fire-resistance rated floor/ceiling or roof/ceiling assembly shall be protected by either:

1. A shaft enclosureshaft enclosure in accordance with Section 707, OR,

2. A ceiling radiation damperceiling radiation damper installed at the ceiling line.

EXCEPTIONS: 1.Tested per ASTM E119 without a ceiling radiation damper.

2.Exhaust ducts are located within the cavity of the wall, are protected per 712.4.1.2, and do NOT pass through another dwelling unit or tenant space.

Membrane Penetrations – 716.6.2 2007 Damper Requirements

Note: The above applies to ALL BUILDINGS.

Page 17: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

The fire damper shall close upon actuation one of the following:

1. The operating temperature is ~ 50°F > the normal duct temperature, but not < 160°F.

2. The operating temperature is ≤ 286°F where located in a 909 smoke control system.

3. Combination fire/smoke dampers located in a 909 smoke control systemThe operating temperature ≤ the UL 555S degradation test temperature and is:

a) ~ 50°F > the maximum smoke control system designed operating temperature, AND

b) ≤ 350°F

Fire Damper Actuating Device

Note: 1.The above applies to ALL BUILDINGS

2.Option 1 & 2 matches 2001-CBC Section 713.101 matches 2001-CBC Section 713.101 NO CHANGENO CHANGE

3.Option 3 is NEWNEW

Page 18: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Eliminates Dual Temperature SystemsEliminates Dual Temperature Systems Eliminates Emergency Override @ Damper Simplified Design One Less Circuit to Wire and Program Reduces Cost Damper Closure @ Max Temp Maintains Safety

Dual Temperature Circuit2001-CBC (T >286°F)

Single Temperature Circuit2007-CBC

Fire Damper Override

Required in2001-CBC

Fire Damper Actuating Device350°F Maximum Temperature

Smoke Detector

Override Only in 2007-CBC

Page 19: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Smoke Damper – 716.3.2.1 Actuating Device

The smoke damper shall close upon actuation of a listed smoke detector installed in accordance with 907.10 and one of the following:

1. A duct mounted smoke detector installed within 5 feet of the damper.

2. A spot-type detector where a damper is installed above smoke barrier doors.

3. A spot-type detector installed within 5 feet of an unducted damper.

4. Where a damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.

5. A total-coverage smoke detector systemA total-coverage smoke detector system.

Note: 1.The above applies to ALL BUILDINGS

2.The above matches 2001-CBC Section 713.10 matches 2001-CBC Section 713.10 NO CHANGENO CHANGE

Page 20: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

2001-CBC2001-CBC• 404.3.3 – Covered Malls

• 403.4 – High-Rise Buildings (B & R-1)

• 402.2 – Atria

• 405.3.3.1 – Stages & Platforms

Smoke Control Required Locations

2007-CBC2007-CBC• 402.9 – Covered Malls

• 403.13 – High-Rise Buildings

• 404.4 – Atriums

• 405.5 – Underground Buildings

• 408.8 – Windowless Buildings (I-3)

• 410.3.7.2 – Stage & Platforms

• 1025.6.2.1 – Assembly (Means of Egress)

Page 21: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

2007-CBC 2007-CBC Big Changes Big Changes• CAUTIONCAUTION CSFM vs. NON-CSFM Regulated Buildings

• CSFM Bldg Similar to 2001-CBC

• NON-CSFM Big Difference

• New Format Barrier Driven + Detail + Trade-Offs

• 350350°F Single Temp Closure°F Single Temp Closure Simple + Cost + Safety

Summary

Page 22: Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.

Thank You for Your Time!Thank You for Your Time!