Directing the o & m of Motors

download Directing the o & m of Motors

of 58

Transcript of Directing the o & m of Motors

  • 8/13/2019 Directing the o & m of Motors

    1/58

    Note: The source of the technical material in this volume is the ProfessionalEngineering Development Program (PEDP) of Engineering Services.

    Warning: The material contained in this document was developed for SaudiAramco and is intended for the exclusive use of Saudi Aramcos

    employees. Any material contained in this document which is notalready in the public domain may not be copied, reproduced, sold, given,

    or disclosed to third parties, or otherwise used in whole, or in part,

    without the written permission of the Vice President, Engineering

    Services, Saudi Aramco.

    Chapter : Electrical For additional information on this subject, contact

    File Reference: EEX20305 W.A Roussel on 874-1320

    Engineering EncyclopediaSaudi Aramco DeskTop Standards

    Directing The Operation And Maintenance

    Of Electric Motors

  • 8/13/2019 Directing the o & m of Motors

    2/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards

    CONTENTS PAGES

    PREVENTIVE MAINTENANCE REQUIREMENTS....................................................1

    Minimum Annual Requirements................................................................................2Visual Inspection..................................................................................................2

    Bearing Inspection ...............................................................................................4

    Vibration Level Testing........................................................................................9

    Insulation Resistance (IR) and Polarization Index (PI) Testing .........................11

    Additional Requirements .........................................................................................13

    Motor Alignment................................................................................................13

    Motor Lubrication ..............................................................................................19

    Oil Lubricant Testing .........................................................................................20

    Inspection of RTDs ............................................................................................22

    Insulation Cleaning and Drying .........................................................................22

    Measure Bearing Insulation ...............................................................................25DETERMINING WHETHER MOTORS ARE FUNCTIONING PROPERLY ............29

    Motor Maintenance Record and Interpretation ........................................................29

    Insulation Resistance Data and Data Interpretation............................................31

    Vibration Level Data and Data Interpretation ....................................................32

    Maintenance History of Motors .........................................................................35

    DETERMINING THE CORRECTIVE ACTIONS FOR COMMON MOTOR

    PROBLEMS ..................................................................................................................37

    Vibration Alarms......................................................................................................37

    Temperature Alarms ................................................................................................39

    Winding Alarms.......................................................................................................40Bearing Alarms ..................................................................................................41

    Motor Trips ..............................................................................................................42

    Faults..................................................................................................................42

    Process Interlocks...............................................................................................43

    WORK AID 1: PROCEDURE AND ACCEPTABLE TEST VALUES

    (PERFORMED DURING MOTOR MAINTENANCE AND COMPILED

    FROM SADP-P-113, NFPA 70B, AND ESTABLISHED ENGINEERING

    PRACTICES) FOR DETERMINING WHETHER MOTORS ARE

    FUNCTIONING PROPERLY .......................................................................................44

    WORK AID 2: PROCEDURE FOR DETERMINING CORRECTIVE

    ACTIONS FOR COMMON MOTOR PROBLEMS (BASED ONESTABLISHED ENGINEERING PRACTICES) .........................................................48

    ADDENDUM ................................................................................................................56

  • 8/13/2019 Directing the o & m of Motors

    3/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 1

    PREVENTIVE MAINTENANCE REQUIREMENTS

    Electrical preventive maintenance consists of routine inspections, tests, and service on

    electrical equipment. The purposes of electrical preventive maintenance are:

    To reduce the hazards to life and property that can result from a failure of

    electrical equipment.

    To detect impending equipment trouble and to reduce or to eliminate

    unscheduled downtime of equipment and systems.

    The performance and the extent of an EPM program must be determined through a cost

    analysis of the performance of the EPM program versus the cost of nonperformance of the

    EPM program. An EPM program that will collectively cost more than the replacement of the

    equipment would not be cost-effective. The determination of the EPM programs content andof the frequency of program performance must consider the following items:

    The impact of the program on personnel safety.

    The potential for equipment loss or damage.

    The impact of the maintenance schedule on production.

    This section of the Module will present information on the following preventive maintenance

    requirements:

    Minimum Annual Requirements

    Additional Requirements

  • 8/13/2019 Directing the o & m of Motors

    4/58

  • 8/13/2019 Directing the o & m of Motors

    5/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 3

    The first part of the annual visual inspection is performed while the motor is in operation.

    The inspection should be performed through use of a look-listen-feel approach. The

    maintenance person should look at the motor to ensure that there is no physical damage to the

    motor or to the connected equipment. The operational parameters of the motor (amperes,

    voltage, and power factors) also should be observed to be within the established limits that are

    listed on the motors nameplate. The maintenance person should listen carefully to the

    sounds that the motor makes while it is in operation. A motor that is operating correctly will

    make a smooth, steady sound. Oscillations or unusual sounds can indicate a pending

    electrical or mechanical failure. The maintenance personnel also should feel the motor for

    excessive heat in the vicinity of the motor stator and the motor bearings (e.g., feel the stator

    case and end bells).

    The second part of the annual visual inspection is performed while the motor is deenergized.

    The following is a list of the general items to inspect while the motor is deenergized. (The

    manufacturers technical information should be consulted for specific requirements.)

    Inspect for water and for condensation on or in the motor.

    Inspect for rust and for corrosion on the connection boxes and seal points.

    Inspect for dirt, for dust, and for foreign objects on or around the motors

    ventilation ports.

    Inspect for proper anchors, mounts, grounds, and ground connections.

    Check the air gap at eight radial locations or at all poles of a synchronousmotor. Record this information. Excessive variation of the air gaps may

    suggest misalignment or excessive wear of the motors bearings.

    Inspect for signs of excessive heat such as charred or cracked insulation and

    discolored or blistered paint and varnish.

    Inspect the integrity of the electrical terminals.

    Inspect for frayed or worn insulation.

    Inspect the stator and the rotor coil insulation for thermal aging, cleanliness,and tightness of bracing.

  • 8/13/2019 Directing the o & m of Motors

    6/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 4

    Ensure that all fasteners are properly secured.

    Inspect for clogged rotor and stator ventilation ducts.

    If possible, inspect the end windings of the motor for dirt, dust, grease, oil, or

    other foreign material.

    DC motors require the following additional inspection items:

    Inspect the commutator surface for indications of faulty commutation and for

    high mica insulation between commutator segments..

    Inspect all brushes for satisfactory operation, for proper length, and for proper

    brush holder compression.

    Inspect for cleanliness in the commutator area. An excessive runout or an

    irregular commutator surface can generate excessive amounts of carbon dust in

    the commutator area. An excessive accumulation of carbon dust can contribute

    to flashovers.

