DIVISION 2- SITEWORK GENERAL NOTED: SECTION 02100 PART 1 WORKING DRAWINGS 1.1 In the interpretation of Structural Plans, indicated dimensions shall govern and distances or sizes shall not be scaled for construction purposes. 1.2 In case of conflict in details or dimensions between the Architectural and Structural Plans, verify with the Structural Engineer or his authorized representative for decision. 1.3 In case of conflict between the Structural Plans and Structural Specifications, the plans shall govern. PART 2 EQUIPMENT LOADING 2.1 Equipment not indicated in the plans shall not be installed without the approval of the Structural Engineer. 2.2 The Manufacturer shall submit equipment data specifying the service weight, its reaction at the base, and its vibration characteristics. PART 3 REINFORCE CONCRETE BEAMS 3.1 Unless otherwise noted in the plans or specifications, camber all reinforced concrete slabs 8mm per 3000mm of shorter span and 14mm for every 2000mm of cantilever span. 3.2 When abeam crosses a girder, rest beam bars on the top of the girder bars. At column intersection girder bars shall be on the top of beam bars. PART 4 REINFORCE CONCRETE SLABS 4.1 Unless otherwise noted in plans or specifications, camber all reinforced concrete slab 8mm per 3000mm of shorter span and 14mm for every 2000mm of cantilever span. 4.2 If bars are reinforced both ways, bar along shorter span shall be placed below those along the long span at the center and over the longer span bars near the supports. PART 5 STRUCTURAL TOLERANCES

Transcript of DIVISION 2 Site Work.docx

Page 1: DIVISION 2 Site Work.docx

DIVISION 2- SITEWORK GENERAL NOTED: SECTION 02100

PART 1 WORKING DRAWINGS

1.1 In the interpretation of Structural Plans, indicated dimensions shall govern and distances or sizes shall not be scaled for construction purposes.

1.2 In case of conflict in details or dimensions between the Architectural and Structural Plans, verify with the Structural Engineer or his authorized representative for decision.

1.3 In case of conflict between the Structural Plans and Structural Specifications, the plans shall govern.

PART 2 EQUIPMENT LOADING

2.1 Equipment not indicated in the plans shall not be installed without the approval of the Structural Engineer.

2.2 The Manufacturer shall submit equipment data specifying the service weight, its reaction at the base, and its vibration characteristics.

PART 3 REINFORCE CONCRETE BEAMS

3.1 Unless otherwise noted in the plans or specifications, camber all reinforced concrete slabs 8mm per 3000mm of shorter span and 14mm for every 2000mm of cantilever

span.

3.2 When abeam crosses a girder, rest beam bars on the top of the girder bars. At column intersection girder bars shall be on the top of beam bars.

PART 4 REINFORCE CONCRETE SLABS

4.1 Unless otherwise noted in plans or specifications, camber all reinforced concrete slab 8mm per 3000mm of shorter span and 14mm for every 2000mm of cantilever span.

4.2 If bars are reinforced both ways, bar along shorter span shall be placed below those along the long span at the center and over the longer span bars near the supports.

PART 5 STRUCTURAL TOLERANCES

5.1 Unless otherwise specified by the structural Engineer, the following are the acceptable tolerance for cast in place concrete construction. All dimension not within the required.

Tolerance shall be corrected prior to pouring of concrete.

5.2 Cross sectional dimensions and location of reinforcement

Dimension less than 200mm - +6mm

200mm to 600mm - +9mm

Over 600mm - +12mm

Page 2: DIVISION 2 Site Work.docx

DIVISION 2-SITEWORK General Notes: SECTION 02100

5.3 Deviation from straight line - + 6mm per 3000mm(Sweep and/or Plumbness)

5.4 Location of bar cut-off or bonds - + 50mm

PART 6 CONCRETE PROTECTIONS

6.1 For Bundled bars, the minimum concrete cover shall equal to equivalent diameter of the bundled bars, but need not be greater than 50mm.

PART 7 STANDARD HOOKS

7.1 “Standard hook” for rebar shall mean either of following:

7.1.1 A semi-circular turn plus an extension of at least 4 bar diameter at the free end of bar.

7.2 Minimum diameter of bend measured on the inside of the bar shall be as follows:

10mmo to 25mmo – 6 bar diameter

28mmo to 32mmo -8 bar diameter

No. 11 to No. 18 – bar diameter

PART 8 WELDED SPLICES

8.1 The Contractor shall submit details of all welded splices for approval by the Structural Engineer.

8.2 Only Certified welders shall be allowed to perform welding operation

8.3 Connection of crossing bars by tack welding is not allowed.

PART 9 CONSTRUCTION JOINT

9.1 Where a joint is to be made, the surface of the concrete shall be thoroughly cleaned and all laitance and standing water removed. Vertical joint also shall be thoroughly wetted and coated with rich cement grout immediately before pour of new concrete.

PART 10 PIPES EMBEDDED IN CONCRETE

10.1 Conduits and pipes, with their fittings, embedded within a concrete column shall not displace.

More than 4 percent of the cross sectional area where strength is calculated or required for fire protection.

