Dubai Municipality
Continue Regulation of Building Conditions & Specifications
Article (42): Sanitation Works:-
(A) No drainage works shall be made except after obtaining the
building license from the competent authority.
(B) All materials used in the sanitation works and designing the drainage
works in the buildings and constructions must be compatible with the
standard conditions and specifications issued by the competent
authority.
(C) Connection of the buildings relating to the public drainage network
shall in no way be made apart from the Municipality as the concerned
authority is the sole party authorized to do the same.
(D) No changes shall be made to the drainage designs of any building after
the issuance of the building license without obtaining the necessary
license even if such changes are acceptable as to the technical andengineering aspects thereof.
(E) The competent authoritys approval to connect drainage lines of the
buildings to the public network as set forth in the drawings of the
building license is an initial approval not binding the Municipality if it
has become clear thereafter that the connection in this manner is
difficult or impossible. The competent authority may ask for making
changes to drainage system of the building in such cases in order toconnect drainage lines of the building to the public network in the
proper technical and engineering manner.
1
-
7/27/2019 DM Condition & Specification of Building
2/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
Article (43): Provisions and Conditions of Sanitation Works:-
(A) The following documents and plans must be presented as minimum for
the sanitation works upon applying for the building license:-
1- Paying the drainage connection fees if there is public drainage
network and the connection location document (home joint F.I.C) with
this network.
2- Sheet of the sanitation works conditions and specifications according
to the competent authority instructions signed and approved by the
Engineer.
3- Setting-out plan explaining the public drainage lines in the area
surrounding the plot of land, if any, and the external drainage lines,
check rooms within the plot, the last check room, and the home jointlocation with the public drainage network lines and levels, and
dissolution tank and absorption hole if there is no public drainage
network.
4- Plans of sanitary supplies and water supplies of all floors of
the building.
5- Any other documents or details required by the competent authority.
(B) Surfaces of toilets, urinals and washbasins must be soft, easily cleaned
and non-absorbable. Such installations must be made and installed in a
2
-
7/27/2019 DM Condition & Specification of Building
3/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
way insuring complete draining of their contents through a water spigotproofed against water evaporation and dryness. In addition, all siphons
of the latrines and urinals must be of an efficient and powerful type to
clean the excrements and to endure heavy usages in public places.
(C) In the buildings which are less than 20 floors in height, the drainage in
the ground floor shall be separately connected to the check rooms
directly and not to be connected on the same vertical columns of the
higher floors.
(D) In the buildings which are more than 20 floors in height, the drainage in
the ground and first floors shall be separately connected to the check
rooms directly and not to be connected on the same vertical columns of
the higher floors.
(E) The internal drainage system in the buildings must be supplied with the
necessary ventilation pipes and with a size sufficient to the purpose oftheir use provided that the internal caliber thereof shall in no way be
less that (50) mm. in the internal connections and (75) mm. inn the
vertical columns. In addition, they must be vertically installed and
raised to its minimum by one meter above the highest hole in the
building and by horizontal distance of not less than (2) meters.
The competent authority may ask to raise the ventilation pipe or to take
it away from the pits beyond what was mentioned if there are technicalreasons requiring the same. In addition, the pipes ends must be covered
by their own covers.
3
-
7/27/2019 DM Condition & Specification of Building
4/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(F) The washers water shall not be discharged to the ground drains or thenormal drainages columns, and it must be discharged directly to the
work columns or check rooms by way of a deep water spigot.
(G) The work pipes and normal drainage pipes buried under ground must be
made of strong and solid materials, and their calibers and inclinations
must be compatible with the specifications determined by the competent
authority. In addition, the joints thereof must be water- and air-proof
and not producing any obstacles inside the pipes, and to be able toendure a pressure of not less than the minimum pressure, a height of (3)
meters of water. Such pipes must be extended and spread out according
to the conditions of the soil and load and based on the instructions of the
manufacturer companies.
