Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1...
Transcript of Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1...
![Page 1: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/1.jpg)
January 26, 2016 Frederick A, Mueller, P.E., Principal Engineer Ruth Gay, Environmental Systems Corporation Anthony Piazza, WPCF Superintendent
Down the Drain: Trimming Energy Waste from a Wastewater Facility without Breaking the Bank
SIMSBURY, CT WPCF
![Page 2: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/2.jpg)
■ Plant Overview
■ Plant Optimization Goals
■ Energy Savings Opportunities
■ Utility Rebate/Financing
■ Design & Code Approach
■ Discussion
![Page 3: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/3.jpg)
Map courtesy of CT Department of Economic
and Community Development
■ Located in North Central CT § Farmington River § CT Nitrogen Trading Program § Future Phos Limit ~2.5 mg/l
■ Oxidation Ditch Plant § 2006 Major Upgrade $22 Million § Average Flows
o 3.8 MGD Design o 2.1 MGD Actual
§ $260,000/yr Gas & Elec
![Page 4: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/4.jpg)
■ Oxidation Ditch o Run 2 Winter
o Run 1 Summer
■ Designed for Nitrogen Removal § 2 Stage Anoxic Zone (Fixed Speed
Submersible Mixers)
![Page 5: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/5.jpg)
■ Upgraded solids handling system § Sludge Storage Tanks (2)
§ Belt Filter Presses (2)
■ Odor Control System § Chemical Scrubber
■ Modern SCADA Based Control System
![Page 6: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/6.jpg)
Headworks
Primary Clarifiers
(Not Used)
Pre-Anoxic Tanks
Secondary Clarifiers
UV Disinfection
To River
Oxidation Ditch
![Page 7: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/7.jpg)
■ Reduce Energy Usage, Improve Nutrient Removal § Low Cost Control Changes
ü Optimize Aerators Speed Controls
ü Minimum Dissolved Oxygen
ü Sequencing Anoxic Mixers On/Off
ü Bio Phos Removal < 1 mg/l TP
§ Next Step - Invest in Mixer VFDs ?
o Off – Hi – Low - Off
o Save $
![Page 8: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/8.jpg)
Belt Filter Press Room (Thickening) Dewatering of WAS
Aerated Sludge Storage
WAS
Primary Sludge (None)
![Page 9: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/9.jpg)
Chemical Scrubber & Fan @ 22,500 SCFM
Filter Press Room (14,000 SCFM)
Sludge Storage (3,500 SCFM)
Headworks (2500 SCFM)
Septage, Grit, Primary Channels (2500 SCFM)
![Page 10: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/10.jpg)
■ Design Build Contractor § HVAC § Building Automaton
■ Specialty: Deliver Energy Saving Projects § Create Financial Package § Facilitate Utility Involvement § Act as GC to Install Measures § HVAC Controls Programming
![Page 11: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/11.jpg)
■ 2 Office HVAC RTUs § Original Controls
provided scheduled heating and cooling
■ Proposed: § Dual Enthalpy Economizer
§ Demand Based Ventilation
§ Improved scheduling
![Page 12: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/12.jpg)
■ Four 15 HP Mixers § Cycle On and Off at full
speed
§ On 50% of Time
■ Proposed: § Better process control
§ Reduced motor speeds
o Hi 10 min
o Low 110 min
![Page 13: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/13.jpg)
■ Odor Control Fan § Exhaust Fan: Two Speed 40/18 HP
§ Runs Hi Most time (Can’t shut off)
§ Manual Dampers
■ Belt Press Room MAU § 15 HP / 12,000 CFM Gas Fired
§ One Speed – Full Time
■ Proposed: § Reduced Ventilation when Presses are Off
§ VFDs /Better Controls
![Page 14: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/14.jpg)
■ Wastewater Process
■ Process Controls Redesign
■ Code (NFPA 820) Review
■ Submittal Review on Control Panel Modifications
■ SCADA Programming
§ 5 Min 100% § 115 Min 62% § 240 Min Off
![Page 15: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/15.jpg)
■ Each – their Own Language
HVAC (Supply)
HVAC (Exhaust)
HVAC Controls
Odor Scrubber
& Fan
Room
Process Controls
T
![Page 16: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/16.jpg)
■ Is Press Running (Sludge in Room)? § Yes – Ventilate at 6 Air Changes Per Hour
o NFPA – 820 Para 6.2A Row 12
§ No - Treat Like a Normal Room
o Minimize Ventilation for Energy Conservation
• Cycle on-off (keep Room Fresh)
• Vent for Summer Cooling
• Rely on Fin Tube Radiation for Winter Heating
![Page 17: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/17.jpg)
Scrubber
Fan
BFP Room
Headworks
Sludge Tank 1 Other Sludge
Tank 2
MAU1 MAU2 Blower Blower
■ BFPs Run 24 hrs/wk § MAU1 Runs Continuously
§ O.C Fan Runs 24-7 “High” Speed
§ All Manual Controls
![Page 18: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/18.jpg)
Scrubber
Fan
BFP Room
Headworks
Sludge Tank 1 Other Sludge
Tank 2
MAU1 MAU2 Blower Blower
Haz Gas Detector
VFD
VFD
Motor
§ Ventilate Belt Filter Press Room:
o 6 ACH (Proc. Sludge OR Haz Gas) - Continuous
o << 6 ACH* (No Sludge or Haz Gas)
• Timer –Off
• Timer – On - Lower Speed
![Page 19: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/19.jpg)
Scrubber
Fan
BFP Room
Headworks
Sludge Tank 1 Other Sludge
Tank 2
MAU1 MAU2 Blower Blower
Haz Gas Detector
VFD
VFD
Motor
§ 2 Sludge Storage Tank Blowers
o 0 Operating
o 1 Operating
o 2 Operating
![Page 20: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/20.jpg)
![Page 21: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/21.jpg)
■ Gas & Electric Incentives
■ Comprehensive Bonus (Process & HVAC)
■ Design Build
■ Utility Financed
![Page 22: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/22.jpg)
■ Work Completed Aug 2015
■ Mild Weather Since
![Page 23: Down the Drain: Trimming Energy Waste from a … · Scrubber Fan BFP Room Head works Sludge Tank 1 Other Sludge Tank 2 MAU1 MAU2 Blower Blower Haz Gas Detector VFD VFD Motor ! Ventilate](https://reader030.fdocuments.net/reader030/viewer/2022011801/5af7bc887f8b9a44658b7629/html5/thumbnails/23.jpg)
■ Discussion & Questions for the Team?
§ Fred Mueller (Tighe & Bond) [email protected] § Ruth (ESC) [email protected] § Tony Piazza [email protected]