01Multifunction IEDs
MiCOM P43x range provides the complete solution for
distance protection and switchgear control by using one
common platform. Starting from stand-alone distance
protection up to multifunctional One-Box feeder management
solutions, including specific operation and control automatism
like synchronizing, 2pole bay control and direct switchgear
control.
The broad spectrum of protection functions enables the
user to cover a wide range of applications in the protection
of cables and overhead lines in solidly-, low-impedance-,
resonant-grounded or isolated network systems.
Individual customizing allows the user to optimize the
configuration in view to find best technical solution by
optimized investment costs. Together with the high hardware
robustness, excellent reliability and guaranteed long live
time bring customers the confidence to get exactly the right
solution with selecting MiCOM P43x.
The intuitive user interface and the various communication
interfaces allow fast comprehensive parameter setting as well
as reading from extensive recordings. Numerous integrated
communication protocols provide interfacing to almost any
kind of substation control or SCADA system.
Furthermore the integrated InterMiCOM protection interface
provides direct end-to-end communication between two
protection devices.
The flat compact case of the P430C and the 19’’ modular
case variants of the P433/P435/P437/P439 with a variable
number of plug-in modules provide a flexible solution for
easy integration of the devices into the substation. Both case
variants are available for flush mounting and wall-surface
mounting.
MiCOM P43xDistance Protection and Switchgear Control
Customer Benefits•Standardized functionality for all
MiCOM P43x•1A/5A software setting•Function keys for easy maintenance
and operation•High availability and reliability with
redundant communication facilities• Integrated 2pole and direct motor
drive control for switchgears• Integrated protection communication
interface•Best adaptation to varying system
conditions by providing four setting groups
•Proven long years operation experience
MiCOM P439 - One box distance & control
MiCOM P433 - P435 - P437 - Tailored distance protection
MiCOM P430C - Compact distance protection
02Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
Application
Distance protection and control units MiCOM P43x provide a wide range of protection and control functions. The integrated protection func-tions reflect the different requirements in medium and high-voltage power system. The preferred applications are as follows:
• P430C: MV systems with 3pole tripping only, low protection requirements
• P433: MV systems with 3pole tripping only• P435: MV - HV systems with 1/3pole trip• P437: HV - EHV systems with 1/3pole trip • P439: MV systems with 3pole tripping only.The integrated switchgear control capabilities cover the requirements of medium voltage bays:• P433 and P435: basic control of up to 3
devices• P439: enhanced control of up to 6 (10)
devices, incl. graphic bay type display.
Further options are provided for various protection and control requirements for example increasing the number of switchgear units from 3 to 10 for control and monitoring and selection of automatic synchronism check.
Global functions
Following global functions are available in all devices:
• Parameter subset selection (4 setting groups)
• Metering
• Operating data recording
• Overload recording
• Ground fault recording
• Fault recording of all CT/VT inputs and binary signals
Functional Overview (Description of ANSI code nos. see Function Overview)
Self Monitoring
LGCILOCK
Communication 16SCOMM1
16SCOMM2
16EIEC
52DEV
CLKIRIGB
CMD_1SIG_126
MEASI MEASO Distance Protection and Bay Control MiCOM P439
Always availableOptional
conventionalserial
Scheme signaling77
InterMiCOM
LIMIT
Control and Monitoring
of 3 switchgear units(max. 6(10))
Metering
Ground flt . rec.
Fault rec .
Recordingand Data Acquisition
Overload rec .
50/51 P,Q,NDTOC
51/67 P,Q,NIDMTMCMON
85-21PSIG
50/27SOTF TGFD
LGCLOGIC , LOG_2
51 P,NBUOC
21DIST
68PSB
25ASC
79ARC
I
V
Vref
CBM
67WGFDSS
85-67WGFSIG GFTRP
32P<>
49THERM
27/59 P,Q,NV<>
81 O/Uf<>
COUNT
50BF/62CBF
to SCADA / substation control / RTU / modem ...via RS485 or Fiber opticsusing IEC 60870 -5-101 , -103, Modbus , DNP3, Courier
resp.via RJ45 or Fiber optics using IEC 61850 (single or redundant Ethernet )
DM
1011
33E
N
Simple function selection by Mouseclick
EM
1000
38E
N
03Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
Main functions
Main functions are autonomous function groups and can be individually configured or disabled to suit a particular application. To improve user friendliness and clarity only activated function groups can be customized, all other parameter are not visible.