    Inspect the brush fit in the brush box to ensure ease of movement of the

    brushes in the brushbox.

    The value that is obtained through performance of an annual visual inspection often is

    dependent on the mental approach that the inspector uses to perform the inspection. If the

    annual visual inspection is performed under the mental assumption that no problems exist, theinspector often will miss the subtle signs of potential problems; however, if the annual visual

    inspection is performed under the mental assumption that a problem does exist and that the

    purpose of the inspection is to identify the problem, the inspector is more likely to locate the

    signs of potential and existing problems.

    Bearing Inspection

    The complexity of the bearing inspection will depend upon the actual type of bearing and

    lubrication system that is installed. Anti-friction bearings that use a grease lubrication system

    require the least amount of maintenance of all the types of bearings that are used in SaudiAramco installations. Sleeve bearings that use an oil transfer system require the greatest

    amount of maintenance. The exact bearing inspection requirements should be in accordance

    with the manufacturers technical manual.

  • 8/13/2019 Directing the o & m of Motors

    7/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 5

    The first portion of an anti-friction bearing inspection is performed while the motor is in

    operation. This portion of the inspection involves listening for sounds such as squeals,

    screeches, and clicks that emanate from the bearings. Such sounds are usually a sign of

    improper lubrication or of a dirty bearing.

    After the motor is shut down, the bearing housing should be opened, and the bearing should

    be checked for proper lubrication (grease), signs of excessive heat, and indications of high

    currents across the bearing. On relatively small motors, the shaft should be checked for

    excessive endplay or for freeplay while the shaft is manipulated by hand. On motors that

    have shafts that are less than five inches in diameter, the shafts also should be rotated by

    hand. While the shafts on the motors are rotated, the inspector should feel for any hard points

    on the bearings.

    Anti-friction bearings that use grease for lubrication should have the bearing cleaned and

    should have the grease changed during the annual bearing inspection. Anti-friction bearingsthat use oil for lubrication should be inspected to ensure that the oil is clean and that the oil is

    at the proper level. If necessary, oil should be added to the bearing. The manufacturers

    technical manual should be consulted to ensure that the proper amount and the correct type of

    grease or oil is used.

    Sleeve bearings require more maintenance than anti-friction bearings because these bearings

    must be disassembled to allow an adequate inspection. The exact procedure for disassembly

    and for inspection of motor sleeve bearings should be in accordance with the motor

    manufacturers technical manual.

    After the bearing is disassembled, the bearing should be checked for unusual signs of wearand for signs of excessive heat. An exact check of bearing wear can be performed through

    measurement of the air gap around the rotor and through comparison of these measurements

    to the manufacturers specifications and to previous air gap measurements. The bearing also

    should be checked for signs of circulating currents that are evidenced by localized pitting or

    heating on the soft metal inner surface of the bearing. Large motors are provided with

    bearing pedestal insulation to prevent circulating currents; therefore, excessive bearing current

    would indicate a failure of the bearing insulation. The oil lubrication system also should be

    inspected to ensure that there is adequate oil flow to the bearing and to ensure that bearing

    temperatures are within specifications.

    The Electrical Engineer should be able to inspect the bearing and to identify the type ofbearing damage. This identification of damage is especially useful in cases of chronic

    (repetitive) bearing failures.

  • 8/13/2019 Directing the o & m of Motors

    8/58

  • 8/13/2019 Directing the o & m of Motors

    9/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 7

    The babbitt surfaces must be examined for evidence of the following unusual conditions:

    Rub marks in the top half of the bearing usually are a result of machine

    misalignment.

    Rub marks on the babbitted thrust faces are an indication of axial thrust loads.

    These rub marks usually result from improper axial alignment or from

    excessive shaft end play.

    The bearing should be checked for evidence of wiping or of pulling of the

    babbitt metal. This bearing wiping generally is the result of the bearing

    overload due to machine misalignment or due to machine vibration.

    The wear pattern on the babbitt surface of the bottom half of the bearing should

    be noted. The wear pattern should extend axially along the lower half of thebearing and should be centered on the bottom of the babbitt surface. The width

    of the wear pattern should be uniform from one end of the bearing to the other.

    Uneven wear patterns typically are due to improperly fitted bearings or are due

    to a bent shaft.

    The lower bearing babbitt should be checked for circumferential scratches.

    These scratches run perpendicular to the bearing wear marks and commonly

    are caused by foreign particles that pass through the oil film.

    The upper and lower halves of the bearing should be checked for general

    surface roughness. This roughness may be caused by abrasive particles in theoil.

    The journal surface should be checked for protruding sharp edges.

    The bearing surface should be checked for pitting. This pitting is normally due

    to corrosion, to careless handling, or to bearing currents.

    After the bearing surface inspection has been conducted, the bearing oil reservoirs should be

    drained and flushed.

  • 8/13/2019 Directing the o & m of Motors

    10/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 8

    Split Sections of a Sleeve Bearing

    Figure 1

  • 8/13/2019 Directing the o & m of Motors

    11/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 9

    Vibration Level Testing

    Vibration level tests are performed to check for excessive vibration or for changes in vibration

    that are above the established limits. All equipment that rotates will vibrate to some degree;however, changes in the vibration levels can be a sign of a pending malfunction. These

    abnormal vibration levels, if left unattended, can cause damage to the motor shaft, to the

    motor rotor, to the motor endbells, to the motor bearings, and to the other equipment that is

    connected to the motor.

    Different types of vibration must be considered when a vibration level test is performed.

    Because motors rotate in the radial plane and the axial plane, a complete vibration analysis

    must consider both vibrational planes. The number of test points that should be checked on a

    specific motor application should be based on the manufacturers recommendations, motor

    history, and instructions for technical services.

    The source of vibration can be identified through performance of a frequency analysis. The

    frequency analysis will identify the frequency at which the excessive vibrations occur. This

    frequency can then be used to determine the cause of the excessive vibration. The amplitude

    of the frequency will indicate the severity of the problem. The following is a list of the

    typical sources of vibration:

    Imbalance

    Misalignment

    Resonance

    Bearings

    Gears

    Vane Passing

    Fans

    Air gap eccentricity

    Cavitation

    Oil whirl

    Pipig

    Bent shaft and bowed rotor

    Looseness

    Belts and pulleys

  • 8/13/2019 Directing the o & m of Motors

    12/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 10

    Figure 2 shows a sketch of a motor and illustrates where the vibration measurements should

    be made. The axial plane of vibration is measured at two locations, the front end (AF) of the

    motor and the rear end (AR) of the motor. The radial plane of vibration is divided into two

    components: vertical and horizontal. The vertical component consists of VRand VFand thehorizontal component consists of HR and HF. Four vibration level measurements must be

    made in the radial plane: one at VR, one at VF, one at HR, and one at HF.