10.2 Vertical pipes are not allowed to punch through beams or girders.

10.3 Aluminum pipes shall not be embedded in concrete.

Page 3: DIVISION 2 Site Work.docx

DIVISION 2-SITEWORK Clearing and Grubbing SECTION 02100

PART 1 GENERAL

1.1 SCOPE

The work shall consist of the removal of all superficial obstruction including tress, shrubs and the like on the site in the way of or otherwise affected by the work as shown on the drawings. The Contractor shall clear each part of the site at times and to the extent required or approval by the Engineer.

PART 2 PRODUCTS

2.1 MATERIALS

All materials and equipment required for the proper execution of the work of this section shall be selected by the Contractor subject for approval of the Engineer.

PART 3 EXECUTIONS

3.1 CLEARING AND GRUBBING

A. Where shown on the drawing or directed by the Engineer trees shall be unprotected or cut down as near as possible to ground level. Any individual tree as the Engineer may mark in white paint shall be left standing. When necessary to prevent injury to structures. Other trees shall be cut in sections from the top downward.

B. Stump, tree roots, undergrowth, bushes vegetation, logs, branches and the like and rubbish and other objectionable materials shall, unless otherwise directed by the Engineer, be grubbed up or clear disposed of in accordance with item 3.2 of this section.

C Holes left by stumps of roots shall, within one week, be filled with the suitable material and compacted in accordance with Section 02200-Earthwork.

3.2 DISPOSAL OF MATERIALS

All cleared materials shall be burnt or disposed of the site dumps to be provided by the Contractor in a manner approved by the Engineer.

Page 4: DIVISION 2 Site Work.docx

DIVISION 2-SITEWORK Excavation, Filling and Backfilling Construction SECTION 02100

PART 1 SCOPE

The work includes all operation in connection with excavation, filling, backfilling and finish grading, complete.

PART 2 EXCAVATIONS

2.1 Excavation shall be made to the depths indicated, reckoned from the pre-established datum. The indicated depth is the minimum requirements for excavation. However if in the opinion of the Engineer, the soil bearing pressure is not attained at he indicated depth, the Contractor shall extend the excavation until the required soil bearing pressure will be obtained. No extra excavation shall be done without the written approval of the Engineer. In no case shall footings rest fill.

2.2 All excavation shall extend to a sufficient distance from wall and footings to allow the proper erection and dismantling of forms, installation of service lines and for inspections, unless firm rock is encountered wherein the Contractor shall bearing materials are encountered at evaluation other than those specified or shown on the drawings, the Engineer, at his discretion, may direct in writing excavation to stop above or below those indicated on the drawings. All excavation shall be inspected and approve by the Engineer before pouring any concrete laying underground service or placing backfill materials. The Contractor shall control the grading in vicinity of all excavated to prevent surface drainage running into excavation. Water which accumulates in excavated areas, shall be removed by pumping or by other approve methods. Before filling or pouring concrete. All necessary shoring’s, sheet piles rock anchors rock nails or bolts, and or other protective works to protect banks and adjacent paving structures and utilities shall be installed by the contractor if deemed necessary by the Engineer, the Contractor shall apply reinforce mortar, with adequate thickness on bank deemed to susceptible to erosion during heavy rainfall.

2.3 Excavation shall be shored and braced by members with suitable sizes where necessary to prevent danger to person’s injuries caving or erosions. Shoring, bracing and sheathing shall be removed as the excavations are backfilled, in a manner such as to prevent injurious caving. The Contractor shall keep all the excavation free from water while construction is in progress.

PART 3 DESIGNS OF SHORING, BRACING AND PROTECTION FOR EXCAVATION

3.1 The Contractor shall be responsible of providing all necessary shoring, bracing and protection excavation including protections of the existing adjacent structure. The design shall be qualified Geotechnical Engineer a submitted to the Structural Engineer of record for review. However review of the design shall not relieve the Contractor of his responsibility in case of any failure or damage to excavation and/or structure and utilities within and adjacent to the property.

Page 5: DIVISION 2 Site Work.docx

DIVISION 2- SITEWORK Excavation, Filling and Backfilling for Building construction SECTION 02221

3.2 Indicated drawing for slope protection are suggested by the Structural Engineer and subject to the concurrence of the Contractor’s Geotechnical Engineer prior to submission for permit application.

3.3 The Contractor shall be responsible for monitoring requirement for the adjacent buildings. Any sign of the failures of defects must be reported immediately to Structural Engineers. It is further required that the joint inspection to document all existing defects of adjacent building be done prior to start to excavation in the presence of all concern parties including representatives of adjacent structures.

PART 4 BACKFILLING

4.1 After the forms are removed, all trash, wood chips and other debris shall be removed from areas to be backfilled. Backfill materials shall consist of approved site excavated material shall be free from brush, roots and other unsuitable materials which should be detrimental to compaction requirements.

4.2 No backfill shall be place against wall or other vertical surfaces until they have been inspected and backfilling is authorized.

4.3 Trenches shall be not backfilled until lines have been tested and approved by the Engineer. Material for backfill shall be approved as specified above and shall be carefully place and compacted to the density equal to the adjacent area. Approved portable tamper shall be used for compacting fill material in trenches and fill adjacent to walls.