That permits an extensive scope of functions and universal application of the device in a single design version, while at the same time providing for a clear and straight-forward setting procedure and adaptation to the protection and control tasks under consideration.
ANSI IEC 61850 Group Function P430C P433 P435 P439 P43721 DisPDISn DIST Distance protection
Overcurrent starting, undervoltage startingUnderimpedance starting with adjustable load blindingPolygonal-/ or circular tripping-characteristicSix distance zones, one zone for special applicationsEight timer stages, including two backup stagesDirectional voltage memory
68 RPSB1 PSB Power swing blocking and out-of-step tripping
30/74 AlmGGIO1 MCMON Measuring circuit monitoring, incl. Broken Conductor (BC)
50TD P/N
DtpPhs-/DtpEftPTOCx BUOC Backup overcurrent protection
50/27 SofPhs-/ SofEftPSOF1 SOTF Switch onto fault protection
85-21 PsgPhsPSCH1 PSIG Protective signaling
79 RREC1 ARC Auto-reclosure control 3-pole 3-pole 1/3-pole 3-pole 1/3-pole25 RSYN1 ASC Automatic synchronism check ( ) ( ) ( ) ( )67N GfsResPTOC1/-PTOV1/-
DIR1GFSC Ground fault short circuit protection
85-67N PsgGfsPSCH1 GFCSG Ground fault short circuit protection signalling
67W/YN PSDE1 GFDSS Ground fault direction determination ( wattmetric )
GFTRP Ground fault tripping
85-67W PsgGfdPSCH1 GFSIG Ground fault protection signaling
PTEF1 TGFD Transient ground fault direction determination ( ) ( ) ( )50TD P/Q/N
DtpPhs-/DtpEft-/DtpNg-sPTOCx
DTOC Definite-time o/c protection, four stages, max. phase/ negative-sequence/ neutral or residual OC, directional neutral OC
51P/Q/N ItpPhs-/ItpEft-/ TtpNg-sPTOCx
IDMT Inverse-time o/c protection, single-stage, max. phase/ negative-sequence/ neutral or residual OC
49 ThmPTTR1 THERM Thermal overload protection
27/59/47 P/Q/N
VtpPhs-/VtpNgs-/tpPss-/Vtpres-/VtpRefPTyVx
V<> Over/ Undervoltage protection
81 FrqPTyFx f<> Over- / Underfrequency protection
32 PdpAct-/PdpRealPDyPx P<> Directional power protection
50/62BF RBRFx CBF Circuit breaker failure protection ( )
LIMIT Limit value monitoring
LGC PloGGIOx LOGIC Programmable logic, incl. Trip Circuit Supervision (TCS)
CT / VT inputs
Phase and neutral currentsPhase and neutral voltagesSync-check reference voltageParallel line neutral current for mutual coupling comp.