    Motor Vibration Measurements

    Figure 2

  • 8/13/2019 Directing the o & m of Motors

    13/58

  • 8/13/2019 Directing the o & m of Motors

    14/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 12

    The following steps can be used as a guide to insulation resistance testing:

    All leads of the motor should be connected together, and the insulation

    resistance should be recorded from the leads to ground. If the individual

    winding phase connections are accessible, each phase winding should be

    disconnected, and phase-to-phase measurements also should be taken.

    The insulation resistance check should be performed as soon as the motor is

    turned off and the motor windings are still hot.

    The insulation resistance test voltage should be determined by the voltage of

    the motor. A 500 volt handcrank instrument can be used for motors that are

    less than 600 volts. A 1000 volt or 2500 volt motor driven or rectifier type

    instrument should be used for motors of 2300 and 4000 volts. A 5000 volt

    megger should be used for 13.2 kV motors.

    Spot measurements should be conducted for 60 seconds.

    Ambient temperature and moisture should be recorded.

    All resistance values should be corrected to 50oC.

    The results of the 60 second spot measurement should be recorded on the

    maintenance form and should be compared to previous measurements.

    The Polarization Index (PI) is a ratio of the ten minute insulation resistance to the one minuteinsulation resistance. The following equation can be used to determine the Polarization Index

    (PI) of a motor.

    The value of the PI should be equal to or greater than two to be considered satisfactory.

  • 8/13/2019 Directing the o & m of Motors

    15/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 13

    Additional Requirements

    In some instances, the Electrical Engineer may determine that the minimum annual

    requirements do not provide sufficient data to determine if a motor is operating properly.This section provides additional tests that can be performed to obtain more specific data on

    motors. Prior to the performance of these preventive maintenance items, the Electrical

    Engineer must consider if the benefits that are derived from this maintenance are worth the

    additional cost. Sound engineering practices dictate that the following are advisable

    preventive maintenance items to be considered when extra maintenance data are desired:

    Motor Alignment

    Motor Lubrication

    Oil Lubricant Testing

    Inspection of RTDs

    Insulation Cleaning and Drying Measure Bearing Insulation

    Motor Alignment

    Many failures of motors and motor bearings can be attributed to a motor alignment problem.

    Motor misalignments often appear as other motor problems, such as bearing overheating,

    excessive bearing wear, motor overheating, excessive noise, and excessive motor vibration.

    Motor misalignment also can appear as problems with the connected load such as overheating

    of connected equipment and connected equipment bearing damage.

    The motor alignment should be checked whenever the following indications are present:

    The bearing temperature (of the motor or of the connected equipment)

    increases with no lubrication system problems.

    The motor air gap increases/decreases.

    The noise that is generated by the bearing (motor or connected equipment)

    increases.

    Motor or connected equipment vibration increases.

  • 8/13/2019 Directing the o & m of Motors

    16/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 14

    A straight edge, a feeler gauge, or a dial indicator can be used to check motor alignment

    through comparison of the motor shaft position to the load shaft position. Each instrument

    will check for a different type of motor misalignment. The straight edge will ensure that the

    motor shaft and the load shaft line up axially and will ensure that no lateral displacement has

    occurred. This method is especially useful for alignment of belt drives because the straight

    edge will contact the motor sheave and load sheave squarely when the motor and the load are

    properly aligned. Figure 3 illustrates the use of a straight edge for alignment of belt drives.

    Figure 3 shows one correct alignment of a belt drive and two incorrect alignments of belt

    drives. In the correct alignment, the straight edge is used to line up the sheaves of the motor

    and of the load. In the first incorrect alignment, the motor and the motor sheave are cocked in

    relation to the load sheave. The installation that is shown would produce rapid belt wear and

    would place an unnecessary combination load on the shaft of the motor.

    The second incorrect alignment shows that the motor and the load are not lined up in the axial

    direction. This type of installation would also produce rapid belt wear and would develop anunnecessary combination load on the shaft of the motor and the shaft of the load.

  • 8/13/2019 Directing the o & m of Motors

    17/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 15

    Alignment of Belt DrivesFigure 3

  • 8/13/2019 Directing the o & m of Motors

    18/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 16

    A feeler gauge can be used to check for an angular displacement between the motor shaft and

    the load shaft (the face of both shafts should meet). The dial indicator can be used to check

    for any type of rotational misalignment of the motor shaft and the load shaft. A rotational

    misalignment will usually be caused by a bend in one of the shafts.

    The most accurate method to use to check motor alignment is the dial indicator method. The

    dial indicator can be used to check angular misalignment and to check run out. Figure 4

    shows a motor shaft and a load shaft with the coupling hubs installed.

    The following steps can be used as a guide to check angular misalignment:

    The alignment of the motor and the load should be checked after the coupling

    hubs have been installed.

    The dial indictor base should be mounted to the side of one coupling hub (Hub1).

    The button of the dial indicator should be placed against the finished face of the

    other hub (Hub 2).

    A reference mark should be inscribed on Hub 2 to mark the position of the dial

    indicator button.

    Both shafts should be rotated simultaneously while the indicator button is kept

    on the reference mark on Hub 2.

    The dial indicator reading should be noted at each quarter revolution.

    The angular misalignment of the shafts will be indicated by a deflection of the

    dial indicator dial. The misalignment of the shafts should not exceed a total

    dial indicator reading of .001 for each one inch of radius of the coupling hub.

  • 8/13/2019 Directing the o & m of Motors

    19/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 17

    Angular Alignment

    Figure 4

    After the shafts have been checked for angular misalignment and are parallel within the limits

    that are specified, the shafts should be checked for run out to ensure concentricity of the

    shafts.

  • 8/13/2019 Directing the o & m of Motors

    20/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 18

    The following steps, in reference to Figure 5, can be used as a guide to check run out of the

    shafts:

    The dial indicator base should be mounted to one coupling hub (Hub 1).

    The dial indicator button should be placed on the machined diameter of the

    other hub (Hub 2). A reference mark (not shown in Figure 5) should be scribed

    on Hub 2 to mark the location of the indicator button.

    Both shafts should be rotated simultaneously while the indicator button is kept

    at the reference mark on Hub 2.

    The dial indicator reading should be noted at each quarter revolution.

    The run out between the hubs will be indicated by a deflection of the dialindicator dial. The total run out between the hubs should not exceed .002 inch.