PART 5 PLACING AND COMPACTING FILL

5.1 Materials

5.1.1 Common fill shall be approved materials free from roots and stumps. Common or borrow fill shall be used if site excavated materials are unsuitable or insufficient.

5.1.2 Select fill: Materials shall be placed where specified and indicated on the plan and shall consist of gravel, crushed rock, crushed adobe or combination thereof. The material shall be free from rock 100mm in size, fine clays vegetable matter or other undesirable matter and shall be thoroughly compacted after placing as herein specified.

5.2 Placing Fill: Before placing fill materials, the surface upon which it be placed shall be cleared of all brushes, roots vegetable matters and debris scarified and thoroughly wetted to insure good bonding between the ground and the fill materials. Fill, which shall be contact with new contact with new concrete work shall not be placed until at least 48 hours after removal of forms.

5.3 Compaction: Fill shall be evenly spread I horizontal layer or not more than 200mm in thickness. Each layer shall be wetted and compacted by approved mechanical vibratory compaction machine. Roller or portable to a density of at least 90 percent of its maximum density for non-cohesive soils as determined by ASTM method D-1557 or AASHTO method T-180.

Page 6: DIVISION 2 Site Work.docx

DIVISION 2 – SITEWORK Excavation, Filling and Backfilling for Building construction SECTION 02221

PART 6 FINISH GRADING

The Contractor within the Contractor’s scope of services shall fill and grade the whole area around the building to the indicated subgrade elevation as directed by the Architect or Engineer. The contractor shall verify the finish grade evaluation of the propose pavement around the building. Prior to grading operations, the area shall be cleared of all heavy growth of vegetation stumps, roots, cable, wires, rocks and other debris. The finished sub-grade shall be reasonable smooth, compacted and ready to receive the base course for the propose pavements.

PART 7 MONITORING

The Contractor shall notify the Engineer in the event of any change of soil material encountered during excavation work other than what is indicated in the log of bore holes. If required the Contractor shall survey and make observations of elevations and alignment at the adjacent properties to determine any settlement as well as to determine any horizontal movements.

PART 8 DISPOSALS OF EXCESS MATERIALS

Any excess materials resulting from the finish grading operations, not required or unsuitable for fill or backfill, shall be disposed of by the Contractor to any location selected by and at expense of the Contractor.

Page 7: DIVISION 2 Site Work.docx

DIVISION 3 Concrete Reinforcement SECTION 03200

PART 1 GENERAL

SUMMARY

Section include: Steel reinforcement, including fabrication and installation accessories, for precast concrete and cast in place concrete and masonry.

1.2 REFERENCE STANDARDS

1.2.1 The publications listed below from a part of this specification to the extent referenced. The publications are referred to in the next by basic designation only.

AMERICAN CONCRETE INSTITUTE (ACI)

ACI 117 Standard Tolerance for concrete construction and materials

ACI 135 Manual of standard practice for detailed reinforce concrete structures

ACI 318 Building Code requirements for reinforced concrete

AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)

ASTM A 120 Pipe, Steel, black and dipped Zink coated (Galvanize) welded and seamless, for ordinary uses.

ASTM A 184 Fabricated Deformed Steel bar Mats for Concrete Reinforcement

ASTM A 185 Welded steel wire fabric for concrete reinforcement

ASTM A 497 Welded deformed steel wire fabric for concrete reinforcement

ASTM A 499 Steel bar and shapes, carbon rolled from “T” rails

ASTM A 615 Deformed and plain billet-steel bar for concrete reinforcement

ASTM A 675 Steel bar, Carbon, Hot-wrought, Special Quality, Mechanical properties

ASTM A 706 Low alloy steel deformed bar for concrete reinforcement

AMERICAN WELDING SOCIETY (AWS)

AWS D 1.4 Structural building code- Reinforcing steel

AMERICAN CONCRETE REINFORCEMENT STEEL INSTITUTEM (CSRI)

CSRI 01 Manual of standard practice

Page 8: DIVISION 2 Site Work.docx

DIVISION 3 Concrete Reinforcement SECTION 03200

1.3 SUBMITALS

1. Shop Drawings

A. Detail drawing shall me prepared in accordance with ACI 315. Submittal shall show reinforcing steel schedule, placing plans, sizes, and grades and splicing and bending details. Any embedded plates, bolts, etc., shall for purpose of checking for potential inference. Drawing shall show support details including type, sizes and spacing. Scaling of drawing will not be permitted to determine require bar lengths.

2. Welding procedures and qualifications

A. Owner representative shall be furnished a list of qualified welders

3. Certificate of Compliance

A. Certified copies of mill reports attesting that the reinforcing steel furnished meets the requirement specified shall be obtained from the supplier prior to the installation of reinforcing steel.

1.4 QUALIFICATIONS

1. Welders shall be qualified in accordance with AWS D1.4. Qualification test shall be performed at the worksite and the Contractor shall notify the Owner’s Inspector/Representative 24 hours prior to the conducting tests. Welding procedure qualified by others and Welders qualified by another employer may be accepted as permitted by AWS D1.4.

