MiCOM P437 Distance Protection Device P437/EN M/R-11-A Version P437 -311 -412/413 -650 Technical Manual

Transcript of Distance Protection Device P437/EN M/R-11-A MiCOM … · Distance Protection Device P437/EN...

  • MiCOM P437

    Distance Protection Device

    P437/EN M/R-11-A

    Version P437 -311 -412/413 -650

    Technical Manual

  • General Note on the PDF Version of this Technical ManualAll entries in the Table of Contents and all cross-references to other sections,figures etc. in green letters are hyperlinks, i.e. by a single mouse click on thereference one can navigate directly to the referenced part of the manual.In the Adobe Reader (or the Acrobat Pro), one can return back to the previousview by using the menu point View / Page Navigation / Previous View (keyboardshortcut: ALT + Left cursor key). (It might be necessary to do this several times,if the view at the target location has also been changed (e.g. by scrolling orchanging the zoom setting).

  • WARNINGWhen electrical equipment is in operation dangerous voltage will be presentin certain parts of the equipment. Failure to observe warning notices,incorrect use or improper use may endanger personnel and equipment andcause personal injury or physical damage.Before working in the terminal strip area, the P437 must be isolated. Wherestranded conductors are used, insulated crimped wire end ferrules must beemployed.The signals MAIN: Blocked/faulty and SFMON: Warning (LED)(permanently assigned to the LEDs labeled OUT OF SERVICE and ALARM) canbe assigned to output relays to indicate the health of the P437. SchneiderElectric strongly recommends that these output relays are hardwired into thesubstation's automation system, for alarm purposes.Any modifications to this P437 must be in accordance with the manual. If anyother modification is made without the express permission of SchneiderElectric, it will invalidate the warranty, and may render the product unsafe.Proper and safe operation of this P437 depends on appropriate shipping andhandling, proper storage, installation and commissioning, and on carefuloperation, maintenance and servicing.For this reason only qualified personnel may work on or operate this P437.The User should be familiar with the warnings in the Safety Guide(SFTY/4LM/G11 or later version), with the warnings in Chapter 5, (p. 5-1),Chapter 10, (p. 10-1), Chapter 11, (p. 11-1) and Chapter 12, (p. 12-1) and with the content of Chapter 14, (p. 14-1), before working on theequipment. If the warnings are disregarded, it will invalidate the warranty,and may render the product unsafe.

    Qualified Personnelare individuals who

    are familiar with the installation, commissioning and operation of the P437and of the system to which it is being connected;

    are able to perform switching operations in accordance with safetyengineering standards and are authorized to energize and de-energizeequipment and to isolate, ground and label it;

    are trained in the care and use of safety apparatus in accordance withsafety engineering standards;

    are trained in emergency procedures (first aid).

    NoteThis operating manual gives instructions for installation, commissioning andoperation of the P437. However, the manual cannot cover all conceivablecircumstances or include detailed information on all topics. In the event ofquestions or specific problems, do not take any action without properauthorization. Contact the appropriate technical sales office of Schneider Electricand request the necessary information.Any agreements, commitments, and legal relationships and any obligations onthe part of Schneider Electric, including settlement of warranties, result solely

  • from the applicable purchase contract, which is not affected by the contents ofthe operating manual.

  • Changes after going to press

  • Table of Contents

    1 Application and Scope ........................................................................................ 1-11.1 Overview .....................................................................................................................1-11.2 General Functions ....................................................................................................... 1-51.3 Global Functions ......................................................................................................... 1-61.4 Design .........................................................................................................................1-71.5 Configurable Function Keys ........................................................................................ 1-81.6 Inputs and Outputs ..................................................................................................... 1-91.7 Control and Display ...................................................................................................1-101.8 Information Interfaces ...............................................................................................1-11

    2 Technical Data ....................................................................................................2-12.1 Conformity .................................................................................................................. 2-12.2 General Data ...............................................................................................................2-22.2.1 General Device Data ..................................................................................................................................... 2-22.2.2 Environmental Conditions ..............................................................................................................................2-32.3 Tests ........................................................................................................................... 2-42.3.1 Type Tests ..................................................................................................................................................... 2-42.3.2 Routine Tests .................................................................................................................................................2-72.4 Inputs and Outputs ..................................................................................................... 2-92.4.1 Measuring Inputs ...........................................................................................................................................2-92.4.2 Binary Signal Inputs .....................................................................................................................................2-102.4.3 IRIGB Interface ........................................................................................................................................... 2-112.4.4 Direct Current Input .....................................................................................................................................2-112.4.5 Resistance Thermometer ............................................................................................................................ 2-112.4.6 Direct Current Output ..................................................................................................................................2-112.4.7 Output Relays ..............................................................................................................................................2-122.4.8 BCD Measured Data Output ........................................................................................................................ 2-122.5 Interfaces ..................................................................................................................2-132.5.1 Local Control Panel ......................................................................................................................................2-132.5.2 PC Interface .................................................................................................................................................2-132.5.3 Serial Communication Interface .................................................................................................................. 2-132.5.4 IEC Communication Interface ...................................................................................................................... 2-142.5.5 IRIGB Interface ........................................................................................................................................... 2-152.6 Information Output ................................................................................................... 2-162.7 Settings Typical Characteristic Data .......................................................................2-172.7.1 Main Function .............................................................................................................................................. 2-172.7.2 Distance Protection ..................................................................................................................................... 2-172.7.3 Definite-Time and Inverse-Time Overcurrent Protection ............................................................................. 2-172.7.4 Time-Voltage Protection .............................................................................................................................. 2-172.7.5 Power Directional Protection ....................................................................................................................... 2-172.8 Deviations .................................................................................................................2-182.8.1 Deviations of the Operate Values ................................................................................................................2-182.8.2 Deviations of the Timer Stages ................................................................................................................... 2-192.8.3 Deviations of Measured Data Acquisition .................................................................................................... 2-202.9 Resolution of the Fault Data Acquisition ................................................................... 2-212.9.1 Time Resolution ...........................................................................................................................................2-212.9.2 Phase Currents System ............................................................................................................................... 2-212.9.3 Residual Current ..........................................................................................................................................2-212.9.4 Phase-to-Ground Voltages and Neutral-Point Displacement Voltage ...........................................................2-21

    P437

    P437/EN M/R-11-A // P437311650 1

  • 2.10 Recording Functions ................................................................................................. 2-222.10.1 Organization of the Recording Memories .................................................................................................... 2-222.11 Power Supply ............................................................................................................ 2-242.12 Current Transformer Specifications .......................................................................... 2-252.12.1 Symbols .......................................................................................................................................................2-252.12.2 General Equations ....................................................................................................................................... 2-272.12.3 Distance Protection ..................................................................................................................................... 2-27

    3 Operation ............................................................................................................3-13.1 Modular Structure ....................................................................................................... 3-13.2 Operator-Machine Communication ............................................................................. 3-33.3 Configuration of the Bay Panel and of the Measured Value Panels, Selection of the