    Run-Out

    Figure 5

  • 8/13/2019 Directing the o & m of Motors

    21/58

  • 8/13/2019 Directing the o & m of Motors

    22/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 20

    The lubrication of antifriction bearings and sleeve bearings with oil is a continuous function;

    therefore, only a periodic inspection of the oil system is required. The inspection of the oil

    system depends on the complexity of the oil system. As a minimum, however, the following

    items should be checked:

    That the oil level in the oil level indicators is in the normal range. If the oil is

    out of the normal range, the proper type of oil should be added.

    That the oil flow indicators on circulating oil systems indicate proper oil flow.

    If improper oil flow is noticed, the circulating oil system should be investigated

    to determine the cause of the lack of oil or of the loss of oil flow.

    Oil pressure indicators on forced-flood oil lubrication systems should be

    checked to verify that the oil pressure to the bearing is in the normal range.

    Under normal operating conditions, the lubricating oil will not need to be changed over a two

    year period. However, if the annual oil lubricant tests identify foreign particles in the oil or

    contamination of the oil, the oil system needs to be drained, flushed, and refilled with the

    proper lubricant.

    Oil Lubricant Testing

    Oil lubricant testing is performed to ensure that the oil is free from contamination and that the

    oil still performs as a lubrication agent. Over time, all lubricants will chemically break down

    and will eventually cease to effectively lubricate. A test of the oil will help to identify any

    potential lubrication problems prior to failure.

    Two types of tests are performed on oil lubricants: a simple foreign material contamination

    test and a complex chemical analysis of the lubricant. The foreign material contamination test

    is performed to ensure that contaminants such as water, sand, or other foreign material have

    not entered the lubricant. The presence of any foreign material could cause damage to the

    bearing. The chemical analysis checks for a breakdown of the lubricant on a molecular level

    and includes an analysis of viscosity and of viscosity index to determine if there have been

    any changes in the performance of the lubricant. The chemical analysis should be performed

    in a laboratory.

  • 8/13/2019 Directing the o & m of Motors

    23/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 21

    The foreign material contamination test is easy to perform in the field. A sample is drawn

    from the oil lubrication system and then the lubricant is allowed to settle. Once the oil has

    settled, it should be inspected for any foreign material. This test should also include a check

    of the level of the oil in the oil reservoir or in the bearing to verify that the level is correct.

    Because the chemical analysis is performed in a laboratory environment, the exact procedures

    for the chemical analysis are beyond the scope of this module. The oil lubricant sample

    should be obtained from the motor and then the sample should be sent to a laboratory facility

    for testing.

    The foreign material contamination test should be done on a quarterly basis or more often if

    experience shows that the motor has a history of contamination problems. The oil lubrication

    chemical analysis is done less often but should be done at least every six months. The oil in a

    oil lubrication system should be changed every one or two years.

    The periodicities of the oil tests can be changed based on the history of the motor. Prior toany change in oil lubrication test frequencies, the following items should be considered:

    The average temperature of the lubricant.

    The likelihood and the severity of bearing overloads.

    The likelihood that contaminants will enter the system.

    If the temperature of the bearing lubricant has been operating in the upper portion of the

    lubricants temperature range, the lubricant should be tested more often. If the temperature of

    the lubricant has exceeded its normal operational range, the lubricant should be immediately

    tested. Follow-up testing of the oil should occur weekly for the next month.

    If the bearing is subjected to periodic overloads or to cyclic overloads, the periodicity of the

    oil tests should be reduced.

    If there is a high likelihood that contaminants will enter the oil system, or if the oil system has

    a history of contamination, the oil tests should be scheduled on a more frequent basis.

    Decreased oil test periodicity does not remove the responsibility for determination of the

    cause of contamination or for elimination of the source of the contaminants.

  • 8/13/2019 Directing the o & m of Motors

    24/58

  • 8/13/2019 Directing the o & m of Motors

    25/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 23

    Several methods can be used to clean motor insulation. The most effective method depends

    upon the type of dirt and upon the amount of dirt that are lodged on the insulation. The

    methods that can be used to clean motor insulation are listed below in the order of preference:

    Dry wiping

    Brush or suction cleaning

    Blowing

    Solvent cleaning

    Water, emulsion, and alkali cleaning

    Shell blasting

    Dry wiping should be used to remove dry dirt from the surfaces of insulation that are located

    in accessible areas. Dry wiping is performed through use of clean, dry, lint free cloths. Non-

    lint free cloths should not be used because the lint will adhere to the insulation and will

    increase the dirt collection. Lint is particularly objectionable on high-voltage insulationbecause the lint tends to cause a concentration of corona discharge.

    Brush or suction cleaning also should be used to remove dry dust and dirt from the surfaces of

    insulation that are located in accessible areas. The dry dust and dirt should be removed by

    brushing with bristle brushes and then vacuum suction cleaning. Wire brushes should not be

    used. Brush or suction cleaning is a desirable method to clean insulation because the dirt is

    not scattered and the dirt does not settle on other apparatus. The use of this cleaning method

    is limited to accessible areas that can be reached by the brush and the vacuum.

    Blowing out dirt with a jet of air only should be done to remove dirt from inaccessible

    crevices and only when the motor is dry. Blowing is performed through use of drycompressed air (30 psi or less) and vacuum suction. A vacuum suction is connected to one

    end of the motor, and the compressed air is directed into the other end of the motor. The air

    should be directed in a manner that will dislodge the dirt from the insulation and will allow

    the vacuum suction to draw the dirt out of the motor.

    Solvent cleaning is particularly effective for removal of tar, grease, wax, and oil from

    electrical apparatus. The surfaces should be wiped with a cloth that is wet with the solvent,

    and then the surfaces should be wiped with a dry cloth. To avoid lint deposits on the

    insulation, non lint free rags should not be used. If solvents are used on windings with

    silicone rubber or with an abrasion resistant coating, severe damage to the coating can occur.

    The manufacturers technical manual should be consulted for the solvent that should be usedfor insulation cleaning.

  • 8/13/2019 Directing the o & m of Motors

    26/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 24

    Motors can be cleaned by hose washing or by pressure spray from a steam generator. Steam

    from a shop line or a spray of hot water and compressed air may be used. When insulation is

    cleaned through use of this method, the jet pressure and temperature should not exceed 30 psi

    and 80C (176F), respectively. To remove tar, wax, grease, or oil from insulation, a

    nonconductive detergent compound must be added to the water. These detergent compounds

    contain non-ionic emulsifying agents.

    Emulsion cleaners also contain solvents to soften hard deposits so that these deposits can

    more easily be removed. These detergent compounds are not electrical conductors and are

    safe for use on insulation. After the deposits have been removed, the motor windings should

    be thoroughly rinsed with water to remove all traces of the cleaning compound. The water

    should then be promptly removed from the motor windings through use of air pressure and

    lint free rags.