1.5 DELIVERY AND STORAGE

1. Reinforcement and accessories shall be stored off the ground on platforms, skids or other supports.

PART 2 PRODUCTS

2.1 MATERIALS

1. Welded wire fabric: ASTM A 185; wire in accordance with ASTM A 496; mesh and wire sizes

2. Epoxy Grout: Epoxy grout shall be of type and manufacturers as indicate in drawings.

3. Reinforcing Steel shall be deformed bar for 10mm diameter and above and round bar 8mm diameter and below.

4. Wire Ties: Wire Ties shall be ASTM A 82 16-gauge double annealed wire. Provide corrosion resistant wire precast concrete.

5. Supports: Bar support for formed surfaces shall be designed and fabricated in accordance with CRSI 01 Class A, C or D or precast concrete blocks.

Page 9: DIVISION 2 Site Work.docx

DIVISION 3 Concrete Reinforcement SECTION 03200

Precast concrete block shall not be less than 4 inches square when supporting reinforcement on the ground. Precast Concrete block shall have comprehensive strength equal to that surrounding concrete. Where concrete formed surfaces will be exposed to the weather or where surfaces are to be painted, steel support shall be class C or D.

2.2 FABRICATED

1. Steel bar Reinforcement: Fabricate and details to shape and dimension shown on the drawing in accordance with ACI 315

2. Bending and straightening: in accordance with ACI 138 chapter 7 unless otherwise noted on drawing; No bending or straightening of reinforcement will be permitted after partial embedment in concrete; heating of reinforcement will be permitted only if entire operation is approved.

3. Welding: Welding of reinforcing bars is not permitted unless specifically shown welded on structural drawing. When welding of reinforcement indicated and required provided, welds in accordance with AWS D1.4

4. Splicing:

A. Reinforcing bars shall be lap spliced for tension unless otherwise noted on drawings

B. At the contractor’s option mechanical butt splicing using an exothermic welding process and high strength sleeves or threaded splicing may be substituted for lap splices with prior approval. Butt welds, thermite welds and threaded splices shall be capable in developing in tension at least 125% of the specified yield strength (FY) on the bar.

C. Mechanical coupler shall be allowed provide they are capable in developing in tension at least 125% of the specified yield strength (FY) of the bar. In no case should the result fail in the threaded portion, submit test results and product literature for approval.

D. Welding or tack welding of reinforcing bars to other bars or to plates, angle etc. , is prohibited, expect where specifically detailed on the approved, it shall be done by AWS Certified Welders using E9018 or approve electrodes. Welding procedures shall conform to the requirements of AWS D1.4.

5. Welded fire fabric: In accordance with CRSI, Chapter 2 unless otherwise noted or indicated.

Concrete block shall have comprehensive strength equal to that surrounding concrete. Where concrete formed surfaces will be exposed to the weather or where surfaces are to be painted, steel support shall be class C or D. Concrete supports used in concrete exposed to the view shall be class C or D.

Page 10: DIVISION 2 Site Work.docx

DIVISION 3 Concrete Reinforcement Sections 03200

2.2 FABRICATED

1. Steel bar Reinforcement: Fabricate and details to shape and dimension shown on the drawing in accordance with ACI 315.

2. Bending and straightening: in accordance with ACI 318 chapter 7 unless otherwise noted on drawing; No bending or straightening of reinforcement will be permitted after partial embedment in concrete; heating of reinforcement will be permitted only if entire operation is approved.

3. Welding: Welding of reinforcing bars is not permitted unless specifically shown welded on structural drawings. When welding of reinforcement indicated and required provided, welds in accordance with AWS D1.4.

4. Splicing:

A. Reinforcing bars shall be lap spliced for tension unless otherwise noted on drawings.

B. At the contractor’s option mechanical butt splicing using exothermic welding process and high straight sleeves or threaded splicing may be substituted for lap splices with prior approval. Butt welds, termite welds and threaded splices shall be capable in developing in tension at least 125% of the specified yield strength (FY) on the bar.

C. Mechanical coupler shall be allowed provide they are capable in developing in tension at least 125% of the specified yield strength (FY) of the bar. In no case should the result fail in the threaded portion, submit test results and product literature for approval.

D. Welding or tack welding of reinforcing bars to other bars or to plates, angle etc., is prohibited, expect where specifically detailed on the approved, it shall be done by AWS Certified Welders using E9018 or approved electrodes. Welding procedures shall conform to the requirements of AWS D1.4.

5. Welded fire fabric: In accordance with CRSI, Chapter 2 unless otherwise noted or indicated.

Page 11: DIVISION 2 Site Work.docx

DIVISION 4- MASONRY Unit Masonry SECTION 04200

PART 1. GENERAL

APPLICABLE PUBLICATIONS: The latest edition of the publications listed below form a part of this specification to the next extent referenced.

1.1.1 American Society for Testing and Materials (ASTM) Publications:A 82 cold drawn Steel wire for concrete reinforcementA 90 Weight of coating on Zinc- Coated (Galvanized Iron or Steel Articles.)A 153 Zinc Coated (Hot-dip on iron and steel hardware.)A 615 Deform and plain Billet-steel Bars for concrete ReinforcementC 90 hollow load-bearing concrete masonry unitsC 91 Masonry cementC 144 Aggregate for masonry mortarC 150 Portland cementC 270 Mortar for unit masonryC 476 Grout for reinforced and non-reinforced masonry

1.2 SUBMITTALS:

1.2.1 Samples: Submit for approval samples of each type of the wall reinforcement and wall ties and design mix for grout.