(H) A check room must be constructed at every point in which the direction
of the drainage pipes shall be changed or at which the degree of their
declination shall be changed or at which a pipeline shall be connected toanother one. The distance between any two subsequent check rooms
must not be more than (15) meters, and the check rooms must be made
in accordance with the specifications determined by the competent
authority.
(I) It is not permissible to build check rooms inside the ceiled buildings
except in the skylights, corridors, services rooms, garages, and passages
of sufficient ventilation provided that they shall be of the dry kind. Inaddition, the drainage pipes extended under ground and wall must be
protected against any external works or against the floor collapse, and
4
-
7/27/2019 DM Condition & Specification of Building
5/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
the cleaning pits thereon must be secured by distances of not more than(10) meters.
(J) All check rooms must be constructed within the limits of the plot, and at
the time of designing and determining the check rooms locations, it is
necessary to take into consideration choosing the location and the
appropriate levels of the last check room as to the easiness of
connection to the public drainage network and fulfilling the conditions
of the competent authority.
(K) All ground floors (vaults) must be supplied with the means and
equipment appropriate to water discharge and purification such as (sand
sedimentation rooms pumps fat traps.. etc.) and in case there in no
need to the fat traps in the current supposed design, it is necessary to
make the supplies required to install them if need be.
(L) The drainage lines shall not be extended through the columns, bridges,foundations and electricity rooms except as approved by the competent
authority. In such cases, the pipes shall be extended through pits to be
constructed in advance at the time of founding the concrete. The pipes
must be supplied with the necessary flexible joints.
(M) In case of discharging large amounts of fats or oils to the drainage
network from the restaurants or kitchens and the like, a spigot of a
design approved by the concerned authority must be installed for fatsand oils.
5
-
7/27/2019 DM Condition & Specification of Building
6/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(N) The commercial and industrial wastes shall not be discharged to thepublic drainage network without obtaining the consent of the concerned
authority, and this consent shall not be granted except in case of
providing the supplies appropriate for initial management of such
wastes. In addition, the heaters water exceeding (37 C.) shall not be
discharged to the public drainage network before being cooled.
Article (44): Sanitary Accommodations:-
(A) Minimum sanitary accommodations required to be provided in the
buildings shall be as follows provided that at least (75%) thereof
(toilets) in the public activities locations must be of the eastern model:-
1- Housing Units:
Every housing unit in the building must be supplied with the necessary
sanitary accommodations including bathrooms, toilets and kitchens andat least one toilet not to be entered thereto from any housing room.
2- Studios:
Every studio in the building must be supplied with the necessary
sanitary accommodations including bathrooms, toilets and kitchens as
minimum.
3- Offices, Shops and Fairs:A- Offices:
6
-
7/27/2019 DM Condition & Specification of Building
7/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
One water closet (WC) must be provided for every separateoffice or for every (2000) square meters of the open offices in
case of making collective bathes.
B- Shops and Fairs:
One WC at least must be provided for the commercial space from (1) to
(3000) square meters, and two WCs for men and one for women for the
space from (3001) to (10000) square meters, and adding one WC for
men and another one for women for every increase of (10000) squaremeters.
4- Trade Centers and Public Entertainment Buildings:
A- At least three WCs for men and two WCs for women must be
provided for the commercial or entertaining space from (1) to (10000)
square meters, and adding one WC for men and another one for women
for every increase of (5000) square meters along with providing WCs
for women equal to half of the number of men WCs.
B- At least two additional WCs one for men and one for women must
be provided the handicapped people if the commercial or entertaining
space is more than (20000) square feet.
5- Labor Housing:
A- The sanitary accommodations must be provided in accordance
with the labor housing stipulations referred to in article (31) ofthis Regulation.
7
-
7/27/2019 DM Condition & Specification of Building
8/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
B- WCs shall be separated from the washbasins and bathrooms insidethe collective services.
6- Nurseries and Schools:
The sanitary accommodations must be provided for schools and
nurseries in accordance with their stipulations referred to in article (34)
of this Regulation.
7- Stores and Workshops:A toilet and washbasin must be provided for every store and workshop.