    Shell blasting is the process of air blasting with ground nut shells to remove hard dirt depositsfrom insulation. Shell blasting may abrade the insulation and should only be performed under

    the direction and supervision of the manufacturer.

    In Saudi Aramco, solvent cleaning, water/emulsion/alkali cleaning, and shell blasting are not

    recommended for field maintenance. Motor windings with heavy oil and dirt contamination

    must be sent to Dhahran shops for cleaning.

    The best method for use in cleaning a given motors insulation should achieve the following

    objectives:

    The method should be able to remove the type of dirt that is present.

    The method should cause the least amount of insulation damage.

    The manufacturer should be consulted when there is a doubt as to the best method of

    insulation cleaning.

    The motor windings can be dried after they are cleaned through the use of external heat or

    through the circulation of current through the windings. The use of resistance heaters or

    steam coils is advisable when external heat is to be applied to the motor. Because the space

    heaters that are located inside of the motor are not of sufficient capacity for use in drying the

    motor windings, additional heaters are required. The additional heaters should be placed nearthe bottom of the motor, and care must be taken to protect the windings against direct heat

    radiation from the heaters.

  • 8/13/2019 Directing the o & m of Motors

    27/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 25

    A dc welding set can be used to heat the motor windings through use of the circulation of

    current in the windings. The current that is circulated in any part of the winding should not

    exceed the rated current value of the motor.

    Motor windings cannot effectively be dried unless means are provided to circulate air through

    the motor to remove the moisture. Openings must be provided near the bottom of the motor

    for the entry of fresh air, and openings must be provided near the top for the discharge of the

    heated moist air. A small fan might be necessary to provide assistance in the circulation of

    air.

    Regardless of the method that is chosen to dry the motor windings, the heat to dry the motor

    windings must be applied gradually to allow the water vapor that is produced to travel out

    through the insulation. A rapid application of heat could cause steam pressure to rupture the

    insulation; such as a rupture would permanently damage the insulation.

    Measure Bearing Insulation

    The bearing insulation is tested to ensure that the bearing pedestal has sufficient dielectric

    strength to resist the flow of current through the bearing to ground. Bearing insulation that

    does not have sufficient dielectric strength will allow current to flow in the bearing; such

    current flow has a destructive effect on the shaft journals and the bearings.

    Bearing insulation consists of placement of a non-conductive sheet barrier between the

    bottom of the bearing pedestals and the sole plates. Care must be taken to ensure that all

    hold-down bolts, dowels, and oil piping are insulated from the pedestal. Figure 6 shows an

    insulated bearing pedestal. The bearing pedestal rests on the sole plate and is insulated from

    the sole plate through use of a micarta insulation strip. All dowel pins and hold-down bolts

    are insulated with micarta tubes to prevent a short circuit between the pedestal and the sole

    plate.

  • 8/13/2019 Directing the o & m of Motors

    28/58

  • 8/13/2019 Directing the o & m of Motors

    29/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 27

    Ball-type bearings also can be insulated through placement of an insulating material between

    the outer race of the motor bearing and the motor housing end shield. Figure 7 shows an

    expanded view of an end-shield type bearing with a sleeve insulator. When the bearing is

    constructed, a non-conductive insulating sleeve is molded to the motor bearing. After the

    insulating sleeve is molded, the sleeve is machined into the motor housing end shield. The

    combination bearing/insulating sleeve is press-fitted into the motor housing end shield. The

    insulating sleeve that is bonded to the motor bearing electrically isolates the rotor

    shaft/bearing from the motor housing end shield. Such electrical isolation prevents the flow

    of current through the bearing to ground.

    Bearing insulation is tested through use of a megger. The megger is connected between the

    motor shaft and ground. After the megger is connected, a test voltage of 500V is applied

    between the motor shaft and ground. The test voltage is applied for one minute, and at the

    end of one minute, the bearing insulation resistance is read from the meter that is on the face

    of the megger.

    End Shield Type Bearing with Sleeve Insulator

    Figure 7

    The bearing insulation test is performed to ensure that the insulation material has not been

    damaged or short circuited. The test will also verify that no external or control device has

    bridged the bearing insulation. It is possible to bridge the insulation gap when external

    equipment such as metal oil ports or supports are attached to the motor.

  • 8/13/2019 Directing the o & m of Motors

    30/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 28

    The following are the general steps that are necessary to verify the integrity of the bearing

    insulation:

    Uncouple the shaft from connected equipment.

    Disconnect the ground strap at the base of the pedestal.

    Disconnect all temperature monitoring equipment.

    Megger the insulation that is between the bearing housing and ground.

    The test results are considered unsatisfactory if the insulation measures less than 200k ohms;

    however, the desired insulation value is one megohm. Before the pedestal insulation is

    considered defective, all other sources of a short circuit must be eliminated. These sources

    include but are not limited to the following items:

    Uninsulated pipes that touch both the pedestal and sole plate.

    Guard rails in contact with the pedestal.

    Tools, ladders, or other equipment in contact with the pedestal.

    Pumps or other equipment that are geared or coupled to the motor.

    Other items that should not be overlooked are good housekeeping measures. Tools or other

    miscellaneous items are often the cause of low insulation measurements.

  • 8/13/2019 Directing the o & m of Motors

    31/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 29

    DETERMINING WHETHER MOTORS ARE FUNCTIONING PROPERLY

    Determining whether motors are functioning properly is one of the major tasks involved in

    equipment management. The Electrical Engineer must be able to evaluate motor maintenancerecords to determine if the motor is functioning properly. To determine if the motor is

    functioning properly, the Electrical Engineer must compare motor maintenance values against

    the acceptable limits and against the normal operational values. More importantly, the

    Engineer must be able to recognize trends that indicate a deterioration of the motors

    operation. Many times a motor will show early signs of a pending failure through trends, and

    if the Electrical Engineer learns to recognize these trends, major equipment failures can be

    averted.

    Motor Maintenance Record and Interpretation

    Motor maintenance record forms contain the information and the data that are obtained from

    motor testing. The Motor Maintenance Record is a two-part form. Part I of this form

    contains the motor identification data and a record of the insulation resistance test data and the

    vibration test data. Part II of this form is a record of the work that was performed on the

    motor over the motors life. As Figure 8 shows, Part I of the Motor Maintenance Record is

    divided into the following four areas:

    The Motor Identification Data

    The 60 Second Insulation Resistance Graph

    The Insulation Resistance Data

    The Vibration Level Data

    The first section of the Record Motor Maintenance Record contains the following data for

    motor identification:

    Make

    Type

    Serial No.

    Voltage

    Amps

    Frequency

    Speed Rating (hp/kW)

    S.F.