1.2.2 Certified of Conformance: Submit certificate attesting that masonry cement, masonry unit’s aggregates and accessories meet the requirement specified herein.

1.3 DELIVERY AND STORAGE: Deliver cement and others cementitious materials to the site in unbroken bags, barrels or other approved container plainly marked and labeled with manufacturer’s names and brands. Store cementitious materials in dry, weather tight sheds or enclosures and handle so as to prevent entry of foreign materials and damaged by water or dampness. Handle Masonry material from damage, and expect for sand, keep dry until used.

PART 2. PRODUCTS

2.1 MASONRY UNITS

2.1.1 CONCRETE MASONRY UNITS: Units modular dimension and air, water or stream cured. Store type II units at the site before used a minimum of 28 days of atmospheric stream of water-cured units, and 3 days for units cured with steam at pressure of 120- 150 psi and at temperature of 350 to 35 degrees F for at least 5 hours. Surface of units which are to be plastered or stuccoes shall be sufficiently rough to provide a suitable bond; elsewhere exposed surface of unit shall be comparatively smooth and/ or uniform in texture.

Page 12: DIVISION 2 Site Work.docx

DIVISIO 4- MASONRY Unit Masonry SECTION 04200

A. Hollow Load-Bearing Units; ASTM C 90, Grade N-1 or N-II made with normal weight aggregates with ultimate comprehensive strength of at least 1,200 psi at 28 days.

B. Hollow Non-Load Bearing Units: ASTM C-129 made with normal weight aggregates and with ultimate comprehensive strength of at least 650 psi at 28 days.

C. Special Shapes: Provide special shapes such as closure, header units and jamb units as necessary to complete the works. Special shape shall conform to the requirement for the units with which they are used.

2.2 PRECAST CONCRETE LINTELS: Same materials and surface texture as adjacent masonry units, with a 28 days comprehensive strength of not less than 2,000 psi. Provide lintels of sizes indicated, straight and true with at least 8 inches of bearing at each end.

2.2.1 PORTLAND CEMENT: ASTM C 150, TYPE I.

2.2.2 MASONRY CEMENT: ASTM C 91 expects that the air content of the mortar specimen shall be not more than 16% volume in lieu of 22%. Containers shall bear complete instructions for proportioning and maxing obtains the required types of mortar.

2.2.3 SAND: ASTM C 144.

2.2.4 WATER: Clean portable and free from substance which could adversely affect the mortal.

2.2.5 MORTAR TYPES: ASTM C 270: Types M. for foundation walls, Type N or S for non-load bearing, none shear wall interior concrete masonry and type S for all other masonry works. If Masonry cement is used, submit the manufacturer’s printed instruction on proportion of water and aggregates and on mixing the type of mortar required.

2.3 ACCESSORIES

2.3.1 HORIZONTAL JOINT REINFORCEMENT: Horizontal joint reinforcement shall be reinforcing bars. As indicated conforming to ASTM A615, or fabricated from cold drawn steel wire, conforming to ASTM A82. The wire shall be zinc-coated after fabrication by the hot deep processes in accordance with ASTM 153 either bright steel, cooper clad steel, cooper clad steel or Zinc coated after fabrication. Reinforcement shall consist of two or more parallel longitudinal wires, not least than 0.1350 inches (9-gage) in diameter. Cross wires, shall be crimped to provide an affective moisture drip in the wall cavity. The out-to-out spacing of the longitudinal wires shall be 1-1/2 to 1-3/4 inches less than the actual with of masonry. The distance between contacts of cross wires with each longitudinal wire shall not less than 10 feet in length, expect that corner reinforcement and other special shapes may be less in length.

Page 13: DIVISION 2 Site Work.docx

DIVISION 4-MASONRY Unit Masonry SECTION 04200

2.3.2 TIES: Provide approved design of cooper clad steel, zinc coated steel or non-corrosive metal having the equivalent total strength of steel types. Zinc coated item by the hot dip process after fabrication to a minimum of 1.25 ounces of zinc per square foot of the surface when tested in accordance with ASTM A 90.

A. Wire mesh ties: wire not lighter than 20-gega galvanized ½ inches mesh width of one inches less than thickness of masonry.

B. Corrugated Metal Ties: Not less than 7/8 inches wide by approximately 6 inches long and not lighter than 22-gage.

2.3.3 Fastening: Provide suitable metals wall plugs or others approved metal fastening of securing furring to masonry and elsewhere as necessary. Bolt or others approved metal fastening longer than 1-1/2 inches (40mm) shall be attached to masonry units only where there are grouted cells.

PART 3 EXECUTIONS

3.1 INSTALLITION: Coordinate masonry work with the works of others trades to accommodate built-In items and to avoid cutting and patching. Do not change sources of supply materials after works has started if the appearance of the finished work would be affected.

3.1.1 PROTECTION

A. Stains: Protect exposed surface from mortar and other stains when mortar joint are tooled, removed mortar exposed surfaces from splash stain from covering adjacent ground with sand sawdust or polyethylene.

