Dr Ivan Dudurych Dynamic Security of a Synchronous System with High Wind PenetrationDynamic Security of a Synchronous Power System with High Wind Penetration Dr Ivan Dudurych EirGrid, Ireland

Transcript of Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported...

Page 1: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Dynamic Security of a Synchronous Power System with High Wind

Penetration

Dr Ivan Dudurych EirGrid, Ireland

Page 2: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

European Targets

Page 3: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

* Based on analysis of National Renewable Action Plans (NREAPs) as submitted by Member States

European Targets

Page 4: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Topics

• Operational Security Standards

• How Operational Security is Affected by a Significant Penetration of Wind Generation?

• Secure Wind Generation Level (SWL) and system non-synchronous penetration (SNSP) Concepts

• Experience with on-line Tool for Monitoring Dynamic Security of the Power Transmission System with high wind penetration (WSAT) and other EMS Tools

Page 5: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Page 6: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

How Operational Security is Affected by a Significant Penetration of Wind (Non-synchronous) Generation and

what Mitigation Measures are?

Page 7: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Ireland: Storm “Darwin” 12 February 2014 EMS

Storm Darwin brought 160kph hurricane winds heavy

rain and snow. 200,000 homes affected

Page 8: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Ireland: Storm “Darwin” 12 February 2014 EMS

Storm Darwin brought 160kph hurricane

winds heavy rain and snow. 200,000

homes affected

Page 9: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Ireland: Storm “Darwin” 12 February 2014 EMS

Screenshot – 13:20 16 February

Page 10: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Wind – 12 February

Page 11: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Wind variability

Page 12: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability limits Static limits

Page 13: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Transient Stability

Page 14: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability limits Static limits

Page 15: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Fault ride through capability (New Grid Code)

Page 16: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Fault ride through capability: 55% voltage dip - slow active power recovery

Page 17: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability limits Static limits

Page 18: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Wind Generation Effects on the Power System Operation

57.

09

107

.09

157

.09

207

.09

257

.09

307

.09

357

.09

407

.09

457

.09

507

.09

557

.09

607

.09

657

.09

707

.09

757

.09

807

.09

857

.09

907

.09

957

.09

100

7.09

105

7.09

110

7.09

115

7.09

120

7.09

125

7.09

130

7.09

W ind

1.00042

1.00542

1.01042

1.01542

1.02042

1.02542

1.03042

1.03542

1.04042

1.04542

1.05042

1.05542

1.06042

1.06542

1.07042

pu

/eirgrid230 Wed 08 JUN 2011 14:33 EOC [EGODEN1]

Merit ScaleUp

Bus Voltage (pu) Contingency: GEN 10475 05

BUS SLIGO 10 49810 110.00

BUS POOLBE20 44620 220.00

VSAT 10.3 13-OCT-11 15:41

East

West

Page 19: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Wind Increases a Probability of Wind Power Trips on Transmission Faults

Page 20: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

16 Wind farms!

V

Wind Power Stations tripped following transmission fault

VRN VSN VTN OPEN DELTA

t/s0.00 0.10 0.20 0.30 0.40 0.50 0.60

U/kV

-100

0

100

Page 21: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability

limits

Static limits

Page 22: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

60 MW wind

1000 MW wind

Wind Increases Frequency Deviations

Page 23: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

System Inertia and RoCoF Monitor

23

Page 24: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability

limits

Static limits

Page 25: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Stability

limits

Static limits

Page 26: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Making it happen: EirGrid’s DS3 Programme

System Services

Performance Monitoring

Grid Code

Demand Side Management

Frequency Control

Voltage Control

Renewable data

System inertia

Models Development

Control Centre Tools

AI Wind Secure Level Assessment Tool (WSAT)

Page 27: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Secure Wind Generation Level (SWL) and System Non-synchronous Penetration (SNSP) Concepts

Page 28: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Secure Wind Generation Level (SWL)

Reduce wind

Page 29: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

SWL and Secure SNSP

SNSP = Wind + Imports Load + Exports

Load + Exports = Generation + Imports

SWL = Secure Wind

Generation + Imports

SNSP = Wind + Imports

Generation + Imports

SSNSP = Secure Wind + Imports Generation + Imports

SWL is equivalent to Secure SNSP

Page 30: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Operational Limits and Impact on RES-E

50% 75%

Wind Curtailment Levels Maximum Allowable Real Time Wind Level

Page 31: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Analysis of SNSP % on System During Daylight Hours (8am to 10pm)

Page 32: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Experience with on-line Tool for Monitoring Dynamic Security of the

Power Transmission System with high wind penetration(WSAT)

Page 33: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

WSAT – Software Structure

Near real-time Wind limits

Security violation details

Results Display

WSAT Manager

On-line VSAT

On-line TSAT

Study WSAT

Real-time system

snapshot

Wind ForecastP

yth

on

Inte

rfa

ce

Other information

Input data

Security AssessmentReal-time

Contingencies

Page 34: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Page 35: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Example: Transient Insecurity Warning

35

WSAT reported a v transient stability problem. The loss of Kilbarry Marina 2 110kV line resulted in AD2 and WG1 going unstable. Factors which influenced NCC response included high output of AD2 and WG1 at the time The following action was taken reduced both AD2 and WG1 to 410MW exported.

Page 36: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Example: Voltage Insecurity Warning

36

WSAT reported a voltage stability problem.

The loss of the Castlebar SVC resulted in voltage issues in

Moy, Tawnaghmore and Glenree (currently on a tail)...

Decision taken to switch in Moy 110 kV Cap 1 as soft closing is

available on this cap.

Page 37: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Further work with WSAT: Including the Frequency stability analysis

Page 38: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Further work with WSAT: Reversed Transfers

SecureThermal/Voltage Violations Collapse

Wind MW

Initial

Value

WSAT

Limit

Secure Thermal/voltage violations

Wind MW

Initial

Value

WSAT

Limit

Page 39: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Page 40: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Wind Dispatch Tool

Page 41: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

WSAT: Near real time calculations

Page 42: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Further work with WSAT: Forecast calculations

Up to 6 hr ahead

Up to 24 hr ahead

Page 43: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

Final Remarks • Transmission System Operational Security will be affected by a

significant penetration of wind Generation

• In order to maintain Operational Security standards, even better balancing of active and reactive power across the power transmission system is needed

• Secure Wind Generation Level (SWL) and Secure SNSP Concepts denote how much wind power can be kept instantaneously on the system without compromising Operational Security standards.

• On-line Tool for Monitoring Dynamic Security of the Power Transmission System WSAT in combinations with other EMS tools gives opportunity to operate system securely while maximizing renewable penetration

Page 44: Dynamic Security of a Synchronous Power System with ... Voltage Insecurity Warning 36 WSAT reported a voltage stability problem. The loss of the Castlebar SVC resulted in voltage issues

Dr Ivan Dudurych “Dynamic Security of a Synchronous System with High Wind Penetration”

* Based on analysis of National Renewable Action Plans (NREAPs) as submitted by Member States

European Targets