DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible...

25
DISINTEGRATION OF QUICK COUPLING DISINTEGRATION OF QUICK COUPLING THE RESULT: SIGNIFICANT WATER DAMAGE THE RESULT: SIGNIFICANT WATER DAMAGE

Transcript of DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible...

Page 1: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

DISINTEGRATION OF QUICK COUPLINGDISINTEGRATION OF QUICK COUPLING

THE RESULT: SIGNIFICANT WATER DAMAGE

THE RESULT: SIGNIFICANT WATER DAMAGE

Page 2: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

COMMON CAUSESCOMMON CAUSES

1. Imperceptible Leakage attacking one of the QC Bolt

2. Shallow Groove causing QC to remain partly open.

3. QC that was not fully closed.

4. Groove Too Deep.

5. Pressure Surge.

6. Combination of the above

Page 3: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Case No. 1- Surface Imperfection causing Leakage below the Seal and resulting 4” QC Failure

Case No. 1- Surface Imperfection causing Leakage below the Seal and resulting 4” QC Failure

Page 4: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Failure of 4” QC due to corrosion

Which was caused by water seeping from the Pipe. .

Page 5: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Water Damage to stored Books.

Page 6: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The Quick-Coup.

Page 7: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The Quick-Coup.

Page 8: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The bolt was consumed by the Corrosion

Page 9: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The 4” Pipe: Extensive Corrosion

Page 10: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Imperfection enabled water seeping below the Seal.

Page 11: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Example No. 2- Surface Imperfection causing Leakage below the Seal

Example No. 2- Surface Imperfection causing Leakage below the Seal

Page 12: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Imperfection in the Pipe Seam.

Page 13: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Imperfection in the Pipe Seam.

Page 14: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Imperfection in the Pipe Seam.

Water Seeping Direction

The Result: Multiple Dripping

Page 15: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Case No. 3- Internal Leakage causing disintegration Case No. 3- Internal Leakage causing disintegration

Page 16: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The Bolt Was Destroyed by Corrosion

Page 17: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The Bolt Was Destroyed by Corrosion

Page 18: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The QC was just Replaced. The Cause remained.

Page 19: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Case No. 4- Disengaging 4” Pipe from 4” Quick Coup Causes Significant Water Damage

Case No. 4- Disengaging 4” Pipe from 4” Quick Coup Causes Significant Water Damage

Page 20: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Too Deep Groove helped the failure.

Bolt Was Left Open

Page 21: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The Contractor did not close the QC properly leaving a significant Gap between the two parts of the QC

Page 22: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Case No. 5- Disengaging 2” Pipe from 2” Quick Coup Causes Significant Water Damage in Apartment in High Rise Building

Page 23: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

2” Pipe within the Gypsum wall in an apartment. Following a repair of a failed QC

Page 24: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

The 2” Pipe section and the QC were replaced

Too deep Grooves.

Page 25: DISINTEGRATION OF QUICK COUPLING · SIGNIFICANT WATER DAMAGE. COMMON CAUSES 1. Imperceptible Leakage attacking one of the QC Bolt 2. Shallow Groove causing QC to remain partly open.

Too Deep Groove caused the Dis-engagement

Pressure exceeded 225PSI