    Insulation Class

    Location

    Date Installed

    Description of Duty

  • 8/13/2019 Directing the o & m of Motors

    32/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 30

    Motor Maintenance Record (Part I)

    Figure 8

  • 8/13/2019 Directing the o & m of Motors

    33/58

  • 8/13/2019 Directing the o & m of Motors

    34/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 32

    The temperature of the motor windings also should be measured and recorded in the

    appropriate block on the form. The temperature of the motor windings can be measured

    through use of the RTDs that are installed in the motor If the motor does not have installed

    RTDs, temporary temperature probes that are inserted into the motor housing are used. The

    temperature of the motor windings is then used to calculate the temperature corrected, 60

    second phase-to-ground IR measurement. The equation for use in temperature correction of

    IR measurements is located in Work Aid 1.

    The temperature corrected, 60 second phase-to-ground IR measurement and the calculated

    phase-to-ground polarization index should be compared to the minimum acceptable values

    and to the previously recorded values to determine whether these values are acceptable.

    Work Aid 1 contains the minimum acceptable values for IR and for PI.

    On motors that have accessible phase connections, the phase-to-phase insulation resistance

    should be measured and should be recorded for all possible phase combinations. A one-minute and a ten-minute insulation resistance measurement should be recorded for each phase

    combination. Through use of the one-minute and the ten-minute phase-to-phase insulation

    resistance measurements, the phase-to-phase Polarization Index (PI) can be calculated. The

    one-minute, the ten-minute, and the PI measurements should be compared to the minimum

    acceptable values and to the previous readings to ensure that the values are acceptable. Work

    Aid 1 provides the minimum acceptable values for IR and for PI.

    Vibration Level Data and Data Interpretation

    The vibration level of the motor should be determined through use of installed probes or

    through use of temporary vibration probes, and the vibration level data should be recorded in

    the Vibration Levels Data section of the form. The vibration level for both the drive end

    bearing and for the non-drive end bearing should be recorded. The level of vibration should

    be compared to the minimum acceptable values and to the previous values. Any changes in

    the vibration level could be a signal of pending trouble and should be investigated. A trend of

    an increase vibration could indicate wear on the motor bearings and would warrant further

    investigation.

  • 8/13/2019 Directing the o & m of Motors

    35/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 33

    Figure 9 is a typical vibration level trend chart that shows a graph of vibration level (in in/sec)

    with time (in months). This graph shows a relatively constant vibration level from January of

    1986 to November of 1986. Such a graph is consistent with normal motor operation. The

    graph also shows a sharp rise in the vibration levels for two consecutive months: December

    of 1986 and January of 1987. Such a rise indicates that a problem has developed and that the

    problem is getting worse. If this problem is not corrected, it eventually will lead to a

    breakdown as shown by the dotted line on the graph. Warning time and repair level, also

    shown in Figure 9, illustrate the use of trend analysis in directing the operation and

    maintenance of electric motors. Through establishment of a repair level that is below the

    breakdown level, a sufficient amount of warning can be provided to schedule corrective

    maintenance before a failure occurs.

    The point at which a breakdown will occur can be predicted from experience with a similar

    machine or from vibration standards. Work Aid 1 contains the maximum acceptable vibration

    levels for Saudi Aramco motors. The value that is displayed on the graph in Figure 9 is anoverall value that represents the energy content of all the vibration frequencies.

    Trend Chart

    Figure 9

  • 8/13/2019 Directing the o & m of Motors

    36/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 34

    Vibration level measurements indicate the magnitude of the vibration, but these

    measurements do not indicate the source or the cause of the vibration. A narrow band

    frequency analysis should be performed through use of a vibration spectrum, shown in Figure

    10, to determine the exact source of the vibration. Figure 10 shows a frequency spectrum

    graph of acceleration (in gs) versus frequency. The graph shows low values of acceleration

    at the lower frequency ranges and higher values of acceleration at the higher frequency

    ranges. These higher values indicate problem areas, and these frequencies can be pin-pointed

    to specific sources of vibration.

    The analysis of the vibration spectrum is beyond the scope of this Module. If a problem is

    identified through use of trend analysis, a narrow band frequency analysis should be

    performed by the appropriate personnel.

    Typical Vibration Spectrum

    Figure 10

  • 8/13/2019 Directing the o & m of Motors

    37/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 35

    Maintenance History of Motors

    As Figure 11 shows, Part II of the Motor Maintenance Record is divided into the following

    sections:

    Motor Identification Data

    Description of Preventive and Corrective Maintenance Performed

    The Motor Identification Data for Part II of the Motor Maintenance Record are the same as

    previously discussed for Part I of the Motor Maintenance Record. The identification data are

    duplicated so that the motor to which the information pertains can be identified if the forms

    become separated. Part II of the Motor Maintenance Record is a narrative of the preventive

    and corrective maintenance that is performed on the motor. The results of all inspections and

    tests that are performed on the motor should be recorded in this section.

    The information that is recorded in this section will allow others to better understand themaintenance history of the motor. The following are examples of the types of information

    that are placed in the Description of Preventive and Corrective Maintenance Performed

    section:

    Results of the visual inspection.

    Results of the bearing inspection.

    Results of the RTD inspection.

    Motor alignment data.

    Dates and methods of insulation cleaning and drying.

    Signs of abnormal operation.

    Corrective troubleshooting.

    Corrective maintenance.

    A list of parts that were replaced or that were refurbished.

    Any pertinent data that will help in future maintenance activities.

  • 8/13/2019 Directing the o & m of Motors

    38/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 36

    Motor Maintenance Record (Part II)

    Figure 11

  • 8/13/2019 Directing the o & m of Motors

    39/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 37

    DETERMINING THE CORRECTIVE ACTIONS FOR COMMON MOTORPROBLEMS

    In addition to being able to identify motor problems, the Electrical Engineer must be able todetermine the proper corrective actions for the identified problems. If the wrong corrective

    actions were taken, the problem could be compounded, and the damage to the motor could

    escalate. This section of the module will discuss common motor problems and the corrective

    action for each problem. The corrective actions that are presented are by no means the only

    method to solve the problem. Determination of the appropriate corrective actions for a

    specific problem must be accomplished through use of manufacturers troubleshooting guides

    and the Electrical Engineers knowledge and experience. The following common motor

    problems and their corrective actions are discussed in this section:

    Vibration Alarms

    Temperature Alarms Motor Trips

    Vibration Alarms

    A sudden and significant increase in vibration amplitude is a very apparent indicator that

    something is wrong with a motor. A gradual increase in vibration amplitude may not be

    noted until damage occurs. Vibration monitoring equipment is installed on motors above 185

    kW

    (250 Hp) to alert personnel to abnormal vibration levels so that action can be taken to correct

    the problem before damage occurs. The vibration limits of motors are set so that the motoralarms or shuts down prior to serious damage to the motor. Motors below 185 kW (250 hp)

    are not equipped with vibration monitoring equipment and must be monitored by experienced

    personnel to judge changes in vibration levels.