B. Loads: do not apply uniform loads for at least 12 hours or concentrated load for at least 72 hour after masonry is constructed.

3.1.2 WORKMANSHIP: Masonry wall shall be carried up level and plumb all around. One section of the walls shall not be carried up in advance of the others, unless specifically approved by the Engineer. Unfinished work shall be step back for joining with new work; too thing will not be permitted, except where specified. Height of masonry shall be checked with an instrument at each floor and at sills and heads of openings, to maintain the level of the walls. Door and window frames louvered openings, anchors, pipes, duct conduits shall be built in carefully and neatly as the masonry work progresses. Spaces around metal doorframe shall be filled solidly with mortar. Masonry units shall be handling with care to avoid chipping cracking and spalling of faces and edges. Drilling, cutting, fitting and patching to accommodate the works of other, shall be performed by masonry mechanics. Masonry shall be cut with masonry saws in exposed work, where indicate by the Engineers, Structural steel works, bolts, anchors, inserts, plugs ties, lintels and miscellaneous metalwork specified elsewhere shall be placed in position as the work progresses. Chase of two approved dimension for pipes and other purposes shall be provided where indicated.

Page 14: DIVISION 2 Site Work.docx

DIVISION 4 – MASONRY Unit Masonry SECTION 04200

or necessary. Tops of expose wall and partition, not being worked on shall be covered a waterproof membrane well secured in place unless indicated otherwise, partition shall

Extend from floor to the bottom of the floor or roof construction above. Well and partition shall be structurally bounded or anchored to each other and to beams and columns. Non load bearing partitions and interior wall shall be securely anchored to the construction above, in a manner that provides lateral stability while permitting unrestricted deflection of construction above. Scaffolding shall be inspected regularly, and shall be amply strong well braced and securely tied in position. Overloading of scaffolding will not be permitted.

3.1.3 Mortar Mixing: Measure mortar materials in proper containers to maintain control and accuracy of proportions. Do not measure materials with shovels. Unless specified otherwise, mix mortar in proportion by volume. Introduce and mix aggregate in such a manner that the materials will be distributed uniformly throughout the mass. Add water gradually and mix not less than 3 minutes, until proper plasticity is obtained machine mix mortar, is mixer of the type in which the quantity of water can be controlled accurately and uniformly. Hand mixing may be used only when specifically approved. Keep mortar boxes, pans and mixer drums clean and free of debris or dried mortar. Do not used re=tempered mortar which has been placed in its position within 1-1/2 hours after the initial mixing.

A. MORTAR: Mix mortar at the site using materials conforming to ASTM C 270 to obtain type of mortar required. Measurement and mixing shall conform to ASTM C 270. When masonry cement is used conform to printed mixing instructions of the masonry cement manufacturer.

B. GROUT: ASTM C 476. Provide fine grout in grout spaces less than 2 inches in any horizontal dimension or in which clearance between grout spaces 2 inches or greater in all horizontal dimensions, provided the clearance between reinforcing and masonry is not less than ¾ inch.

3.1.4 Mortar Joints: Uniform thickness of 3/8 inch (10mm), unless otherwise indicated. Toll exposed joints slightly concave with a round or other suitable jointer slightly larger than the width of the joint so that complete contact is made along the edges of the units, compressing and sealing the surface of the joint. Strike flushed joints that will not be exposed. Tools horizontal joint first. Brush joints to remove all loose and excess mortar. All horizontal joints shall be level; vertical joints shall be plumb and in alignment from top to bottom of wall within a tolerance of not more than ½ inch in 40 feet.

Page 15: DIVISION 2 Site Work.docx

DIVISION 4- MASONRY Unit Masonry SECTION 04200

Provide concrete curb or pedestal at the bottom with the necessary height to obtain a clear height of the masonry wall in module of masonry unit height plus mortar of 3/8 inch (10mm) to avoid cutting of masonry units. Insertion of broken masonry units at the top of wall below a beam or slab will not be permitted.

3.1.5 Concrete Masonry Unit Work: Lay the first course in a full bed of mortar for the full width of the unit. Lay succeeding course in running bond unless otherwise indicated. From Bed-joints by applying the mortar to the entire top surfaces of the inner and outer face shells. From head joints by applying the mortar for a width of about 1 inch to the end of adjoining units laid previously. The mortar shall be smooth; out furrowed, and shall be such thickness that it will be forced out the joints as the units are being placed in position. Where anchors, bolts, and ties occurs within the cells of the units, placed metal lath in the joint at the bottom of such cells and fill the cells with mortar or grout as the work progresses. Use concrete brick for bonding walls, working out the coursing, topping out walls under sloping slabs, distributing concentrated loads, backing brick headers, and elsewhere, as required. Do not dampen concrete masonry units before or during laying.

A. Special Concrete Masonry Unit Work: Where exposed concrete masonry unit walls and portions are indicated, provide special concrete masonry unit work. Select units for uniformity of size, texture, true plane, and undamaged edges and ends of the exposed surfaces. Places units plumb, parallel, and with properly tooted joints of maximum 3/8 inch (10mm) thickness. Keep exposed surfaces clean and free from blemishes or defects. Lay units the bond pattern indicated.

