Dorrance H. Hamilton Building
Josh KreutzbergerLighting/ElectricalPenn State Architectural EngineeringSenior Thesis
![Page 2: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/2.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 2
Building OverviewThomas Jefferson University (TJU)
Philadelphia, PAMedical Education129,000 ft2 with an additional 60,000 ft2plaza area6 stories above grade with 2 story underground parking garageArchitect: Burt Hill
![Page 3: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/3.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 3
Presentation Outline
Lighting DepthClassroomAuditoriumLobby
Electrical DepthCentral Transformer vs. Distributed Transformers
Construction Management BreadthCost Analysis
Bus Duct vs. FeedersConstruction Management Breadth
Cost AnalysisMotor Control Center
Conclusions
![Page 4: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/4.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 4
Classroom (5th Floor)
Design ObjectivesReading/Writing TasksIlluminance target = 50fc Accent BlackboardDimmable Fixtures for use with VDT ScreenASHRAE 90.1 Standards
1.4 W/ft2
![Page 5: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/5.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 5
Classroom Lighting Plan
![Page 6: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/6.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 6
Classroom Isolines
Power Density = 1.31 W/ft2Average Illuminance on Workplane = 49.6 fc
![Page 7: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/7.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 7
Classroom Renderings
![Page 8: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/8.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 8
Auditorium
Design ObjectivesReading/Writing TasksIlluminance target = 50fc Accent BlackboardDimmable Fixtures for use with VDT ScreenUse Cove LuminairesASHRAE 90.1 Standards
1.4 W/ft2
![Page 9: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/9.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 9
Auditorium SectionCove Luminaires
![Page 10: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/10.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 10
Auditorium Lighting Plan
![Page 11: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/11.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 11
Auditorium Renderings
![Page 12: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/12.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 12
Auditorium Pseudo Color
Average Illuminance on the Work Plane is 42.3 fc.
Power Density is 1.47 W/ft2.
![Page 13: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/13.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 13
Lobby
Design ObjectivesCirculation - TaskIlluminance target = 5fc Aesthetically AppealingSparkleAccent ArchitectureHighlight Elevators & DoorwaysASHRAE 90.1 Standards
1.3 W/ft2
![Page 14: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/14.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 14
Lobby Lighting Plan
![Page 15: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/15.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 15
Lobby Isolines
Average Illuminance on the Work Plane is 22.1 fc.
Power Density is 1.05 W/ft2.
![Page 16: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/16.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 16
Lobby Renderings
![Page 17: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/17.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 17
Central vs. Distributed Transformers
![Page 18: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/18.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 18
Central vs. Distributed TransformersCost Analysis – Construction Management Breadth
Distributed Transformers are 10.0% cheaper and cost $24,120 less than the Central Transformer.
![Page 19: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/19.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 19
Busduct vs. Feeders
![Page 20: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/20.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 20
Busduct vs. FeedersCost Analysis – Construction Management Breadth
Busduct is 7.6% cheaper and costs $4,508 less than the individual feeders.
![Page 21: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/21.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 21
Motor Control Center
![Page 22: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/22.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 22
Motor Control Center - Sizing600 amp busduct is needed.
A 600-amp busduct will need 6X number of spaces.
Total of 93X number of spaces. Since there are 12X spaces per section, I will need 8 sections.
Final dimensions of the motor control center are 16”deep, 90” high, and 180”long.
![Page 23: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/23.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 23
Motor Control Center Layout
![Page 24: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/24.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 24
ConclusionLighting Depth
ClassroomTarget Illuminance = 50 fc, 49.6 fc averageAccent BlackboardDimmable Fixtures for use with VDT ScreenASHRAE 90.1 Standards
1.31 W/ft2 calculated, 1.4 W/ft2 allowed Auditorium
Target Illuminance = 50 fc, 42.3 fc averageAccent BlackboardDimmable Fixtures for use with VDT ScreenUse Cove LuminairesASHRAE 90.1 Standards
1.47 W/ft2 calculated, 1.4 W/ft2 allowed Lobby
Target Illuminance = 5 fc, 22.1 fc averageAesthetically Appealing/SparkleAccent ArchitectureHighlight Elevators and DoorwaysDimmable Fixtures for use with controlsASHRAE 90.1 Standards
1.05 W/ft2 calculated, 1.3 W/ft2 allowed
![Page 25: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/25.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 25
ConclusionElectrical Depth
Distributed Transformers vs. Central TransformerDistributed Transformers are 10.0% cheaper and cost $24,120 lessthan the Central Transformer.Recommendation: Go with the Distributed Transformers due to thecheaper system cost even when the sixth floor transformer is added.
Busduct vs. FeedersBusduct is 7.6% cheaper and costs $4,508 less than the individual feeders.Recommendation: Go with the Busduct due to the cost savings and square footage savings.
Motor Control CenterRecommendation: Go with the MCC due to the square footage savings and the organization provided with a MCC.
![Page 26: Dorrance H. Hamilton Building · Josh Kreutzberger Dorrance H. Hamilton Building 22 Motor Control Center - Sizing ¾600 amp busduct is needed. ¾A 600-amp busduct will need 6X number](https://reader034.fdocuments.net/reader034/viewer/2022051604/600078aade5d67618252761d/html5/thumbnails/26.jpg)
Josh Kreutzberger Dorrance H. Hamilton Building 26
Thanks!
Questions?
Comments?
Acknowledgments
Design Firms
The Lighting Practice
Burt Hill
AE Faculty
Dr. Mistrick
Prof. Dannerth
Prof. Parfitt
Prof. Holland
Family & Friends