    Control Point (Function Group LOC) ............................................................................ 3-43.3.1 Operation Panel .............................................................................................................................................3-53.3.2 Fault Panel .....................................................................................................................................................3-63.3.3 Overload Panel .............................................................................................................................................. 3-73.3.4 Configurable Clear Key ..................................................................................................................................3-73.4 Serial Interfaces ..........................................................................................................3-83.4.1 PC Interface (Function Group PC) .................................................................................................................. 3-93.4.2 Communication Interface 1 (Function Group COMM1) ................................................................................ 3-103.4.3 Communication Interface 2 (Function Group COMM2) ................................................................................ 3-193.4.4 InterMiCOM Protective Interfaces (Function Groups COMM3, COMM4) ........................................................3-213.4.5 Communication Interface IEC 61850 (Function Groups IEC, GOOSE and GSSE) .......................................... 3-263.5 IRIG-B Clock Synchronization (Function Group IRIGB) ...............................................3-383.6 Configurable Function Keys (Function Group F_KEY) ................................................ 3-393.6.1 Configuration of Function Keys with a Single Function ................................................................................3-393.6.2 Configuration of Function Keys with Menu Jump Lists ................................................................................. 3-393.6.3 Configuration of the READ Key .................................................................................................................... 3-393.6.4 Operating Mode of the Function Keys ..........................................................................................................3-393.6.5 Handling Keys ..............................................................................................................................................3-393.7 Configuration and Operating Mode of the Binary Inputs (Function Group INP) ......... 3-413.8 Measured Data Input (Function Group MEASI) .......................................................... 3-433.8.1 Direct Current Input on the Analog (I/O) Module Y ...................................................................................... 3-443.8.2 Connecting a Resistance Thermometer to the PT 100 Analog Input on the Analog (I/O) Module Y .......... 3-473.9 Configuration, Operating Mode, and Blocking of the Output Relays (Function Group

    OUTP) ........................................................................................................................3-493.10 Measured Data Output (Function Group MEASO) ......................................................3-523.10.1 General Settings ..........................................................................................................................................3-523.10.2 BCD Measured Data Output ........................................................................................................................ 3-543.10.3 Analog Measured Data Output .................................................................................................................... 3-583.10.4 Output of External Measured Data ...........................................................................................................3-643.11 Configuration and Operating Mode of the LED Indicators (Function Group LED) ...... 3-653.11.1 Configuring the LED Indicators .................................................................................................................... 3-653.11.2 Layout of the LED Indicators ........................................................................................................................3-653.11.3 Operating Mode of the LED Indicators .........................................................................................................3-663.12 Main Functions of the P437 (Function Group MAIN) .................................................. 3-693.12.1 Conditioning of the Measured Variables ...................................................................................................... 3-693.12.2 Operating Data Measurement ..................................................................................................................... 3-713.12.3 Configuring and Enabling the Device Functions .......................................................................................... 3-873.12.4 Current Flow Monitoring .............................................................................................................................. 3-883.12.5 Inrush Stabilization (Harmonic Restraint) ....................................................................................................3-893.12.6 Multiple Blocking ......................................................................................................................................... 3-913.12.7 Blocked/Faulty .............................................................................................................................................3-92

    P437 Table of Contents

    2 P437/EN M/R-11-A // P437311650

  • 3.12.8 Monitoring and Processing of CB Status Signals ..........................................................................................3-923.12.9 Close Command .......................................................................................................................................... 3-943.12.10 Starting Signals and Tripping Logic ............................................................................................................. 3-963.12.11 Time Tagging and Clock Synchronization ..................................................................................................3-1043.12.12 Resetting Actions .......................................................................................................................................3-1063.12.13 Assigning Communications Interfaces to Physical Communications Channels ..........................................3-1093.12.14 Test Mode ..................................................................................................................................................3-1103.13 Parameter Subset Selection (Function Group PSS) ................................................. 3-1113.14 Self-Monitoring (Function Group SFMON) ................................................................3-1133.14.1 Tests During Start-up ................................................................................................................................ 3-1133.14.2 Cyclic Tests ................................................................................................................................................3-1133.14.3 Signal ........................................................................................................................................................ 3-1133.14.4 Device Response ....................................................................................................................................... 3-1143.14.5 Monitoring Signal Memory .........................................................................................................................3-1153.14.6 Monitoring Signal Memory Time Tag ......................................................................................................... 3-1153.15 Operating Data Recording (Function Group OP_RC) ............................................... 3-1163.16 Monitoring Signal Recording (Function Group MT_RC) ............................................3-1173.17 Overload Data Acquisition (Function Group OL_DA) ............................................... 3-1183.17.1 Overload Duration ..................................................................................................................................... 3-1183.17.2 Acquiring Measured Overload Data from the Thermal Overload Protection .............................................. 3-1193.18 Overload Recording (Function Group OL_RC) ..........................................................3-1203.18.1 Start of Overload Recording ...................................................................................................................... 3-1203.18.2 Counting Overload Events .........................................................................................................................3-1203.18.3 Time Tagging .............................................................................................................................................3-1203.18.4 Overload Logging ...................................................................................................................................... 3-1213.19 Fault Data Acquisition (Function Group FT_DA) ...................................................... 3-1223.19.1 Running Time and Fault Duration ..............................................................................................................3-1223.19.2 Fault Data Acquisition Time .......................................................................................................................3-1233.19.3 Selection of the Measuring Loop for Determining Fault Data .................................................................... 3-1243.19.4 Acquisition of Short Circuit Data ................................................................................................................3-1263.19.5 Acquisition of Fault Location ......................................................................................................................3-1283.19.6 Fault Data Reset ........................................................................................................................................3-1293.20 Fault Recording (Function Group FT_RC) ................................................................ 3-1303.20.1 Start of Fault Recording .............................................................................................................................3-1303.20.2 Fault Counting ........................................................................................................................................... 3-1313.20.3 Time Tagging .............................................................................................................................................3-1313.20.4 Fault Recordings ........................................................................................................................................3-1323.20.5 Fault Value Recording ............................................................................................................................... 3-1333.21 Distance Protection (Function Group DIST) .............................................................3-1353.21.1 Fault Detection Logic .................................................................................................................................3-1353.21.2 Selection of Measured Values ....................................................................................................................3-1483.21.3 Distance and Directional Measurement .....................................................................................................3-1533.21.4 Impedance-Time Characteristics ............................................................................................................... 3-1723.21.5 Distance Protection Trip Signals ................................................................................................................3-1763.21.6 Selection of Trip Mode for Zone 1 ..............................................................................................................3-1813.22 Power Swing Blocking (Function Group PSB) .......................................................... 3-1833.22.1 Measurement ............................................................................................................................................ 3-1833.22.2 Power Swing Detection ..............................................................................................................................3-1843.22.3 Load Blinding .............................................................................................................................................3-1853.22.4 Behavior with a Short-Circuit Fault During a Power Swing Event .............................................................. 3-1883.22.5 PSB Blocking ..............................................................................................................................................3-1893.22.6 Out-of-Step Tripping .................................................................................................................................. 3-1913.22.7 Enhanced Counting-Based Trip Logic ........................................................................................................ 3-191

