Eco-Damper - ICD damper, ICC Check valve and ICS control valve
Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.
-
Upload
prudence-walters -
Category
Documents
-
view
231 -
download
5
Transcript of Dynasonics California Building Code UL Damper Requirements 2007 vs. 2001.
Dynasonics
California Building Code
UL Damper Requirements
2007 vs. 2001
2007-CBC 2007-CBC Big Changes Big Changes• IBC / CBC Brief History
• UL Damper Requirements (2007-CBC)
• Smoke Control – Overview of Required Locations
• Q&A – as we go
Agenda
International Building CodeDevelopment History
19941994: ICBO, BOCA, & SBCCI form the International Code Council (ICC) to create a single national model single national model building codebuilding code.
19971997: 1st Edition of the International Building Code (IBC) NFPA & ICC Split over consensus process
20032003: 3rd Edition of IBC – Widely Adopted
20062006: 4th Edition of IBC – Current Edition
IBC Adoption - Nationwide
IBC - 47 states + Washington, D.C.
IRC - 45 states + Washington, D.C.
IFC - 41 states + Washington, D.C.
State or Local AdoptionState or Local Adoption
California Building CodeRecent History
19971997: Final UBC Cycle (1997-CBC)
20002000: Readopted 1997-UBC (2001-CBC)
20032003: NFPA-5000 adopted in split vote Never published due to recall of Gov. Davis
20052005: Rescinded NFPA-5000 & adopted IBC
20062006: 2006-IBC modified to meet California requirements
20072007: 2007-CBC Published July 1, 2007
January 1, 2008: 2007-CBC Enforcement Statewide2007-CBC Enforcement Statewide
UBC vs. IBCOverview
2001-CBC2001-CBC Progressive Sprinklers + Compartmentalization Balanced & ComplementaryBalanced & Complementary
2006-IBC 2006-IBC Chapter 7 Based on BOCA Extensive Sprinkler Tradeoffs
Singular Focus on Sprinklers Height & Area
Fire Resistive Construction
Smoke Control
2007-CBC2007-CBC* Amended to ~ 2001-CBC Eliminated numerous tradeoffs
Sprinklers + Compartmentalization Height & Area
Fire Resistive Construction
+ Smoke Control in High-Rise
* CSFM modifications DON’T apply to:Group B, F, M, S, & U, except as required in Section 111.
2007-CBC2007-CBC
Organized by Barrier Type
Fire Walls Fire Barriers Shaft Enclosures Fire Partitions Smoke Barriers ... Ducts & Air Transfer Openings ...
Chapter 7 New Layout
2001-CBC2001-CBC
Organized by Systems
Structural Members Projections Joint Systems ... Protection of Openings ...
2007-CBC2007-CBC
By Barrier Type – Many Trade-offs
716.3.2 Smoke DampersSmoke DampersUL-555SClass-2, 250°F (min)
716.3.1 Fire DampersFire DampersUL-555
1-1/2 Hour (Assemblies < 3hr)
3 Hour (Assemblies ≥ 3hr)
716.6.2.1 Ceiling Radiation DampersCeiling Radiation DampersUL-555C
2001-CBC2001-CBC
Concise – Few Trade-offs
713.10 Smoke DampersSmoke DampersUL-555SClass-2, 250°F (min)
713.11 Fire DampersFire DampersUL-5551-1/2 Hour (Assemblies <
3hr)3 Hour (Assemblies ≥
3hr)
710.3 Ceiling Radiation DampersCeiling Radiation DampersNot Specified
UL Dampers Ratings
Walls located on lot lines or that segregate areas into separate buildings. Fire walls run from exterior wall to exterior wall, from foundation to or through the roof, and are self supporting during a fire.
All Buildings Fire Dampers OnlyFire Dampers OnlyNO EXCEPTIONS
No penetrations are allowed on lot lines. (705.11)
One of the few allowable penetrations to fire walls is between an anchoring building and a covered mall. (402.7.3)
Fire Walls – 716.5.12007 Damper Requirements
Fire Barriers – 716.5.2 2007 Damper Requirements
Shaft enclosures, exit enclosures, exit passageways, horizontal exits, incidental use areas, occupancy separations, and exterior walls
CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.