3 + 13
3 + 13 + 1(1)
3 + 13 + 1(1)
3 + 13 + 1(1)
3 + 13 + 1(1)(1)
Binary I/O
INPOUTP
Optical coupler inputsOutput relays ( incl. optional high break outputs )
2 4 … 448 … 30 (4)
4 … 568 … 46 (4)
10 … 4614 … 26 (4)
4 … 208 … 30 (4)
F_KEY Function keys 4 6 6 5 626 RtdGGIO1
IdcGGIO1MEASI/MEASO
1 x RTD input1x Measuring data input 20 mA2 x Measuring data output 20 mA
( )( )( )
( )( )( )
( )( )( )
( )( )( )
LLN0.SGCB PSS Parameter subset selection
PTRCx/ RDRE1 FT_RC Fault recording
52
LGC
XCBRx, XSWIx,CSWIx DEVxxCMD_1SIG_1ILOCK
Control and monitoring of switchgear unitsSingle-pole commandsSingle-pole signalsInterlocking logic
( 3 )(12)(12)( )
( 3 )(12)(12)( )
3 (6)2640
COUNT Binary counters 4 4 416S COMMx 2 Communication interfaces, serial, RS 422/485 or FO ( ) ( ) ( ) ( ) ( )CLK IRIGB Time synchronisation IRIG-B ( ) ( ) ( ) ( ) ( )16E
GosGGIOx
IEC
GOOSE
Communication interface Ethernet, IEC 61850Redundant Ethernet interface ( RSTP, SHP, DHP )GOOSE Communication
( )( )( )
( )( )( )
( )( )( )
( )( )( )
COMM3 Protection communication interface InterMiCOM, serial, RS 422/485, RS 232 or FO
( ) ( ) ( ) ( ) ( )
= STANDARD; ( ) = ORDER OPTION
04Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
Distance protectionThe devices are equipped with elaborate fault detection elements that can be adapted to the individual application. They provide reliable fault detection and fault type determination even under difficult system conditions.The following criteria are continuously monitored:• Overcurrent (I>>)• Undervoltage (V<)• Underimpedance with load blinding (Z<)• Ground fault detection adaptable to system
grounding. All fault detection measurement elements operate simultaneously.Inrush stabilization and fuse failure monitoring (VT circuit supervision) are integrated.A well proven voltage memory eliminates all problems with directional determination in case of small fault voltage, CVT transients or in series compensated lines applications. Six distance zones can be set in total. Each zone can be set as forward, backward or non-directional to suit requirements. Zone 1 extension is provided and controlled by integrated functions such as auto-reclosing control or protective signaling or by an external signal. Special zone 4 is provided, to allow auto-reclosing only on the overhead-line section in cable/line systems or to compensate the bundle conductor effect. P437 could optionally be equipped with an additional CT input to measure the residual current of a parallel line to provide mutual coupling compensation.
Power Swing Blocking / Out-of-Step TrippingPower swings between generators due to severe load variations or system faults may cause measured impedances to enter distance zones. To avoid incorrect tripping, the devices measure the rated change of power to implement blocking for the duration of the swing. In case of short-circuits during a power swing, the blocking is disabled immediately to allow distance elements to operate.Alternatively an out-of-step tripping feature can be activated which operates either on fast power change or upon detection of instable swings.
Tripping Characteristics
n: 1 .... 6
Zn
X
R
45° n
Fault Detection Characteristics
XfWX
ZfW,PPZ
fW,PG
Z fW
Z r
70°Load area
R
Rfw, PP Rfw, PG
Underimpedance detection Circular tripping characteristic
MiCOM P43x for rapid and selective fault clearance in your power system
R
X
1
2
Z (t)+R
1: stable power swing2: instable power swing (out-of-step condition)
-R
posX
negX
R
X
+Roos
posXtrip
-Roos
negXtrip
Power swing detection characteristic Out-of-step tripping characteristic
Rn, PG
X
R
Rn, PP45°
1
n
Xn
n: 1 ... 6
I/I nom0 1I> I>>
1
0,5
V<
V
Vnom / 3
Load area
Overcurrent and undervoltage detection Polygonal tripping characteristic
Power swing Characteristics
DM
1011
42E
ND
M10
1143
EN
DM
1011
44E
NE
M10
1145
EN
EM
1011
47E
N
EM
1011
48E
N
05Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
Ground-Fault ProtectionFor the determination of the ground-fault direction in isolated or Peterson-coil compensated power systems two proven methods are provided:• Wattmetric method (analysis of steady-state
signals), with signaling scheme and trip logic;
• Transient method (optional).
A highly sensitive zero-sequence power directional protection is integrated as back-up protection for high-resistance ground short-circuits in low impedance grounded systems. In order to achieve high-speed tripping, the function is provided with a supplementary ground fault (short-circuit) protection signaling logic with release (permissive) or blocking scheme.This scheme logic can be set up in parallel and independently from the distance scheme logic.