However in case of the collective services, a toilet and washbasin must
be provided for every (5000) square meters for the first ten thousand
square meters of the total space of the buildings then one toilet and
washbasin for every (15000) square meters following the first ten
thousand square meters provided that such washbasin must be external.
8- Hotels, Hotel Restaurants and Hostels:The sanitary accommodations must be provided in accordance with
hotel stipulations referred to in article (37) of this Regulation.
9- Mosques:
The sanitary accommodations must be provided thereto in accordance
with mosque stipulations referred to in article (32) of this Regulation.
10- Other Specialized Buildings:The sanitary accommodations must be provided thereto in
accordance with the special studies and approved international
specifications and measurements.
8
-
7/27/2019 DM Condition & Specification of Building
9/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
Article (45): Dissolution Tanks and Absorption Pits:-
In case there is no public drainage network in the area in which the
building is to be constructed, the building must be provided with
drainage, collection and dissolution tanks in accordance with the
following conditions:-
A- To be within the limits of the plot.
B- To be in a location near the road and away from the main building
and neighboring area, and to be easily reached for cleaning,
maintenance and discharge purposes provided that the competent
authority shall approve such location, and to be easily connected to the
public drainage network in the future.
C- The ceilings of such tanks must be built by reinforced concrete so
that they shall endure the cars passing above them in need by.
D- To have an opening with a heavy type cover that can be tightly
closed, and with sufficient dimensions.
E- The level of their ceilings shall not be higher than the level of the
ground of its location.
F- The capacity of such tanks must be appropriate and calculated based
on the daily personal consumption according to the standard tables.
9
-
7/27/2019 DM Condition & Specification of Building
10/24
-
7/27/2019 DM Condition & Specification of Building
11/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(B) Every open surface in any building must be made with an inclination ofnot less than (50:1 to 70:1) so that the water shall flow out thereupon to
appropriate ductules or outlets leading to drainage pipes or waterspouts
appropriate for this purpose.
(C) The ductules, waterspouts, outlets and drainage pipes must be made
with an inclination angle of not less than (90:1) and made of strong
materials and waterproof joints, of sufficient sizes and installed in a
strong and secure manner.
(D) Rainwater shall not be discharged in the drainage pipes, dissolution
tanks, absorption pits or in the neighboring areas, but it should be
discharged in the surfaces of roads and ways. The rainwater may be
discharged directly into the public rainwater drainage network or the
absorption pits in coordination with the concerned authority.
(E) Conditioners and terraces water shall not be discharged to the streetsdirectly or to the rainwater drainage lines, and they must be discharged
to the public drainage network.
(F) Waste waters shall not be discharged to the rainwater drainage network
regardless of any reason.
Article (47): Water Supply:-
11
-
7/27/2019 DM Condition & Specification of Building
12/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(A) All used materials and their specifications, network designs,workmanship of water supplies must be in accordance with the
conditions and specifications of Dubai Electricity & Water Authority.
(B) Every building or construction must be connected to the public water
network except no water is procured in any way approved by the
competent authority.
Article (48): Drink Water Tanks:-
(A) Drink water tanks must be made of stainless or non-wearing materials,
and not to affect the natural and chemical properties of water, and not to
cause any change in the color, taste or odor of the water, and not to be
affected with heat or moisture, ant to be non-penetrable of light and
having no harmful effect on the human health.
(B) The tanks must be provided with openings for cleaning with an
appropriate measurement and allowing tight closing and of the type
specialized to the water tanks (double seal) and such openings to be
with a capacity sufficient for the entry of one person to perform the
regular cleaning inside the tank, and its location to be in a clean area
and away from the daily direct movement and way from the pollution
sources, and to be higher than the ground level.
(C) Upon designing, it is necessary to take into consideration to make the
tank free of any strict angles causing the accumulation of dirts and
microbes or hindering the regular cleaning works.