EXCEPTIONS: 1. Tested per ASTM E119 without fire damper Doesn’t exempt the smoke damper.
2. The fire or smoke damper interferes with 909 smoke control system.
Non-CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group B, F, M, S, & U, except as required in Section 111. NO SMOKE DAMPERS REQUIRED
EXCEPTIONS: 1. Tested per ASTM E119 without fire damper.
2. The fire damper interferes 909 smoke control system.
3. In barriers rated ≤1 hour with minimum 26 ga fully ducted HVAC system in fully sprinklered buildings (other than group H).
Extending through one or more stories in a building, connecting vertical openings in successive floors, or floors and roof.
All Buildings Fire & Smoke DampersFire & Smoke Dampers
Fire Damper EXCEPTIONS: 1.122 inch subduct with continuous exhaust airflow.
1.2 Tested per ASTM E119 without fire damper.
1.3The fire damper interferes with 909 smoke control system.
1.4Parking garage shaft separated by 2-hour rated construction.
Smoke Damper EXCEPTIONS: 2.Kitchen, dryer, and bathroom exhaust in fully sprinklered group B or R occupancies with 22” subduct and continuously running fan per 909.11.
3.Parking garage shaft separated by 2-hour rated construction.
4.The smoke damper interferes with 909 mechanical smoke control system.
Shafts – 716.5.32007 Damper Requirements
Walls separating dwelling units or tenant spaces in covered malls, corridor walls, elevator lobby separations, and exterior walls.
CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111. NO EXCEPTIONS
Non-CSFM Regulated Buildings Fire Dampers OnlyFire Dampers Only Group B, F, M, S, & U, except as required in Section 111.
EXCEPTIONS: 1. Tenant separations or corridor walls in fully sprinklered buildings with ducts protected as through penetration per Section 712.
2. Tenant partitions in covered malls where walls do not extend to the underside of the floor or roof.
3. 26 ga duct < 100 in2 with no openings to corridor or adjacent rooms, AND
The opening is protected with a 12” x 16 ga sleeve with 1-1/2” x 1-1/2” x 16 ga retaining angles AND
The annular space between the wall and sleeve is filled with mineral wool bating on all sides.
Fire Partitions – 716.5.42007 Damper Requirements
Smoke Dampers are required for all fire-resistance rated corridors. Table 1017.1 defines fire-resistance rating by occupancy.
All CSFM regulated buildings require 1-hour rated corridors.
707.14.1 Elevator Lobbies Smoke dampers requirements = corridor requirement.
CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.
Fire Damper EXCEPTIONS: See Fire Partitions.
Smoke Damper EXCEPTIONS: 1. The smoke damper interferes with 909 mechanical smoke control system.
2. 0.019” thick duct and no openings to corridor serving the corridor.
Non-CSFM Regulated Buildings Fire & Smoke DampersFire & Smoke Dampers
Group B, F, M, S, & U, except as required in Section 111. NO SMOKE DAMPERS IN SPRINKLERED BLDG
Same exceptions as SFM Regulated Buildings
Corridors – 716.5.4.12007 Damper Requirements
Bisects each floor of an underground building, bisects each patient floor of a hospital, hospital egress & areas of refuge.
All Buildings Smoke DampersSmoke Dampers
EXCEPTION: Openings in steel ducts limited to a single smoke compartment.
Smoke Barriers – 716.5.5 2007 Damper Requirements
Note: Fire damper requirements are not clearly spelled out, but it’s a safe bet that they should be included given the 1-hour fire resistance rating of all smoke barriers.
Smoke Partition – 710.72007 Damper Requirements
Smoke partitions are typically not fire-resistance rated and are constructed to limit the transfer of smoke.
Locations: Elevator Lobby Alternative (707.14.1)
CSFM Regulated Buildings Smoke DampersSmoke Dampers Group A, E, H, I, L, & R, High-Rise buildings, & others per Section 111.