B. Reinforced Concrete Masonry Unit Walls: Where vertical reinforcement occurs, fill cores solid with grout. Lay units in such a manner as to preserve the unobstructed vertical continuity of cores to be filled. Embed the adjacent webs in mortar to prevent leakage of grout. Remove mortar fins protruding from joints before grout is placed. Minimum clear dimensions of vertical cores shall be 2 by 3 inches. Position reinforcing accurately as indicate. As masonry work progresses, secure vertical reinforcing in place at vertical intervals not to exceed 160 bar diameter. Embed horizontal reinforcing in grout as grouting proceeds. Minimum clear distance between masonry and vertical reinforcement shall not be less than ½ inch. Unless indicated or specified otherwise, from splices by lapping bars not less than 40 bar diameters and wire tying them together.

3.1.6 Bonding and Anchoring: Unless indicated others, extend partitions from the floor to concrete walls, beams and columns. Surely anchor non-load bearing partition and interior wall to the construction above as indicated completely embed anchors in mortar joints.

Page 16: DIVISION 2 Site Work.docx

DIVISION 4- MASONRY Unit Masonry SECTION

A. Corners of load-Bearing walls proved a true masonry bond in each course, expect where indicated or specified otherwise.

B. Intersection of load-Bearing walls: Provide a true masonry bond in each course or anchor with rigid steel anchors not more than 2 feet apart vertically, unless otherwise indicated.

C. Intersection if Non-load Bearing Partition with other wall or partition: Tie with wire mesh at vertical intervals of not than 2 feet or with masonry bonding in alternative courses,

D. Masonry works facing or butting concrete members: Anchor masonry to the concrete with dovetail or wire type anchor inserted in slots or insert built into the concrete. Locate anchor not more than 18 inches or center vertically and not more than 24 inches on center horizontally.

3.7.1 Horizontal Joint Reinforcement: Provide reinforcement in any other course and in first two courses above and below openings in the walls and partitions of concrete masonry units. Reinforcement shall be continuous expect at control joint and expansion joints. Reinforcement above and below opening shall extend not less than 24 inches beyond each side of openings. Provide reinforcement in the longest available length utilizing the minimum numbers of splices. Overlap end not less than 12inches. Provide welded L-shaped assembled not less than 32 by 32 inches both of the same size members and the same construction as the straight reinforcement. At corners and intersections of wall and partitions. Placed the reinforcement and apply mortar so as to provide mortar cover for the wire at least 5/8 inches for exterior wall face and ½ inches for interior wall face.

3.8.1 Concrete Masonry Units Lintel and Bond Beam: Provide special units, fill cells solidly with grout of concrete, with the strength same as masonry of higher and provide not less than two O16 reinforcing bars, unless indicated otherwise. Reinforcing shall overlap a minimum of 40 bars diameter at splices. Terminate bond beam and reinforcing of each side of expansion joint and control joint. Concrete masonry unit shall be thoroughly wet prior to pouring concrete grout. Concrete masonry unit used for lintels and bon beams shall have exposed surfaces of the same material texture as the adjoining masonry units. Allow lintels to set at least 6 days before shoring in removed. Lintels shall be straight and true shall have at least 8 inches of bearing at each end.

3.1.9 Control Joints: Provide where indicated in concrete masonry unit walls. Provide control Joints of the sawed type or built in type, as the case requires. Joint shall occur directly opposite each other on both faces of the wall and shall be filled with an approved non-staining elastic calking compound or sealant.

Page 17: DIVISION 2 Site Work.docx

DIVISION 4-MASONRY Unit Masonry SECTION 04200

3.1.10 Grout Placement Place grout from the interior side of the walls, except as approved otherwise. Protect sills, ledges, offsets and other surfaces and removed any access grout immediately. Grout shall be well mixed to prevent segregation and shall be sufficiently fluid to flow into joints and around reinforcing without leaving voids. Place grout by pumping or pouring from bucket equipped with spout in lift not exceeding 4 feet keep pour at 1-1/2 inches below the top of masonry in top course, expect at the finish course. Puddle or agitate grout thoroughly to eliminate voids. Do not displace masonry from its original position. Removed masonry displaces by grouting operation and relay I alignment with fresh mortar.

3.1.11 Forms and Shoring: Construct to the shape, lines and dimension of member indicated and make sufficiently rigid to prevent deflections which may result in cracking or other damage to supported masonry forms shall remain or girders and beams than 10 days after completion of members. Not less than 64 hours shall elapse before concrete loads are applied.

3.2 CLEANING

3.2.1 Protection: Protect work which may be damage, stained or discolored during cleaning operations.

3.2.2 Pointing: Upon completion of masonry work, cut out defective mortar joint and tuck joints and holes solidly with mortars.

3.2.3 CLEANING: Clean exposed masonry surface with clean water and stiff fiber brush and rinse with clear water. Where stain, mortar or solid remain, continue cleaning as follow: Clean masonry surfaces by scrubbing with warm water and soap and rinsing thoroughly with clean water. Restore damaged, stained and discolored work to its original condition or replace with new work.