    Table of Contents P437

    P437/EN M/R-11-A // P437311650 3

  • 3.23 Measuring-Circuit Monitoring (Function Group MCMON) .........................................3-1973.23.1 Current Monitoring .................................................................................................................................... 3-1973.23.2 Voltage Monitoring .................................................................................................................................... 3-1983.23.3 Phase-Sequence Monitoring ...................................................................................................................... 3-2003.23.4 Fuse Failure Monitoring of Phase-to-Ground Voltages ............................................................................... 3-2013.23.5 Fuse Failure Monitoring of the Reference Voltage ..................................................................................3-2053.24 Backup Overcurrent-Time Protection (Function Group BUOC) ................................ 3-2063.25 Switch on to Fault Protection (Function Group SOTF) ............................................. 3-2083.25.1 Decision Line dead ................................................................................................................................. 3-2103.26 Protective Signaling (Function group PSIG) .............................................................3-2123.26.1 Disabling and Enabling Protective Signaling ..............................................................................................3-2123.26.2 Readiness of Protective Signaling ..............................................................................................................3-2123.26.3 Three-Ended Line Application ....................................................................................................................3-2143.26.4 Monitoring the Transmission Section .........................................................................................................3-2153.26.5 Frequency Monitoring ................................................................................................................................3-2163.26.6 Transient Blocking .....................................................................................................................................3-2163.26.7 Protective Signaling Operating Modes .......................................................................................................3-2173.26.8 Measuring Zone Extension of Zone 1 of Distance Protection .................................................................... 3-2323.26.9 Weak-Infeed Logic ..................................................................................................................................... 3-2323.26.10 Echo Function ............................................................................................................................................3-2363.26.11 Testing the Communication Channels ....................................................................................................... 3-2383.27 Auto-Reclosing Control in the P437 (Function Group ARC) ..................................... 3-2403.27.1 ARC Operating Modes ................................................................................................................................3-2403.27.2 Enabling and Disabling the ARC Function ..................................................................................................3-2413.27.3 ARC Blocked .............................................................................................................................................. 3-2433.27.4 ARC Tripping Times ................................................................................................................................... 3-2443.27.5 Starting the ARC Cycle .............................................................................................................................. 3-2453.27.6 High-Speed Reclosure (HSR) ..................................................................................................................... 3-2453.27.7 Time-Delay Reclosure (TDR) in the P437 ...................................................................................................3-2573.27.8 Rapid Reclosure (RRC) ...............................................................................................................................3-2593.27.9 Secondary Fault Treatment in the P437 .................................................................................................... 3-2613.27.10 Parallel Blocking in the P437 ..................................................................................................................... 3-2633.27.11 Zone Extension in the P437 .......................................................................................................................3-2663.27.12 Control Using External Auto-Reclosing Control ..........................................................................................3-2683.27.13 General ARC Control Functions in the P437 ...............................................................................................3-2693.27.14 ARC Counters in the P437 ......................................................................................................................... 3-2723.28 Automatic Synchronism Check (Function Group ASC) ............................................ 3-2733.28.1 Disabling and Enabling the ASC Function ..................................................................................................3-2733.28.2 ASC Readiness and Blocking ..................................................................................................................... 3-2753.28.3 Close Request ............................................................................................................................................3-2763.28.4 ASC Operating Modes ................................................................................................................................3-2783.28.5 Continuous Synchronism Check ................................................................................................................ 3-2783.28.6 Extended Settings for the Close Enable Conditions ...................................................................................3-2793.28.7 Considering the CB Close Time ..................................................................................................................3-2803.28.8 Voltage-Checked Close Enable .................................................................................................................. 3-2813.28.9 Synchronism-Checked Close Enable ..........................................................................................................3-2843.28.10 Voltage/Synchronism-Checked Close Enable .............................................................................................3-2873.28.11 Testing the ASC Function .......................................................................................................................... 3-2873.28.12 ASC Counters .............................................................................................................................................3-2893.29 Ground fault (short-circuit) protection (Function Group GFSC) ............................... 3-2903.29.1 Disabling or Enabling Ground Fault (Short-Circuit) Protection ...................................................................3-2903.29.2 Measured Values from the Ground Fault (Short-Circuit) Protection ...........................................................3-2913.29.3 Blocking ground fault (short-circuit) protection .........................................................................................3-2923.29.4 Starting ......................................................................................................................................................3-2933.29.5 Directional Tripping ................................................................................................................................... 3-294

    P437 Table of Contents

    4 P437/EN M/R-11-A // P437311650

  • 3.29.6 Improved Directional Measurement for Series-Compensated Line Applications xyz ................................. 3-2953.29.7 Improved Phase Selection ......................................................................................................................... 3-2973.29.8 Voltage-Dependent or Current-Dependent Tripping ..................................................................................3-2993.29.9 Non-Directional Tripping ............................................................................................................................3-3063.29.10 Counters ....................................................................................................................................................3-3073.29.11 Monitoring the Measured Values ............................................................................................................... 3-3083.30 Ground Fault (Short-Circuit) Protection Signaling (Function Group GSCSG) ............3-3093.30.1 Disabling or Enabling Ground Fault (Short-Circuit) Protection Signaling ................................................... 3-3093.30.2 Readiness of Ground Fault (Short-Circuit) Protection Signaling .................................................................3-3103.30.3 Communication Link Faulty Signal .............................................................................................................3-3133.30.4 Tripping Time ............................................................................................................................................ 3-3143.30.5 Frequency Monitoring ................................................................................................................................3-3143.30.6 Transient Blocking .....................................................................................................................................3-3153.30.7 Operating Modes of Ground Fault (Short-Circuit) Protection Signaling and the Communication Channel . 3-3153.30.8 Signal Comparison Release Scheme ..........................................................................................................3-3163.30.9 Signal Comparison Blocking Scheme .........................................................................................................3-3173.30.10 Weak-Infeed Logic ..................................................................................................................................... 3-3183.30.11 Trip Mode .................................................................................................................................................. 3-3193.30.12 Echo Function ............................................................................................................................................3-3203.30.13 Testing the Communication Channel .........................................................................................................3-3213.31 Definite-Time Overcurrent Protection (Function Group DTOC) ................................3-3233.31.1 Enabling or Disabling DTOC Protection ......................................................................................................3-3233.31.2 Monitoring the Maximum Phase Current ................................................................................................... 3-3233.31.3 Negative-Sequence Current Stages ...........................................................................................................3-3243.31.4 Residual Current Stages ............................................................................................................................ 3-3263.31.5 Hold-Time Logic for Intermittent Ground Faults ........................................................................................ 3-3353.32 Inverse-Time Overcurrent Protection (Function Group IDMT) ................................. 3-3383.32.1 Disabling and Enabling IDMT Protection ....................................................................................................3-3383.32.2 Time-Dependent Characteristics ............................................................................................................... 3-3393.32.3 Enable Thresholds ..................................................................................................................................... 3-3433.32.4 Phase Current Stage ..................................................................................................................................3-3443.32.5 Negative-Sequence Current Stage ............................................................................................................ 3-3463.32.6 Selecting the Measured Variable for the Residual Current Stage .............................................................. 3-3483.32.7 Residual Current Stage ..............................................................................................................................3-3483.32.8 Holding Time ............................................................................................................................................. 3-3493.33 Thermal Overload Protection (Function Group THERM) .......................................... 3-3513.33.1 Readiness of Thermal Overload Protection ................................................................................................3-3513.33.2 Operating Modes ....................................................................................................................................... 3-3513.33.3 Coolant Temperature Effect ...................................................................................................................... 3-3523.33.4 Thermal Overload Protection Operation without Coolant Temperature (Ambient) Acquisition ..................3-3533.33.5 Relative Replica .........................................................................................................................................3-3533.33.6 Absolute Replica ........................................................................................................................................3-3543.33.7 Tripping Characteristics .............................................................................................................................3-3553.33.8 Warning Signal .......................................................................................................................................... 3-3563.33.9 Trip ............................................................................................................................................................ 3-3563.33.10 Cooling ...................................................................................................................................................... 3-3563.33.11 Resetting ................................................................................................................................................... 3-3573.34 Under and Overvoltage Protection (Function Group V) ......................................3-3593.34.1 Disabling and Enabling V Protection .....................................................................................................3-3593.34.2 V Protection Readiness .........................................................................................................................3-3593.34.3 Minimum Current Monitoring .....................................................................................................................3-3603.34.4 Monitoring the Phase Voltages .................................................................................................................. 3-3613.34.5 Monitoring the Positive- and Negative-Sequence Voltages ....................................................................... 3-3663.34.6 Monitoring the Neutral-Point Displacement Voltage ..................................................................................3-3703.34.7 Monitoring the Reference Voltage ............................................................................................................. 3-370