EXCEPTIONS: 1. The smoke damper interferes with 909 smoke control system.
2. 0.019” thick duct and no openings to corridor serving the corridor.
Non-CSFM Regulated Buildings Smoke DampersSmoke Dampers Group B, F, M, S, & U, except as required in Section 111. TRANSFER OPENINGS ONLY
EXCEPTIONS: 1. The smoke damper interferes with 909 smoke control system.
Ducts and air transfer openings that penetrate the ceiling membrane (NOT the floor or roof) of a fire-resistance rated floor/ceiling or roof/ceiling assembly shall be protected by either:
1. A shaft enclosureshaft enclosure in accordance with Section 707, OR,
2. A ceiling radiation damperceiling radiation damper installed at the ceiling line.
EXCEPTIONS: 1.Tested per ASTM E119 without a ceiling radiation damper.
2.Exhaust ducts are located within the cavity of the wall, are protected per 712.4.1.2, and do NOT pass through another dwelling unit or tenant space.
Membrane Penetrations – 716.6.2 2007 Damper Requirements
Note: The above applies to ALL BUILDINGS.
The fire damper shall close upon actuation one of the following:
1. The operating temperature is ~ 50°F > the normal duct temperature, but not < 160°F.
2. The operating temperature is ≤ 286°F where located in a 909 smoke control system.
3. Combination fire/smoke dampers located in a 909 smoke control systemThe operating temperature ≤ the UL 555S degradation test temperature and is:
a) ~ 50°F > the maximum smoke control system designed operating temperature, AND
b) ≤ 350°F
Fire Damper Actuating Device
Note: 1.The above applies to ALL BUILDINGS
2.Option 1 & 2 matches 2001-CBC Section 713.101 matches 2001-CBC Section 713.101 NO CHANGENO CHANGE
3.Option 3 is NEWNEW
Eliminates Dual Temperature SystemsEliminates Dual Temperature Systems Eliminates Emergency Override @ Damper Simplified Design One Less Circuit to Wire and Program Reduces Cost Damper Closure @ Max Temp Maintains Safety
Dual Temperature Circuit2001-CBC (T >286°F)
Single Temperature Circuit2007-CBC
Fire Damper Override
Required in2001-CBC
Fire Damper Actuating Device350°F Maximum Temperature
Smoke Detector
Override Only in 2007-CBC
Smoke Damper – 716.3.2.1 Actuating Device
The smoke damper shall close upon actuation of a listed smoke detector installed in accordance with 907.10 and one of the following:
1. A duct mounted smoke detector installed within 5 feet of the damper.
2. A spot-type detector where a damper is installed above smoke barrier doors.
3. A spot-type detector installed within 5 feet of an unducted damper.
4. Where a damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.
5. A total-coverage smoke detector systemA total-coverage smoke detector system.
Note: 1.The above applies to ALL BUILDINGS
2.The above matches 2001-CBC Section 713.10 matches 2001-CBC Section 713.10 NO CHANGENO CHANGE
2001-CBC2001-CBC• 404.3.3 – Covered Malls
• 403.4 – High-Rise Buildings (B & R-1)
• 402.2 – Atria
• 405.3.3.1 – Stages & Platforms
Smoke Control Required Locations
2007-CBC2007-CBC• 402.9 – Covered Malls
• 403.13 – High-Rise Buildings
• 404.4 – Atriums
• 405.5 – Underground Buildings
• 408.8 – Windowless Buildings (I-3)
• 410.3.7.2 – Stage & Platforms
• 1025.6.2.1 – Assembly (Means of Egress)
2007-CBC 2007-CBC Big Changes Big Changes• CAUTIONCAUTION CSFM vs. NON-CSFM Regulated Buildings
• CSFM Bldg Similar to 2001-CBC
• NON-CSFM Big Difference
• New Format Barrier Driven + Detail + Trade-Offs
• 350350°F Single Temp Closure°F Single Temp Closure Simple + Cost + Safety
Summary
Thank You for Your Time!Thank You for Your Time!