Overcurrent ProtectionVarious multi-stage, partly directional OC elements, with instantaneous or timed operation are provided for complementary protection schemes
Switch on to Fault ProtectionClosing of a circuit breaker might inadvertently lead to a short-circuit fault due to a maintenance ground clamp not yet removed, for example. ‘Switch on to fault protection’ provides an instantaneous protective tripping during a settable time, after a manual close command has been issued.
Protective Signalling
The distance reach is usually set to values below 100 % line length so as to avoid overlapping with adjacent substations. Teleprotection scheme logic extends the reach of protection to 100 % by a logic operation on the signals received from the remote substation.Protective signaling can be operated using one of the standard schemes:• Direct Transfer Trip (DTT) • Permissive Underreaching Transfer Trip (PUTT) • Zone Extension• Permissive Overreaching Transfer Trip (POTT) • Blocking Scheme (incl. DC loop) • Reverse Interlocking (busbar protection)
With P437 phase-selective signal transmission is possible.Where required, additional features as weak infeed trip and echo logic, transient blocking and deblocking can be activated.
Protection Communication Interface InterMiCOMOptional InterMiCOM allows high performance permissive and blocking type unit protection to be configured, plus transfer of any digital status information between line ends. Intertripping is supported too, with channel health monitoring and cyclic redundancy checks (CRC) on the received data for maximum message security. InterMiCOM provides eight end-to-end signal bits, assignable to any function within a MiCOM relay’s programmable logic. Default failsafe states can be set in case of channel outage.
InterMiCOM interface connection
1
2
3
N
G
CG
1
2
3
G
N
1
2
3
G
N
1
2
3
N
G
isolated starpoint
Petersen-coil compensated
Low impedance earthed/grounded
effectively earthed/grounded
non-effectivelyearthed/grounded
Ground -fault direction determination Ground -short -circuit direction protection
Power system grounding
EM
1011
47E
N
06Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
Switchgear Control functionsThe control functions are designed for the control of up to ten electrically operated switchgear units equipped with electrical check-back signaling located in the bay of a medium- or high voltage substation.External auxiliary devices are largely obviated through the integration of binary inputs and power outputs that are independent of auxiliary voltages, by the direct connection option for current and voltage transformers and by the comprehensive interlocking capability.P439 is provided with over 250 predefined bay types (P433/P435 ~ 80). These include the assignment of binary inputs and outputs for the switchgear unit control and monitoring and the interlocking logic. Predefined IEC standard descriptions for switchgear devices and busbars can be simply modified by setting if there is any need to adapt to customer specification. New customized bay types can be created with the separate tool Bay Type Configurator (BTC) tool and downloaded to the device.The P43x issues switching command outputs with the integration of switching readiness and permissibility tests; subsequently the devices monitor the intermediate position times of the switchgear units. If a switchgear malfunction is detected, this fact will be indicated (e.g. by an appropriately configured LED indicator). Optional high break output contacts allow direct control of motor operated HV/ MV primary switchgears as disconnectors or earthing switches. With this integrated solution external motor power relays could be fully replaced. Minimizing required dimension of the low voltage compartment of metal clad switchgear panels and improving the installation costs and quality by reduction of external components and manual work are two of the advantages here.The acquisition of further binary inputs is in the form of single-pole operating signals; they are processed in accordance with their significance for the substation (circuit breaker readiness, for example). In addition to the switching command output, a triggering of binary outputs by single-pole commands is possible.
Automatic synchronism checkThis option can be used in conjunction with automatic or manual (re)closure and the close command of the optional control function. In non-radial networks this ensures that reclosure will proceed only if the voltage and synchronism conditions are met.
Auto-reclosing controlAuto-reclosing control (ARC) operates in single- or three-phase mode, depending on the device tripping capability. ARC cycles with one high-speed reclosing (HSR) and up to nine subsequent time-delay reclosings (TDR) may be configured by the user.
Binary counterFor the acquisition of binary counts, four binary inputs may be configured. In the event of loss of operating voltage, the counts are stored.