Page 18: DIVISION 2 Site Work.docx

DIVISION 5- METALS Structural Steel SECTION 05120

PART 1 GENERAL

1.1 SUMMARY1.1.1 Structural steel framing and shoring system, complete with plates, bracing anchorage

including the following:A. Erection and connecting structural steel frame and temporary structural steel

frameworks.B. Base plate grouting.

1.2 APPLICABLE PUBLICATION: The publication listed below from a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. The latest edition shall be applicable.1.2.1 American Institute of steel Construction (AISC):

1. “Code of standard Practice for steel building and bridges,” expect Paragraph 4.2.1 is modified be deletion of the following sentence: this approval constitutes the owner’s acceptance of the responsibility for the design adequacy of any connections designed by the fabricator as a part of his preparation of this drawings.”

2. Manual of steel Construction, Allowable Stress Design 9th Edition, 1989.3. “Specification of the design, Fabrication and Erection of structural steel for buildings.4. Specification for Structural Joints Using ASTM A325 or A490 bolts.

1.2.2 American Society of Testing and Materials (ASTM):A6 General Requirements for rolled steel plates, shapes, sheets, pilling and bars for

structural use.A36 STRUCTURAL STEEL.A53 PIPE.A123 Zinc (Galvanized) Coating on products fabricated from rolled pressed and forges

steel shapes, plate, bars and strip.A153 Zinc coating (Hot dip) on Iron and steel hardware.A307 Carbon steel externally and internally threaded standard fasteners.A325 High Strength bolts for structural steel joints.A441 High Strength, low alloy structural manganese vanadium steel.A490 Quenched and tempered alloy steel bolts for structural steel joint.

Page 19: DIVISION 2 Site Work.docx

DIVISION 5-METAS Structural Steel SECTION 05120

A500 Grade B Cold-Formed welded and seamless carbon steel structuring tubing.

A501 Hot-Formed welded and seamless carbon steel structural pipe.

A572 High strength low-alloy columbium-vanadium steel of structural quality.

A588 High strength low-alloy structural steel with 50,000 psi minimum yield point to 4 inches thickness.

1.2.3 American Welding Society (AWS)

A2.4 Welding Symbols

A3-0 Terms and Definition

A5.1 Specification for mild steel for flux cored arc welding.

A5.20 Specification for low-alloy steel covered arc-welding electrodes.

A5.5 Specification for low-alloy steel covered arc-welding electrodes.

A5.17 Specification for carbon steel electrodes and fluxes for submerge arc welding.

A5.23 Specification for low-alloy steel electrodes and fluxes for submerge arc welding.

D1.1 Structural Welding Code-Steel.D1.4 Reinforcing Steel Welding Code, including metal insert and connection in

reinforced concrete.F959 Compressible-washer type direct tension indicator for use with structural

fasteners.1.2.4 Federal Specification (Fed. Spec.):

TT-C-490 Cleaning method and apartment of ferrous surfaces for organic coatings TT-P-645 Primer paint, Zinc Chromate, Alkyd Type

1.2.5 Military Specification Painting Council (SSPC) Publications:SP3 Power tool cleaningSP6 Commercial blast cleaning

Page 20: DIVISION 2 Site Work.docx

DIVISION 5-METALS Structural Steel Section 05120

1.3 QUALITY ASSURANCE1.3.1 Fabrication/Erector: Must have plant, facilities and personnel qualified and sufficient

and fabricate and/ or erect structural metal framing as indicated on drawings. Must have minimum of 5 years experiences and to be able upon request, to show framing of size materials and scope similar to work of this contract.

1.3.2 Material: Provide only structural steel certificate as conforming with specified requirements and fabricated specially to the requirement of this contract may be rejected at any time prior to final acceptance.

1.3.3 Allowance Tolerance: Unless otherwise specified or noted on the drawing, provide structural steel work in accordance with the following minimum tolerances:A. Fabrication Tolerance: In accordance with requirements of AISC

Specification unless noted otherwise and as required to maintain the erection tolerance specified herein.

B. Erection Tolerance: In accordance with requirements of AISG the contractor alone shall be responsible for the correct fittings of all structural members including the elevation and alignments refer to the drawings for additional requirements.

1.3.4 Connection Identification: Each person installing connections shall be assigned an identifying symbols or marks and all shop and field connections shall be so identified so that the Owners Testing Lab can refer to the person making the connection.

1.3.5 Test and Inspection: Work is subject to special testing and inspection. The fabricator/erector shall provide the owner testing lab and Architect/ Engineer access to be places where the material is being fabricated/ erected. Notice shall be given for the joint requiring inspection for proper end preparation, root opening etc., and prior to welding.

1.3.6 Connection Designed on the Structural Drawings:A. Structural shall not deviate from these designs unless approved by the Architect/

Engineer.B. Connection shown on the drawings may eliminate certain method of erection.C. If Contractor elects a method of erection that required a change of some of the

connections, it must be approved by Architect/ Engineer.1.3.7 Engineers by the Contractor: Design and calculation shall be prepared by a contractor’s

Structural Engineer, for the support of hosting equipment, welding machines and other superimposed loads for the stacking materials such as metal decking, etc., and where required for temporary bracing, shoring and other safety related construction procedures.A. It is Contractor responsibility to obtain and pay for such engineering services.