12
-
7/27/2019 DM Condition & Specification of Building
13/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(D) The tanks must be supplied with openings for water filling, distribution,
discharge of washing water and ventilation with measurements
appropriate to the tank size, and consideration must be taken for the
distribution openings to be of a height of less than (6) cm. above the
tank bottom level, and for wash water drainage openings to be inside the
tank bottom, and for the tank filling and ventilation openings to be in
the upper part of the tank, and for all such openings to be supplied with
spigots to control opening and closing, and for the ventilation tube to bedesigned in away preventing the entry of any materials or insects which
may pollute the tank, and for all such openings and connections to be
made of stainless materials of no harmful effects on the human health.
(E) The tank must be placed in clean locations and away from any source of
pollution, and to be raised on poles of not less than (20) cm. from the
ground, and to take into consideration to install the tank in a way not
affecting the insulation layers of the surfaces, and it is recommended toplace the tank in a shaded place and not to appear in a way deforming
and impeding movement on the surface.
(F) The water tanks must be cleaned once every (six months at least) taking
into consideration that the materials used in cleaning shall not include
any toxic materials or harmful to the public health, and the health
conditions must be strictly observed in the cleaning process.
(G) Taking into consideration to choose the water tanks location to be away
as possible from the drainage lines, check rooms, dissolution tanks and
absorption pits. In all cases, it is not allowed to place the drainage lines
13
-
7/27/2019 DM Condition & Specification of Building
14/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
above or beside the water tanks in case the tanks are under the groundsurface level.
(H) The capacity of water tanks shall be calculated based on the actual
needs of the building in accordance with what is determined by the
competent authority.
(I) The inspector has the right to enter to any building to inspect the water
tanks to make sure they are compatible with the health and technicalconditions.
Article (49): Storage of Home Gas Cylinders:-
The following conditions must be met as minimum in the places of
storing the home gas cylinders.
(A) The home gas cylinder must be placed in a covered and well-ventilated
place and such place must be outside the kitchen or housing area.
(B) The cylinders store in the public buildings must be of a well-ventilated
place and easily reached to exchange the empty cylinders and to be
easily isolated and to combat the fires erupted therein in case of
emergency.
(C) All gas supplies must be made in accordance with the approved
standard specifications of the competent authority.
14
-
7/27/2019 DM Condition & Specification of Building
15/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(D) In case there is a central store of gas cylinders in the buildings, thebuilding owner must perform annual inspection for all joints and pipes
of gas connection to the housing units to make sure they are safe and
there is no leaks therein.
(E) All cylinder stores must be supplied with fire combat and alert systems
in accordance with the specifications and conditions determined by the
competent authority, and to regularly maintain the extinguishment
equipments.
(F) Not to store the flammable materials such as car tires, carton and paper
with gas cylinders.
Article (50): Insulating Materials:-
The following provisions shall be applied to the heat and moistureinsulating materials:-
(A) Insulating layers must be placed on the floors of bathrooms, kitchens,
and WCs.
(B) Moisture and heat insulating layers must be placed on the last ceiling of
the building to protect the last floor ceiling from rainwater infiltration
and heat.
(C) Insulating layers must be placed around the building foundations to a
height of one foot above the natural level of the ground.
15
-
7/27/2019 DM Condition & Specification of Building
16/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(D) All metals which are subject to rust must be painted and protected by
insulating materials and to be maintained on regular basis especially the
drainage and supply pipes.
(E) All conditions and specifications set forth in the heat insulation
regulation approved by the competent authority upon designing,
implementing and calculating the heat and electrical works of the
building including (ceilings, walls, windows, doors, building direction,location arrangement, tree planting, electrical lighting, mechanical
ventilation, conditioning, .. etc.)
Article (51): Conditions of Waste Rooms and Complexes:-
(A) Buildings and housing, industrial, educational, health, entertaining and
tourist complexes must be supplied with a waste complex within thelimits of the plot and within the building fence, or in a room to be built
in the ground floor of the building itself, to collect the wastes therein as
a preliminary step toward moving the wastes outside the building to get
rid thereof.
(B) The waste rooms specifications are as follows:-
1- To be built in a place near the street or on the road in case there is nostreet to facilitate the process of getting out the containers and taking
them to the vehicles of waste collection without obstacles.