    Table of Contents P437

    P437/EN M/R-11-A // P437311650 5

  • 3.35 Over-/Underfrequency Protection (Function Group f) ........................................ 3-3733.35.1 Disabling or Enabling Over/Underfrequency Protection ............................................................................3-3733.35.2 Selecting the Measuring Voltage ...............................................................................................................3-3743.35.3 Undervoltage Blocking and Evaluation Time ............................................................................................. 3-3753.35.4 Operating Modes of Over-/Underfrequency Protection .............................................................................. 3-3753.35.5 Frequency Monitoring ................................................................................................................................3-3753.35.6 Frequency Monitoring Combined with Differential Frequency Gradient Monitoring (df/dt) ........................3-3763.35.7 Frequency Monitoring Combined with Mean Frequency Gradient Monitoring (f/t) ................................ 3-3763.35.8 fmin-/fmax Measurement ............................................................................................................................. 3-379

    3.36 Directional Power Protection (Function Group P) ............................................... 3-3803.36.1 Disabling and Enabling P Protection .....................................................................................................3-3803.36.2 Power Determination .................................................................................................................................3-3803.36.3 Power Monitoring .......................................................................................................................................3-3813.36.4 Active Power Monitoring when Set Thresholds are Exceeded ................................................................... 3-3823.36.5 Active Power Direction when Set Thresholds are Exceeded ...................................................................... 3-3833.36.6 Reactive Power Monitoring when Set Thresholds are Exceeded ................................................................3-3843.36.7 Reactive Power Direction when Set Thresholds are Exceeded .................................................................. 3-3853.36.8 Active Power Monitoring when Values Fall Below Set Thresholds ..............................................................3-3863.36.9 Active Power Direction when Values Fall Below Set Thresholds ................................................................ 3-3883.36.10 Reactive Power Monitoring when Values Fall Below Set Thresholds ..........................................................3-3913.36.11 Reactive Power Direction when Values Fall Below Set Thresholds ............................................................ 3-3923.36.12 Starting Signal with Direction ....................................................................................................................3-3953.37 Circuit Breaker Failure Protection (Function Group CBF) ........................................ 3-3963.37.1 Disabling and Enabling Circuit Breaker Failure Protection .........................................................................3-3963.37.2 Readiness of Circuit Breaker Protection .................................................................................................... 3-3973.37.3 Detecting a CB Tripping .............................................................................................................................3-3973.37.4 Current Flow Monitoring ............................................................................................................................ 3-3983.37.5 Evaluation of CB Status Signals .................................................................................................................3-3993.37.6 Startup Criteria ..........................................................................................................................................3-4003.37.7 Timer Stages and Output Logic ................................................................................................................. 3-4003.37.8 Trip Commands ......................................................................................................................................... 3-4023.37.9 Starting Trigger ......................................................................................................................................... 3-4043.37.10 Fault Behind CB Protection ........................................................................................................................3-4043.37.11 CB Synchronization Supervision ................................................................................................................ 3-4053.38 Circuit Breaker Monitoring (Function Group CBM) .................................................. 3-4063.38.1 Disabling and Enabling Circuit Breaker Monitoring ....................................................................................3-4063.38.2 Variants ..................................................................................................................................................... 3-4063.38.3 CB Wear Characteristic ..............................................................................................................................3-4073.38.4 Calculating the CB Wear State .................................................................................................................. 3-4083.38.5 Operating Modes ....................................................................................................................................... 3-4083.38.6 Cycle for Circuit Breaker Monitoring ..........................................................................................................3-4083.38.7 Pole-Selective Counter Values and Measured Values ................................................................................ 3-4103.38.8 Resetting Measured Values ....................................................................................................................... 3-4113.38.9 Setting Measured Values ...........................................................................................................................3-4113.38.10 Monitoring the Number of CB Operations ..................................................................................................3-4133.38.11 Monitoring Ruptured Currents ................................................................................................................... 3-4133.38.12 Blocking Circuit Breaker Monitoring .......................................................................................................... 3-4143.39 Limit Value Monitoring (Function Group LIMIT) ....................................................... 3-4153.39.1 Enable/Disable the Limit Value Monitoring Function ................................................................................. 3-4153.39.2 Monitoring Phase Currents and Phase Voltages ........................................................................................ 3-4153.39.3 Monitoring the Neutral-Point Displacement Voltage ..................................................................................3-4183.39.4 Monitoring the Linearized Measured DC Values ........................................................................................ 3-4193.39.5 Monitoring the Reference Voltage ............................................................................................................. 3-4203.39.6 Monitoring the Measured PT 100 Temperature Value ............................................................................ 3-4213.40 Programmable Logic (Function Groups LOGIC and LOG_2) .....................................3-422

    P437 Table of Contents

    6 P437/EN M/R-11-A // P437311650

  • 3.41 Binary Counts (Function Group COUNT) ..................................................................3-4303.41.1 Enable/Disable the Counting Function .......................................................................................................3-4303.41.2 Debouncing ............................................................................................................................................... 3-4303.41.3 Counting Function ..................................................................................................................................... 3-4303.41.4 Transmitting the Counter Values via Communications Interface ...............................................................3-4313.41.5 Counter Values Reset ................................................................................................................................ 3-431

    4 Design .................................................................................................................4-14.1 Designs ....................................................................................................................... 4-24.2 Dimensional Drawings ................................................................................................ 4-44.2.1 Dimensional Drawings for the 84 TE Case .....................................................................................................4-44.3 Hardware Modules ...................................................................................................... 4-6