    The vibration alarm and shutdown setpoints depend on the speed of the motor and the type of

    vibration probe that is installed. Figure 12 shows the recommended vibration alarm and

    shutdown setpoints for motors with various speeds and vibration monitoring probes.

    The variations in alarm and shutdown levels occur because different speed motors will

    naturally vibrate at different levels. The changes in alarm and shutdown levels for different

    types of vibration probes occur because of the difference in the accuracy of the probes.

  • 8/13/2019 Directing the o & m of Motors

    40/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 38

    Vibration Alarm and Shutdown SetpointsFigure 12

  • 8/13/2019 Directing the o & m of Motors

    41/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 39

    Vibration alarms are symptoms for a variety of motor problems. The following are examples

    of problems that can cause vibration alarms:

    Loose mounting bolts

    Loose coupling

    Motor and load misalignment

    Worn motor bearings

    Mechanically unbalanced load

    Mechanically unbalanced rotor

    Bent or cracked shaft

    Excessively pulsating load

    Out of synchronism (synchronous motor only)

    The corrective action for a vibration alarm will depend on the root cause of the vibration

    alarm. In the case of an alarm, the motor should be stopped immediately to prevent excessivedamage to the motor or to the surrounding equipment. The possible causes of a vibration

    alarm should be investigated one at a time. The most common problems should be

    investigated first. Common problems can be found through a review of the Motor

    Maintenance Record form. Items such as loose bolts, loose couplings, or misalignments also

    are considered common problems. Work Aid 2 contains a procedure for troubleshooting a

    vibration alarm. Possible corrective actions for some of the possible causes also are provided

    in Work Aid 2.

    Temperature Alarms

    The goal of a temperature alarm is to stop a motor when a motor-related high temperature

    condition exists. When properly applied, the high temperature alarm will trip a motor before

    the high temperature condition can cause damage. The following types of temperature alarms

    are associated with motors:

    Winding Alarms

    Bearing Alarms

  • 8/13/2019 Directing the o & m of Motors

    42/58

  • 8/13/2019 Directing the o & m of Motors

    43/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 41

    The temperature alarm or the trip settings will be dictated by the insulation class of the motor.

    The alarm or the trip setting will always be lower than the maximum allowable insulation

    temperature to ensure that no damage occurs to the winding insulation. The motor alarm/trip

    setpoints should be in accordance with the following:

    Motor Alarm or Maximum Allowable

    Insulation Class Trip Setting Insulation Temperature

    degrees C degrees C

    B 120 130

    F 145 155

    H 170 180

    Work Aid 2 contains common winding temperature problems and a course of corrective

    actions for each problem. The corrective actions for each of the possible causes of windingtemperature alarms are different. The proper action to be taken to correct the problem will

    depend upon the root cause of the winding temperature alarm.

    Bearing Alarms

    Bearing alarms are provided to protect the bearings from damage that can be caused by

    excessive temperatures. Excessive heating of a bearing will cause a rapid deterioration of the

    bearing and the bearing lubrication, and such deterioration can lead to a rapid failure of the

    motor.

    Excessive bearing temperatures, although detrimental to the bearings, are generally only a

    symptom of a larger problem. An investigation must be performed to correct the root cause

    of the bearing alarm as well as to repair the bearing, if necessary. The following are some of

    the causes of bearing alarms:

    Loss of lubrication flow

    Motor out of alignment

    Dirt in lubrication system

    Overlubrication of grease lubricated bearings

    Overload on motor

    Old bearings Incorrect bearings

    Bearing alarms must be set to respond at a temperature that is lower than the temperature at

    which bearing damage will occur. The maximum temperature that a bearing can withstand

    without damage will depend on the type of bearing that is installed.

  • 8/13/2019 Directing the o & m of Motors

    44/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 42

    The maximum temperature and bearing alarm setpoints should be as follows:

    Maximum Allowable Bearing

    Alarm and Temperature ino

    C based onBearing Type Trip Setting in oC a 40oC rise above ambient

    Anti-Friction 82 92

    Sleeve 80 90

    The proper corrective action for bearing alarms will depend on the root cause of the bearing

    alarm. In general, the first priority is to stop further heating of the bearing. The next step is to

    cool the bearing. The bearings will start to cool as soon as the motor is tripped or as soon as

    the load is removed from the motor. Motors will automatically trip on a bearing alarm to help

    prevent further heating of the bearings. After the immediate corrective actions have been

    taken, the next step is to determine the cause of the problem and to correct the situation. Afterthe root cause of the problem has been corrected, the bearing and motor shaft should be

    inspected. Work Aid 2 presents some of the possible causes of bearing alarms and a course of

    corrective action for each possible cause.

    Motor Trips

    Motor trips are installed to prevent damage to the motor or to the system due to undesirable

    motor or system conditions. Motor trips are divided into two main categories:

    Faults Process Interlocks

    Faults

    Motor trips are installed to protect against electrical system faults and against mechanical

    faults. The type of motor trip that is provided depends on the specific motor installation. The

    following is a list of the possible motor trips:

    Motor overload

    Phase overcurrent

    Ground fault Current unbalanced

    Vibration

    Temperature alarm

    Phase-to-phase fault

  • 8/13/2019 Directing the o & m of Motors

    45/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 43

    If a motor trip occurs, the Electrical Engineer must use all available indications to analyze the

    cause of the motor trip. On very large motors, alarm panels are provided that make the

    troubleshooting procedure much easier. Smaller motors or motors without alarm panels

    require more thought and troubleshooting skills. Ground faults and phase-to-phase faults

    quickly can result in motor winding insulation break down. Lockout relays (86 devices) are

    used in conjunction with the relays that detect ground faults and phase-to-phase faults to limit

    the motor damage that can be caused by these faults. Because lockout relays must be

    manually reset after they operate, these relays force maintenance personnel to investigate the

    cause of the problem prior to re-energization of the motor. Correct determination of the cause

    of the motor trip is vital in the recovery of the motor. An Electrical Engineer must use his

    knowledge and common sense to analyze the cause of a motor trip. Many times, the obvious

    signs can be overlooked because they seem too simple. Work Aid 2 provides a procedure

    to guide the Engineer in troubleshooting. Work Aid 2 also provides a list of the common

    motor problems and their possible causes. In addition to the troubleshooting guides, the

    Engineer should also obtain the maintenance records and the manufacturers troubleshootingguides for the motor.