16
-
7/27/2019 DM Condition & Specification of Building
17/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
2- The entrance measurements shall be appropriate to get the containersout and in easily therefrom, and the entrances shall be supplied with
slopes with inclinations appropriate for this purpose.
3- The measurements and areas of the rooms and complexes shall be in
accordance with what is determined in article (52) of this Regulation.
4- The floor and entire height of rooms walls shall be made of ceramic
tiles to be easily cleaned.
5- To be supplied with water directly from the network or from the
elevation tank.
6- To be connected with the drainage lines in the building.
7- To be of a good lighting and to be supplied with a good ventilation
system.
8- All windows to be tightly closed and supplied with soft metal screen
to prevent insects and rodents from getting into or out thereof.
9- The collection room door must be made of stainless metal material
(aluminum) along with being supplied from the lower part with
ventilation beams (Louver) or mechanical ventilation system and to
make the door opening direction outwards.
10- Waste containers complex shall be in the ground floor, and the level
thereof shall not be less than the specified areal reference, and its
17
-
7/27/2019 DM Condition & Specification of Building
18/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
entrance shall be connected to the street with a slope of appropriateinclinations, and to be paved with washable ceramic tiles and supplied
with water point.
(C) The building must be supplied with a chute system if the building is
more than three floors in height above the ground floor and the area of
the plot is more than (2500) square feet, and ???????? shall not be
considered as a floor if its use was subsidiary to the ground floor.
(D) In the plots of not less than (5000) square feet, the waste chute may be
replaced by providing small waste rooms with (6x4) feet in every floor
in addition to the main waste room in the ground floor provided that the
width of its door shall not be less than (90) cm and to open outwards
and to be supplied with the door closer along with providing mechanical
ventilation, and it is not allowed to provide ventilation through
ventilation openings (Louver) in the door.
(E) The caliber of waste chute from the floors to the collection room must
not be less than (60) cm provided that the waste throwing openings in
the repeated floors must be preceded by a small room of not less than
(3x3) feet and the width of its door shall not be less than (80) cm. and
its door shall open outwards along with installing the door closer.
(F) In the buildings in which the chute system is not required and the floor
is more than (10000) square feet, small rooms of less than (4x6) feetshall be provided to collect the waste bags in every floor provided that
the width of its door shall be not less than (90) cm and its door shall
open outwards and supplied with the door closer along with providing
18
-
7/27/2019 DM Condition & Specification of Building
19/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
mechanical ventilation and not allowing the ventilation through(Louver) openings in the doors.
(G) Chute system can be replaced with an alternative service elevator to be
placed in an area separated from the main elevators along with building
small rooms for collection with the same area of the elevator in every
floor so that the elevator shall be near the main waste rooms of the
building.
(H) The building owner or his authorized representative shall be responsible
for cleaning inside the building and the external areas surrounding and
attached thereto to the borders of the general street, and for carrying and
moving the waste containers from the waste rooms to the nearest street
in the specified times for the same along with returning the containers to
the rooms after completing the process of discharge.
(I) The normal compactor shall not be considered as an alternative for thenumber of containers or the area of waste rooms.
(J) If the location of chute system is away from the streets surrounding the
plot, a waste collection room can be built in a place near the street or the
road in case no street is there.
(K) It is strictly forbidden to throw the active chemical wastes, toxic
materials or hazardous liquids inside the waste containers.
19
-
7/27/2019 DM Condition & Specification of Building
20/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(L) To contribute to environment protection, the garbage must by recycledthrough assigning and classifying the waste containers based on the
main types of the thrown materials.
Article (52): Measurements of Waste Rooms and Complexes:-
(A) In the buildings which are less than 2000 square meters, a waste room
of (4x6) feet must be provided in the ground floor only along withproviding mechanical ventilation for it provided that the width of its
door shall not be less than (90) cm. and to be supplied with the door
closer.
(B) In the buildings which are more than 2000 square meters, waste rooms
must be provided as follows:-
1- Up to 100 kg. of
wastes
One room taking one container of (1
and 1) cubic meter.
