Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power...

4
power www.ppi.ph pazifik BH-DDS/4 Manufactured by: Double-Break Disconnectors Type SSBIII HAPAM has more than 75 years of experience Durable and reliable design Over 30,000 HAPAM disconnectors and earthing switches are in service in more than 80 countries throughout the world Used by major utility companies in the Philippines Virtually maintenance free Visayan Electric Company Inc. (VECO) Naga 138 kV Switchyard

Transcript of Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power...

Page 1: Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power Voltage Transformer 72,5 to 550 kV Unique design with an open magnetic core –

powerwww.ppi.ph

pazifik

BH-DDS/4Manufactured by:

Double-Break Disconnectors Type SSBIII

• HAPAMhasmorethan75yearsofexperience

• Durableandreliabledesign

• Over30,000HAPAMdisconnectorsandearthing

switchesareinserviceinmorethan80countries

throughouttheworld

• UsedbymajorutilitycompaniesinthePhilippines

• Virtuallymaintenancefree

Visayan Electric Company Inc. (VECO) Naga 138 kV Switchyard

Page 2: Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power Voltage Transformer 72,5 to 550 kV Unique design with an open magnetic core –

General

Thehorizontaldouble-breakdisconnectorconsistsofthreepoles.Eachpoleconsistsofaframe,twosupport-inginsulatorsateachendandonerotatinginsulatoratthecenter,onwhichthemainbladeismounted.

Frame

Theframeismadeofasquaretubeinwhichinthecen-terthebearinghousingandtheturnableareinstalled.

Theturnableissupportedbytworollerbearings.Thebearinghousingissealedandfilledupwithgrease,toensurealonglifetime.

Allsteelpartsofthedisconnectorarehotdipgalvanized.

Insulators

ThedisconnectorscanbeequippedwithinsulatorsinaccordancewithIECorANSIspecifications.

Drive Mechanism

TheDisconnectorsand/orearthingswitchescanbesingle-poleorthree-poleoperatedbymeansofamotor-operateddrivemechanismoramanual-operateddrivemechanism.

Incaseonlyonedrivemechanismisusedforthree-poleoperation,thepolesareinterconnectedbymeansofadjustablecouplingrods.Thedrivemechanismalsohousestheauxilliarycontactsforpositionindication.

Main Blade

Themainbladeconsistsoftwofixedcontracts,mountedonthesupportinginsulators,andamovingblademount-edontherotatinginsulator.Themaincontractsareinstalledinsidethemainblade.Theyaremadeofcopper,withasilver-platedsurface.

Eachcontactfingerisprovidedwithstainlesssteelspringstoensurereliablecontactpressure.

Thecontactsareself-cleansing,whichmakesthedis-connectorsuitableforinstallationinareaswithsevereclimaticconditions.

Dependingonthevoltagerating,anticoronashieldswillbeprovided.

Earthing Switch

HAPAMdisconnectorsmaybeequippedwithearthingswitches,whichcanbebuiltontotherighthandsideand/ortothelefthandside.

Theearthingswitchconsistsofanaluminumtube,pro-videdwithsilver-platedcontactsatbothends.

Page 3: Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power Voltage Transformer 72,5 to 550 kV Unique design with an open magnetic core –

Testing

ThedisconnectorsandearthingswitchesaredesignedandtestedinaccordancewithlatestIECspecifications.HAPAMmaintainsaqualityassurancesystemaccordingtoISO9001,certifiedbyKEMA.

Installation

Thedisconnectorsandearthingswitchesarepre-assem-bledandadjustedinourworksascompleteaspossible.

Theconstructionisdesignedsothatalldisconnectorscanbeinstalledandadjustedatsiteveryeasily,withouttheneedofanyspecialtools.HAPAMprovidesclearinstallationinstructionsandassemblydrawings.Maintenace

ThedisconnectorsandearthingswitchessuppliedbyHAPAMaredesignedsoastoensurethattheyarevirtuallymaintenancefree.However,towarrantalongandtrouble-freeserviceperiodweadvicethatavisualinspectionofthecontactsandbearingpointsbecarriedoutatregularintervals.