    5 Installation and Connection ................................................................................ 5-15.1 Unpacking and Packing ...............................................................................................5-35.2 Checking Nominal Data and Design Type ................................................................... 5-45.3 Location Requirements ............................................................................................... 5-55.3.1 Environmental Conditions ..............................................................................................................................5-55.3.2 Mechanical Conditions ...................................................................................................................................5-55.3.3 Electrical Conditions for Auxiliary Voltage of the Power Supply .................................................................... 5-55.3.4 Electromagnetic Conditions ...........................................................................................................................5-55.4 Installation .................................................................................................................. 5-65.5 Protective and Operational Grounding ......................................................................5-125.6 Connection ................................................................................................................5-135.6.1 Connecting Measuring and Auxiliary Circuits .............................................................................................. 5-135.6.2 Connecting the IRIGB Interface .................................................................................................................. 5-155.6.3 Connecting the Serial Interfaces ................................................................................................................. 5-155.7 Location and Connection Diagrams .......................................................................... 5-195.7.1 Location Diagrams P437 412/413 ...............................................................................................................5-195.7.2 Terminal Connection Diagrams P437412/413 ............................................................................................ 5-19

    6 Local Control (HMI) ............................................................................................. 6-16.1 Local Control Panel (HMI) ............................................................................................6-16.2 Display and Keypad .................................................................................................... 6-26.2.1 Text Display ...................................................................................................................................................6-26.2.2 Display Illumination .......................................................................................................................................6-26.2.3 Contrast of the Display ..................................................................................................................................6-26.2.4 Short Description of Keys .............................................................................................................................. 6-36.3 Display Levels .............................................................................................................6-56.4 Display Panels .............................................................................................................6-66.5 Menu Tree and Data Points .........................................................................................6-76.6 List Data Points ........................................................................................................... 6-86.7 Note Concerning the Step-by-Step Descriptions ......................................................... 6-96.8 Configurable Function Keys ...................................................................................... 6-106.8.1 Configuration of the Function Keys F1 to Fx ................................................................................................6-116.9 Changing Between Display Levels ............................................................................ 6-146.10 Control at Panel Level ............................................................................................... 6-156.11 Control at the Menu Tree Level .................................................................................6-166.11.1 Navigation in the Menu Tree ....................................................................................................................... 6-166.11.2 Switching Between Address Mode and Plain Text Mode ..............................................................................6-17

    Table of Contents P437

    P437/EN M/R-11-A // P437311650 7

  • 6.11.3 Change-Enabling Function ...........................................................................................................................6-186.11.4 Changing Parameters .................................................................................................................................. 6-216.11.5 List Parameters ........................................................................................................................................... 6-226.11.6 Memory Readout ......................................................................................................................................... 6-256.11.7 Resetting ..................................................................................................................................................... 6-286.11.8 Password-Protected Control Actions ............................................................................................................6-296.11.9 Changing the Password ............................................................................................................................... 6-31

    7 Settings ...............................................................................................................7-17.1 Parameters .............................................................................................................. 7-17.1.1 Device Ident i f icat ion ............................................................................................................................. 7-37.1.2 Conf igurat ion Parameters .................................................................................................................. 7-127.1.3 Funct ion Parameters ............................................................................................................................7-88

    8 Information and Control Functions ......................................................................8-18.1 Operation ................................................................................................................. 8-18.1.1 Cycl ic Values ............................................................................................................................................ 8-18.1.2 Contro l and Test ing ............................................................................................................................8-1278.1.3 Operat ing Data Recording ................................................................................................................8-1468.2 Events ................................................................................................................... 8-1478.2.1 Event Counters .................................................................................................................................... 8-1478.2.2 Measured Event Data .........................................................................................................................8-1538.2.3 Event Recording .................................................................................................................................. 8-160

    9 IEC 61850 Settings via IED Configurator .............................................................9-19.1 Manage IED .................................................................................................................9-29.2 IED Details .................................................................................................................. 9-39.3 Communications ......................................................................................................... 9-49.4 SNTP ........................................................................................................................... 9-59.4.1 General Config ...............................................................................................................................................9-59.4.2 External Server 1 ...........................................................................................................................................9-59.4.3 External Server 2 ...........................................................................................................................................9-59.5 Dataset Definitions ..................................................................................................... 9-69.6 GOOSE Publishing ....................................................................................................... 9-79.6.1 System/LLN0 ................................................................................................................................................. 9-79.7 GOOSE Subscribing .....................................................................................................9-99.7.1 Mapped Inputs ...............................................................................................................................................9-99.8 Report Control Blocks ............................................................................................... 9-129.8.1 System/LLN0 ............................................................................................................................................... 9-129.9 Controls .....................................................................................................................9-139.9.1 Control Objects ............................................................................................................................................9-139.9.2 Uniqueness of Control ................................................................................................................................. 9-139.10 Measurements .......................................................................................................... 9-159.11 Configurable Data Attributes .................................................................................... 9-169.11.1 System/LLN0 ............................................................................................................................................... 9-16

    10 Commissioning ................................................................................................. 10-110.1 Safety Instructions .................................................................................................... 10-110.2 Commissioning Tests ................................................................................................ 10-410.2.1 Preparation ..................................................................................................................................................10-410.2.2 Tests ............................................................................................................................................................10-610.2.3 Checking the Binary Signal Inputs ...............................................................................................................10-6

    P437 Table of Contents

    8 P437/EN M/R-11-A // P437311650

  • 10.2.4 Checking the Output Relays ........................................................................................................................ 10-610.2.5 Checking the Communications Interfaces Signals .......................................................................................10-710.2.6 Checking the Protection Function ................................................................................................................10-710.2.7 Completing Commissioning .......................................................................................................................10-21

    11 Troubleshooting ................................................................................................11-1

    12 Maintenance ..................................................................................................... 12-112.1 Maintenance Procedures in the Power Supply Area .................................................. 12-212.2 Routine Functional Testing ....................................................................................... 12-412.3 Analog Input Circuits .................................................................................................12-512.4 Binary Opto Inputs .................................................................................................... 12-612.5 Binary Outputs ..........................................................................................................12-712.6 Serial Interfaces ........................................................................................................12-8

    13 Storage ............................................................................................................. 13-1

    14 Accessories and Spare Parts .............................................................................14-1

    15 Order Information ............................................................................................. 15-1

    A1 Function Groups ............................................................................................... A1-1

    A2 Internal Signals .................................................................................................A2-1

    A3 Glossary ............................................................................................................A3-1Modules ...................................................................................................................................... A3-1Symbols ......................................................................................................................................A3-1Examples of Signal Names ......................................................................................................... A3-7Symbols Used ............................................................................................................................. A3-8

    A4 Telecontrol Interfaces .......................................................................................A4-1A4.1 Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101 (Companion Standard)

    .................................................................................................................................. A4-1A4.1.1 Interoperability ............................................................................................................................................A4-1A4.2 Communication Interface per IEC 60870-5-103 ........................................................A4-9A4.2.1 Interoperability ............................................................................................................................................A4-9

    A5 P437 Version History ........................................................................................ A5-1

    Table of Contents P437

    P437/EN M/R-11-A // P437311650 9

  • P437 Table of Contents

    10 P437/EN M/R-11-A // P437311650

  • 1 Application and Scope

    1.1 OverviewThe P437 distance protection device has been designed for selective short-circuitprotection, ground fault protection, and overload protection of transmission linesand cables in medium-, high- and extra-high-voltage systems. The systems canbe solidly-grounded or resistance grounded.