Bay type creation with BTC
Proven control, advanced communication, complete local control, comfortable data handling
Bay type display on local HMI
Bay type selection by setting
07Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
MODEM MODEM
COMM2Remote access
PC Local access
COMM1 or IEC 61850 SCADA / Substation control interface
HMI - Local control ofswitchgear units.Full access to all settings,signals and measurements
Information Interfaces
Information interfaces
Information exchange is done via the local control panel, the PC interface and two optional communication interfaces. The first communication interface has settable protocols conforming to IEC 60870-5-103/ -101, DNP 3.0, Modbus and Courier or provides alternatively protocol conforming to IEC 61850 (Redundant) and is intended for integration with substation control systems. The 2nd communication interface (COMM2) conforms to IEC 60870-5-103 and is intended for central settings or remote access. Clock synchronization can be achieved using one of the protocols or using the IRIG-B signal input.
Function keys
The function keys provide an easy local control of processes or functions by the user. A single function can be assigned to each function key that allows manually opening and closing of the CB, enabling and disabling of functions, a quick navigation with the selected menu jump list or a reset of stored information. For each function key, the user can define an operating mode suitable to the assigned functionality. To guard against inadvertent or unauthorized use each function key is protected with a password.
Local Control and Graphic Display
From the Local Control Panel all data required for operation of the protection and control unit could be entered, the data important for system management are read out and the local control of switchgear units is executed.
With the help of the Display Panels, the user is able to carry out a quick and up-to-date check of the state of the bay.On the Bay Panel the selected bay is displayed as a single-pole equivalent network (single line diagram) with the updated switchgear states. Moreover, ancillary information are displayed. Up to 28 status signals are displayed on the Signal Panels which are activated automatically upon status changes. Moreover, presentation modes for the display of status data and status change information can be selected. Selected measured values are displayed on the Measured Value Panels. The type of measured values shown (such as measured operating data or measured fault values) will depend on the prevailing conditions in the substation.The Event Panel displays the most recent events with time-tagging such as the opening of a switchgear unit.
Signal Panel(s) Event PanelBay Panel(s)
Control and Display Panels
Measured Value Panel(s)(depending on system condition)
Menu Tree (settings/operation/events)
Record view
Events 17:58:54
20.04.9805:21:32.331
23:58:17.501CB closed sig. EXTEnd21.04.98
ARC
MAIN
EnabledStart
05:21:32.331 DEV01Switch.device closedStart
20.04.98
Signals 17:58:44P439 Page H 17:58:34Signals 17:58:44
Signals 17:58:44P439 Page B 17:58:34Signals 17:58:44MAIN :M.C.B. trip V EXTPSS :PS 1 activePSS :PS 2 activeMAIN :Bay interlock. act.MAIN :Subst. interl. act.
P439 Page A 17:58:34
Fault panel 17:58:44Ground-fault 17:58:44
Overload panel 17:58:44Meas. values 17:58:44
Voltage A-B prim. 20.7 kVVoltage B-C prim. 20.6 kVVoltage C-A prim. 20.8 kVCurrent A prim. 416 ACurrent B prim. 415 ACurrent C prim. 417 A
BB 1BB2
LockedRemote
1088 A Curr. IP,max prim.
Q
Q
0
8
Q1 Q2
Oper/Rec/OP_RCOperat. data record
Local control with graphica HMI
EM
1011
49E
N
EM
1011
50E
N
08
07-2013NRJED111086EN
Multifunction IEDs MiCOM P430C, P433, P435, P437, P439
© 2
013
Sch
neid
er E
lect
ric -
All
right
s re
serv
ed
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Publishing: Schneider ElectricDesign: Schneider ElectricPrinting:
This document has been printed on ecological paper
Schneider Electric35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France Tel: +33 (0) 1 41 29 70 00
RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com
Device Track Record50.000 distance protections PDxxx and MiCOM P43x got installed until 2011.
● 1991: First numerical distance protection PD 551 launched
● 1998: First distance one-box solution PD 932 launched.
● 1999: MiCOM P437 distance protection launched
● 2001: Transfer of PD 932 into MiCOM P439 with extended functionality
● 2002: Completion of MiCOM P43x range
● 2006: Implementation of IEC 61850 communication protocol and detachable local HMI
● 2008: Control functions integrated into P433/P435,
HMI with 6 configurable function keys
● 2012: Redundant Ethernet interface for IEC 61850