![Page 1: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/1.jpg)
associate profesor DOMAGOJ DAMJANOVIĆ Construction Testing Laboratory
Faculty of Civil Engineering
University of Zagreb
![Page 2: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/2.jpg)
Test set-up
Setup A Setup B
![Page 3: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/3.jpg)
Test protocol The cyclic horizontal load protocol is composed of three sets of rules:
Definition of a yielding point (the Yasumura and Kawai (1997) procedure for timber shear wall)
Cyclic protocol EN 12512:2001 in the range of low displacement amplitudes (up to 2dy)
Cyclic protocol ATC-24 in the range of high displacement amplitudes (over 2dy)
Displacement (mm)
Hori
zo
nta
l fo
rce
(kN
)
EN 12512 ([%]*dy) ATC-24 ([%]*h or +0.5 dy)
v=0.25 mm/s
v=0.5 mm/s v = 1 mm/s
Time (s)
Sto
ry d
rift [
h/d
] (%
)
dy
2 d
y
![Page 4: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/4.jpg)
Test protocol
Displacement (mm)
Hori
zo
nta
l fo
rce
(kN
)
EN 12512 ([%]*dy) ATC-24 ([%]*h or +0.5 dy)
v=0.25 mm/s
v=0.5 mm/s v = 1 mm/s
Time (s)
Sto
ry d
rift [
h/d
] (%
)
dy
2 d
y
Specimens of each type of joints were loaded by monotonous lateral loads until reaching a 20% drop of load bearing capacity to obtain the load-deformation curve which was used to determine the displacement at a yielding point (dy)
The range of low amplitudes is divided into parts concerning the actuator velocity of 0,25 mm/s up to displacement amplitude equal to dy and velocity of 0,50 mm/s up to a displacement amplitude of 2dy.
![Page 5: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/5.jpg)
Test protocol
Displacement (mm)
Hori
zo
nta
l fo
rce
(kN
)
EN 12512 ([%]*dy) ATC-24 ([%]*h or +0.5 dy)
v=0.25 mm/s
v=0.5 mm/s v = 1 mm/s
Time (s)
Sto
ry d
rift [
h/d
] (%
)
dy
2 d
y
After reaching the limit of 2dy the speed of actuator increased to 1,00 mm/s
Three cycles of loading were performed for each selected amplitude
Testing ended when the complete failure of joints was achieved
![Page 6: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/6.jpg)
Test results for Φ10 mm threaded glued–in steel bar and Setup A
for Φ10 mm threaded glued–in steel bar and Setup B
failure due to timber compressive crushing and reaching tensile strength of steel bar
![Page 7: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/7.jpg)
Test results for Φ14 mm threaded glued–in steel bar and Setup A
for Φ14 mm threaded glued–in steel bar and Setup B
failure due to timber compressive crushing
![Page 8: DOMAGOJ DAMJANOVIĆ - unizg.hr...Test protocol The cyclic horizontal load protocol is composed ofthree sets rules: Definition of a yielding point (the Yasumura and Kawai (1997) procedure](https://reader033.fdocuments.net/reader033/viewer/2022060100/60aeace97cc80347c67d82cb/html5/thumbnails/8.jpg)
Test demonstration for Φ20 mm threaded glued–in steel bar and Setup A