    Fig. 1-1: P437 in a 84 TE sized case.

    The multitude of protection functions incorporated into the P437 enable the userto cover a wide range of applications in the line protection. The relevantprotection parameters can be stored in four independent parameter subsets inorder to adapt the protection device to varying system operation conditions.The P437 is equipped with a large number of protection functions. These can beindividually configured and cancelled.All main functions are individually configurable. The user can adapt the P437flexibly to the scope of protection required in each particular application.The powerful programmable logic provided by the protection device also makesit possible to accommodate special applications.

    P437

    P437/EN M/R-11-A // P437311650 1-1

  • Protection functions P437

    ANSI IEC 61850 Functiongroup Function

    21 DisPDISn DIST Distance protection Overcurrent and undervoltage starting Underimpedance starting with adjustable load

    blinding Polygonal (quadrilateral) or circular tripping

    characteristics Six distance zones, one zone for special

    applications Eight timer stages, including two backup stages Directional voltage memory

    68 RPSB1 PSB Power swing blocking and out-of-step tripping

    30/ 74 AlmGGIO1 MCMON Measuring-circuit monitoring

    50TD P/N

    DtpPhs- /DtpEftPTCOx

    BUOC Backup overcurrent protection

    50/ 27 SofPhs- /SofEftPSOF1

    SOTF Switch on to fault protection

    85 - 21 PsgPhsPSCH1 PSIG Protective signaling

    79 RREC1 ARC Auto-reclosing control

    25 RSYN1 ASC Automatic synchronism check ()

    67 N GfsResPTOC1 / PTOV1 /RDIR1

    GFSC Ground fault short circuit protection

    85 -67N

    PsgGfsPSCH1 GFCSG Ground fault short circuit protection signaling

    50TD P/Q/ N

    DtpPhs- /DtpEft- /DtpNgsPTCOx

    DTOC Definite-time overcurrent protection, four stages,phase-selective

    51 P/ Q/N

    ItpPhs- /ItpEft- /ItpNgsPTCOx

    IDMT Inverse-time overcurrent protection, single-stage,phase-selective

    49 ThmPTTR1 THERM Thermal overload protection

    27/ 59/47 P/ Q/N

    VtpPhs- /VtpNgs- /VtpPss- /VtpRefPTyVx

    V Over- /Undervoltage Protection

    81 FrqPTyFx f Over- /Underfrequency protection

    P437 1 Application and Scope

    1-2 P437/EN M/R-11-A // P437311650

  • Protection functions P437

    ANSI IEC 61850 Functiongroup Function

    32 PdpAct- /PdpRealPDyPx

    P Directional power protection

    50/ 62BF

    RBRFx CBF Circuit breaker failure protection

    LIMIT Limit value monitoring

    LGC PloGGIOx LOGIC /LOG_2

    Programmable logic

    PHAR1 MAIN Inrush stabilization

    Communication functions P437

    ANSI IEC 61850 Functiongroup Function

    16S COMM1,COMM2

    2 communication interfaces serial, RS 422 / 485 orfiber optic

    ()

    CLK IRIGB Time synchronization IRIG-B ()

    COMM3,COMM4

    Protection communication interface InterMiCOM,serial, RS 422/485, or FO

    ()

    16E IEC Communication interface Ethernet ()

    16E GosGGIOx GOOSE IEC 61850 ()

    Measured value functions, binary inputs and outputs P437

    ANSI IEC 61850 Functiongroup Function

    INP 4 to 20 optical coupler inputs ()

    OUTP 8 to 30 output relays ()

    1 Application and Scope P437

    P437/EN M/R-11-A // P437311650 1-3

  • Measured value functions, analog inputs and outputs P437

    ANSI IEC 61850 Functiongroup Function

    Mmuxxx Measuring

    26 RtdGGIO1IdcGGIO1

    MEASI RTD input1 Measuring data input 20 mA, one settable inputvalue

    ()()

    MEASO 2 Measuring data output 20 mA, two settableoutput values

    ()

    Miscellaneous functions P437

    ANSI IEC 61850 Functiongroup Function

    F_KEY 4 configurable function keys

    LLN0.SGCB PSS Parameter subset selection

    PTRCx /RDRE1

    FT_RC Fault recording

    = Standard; () = Ordering option.

    For a list of all available function groups see the Appendix.

    MeteringLIMIT

    Overload Rec.

    Fault Rec.

    IRIGBCOMM2COMM1 IEC

    Communication to SCADA/ substation control/ RTU/modem, via RS485 or fiber optics using IEC 60870-5-101, -103, Modbus, DNP3, Courier, or via RJ45 or fiber optics using IEC 61850.

    Recordingand dataacquisition

    SelfMonitoring

    refV

    V

    I

    50/51 P,Q,NDTOC

    51/67 P,Q,NIDMT

    49THERM

    50BF/62CBF

    25ASC

    Distance ProtectionAlways Available Optional

    MiCOM P437

    16S 16S 16E CLK

    MCMON 51P,NBUOC32

    P27/59 P,Q,N

    V

    81 O/Uf

    GFSC67N

    GFCSG85-67N

    50/27SOTF

    68PSB

    Scheme signaling

    serial conventional

    InterMiCOM77 COUNT MEASOMEASI

    26

    LOGICLGC

    LOG_2LGC

    IN,par

    85-21PSIG

    21DIST

    79ARC

    Fig. 1-2: Functional diagram.

    P437 1 Application and Scope

    1-4 P437/EN M/R-11-A // P437311650

  • 1.2 General FunctionsFunctions listed in the tables above are self-contained function groups (exceptfor ILOCK) and can be individually configured or de-configured according to thespecific application requirements. Unused or cancelled function groups arehidden to the user, thus simplifying the menu.This concept provides a large choice of functions and makes wide-rangingapplication of the protection device possible, with just one model version. On theother hand simple and clear parameter settings can be made.In this way the protection and control functions (except for ILOCK) can beincluded in or excluded from the configuration; they are arranged on the branch"General Functions" of the menu tree.

    1 Application and Scope P437

    P437/EN M/R-11-A // P437311650 1-5

  • 1.3 Global FunctionsIn addition to the listed features, and extensive self-monitoring, the P437 isequipped with the following global functions:

    Parameter subset selection System measurements to support the user during commissioning, testing

    and operation Operating data recording

    (time-tagged event logging) Overload data acquisition Overload recording

    (time-tagged event logging) Ground fault data acquisition Ground fault recording

    (time-tagged event logging) Fault recording

    (time-tagged event logging together with fault value recording of the threephase currents, the residual current as well as the three phase-to-groundvoltages and the neutral-point displacement voltage).

    P437 1 Application and Scope

    1-6 P437/EN M/R-11-A // P437311650

  • 1.4 DesignThe P437 is modular in design. The plug-in modules are housed in a robustaluminum case and electrically interconnected via one analog p/c board and onedigital p/c board.