    The corrective actions that must be taken for a motor trip will depend on what causes the relay

    to actuate. Different corrective actions must be performed for the different causes of relay

    trips. The wrong actions could cause more harm than good. Each set of corrective actions is

    different, but all corrective actions have the same goal. The goal of corrective actions is to

    prevent further damage to the motor until the motor fault is cleared and the motor is repaired.

    The first step in any motor trip corrective action will be to turn off the motor to ensure that the

    motor will not accidentally restart if the relay resets. Work Aid 2 contains the possible

    courses of action for each possible cause of a motor trip.

    Process Interlocks

    The second category of motor trips is process interlocks. Process interlocks are provided to

    control a system and are not provided to protect the motor; therefore, when a motor trips or

    fails to start due a process interlock, the motor control circuit is operating properly. In some

    instances, these process interlocks are confused with a motor problem and delay the recovery

    process. The Engineer must be fully aware of the motors start and stop permissives prior to

    troubleshooting the motor circuit.

    Process interlock trips are varied and depend on the different systems in which motors areinstalled. Process interlocks can be associated with system pressure, temperature, level, or a

    multitude of other parameters. When a motor trips or fails to start, the process interlocks

    should be the first step of the troubleshooting process. Indications of all these parameters

    should be readily available. An example of a process interlock that operates during normal

    operation is a motor that trips after the pump that is driven by the motor fills a storage tank.

    Although the motor tripped, the trip was an expected event, and no further investigation is

    required.

  • 8/13/2019 Directing the o & m of Motors

    46/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 44

    WORK AID 1: PROCEDURE AND ACCEPTABLE TEST VALUES (PERFORMEDDURING MOTOR MAINTENANCE AND COMPILED FROMSADP-P-113, NFPA 70B, AND ESTABLISHED ENGINEERING

    PRACTICES) FOR DETERMINING WHETHER MOTORS AREFUNCTIONING PROPERLY

    Use this Work Ai d to complete Exercise 1.

    Procedure

    Perform the following steps to determine if the motor is operating properly.

    1. Temperature correct the insulation resistance values.

    2. Compare the insulation resistance values to the minimum acceptable insulationresistance values and to the previously measured insulation resistance values to

    determine whether the current insulation resistance values are acceptable.

    3. Calculate the polarization index (PI) and compare this PI to the minimum acceptable

    PI to determine whether the current value is acceptable.

    4. Compare the current vibration level measurements to the maximum allowable

    vibration levels to determine whether the current motor vibration levels are acceptable.

    5. Review the narrative portion of the Motor Maintenance Record to determine whether

    the motor has other discrepancies that require corrective action.

    Technical Requirements

    Insulation Resistance Test - If IR is below the minimum acceptable level, the motor insulation

    should be cleaned and dried.

    The minimum acceptable insulation resistance value is determined from the following

    equation:

    RM = 1 megohm per kV of motor rated voltage plus 1 megohm

    where: RM = Minimum insulation resistance in megohms at 50oC

    kV = Rated voltage of the motor in kilovolts

    Any rapid drop in the IR value, even if the IR is still above the minimum value, is considered

    unacceptable.

  • 8/13/2019 Directing the o & m of Motors

    47/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 45

    Polar ization Index

    Minimum acceptable polarization index - 2:

    Temperature Correction of IR

    Use the following equation to temperature correct insulation resistance values:

    RC= KTx RT

    where: R C = Insulation resistance in megohms, corrected to 40oC

    RT = Measured insulation resistance, in megohms, at winding temperature T

    KT = Insulation resistance temperature correction factor

    To find KT, use Figure 14, Insulation Resistance Variation with Temperature.

  • 8/13/2019 Directing the o & m of Motors

    48/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 46

    Insulation Resistance Variation with TemperatureFigure 14

  • 8/13/2019 Directing the o & m of Motors

    49/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 47

    Vibration Level Measurement

    The maximum allowable vibration levels for motors with seismic velocity transducers is 4.6

    mm/s (0.18 in/s) zero to peak.

    The maximum allowable vibration levels for horizontal motors with proximity probes are as

    follows:

    3600 rpm - 2 mils

    1800 rpm - 2.5 mils

    1200 rpm - 3 mils

    or less

    If the maximum vibration level is exceeded, the cause should be investigated and should be

    corrected.

  • 8/13/2019 Directing the o & m of Motors

    50/58

  • 8/13/2019 Directing the o & m of Motors

    51/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 49

    Troubleshooting Chart for Common Motor Problems

  • 8/13/2019 Directing the o & m of Motors

    52/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 50

  • 8/13/2019 Directing the o & m of Motors

    53/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 51

  • 8/13/2019 Directing the o & m of Motors

    54/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 52

  • 8/13/2019 Directing the o & m of Motors

    55/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 53

  • 8/13/2019 Directing the o & m of Motors

    56/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 54

  • 8/13/2019 Directing the o & m of Motors

    57/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    Saudi Aramco DeskTop Standards 55

    anti friction bearing A bearing that employs an assembly of balls or rollers forrotation

    babbitt Soft metallic lining material of a sleeve bearing.

    bearing race The portion of an antifriction bearing that is connected to theshaft or bearing housing and that allows the ball bearing to

    rotate.

    corrective maintenance The maintenance that is carried out after a failure has occurred.This maintenance is intended to restore an item to a state in

    which it can perform its required function.

    endplay The amount by which the shaft of a motor can move in the axial

    direction.

    freeplay The amount by which the shaft of a motor can move in the radialdirection.

    gs Acceleration that is due to the force of gravity.

    Insulation Resistance (IR) The resistance that is offered by an insulation to the flow ofcurrent that results from an impressed direct voltage.

    Polarization Index (PI) The ratio of the ten-minute insulation resistance measurement to

    the one-minute insulation resistance measurement.

    preventive maintenance The maintenance that is intended to prevent or to reduce theprobability of failure or the performance degradation of an item.

    This maintenance is carried out at predetermined intervals,

    according to prescribed criteria.

    resistance temperature A temperature monitoring device that works on the principle ofa change in resistance as the temperature changes.

    service factor (SF) A multiplier that, when applied to the rated power, indicates thepermissible power loads that can be carried by a motor.

    sleeve bearing A bearing with a cylindrical inner surface in which the journal ofa rotor shaft rotates

  • 8/13/2019 Directing the o & m of Motors

    58/58

    Engineering Encyclopedia Electrical

    Directing the Operation and Maintenance

    of Electric Motors

    ADDENDUM

    Topographic Map of McCamey North, Texas

    Topographic Map of Mc Elroy Ranch, Texas

    Topographic Map of Tatum, New Mexico - Texas

    Design Basis Scoping Paper