2- Up to 250 kg. of
wastes
One room taking one container of (2,5)
cubic meters, or two containers of (1
and 1) cubic meter for every container.
3- Up to 500 kg. of
wastes
One room taking two containers of (2,5)
cubic meters.
4- Up to 750 kg. of One room taking three containers of
20
-
7/27/2019 DM Condition & Specification of Building
21/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
wastes (2,5) cubic meters.
5- Up to 1000 kg. of
wastes
One room taking four containers of
(2,5) cubic meters.
6- More than 1000 kg.
of wastes
Number of waste rooms shall be
determined in accordance with a special
study or the same previous rates shall be
calculated for half of the quantityexceeding (1000) kg.
(C) The quantities of wastes shall be calculated in accordance with the
following rates:
1- The housing usage at a rate of (12) kg. for every (1000) square feet of
the used area.
2- The commercial usage at a rate of (12) kg. for every (1000) square
feet of the used area.
3- The office usage at a rate of (5) kg. for every (1000) square feet of
the used area.
4- Hotels at a rate of (3) kg. for every room and (5) kg. for every suite
and the remaining elements are based on the type of activity.
(D) To determine the areas of waste rooms, the following measurements
shall be approved:
21
-
7/27/2019 DM Condition & Specification of Building
22/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
1- The waste rooms shall take all required containers in accordance with
the measurements approved for the containers as follows:
- Container of (1 and 1) cubic meter (188 x 136) cm.
- Container of (2,5) cubic meters (148 x 204) cm.
2- A distance of one foot shall be left between the containers and the
waste room walls.
3- A distance of one foot shall be left between the containers with one
another and away from all directions.
4- A distance of two feet shall be left between the container and the
room front in which the waste room is existing.
5- The width of the internal passage of waste room shall not be less than
(4) feet.
(E) The door of waste room must be of a width allowing the containers to
get in and out easily provided that such width shall not be less than (6)
feet as minimum.
(F) The height of waste room must not be less than (8) feet as minimum.
(G) Measurement of the waste room and its door depends on the manner of
distribution and movement of containers therein and the possibility of
access to all containers and taking them out.
22
-
7/27/2019 DM Condition & Specification of Building
23/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(H) In hotels and specialized institutions, a hydraulic compressor can beprovided after presenting a special study and the concerned authoritys
approval provided that its size shall not be less than what is required.
(I) In educational institutions, a complex must be provided for waste
containers taking not less than two containers of (2,5) cubic meters, one
for the paper and the second for the remaining materials.
(J) In health institutions, a complex shall be provided for waste containerstaking not less than two containers of (2,5) cubic meters in addition to
the special and necessary containers for the patient rooms, offices and
administrative areas which shall be calculated based on (12) kg. for
every (1000) square meters of the net area thereof.
(K) In labor housings, a waste complex must be provided taking the number
of required containers at a rate of (2,5) cubic meters for every (10000)
square feet of the total area of buildings and one container as minimum.
(L) In industrial institutions (warehouses or workshops of light industries),
a complex for waste rooms must be provided with an area of not less
than (10 x 10) feet paved with washable tiles and supplied with a water
point for washing so that it shall take the number of required containers
at a rate of (2,5) cubic meters container for every (20000) square feet of
the total area of buildings, and in the areas of heavy industries and
specialized large projects and sports clubs, the waste rooms and typeand number of containers shall be determined in accordance with
studies relating thereto approved by the competent authority.
23
-
7/27/2019 DM Condition & Specification of Building
24/24
Dubai Municipality
Continue Regulation of Building Conditions & Specifications
(M) In housing villas, the following must be observed:-
1- In the complexes of investment villas, collective waste rooms shall
be provided in accordance with the specifications set forth in article (51)
of this Regulation and according to the following table:-
Number of Villas Capacity of
Containers
Number of
Containers
1 10 2,5 cubic meters 1
11 20 2,5 cubic meters 2
21 30 2,5 cubic meters 3
31 40 2,5 cubic meters 4