    1 Application and Scope P437

    P437/EN M/R-11-A // P437311650 1-7

  • 1.5 Configurable Function KeysTo the right of the text display, there are six freely configurable function keysavailable. These may be used for easy control operation access.

    P437 1 Application and Scope

    1-8 P437/EN M/R-11-A // P437311650

  • 1.6 Inputs and OutputsThe following inputs and outputs are available with the basic device:

    1 current measuring input 4 or 5 voltage measuring inputs 8 output relays, freely-configurable 4 binary signal inputs (opto-coupler)

    Depending on the order options (Chapter 15, (p. 15-1)) there are several moremodules available. The location diagrams (Section 5.7, (p. 5-19)) give anoverview of the combinations of modules that are technically possible. Themodule list (Section 4.3, (p. 4-6)) details the designations that appear in thelocation diagrams.The nominal currents and nominal voltages of the standard measuring inputs canbe set.The nominal voltage range of the binary signal inputs (opto-coupler) is 24 to250 V DC. As an option binary signal input modules with a higher operatethreshold are available.The auxiliary voltage input for the power supply is also designed for an extendedrange. The nominal voltage ranges are 60 to 250 V DC and 100 to 230 V AC. Asan option there is a variant available for the lower nominal voltage range 24 V to60 V DC.All output relays can be utilized for signaling and command purposes.The optional PT 100 input (on the analog module Y(4I)) is lead-compensated andbalanced and linearized for PT 100 resistance thermometers as per IEC 751.The optional 0 to 20 mA input provides open-circuit and overload monitoring,zero suppression defined by a setting, plus the option of linearizing the inputvariable via 20 adjustable interpolation points.Two selectable measured variables (cyclically updated measured operating dataand stored measured fault data) can be output as a burden-independent directcurrent via the two optional 0 to 20 mA outputs. The characteristics are definedby 3 adjustable interpolation points allowing a minimum output current (4 mA,for example) for slave-side open-circuit monitoring, knee-point definition for finescaling, and a limitation to lower nominal currents (10 mA, for example). Wheresufficient output relays are available, a selectable measured variable can beoutput in BCD-coded form by contacts.

    1 Application and Scope P437

    P437/EN M/R-11-A // P437311650 1-9

  • 1.7 Control and Display Local control panel with an LC display containing 4 20 alphanumeric

    characters. 23 LED indicators, 18 of which allow freely configurable function

    assignment for the colors red and green. Furthermore there are variousoperating modes and flashing functions available.

    PC interface. One or two communication interface(s) for connection to a substation

    control system (optional).

    P437 1 Application and Scope

    1-10 P437/EN M/R-11-A // P437311650

  • 1.8 Information InterfacesInformation is exchanged through the local control panel, the PC interface, or twooptional communication interfaces (channel 1 and channel 2).Using the first channel of the communication interfaces (COMM1), the P437 canbe wired either to the substation control system or to a telecontrol system. Thischannel is optionally available with a switchable protocol (per IEC 608705103,IEC 8705101, DNP 3.0, MODBUS or Courier).The second communication interface (COMM2, communication protocol perIEC 608705103 only) is designed for remote control.As an order option, there is an Ethernet interface for communication perIEC 61850 available instead of channel 1.External clock synchronization can be accomplished via one of thecommunication protocols or by using the optional IRIGB input.A direct link to one or two other MiCOM protection devices can be set up byapplying the optional InterMiCOM interfaces (COMM3, COMM4).

    1 Application and Scope P437

    P437/EN M/R-11-A // P437311650 1-11

  • P437 1 Application and Scope

    1-12 P437/EN M/R-11-A // P437311650

  • 2 Technical Data

    2.1 Conformity

    NoticeApplicable to P437, version -311 -412/413 -650.

    Declaration of ConformityThe product designated P437 Distance Protection Device has been designedand manufactured in conformance with the European standards EN 6025526and EN 6025527 and with the EMC Directive and the Low Voltage Directiveissued by the Council of the European Community.

    P437

    P437/EN M/R-11-A // P437311650 2-1

  • 2.2 General Data

    2.2.1 General Device Data

    Design Surface-mounted case suitable for wall installation, or Flush-mounted case for 19 cabinets and for control panels.

    Installation Position Vertical 30.

    Degree of ProtectionPer DIN VDE 0470 and EN 60529 or IEC 529.

    IP 52 for the front panel. Flush-mounted case:

    IP 50 for the case (excluding the rear connection area) IP 20 for the rear connection area, pin-terminal connection IP 10 for the rear connection area, ring-terminal connection

    Surface-mounted case: IP 50 for the case IP 50 for the fully enclosed connection area with the supplied rubber

    grommets fitted

    Weight 84 TE case: Approx. 11 kg

    Dimensions and ConnectionsSee dimensional drawings (Section 4.2, (p. 4-4)), and the location andterminal connection diagrams (Section 5.7, (p. 5-19)).

    Terminals

    PC interface (X6) EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin

    Communication interfaces COMM1 to COMM4 Fiber (X7, X8 and X31, X32 and X36, X37)

    F-SMA optical fiber connection per IEC 608742 (for plastic fibers), or optical fiber connection BFOC-ST connector 2.5 per IEC 60874101 (for

    glass fibers).(ST is a registered trademark of AT&T Lightguide Cable Connectors.)

    Wire leads (X9, X10, X33, X38) M2 threaded terminal ends for wire cross-sections up to 1.5 mm.

    IRIG-B Interface (X11) BNC plug

    P437 2 Technical Data

    2-2 P437/EN M/R-11-A // P437311650

  • Communication interface IEC 61850 Fiber (X7, X8)

    optical fiber connection BFOC-ST connector 2.5 per IEC 6087410 (forglass fibers).(ST is a registered trademark of AT&T Lightguide Cable Connectors.)

    Fiber (X13) SC connector per IEC 60874144 (for glass fibers)

    Wire leads (X12) RJ45 connector per ISO/IEC 8877.

    Current measuring inputs (conventional inputs) Threaded terminal ends, pin-type cable lugs: M5, self-centering with cage

    clamp to protect conductor cross-sections 4 mm, or: Threaded terminal, ring-terminal connection: M4.

    Other inputs and outputs Threaded terminal ends, pin-type cable lugs: M3, self-centering with cage

    clamp to protect conductor cross-sections 0.2 to 2.5 mm, or: Threaded terminal ends, ring-type cable lugs: M4.

    Creepage Distances and Clearances Per EN 60255-27. Pollution degree 3, working voltage 250 V, overvoltage category III, impulse test voltage 5 kV.

    2.2.2 Environmental Conditions

    Temperatures

    Recommended temperature range -5C to +55C [+23F to +131F].

    Limit temperature range Operation: -25C to +55C [-13F to +131F]. Storage and transport: -25C to +70C [-13F to +158F].

    Ambient Humidity Range 75 % relative humidity (annual mean). 56 days at 95 % relative humidity and 40C [104F]. Condensation not permitted.

    Solar RadiationDirect solar radiation on the front of the device must be avoided.

    2 Technical Data P437

    P437/EN M/R-11-A // P437311650 2-3

  • 2.3 Tests

    2.3.1 Type Tests

    Type TestsAll tests per EN 60255-26.