Rated Voltage 72.5 123 145 245 550LightningImpulseLightningImpulseWithstandVoltage-toearth kV 325 550 650 1050 1550-acrosstheisolatingdistance kV 375 630 750 1200 1550

+315Power Frequency Withstand Voltage-toearth kV 140 230 275 460 620-acrosstheisolatingdistance kV 160 265 315 530 800

Switching Impulse Withstand Voltage-toearth kV - - - - 1175-acrosstheisolatingdistance kV - - - - 900

+450

Current and Short Circuit Ratings

1600A-80kApeak-32kA/3sec. 2000A-100kApeak-40kA/3sec. 3150A-125kApeak-50kA/3sec. 4000A-160kApeak-63kA/3sec.

Voltage (kV) 72.5 123 145 245 550A 770 1220 1500 2300 4400B 1195 1645 1925 2805 5085C 900 1400 1650 2600 4400D 250 700 825 1300 2200F 485 750 875 1440 2450G 1190 1985 1965 2740 5150J 500 1000 1250 2000 3700K 200 200 200 300 350L - - - 100 200M 175 175 175 210 280

P&H definedbysubstationlay-out

Technical Data - SSBIII

Dimensions (mm) - SSBIII

Page 4: Double-Break Disconnectors Type SSBIII - PPI Pazifik Power, Inc. Break... · 2016. 12. 5. · Power Voltage Transformer 72,5 to 550 kV Unique design with an open magnetic core –

Efficient Electricity SolutionsInaspanoftwodecades,PPIPazifkPower,Inc.successfullysuppliedthePhilippinemarketawiderangeofhighqualityinnovativepowerandinfrastructureequipmentfromthebestmanufacturersinEuropeandfromitsownautomateddesignconcepttomorethan200customerswhoareatforefrontofthecountry’senginesofindustrialgrowth.

AmongPPI’smostsoughtafterpowerproductlinesare:TurnkeyprojectsforSupplyofSubstationsratedvoltageofupto230kV,ElectricityMeters,Transformers,Switchgears,Disconnectors,Fault Indicators,SurgeArresters,ProtectiveRelays,DiagnosticandTestingEquipments,Batteries,HarmonicFilters,UPSandAVRsystems.

PPI’sseasonedElectricalEngineersdelivertheuniquesupporttailoredfitforeachcustomerneeds.PPI’scuttingedgeisitshighproductqualitywithanunparalleleddeliveryofafter-serviceperformance.

Smart Navigator Fault Indicator with Communication

DesignedandengineeredforSmartGridDistribution,Automation,Application

Surge ArresterSiliconarresterincagedesign

SubstationTypeArresterProtectionagainstatmosphericoverloads

ratedupto800kV

Combined Instrument TransformersTypeVAU-72,5to550kV

High-precisionmeasurementaccuracyandprotectionclasseswithsuperior

transientresponse

High Voltage DisconnectorsRated69kVupto800kV

Power Voltage Transformer72,5to550kV

Uniquedesignwithanopenmagneticcore–ensuringferroresonanceimmunity,ratedoutputcapacityof

10-100kVAperphase

Circuit Breaker TestingGuaranteedhighlevelofaccuracy

TRANSMISSIONEqUIPMENT

Medium Voltage SwitchgearsSwitchgearcontributestoimproving

electricaldistributioninMediumVoltagenetworksupto36kVwithratedcurrent

upto2,500A

www.ppi.ph/dlfiles/BH_DDS.pdf

AFFILIATES

4/FSouthParkPlaza,SantiagoStreetPaseodeMagallanesCommercialCenter1232MakatiCity,MetroManila,PhilippinesTel. : +6325118888Fax : +6326288081E-mail : [email protected]

HORSTMANNGmbH

HORSTMANNGmbH

LionaAutomaticonlinePDdetectionandlocalizationonXLPEcables