    2.3.1.1 Electromagnetic Compatibility (EMC)

    Interference SuppressionPer EN 55022 or IEC CISPR 22, Class A.

    1 MHz Burst Disturbance TestPer EN 60255-22-1, Class III.

    Common-mode test voltage: 2.5 kV. Differential test voltage: 1.0 kV. Test duration: > 2 s. Source impedance: 200 .

    Immunity to Electrostatic DischargePer EN 60255-22-2 and IEC 60255-22-2, severity level 4.

    Contact discharge Single discharges: > 10. Holding time: > 5 s. Test voltage: 8 kV. Test generator: 50 to 100 M, 150 pF / 330 .

    Immunity to Radiated Electromagnetic EnergyPer EN 6100043 and ENV 50204, severity level 3.

    Antenna distance to tested device: > 1 m on all sides. Test field strength, frequency band 80 to 1000 MHz: 10 V / m. Test using AM: 1 kHz / 80 %. Single test at 900 MHz: AM 200 Hz / 100%.

    Electrical Fast Transient or Burst RequirementsPer EN 61000-44 and IEC 60255224, severity levels 3 and 4.

    Rise time of one pulse: 5 ns. Impulse duration (50% value): 50 ns. Amplitude: 2 kV / 1 kV or 4 kV / 2 kV. Burst duration:15 ms. Burst period: 300 ms. Burst frequency: 5 kHz. Source impedance: 50 .

    Power Frequency ImmunityPer IEC 60255227, Class A:

    P437 2 Technical Data

    2-4 P437/EN M/R-11-A // P437311650

  • Phase-to-phase RMS value 150 V. Coupling resistance 100 . Coupling capacitor 0.1 F, for 10 s.

    Phase-to-ground RMS value 300 V. Coupling resistance 220 . Coupling capacitor 0.47 F, for 10 s.

    To comply with this standard, it is suggested to set the parameter (010 220)INP: Fi lter to 6 [steps].

    Current/Voltage Surge Immunity TestPer EN 61000-45 and EN 60255-225, insulation class 4.

    Testing of circuits for power supply and asymmetrical or symmetricallines.

    Open-circuit voltage, front time / time to half-value: 1.2 / 50 s. Short-circuit current, front time / time to half-value: 8 / 20 s. Amplitude: 4 / 2 kV. Pulse frequency: > 5 / min. Source impedance: 12 / 42 .

    Immunity to Conducted Disturbances Induced by Radio Frequency FieldsPer EN 61000-4-6 and EN 60255-226, severity level 3.

    Test voltage: 10 V.

    Power Frequency Magnetic Field ImmunityPer EN 61000-4-8 or IEC 61000-4-8, severity level 4.

    Test frequency: 50 Hz Test field strength: 30 A / m.

    Alternating Component (Ripple) in DC Auxiliary Energizing QuantityPer EN 60255-11.

    12 %.

    2.3.1.2 Insulation

    Voltage TestPer EN 60255-27.

    2 kV AC, 60 sOnly direct voltage (2.8 kV DC) must be used for the voltage test on the powersupply inputs. The PC interface must not be subjected to the voltage test.

    Impulse Voltage Withstand TestPer EN 60255-27.

    Front time: 1.2 s Time to half-value: 50 s Peak value: 5 kV Source impedance: 500

    2 Technical Data P437

    P437/EN M/R-11-A // P437311650 2-5

  • 2.3.1.3 Environmental tests

    Temperature Stability TestPer IEC 60068-2-1

    -25C (-13F) storage (96 hours) -40C (-40F) operation (96 hours)

    Per IEC 60068-2-2 +85C (185F) storage (96 hours) +85C (185F) operation (96 hours)

    Per IEC 60068-2-14 Change of temperature, 5 cycles, 1C / min rate of change

    Ambient Humidity Range TestPer IEC 60068-2-3

    56 days at 93% relative humidity and 40C (104F)Per IEC 60068-2-30

    Damp heat, cyclic (12 + 12 hours)93 % relative humidity, +25C +55C (77F 131F)

    Corrosive Environment TestsPer IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3Industrial corrosive environment/ poor environmental control, mixed gas flowtest.

    21 days at 75% relative humidity and 30C (86F) with exposure toelevated concentrations of H2S, NO2, Cl2 and SO2.

    2.3.1.4 Mechanical Robustness 1Applicable to the following case variants:

    Flush mounted case, flush-mounting method 1 (without angle brackets andframe)

    Vibration TestPer EN 6025521-1 or IEC 6025521-1, test severity class 1.

    Frequency range in operation 10 to 60 Hz, 0.035 mm, and 60 to 150 Hz, 0.5 g

    Frequency range during transport 10 to 150 Hz, 1 g

    Shock Response and Withstand Test, Bump TestPer EN 60255-21-2 or IEC 60255-21-2.Acceleration and pulse duration:

    Shock Response tests are carried out to verify full operability (duringoperation), test severity class 1:5 g for 11 ms.

    Shock Withstand tests are carried out to verify the endurance (duringtransport), test severity class 1:15 g for 11 ms.

    P437 2 Technical Data

    2-6 P437/EN M/R-11-A // P437311650

  • Seismic TestPer EN 60255213 or IEC 60255213, test procedure A, class 1.

    Frequency range 5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s, 3 x 1 cycle.

    2.3.1.5 Mechanical Robustness 2Applicable to the following case variants:

    Flush mounted case, flush-mounting method 2 (with angle brackets andframe)

    Surface-mounted case

    Vibration TestPer EN 6025521-1 or IEC 6025521-1, test severity class 2.

    Frequency range in operation 10 to 60 Hz, 0.075 mm, and 60 to 150 Hz, 1.0 g

    Frequency range during transport 10 to 150 Hz, 2 g

    Shock Response and Withstand Test, Bump TestPer EN 60255-21-2 or IEC 60255-21-2.Acceleration and pulse duration:

    Shock Response tests are carried out to verify full operability (duringoperation), test severity class 2:10 g for 11 ms.

    Shock Withstand tests are carried out to verify the endurance (duringtransport), test severity class 1:15 g for 11 ms.

    Shock bump tests are carried out to verify permanent shock (duringtransport), test severity class 1:10 g for 16 ms.

    Seismic TestPer EN 60255213 or IEC 60255213, test procedure A, class 2.

    Frequency range 5 to 8 Hz, 7.5 mm / 3.5 mm, 8 to 35 Hz, 20 / 10 m/s, 3 x 1 cycle.

    2.3.2 Routine TestsAll tests per EN 60255-1.

    Voltage TestPer EN 60255-27.

    2.2 kV AC, 1 sOnly direct voltage (2.8 kV DC) must be used for the voltage test on the powersupply inputs.The PC interface must not be subjected to the voltage test.

    2 Technical Data P437

    P437/EN M/R-11-A // P437311650 2-7

  • Additional Thermal Test 100% controlled thermal endurance test, inputs loaded.

    P437 2 Technical Data

    2-8 P437/EN M/R-11-A // P437311650

  • 2.4 Inputs and Outputs

    2.4.1 Measuring Inputs

    Current Me