Direct Digital Control System Index of Drawings Sheet# Description 1 Title and Cover Page 2 Supervisory Controller 3 FCU Wiring 5 AHU Flow Diagram 6 AHU 1 Wiring Diagram Cover Page Pittsburgh Air Systems, Inc. 208 Bilmar Dr Pittsburgh, PA 412.539.1234 412.539.1245 F www.PittsburghAirSystems.com 06/04/2013 11" x 17" CHECKED BY DRAWN BY REV J. Konley B. Woods 1 SCALE NONE Job# SHEET 1 of 13 7 AHU 2 Wiring Diagram 9 Boiler Panel 10 Boiler Panel Expansion 11 Wireless Temperature Monitoring 12 First Floor Layout 13 Basement Layout 4 FCU Sequence of Operation 8 AHU 1 & 2 Sequence of Operation

Transcript of Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital...

Page 1: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

Direct Digital Control System

Index of DrawingsSheet# Description1 Title and Cover Page2 Supervisory Controller3 FCU Wiring

5 AHU Flow Diagram6 AHU 1 Wiring Diagram

Cover Page

Pittsburgh Air Systems, Inc.

208 Bilmar DrPittsburgh, PA

412.539.1234 412.539.1245 Fwww.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REVJ. Konley B. Woods 1

SCALE NONE Job# SHEET 1 of 13

7 AHU 2 Wiring Diagram

9 Boiler Panel10 Boiler Panel Expansion11 Wireless Temperature Monitoring12 First Floor Layout13 Basement Layout

4 FCU Sequence of Operation

8 AHU 1 & 2 Sequence of Operation

Page 2: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

NOTES:BUS DEVICES ARE NOT LOCATION OR ORDER SPECIFIC ON NETWORK BUS.COMMUNICATION BUS WIRE MUST BE 22 AWG, 3 CONDUCTOR, TWISTED SHIELDED AND RATED FOR 78K BAUD.END DEVICES ON BACnet BUS MUST HAVE NETWORK TERMINATOR.KEEP ALL COMMUNICATION WIRING AWAY FROM LINE VOLTAGE.INSTALL END OF LINE TERMINATORS AT EACH END OF BACnet COMMUNICATION TRUNK

QTY. TAG PART NO. DESCRIPTION

4 E.O.L MS-BACEOL-0 BACnet NETWORK END OF LINE TERMINATOR

RESET

OFF

120V10 amp Max

JOHNSON CONTROLSFX 60

CO

M4

CO

M3

CO

M2

LAN

2

LAN

1

CAT5 OR CAT6 ETHERNET CABLETO BUILDING NETWORK

(BY OTHERS)

BACNET BUS 1

MOUNTED IN BOILER PANEL

1 FX-60 LP-FX6021N-1 FACILITY EXPLORER FRONT END

1 LP-FXPMUS-0 WALL PLUG POWER MODULE FOR FX-20

1 PS-1 PSPT2RB10 ENCLOSED POWER MODULE W/BREAKER SWITCH

PS-1

120 VAC

BY OTHERS

BACNET BUS 2

Supervisory Controller

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 2 of 13

Page 3: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

NOTE:

1.) THERMOSTAT IS PROVIDED WITH

UNIT. UNIT IS FACTORY WIRED.

T-X

THERMOSTAT

DETAIL

BO1/AO1

BO2BO4/AO2

BI1 RS Scom BI2

-

REF

+

FANM

FANL

FANH

24VHOT

24VCOM BO5

AUXBO5AUX

BO3

UI3

BACNET BUS 1

IC FCU Schedule

Unit

TAG #

Siz

e

CFM

MED Location

NOTES

FC1 6 497 VESTRY Bar GRILLS

FC2 3 275 NAVE

FC3 2 186 RIGHT FRONT

ENTRY

Discharge

toward rear

FC4 12 848 NAVE/CHAPPEL

FC5 12 848 NAVE/CHAPPEL

FC6 12 848 NAVE

FC7 12 848 NAVE

FC8 12 848 NAVE

FC9 2 186 RIGHT REAR ENTRY

FC10 4 394 NARTHEX

FC11 4 394 NARTHEX

FC12 2 186 BAPTISTRY Add 2" extra

base height

FC13 2 186 LEFT REAR ENTRY

FC14 12 848 NAVE

FC15 12 848 NAVE

FC16 12 848 NAVE

FC17 12 848 NAVE/CHAPPEL

FC18 12 848 NAVE/CHAPPEL

FC19 12 848 NAVE

FC20 12 848 NAVE

FC21 8 525 SANCTUARY Bar GRILLS

FC22 8 525 SANCTUARY Bar GRILLS

FC23 2 186 LEFT FRONT ENTRY Discharge

toward rear

FC24 3 275 NAVE

FC25 6 497 SACRISTY Bar GRILLS

FC26 4 394 AMBULATORY

FC27 4 394 AMBULATORY

FC28 8 525 CHOIR LOFT

FC29 8 525 CHOIR LOFT

FC30 2 186 LADIES TOILET

FC31 2 186 MENS TOILET

563340 16698

AHU1

AHU2

325200 10400

207 888,540 1,487,660

74.05 TONS

NOTES:

1 ALL UNITS SHALL BE 115 VAC

2 Cooling capacity based on 45 deg entering water 30% EG

3 ALL UNITS SHALL HAVE MODULATING CONTROL VALVE

4 ALL UNITS SHALL HAVE JCI UNIT MOUNT BAC NET CAPABLE T'STAT

5 MIN FLOW VIA 3-WAY VALVES = 88 GPM

GPMCooling

BTU

Heating

BTU

LH/R

H

Unit

Mount

Valve type

Modulating

3.3 15,030 31,520 RH YES 2-WAY

2.5 7,730 17,490 RH YES 2-WAY

1.1 4,860 11,840 LH YES 2-WAY

8 31,780 56,680 RH YES 2-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

1.1 4,860 11,840 RH YES 2-WAY

1.9 8,500 22,850 RH YES 2-WAY

1.9 8,500 22,850 RH YES 2-WAY

1.1 4,860 11,840 LH YES 2-WAY

1.1 4,860 11,840 RH YES 2-WAY

8 31,780 56,680 LH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 RH YES 2-WAY

8 31,780 56,680 RH YES 3-WAY

8 31,780 56,680 LH YES 3-WAY

4 17,110 33,800 RH YES 2-WAY

4 17,110 33,800 LH YES 2-WAY

1.1 4,860 11,840 LH YES 2-WAY

2.5 7,730 17,490 RH YES 2-WAY

3.3 15,030 31,520 RH YES 2-WAY

1.9 8,500 22,850 RH YES 2-WAY

1.9 8,500 22,850 RH YES 2-WAY

4 17,110 33,800 LH YES 3-WAY

4 17,110 33,800 RH YES 3-WAY

1.1 4,860 11,840 RH YES 2-WAY

1.1 4,860 11,840 RH YES 2-WAY

TOTALS 138.9 1087660

34 162,600 200,000 5200 SOCIAL HALL 2-WAY

34 162,600 200,000 5200 SOCIAL HALL 2-WAY

TOTALS 68 400000

NOTE:

1.) INSTALL END OF LINE

TERMINATOR AT THE LAST UNIT ON

EACH BACNET BUS

BACnet Thermostats

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 3 of 13

Page 4: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

SUPPLY FAN CONTROL:

When the thermostat fan mode is set to low, the supply fan will run continuously at low speed. When the thermostat fan mode is set

to medium, the supply fan will run continuously at medium speed. When the thermostat fan mode is set to high, the supply fan will

run continuously at high speed. When the thermostat fan mode is set to auto, Medium & High speed will operate automatically on

temperature error from setpoint. Low speed operates auto on demand. When there is no demand low speed will shutdown and will

reactivate based on demand.

TEMPERATURE CONTROL:

The unit will control to maintain the zone temperature setpoint as sensed by the zone temperature sensor.

OCCUPIED MODE:

The occupancy mode will be controlled via a network input.

HEATING\COOLING COIL:

The heating\cooling coil will be modulated to maintain the temperature setpoint.

CONFIGURATION INSTRUCTIONS:

Hold the menu key for approximately 8 seconds to access the installer configuration menu. If the default value is desired, press the

no key to advance to the next parameter. Press the yes key to edit the parameter. Use the up and down keys to change the value.

PSWRD: sets the protective access password to prevent unauthorized access to the installer configuration menu. (default: 0)

COM ADDR: set MS/TP address of the thermostat (default 254, range 4-127)

BI1: leave at default value (none)

BI2: leave at default value (none)

UI3: leave at default value (none)

MENUSCRO: gives option to have display continuously scroll through parameters (default on)

AUTOMODE: enables auto changeover from heating to cooling via the mode key (default on)

C or F: provides temperature scale options (default F)

LOCKOUT: set to (0) for all access, set to (1) for access to all except occupancy, set to (2) for occupancy and occupied

setpoints, set to (3) for occupied setpoints only, set to (4) for occupancy only, set to (5) for no access.

PIPE NO: number of pipes, set to (2.0 pipes)

CNTRLTYP: define control output for valves, set to (floating)

SEQOPRA: set to (0) for dual temperature coil with automatic changeover

FAN MENU: sets the fan mode options. Set to (2)

ST-BY TM: sets the time delay between the moment where the pir cover detected the last movement in the area and the time

which the thermostat stand-by mode and setpoints become active. (default: 0.5 hours)

UNOCC TM: sets the time delay between the moment when the thermostat controller toggles to stand-by mode and the time

which the thermostat unoccupied mode and setpoints become active. (default: 0.0 hours)

ST-BY HT: sets standy-by heating setpoint value (default 69.0 F/20.5 C)

ST-BY CL: sets stand-by cooling setpoint value (default 78.0 F/25.5 C)

UNOCC HT: sets unoccupied heating setpoint value (default 62.0 F/16.5 C)

UNOCC CL: sets unoccupied cooling setpoint value (default 80.0 F/26.5 C)

HEAT MAX: set to maximum occupied and unoccupied heating setpoint values (default 90 deg F)

COOL MIN: set to minimum occupied and unoccupied cooling setpoint values (default 54 deg F)

PBAND: sets the proportional band used by the thermostat controller proportional-integral (pi) control loop. (default: 3.0F°/

1.2C°)

SET TYPE: provides option of temporarily changing the heating or cooling setpoints via the up/down keys. SET TO (temporar)

for changes to remain effective for specified tocctime, or set to (permnent) to permanently store changes.

SPT FUNC: sets the operation and usage of local setpoint interface by the user (default dual stp)

TOCCTIME: set the duration of temporary occupied (default 2 hours)

DEADBAND: set minimum dead band between heating and cooling setpoints (default 2.0 deg F)

CAL RS: set zone sensor calibration offset (default 0.0)

AUX CONT: set to (0) for unused or used for reheat

AUTO FAN: as = auto speed only: as ad = auto speed / auto demand (set to as ad, 1.5 min)

FL TIME: set maximum actuator stroke time set to (1.0 min)

FCU

Sequence of Operation

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 4 of 13

Page 5: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

TO

SPACEFROM

RTU

MAD-O

HTGCLG-O

SF-C

SF-S DA-TLTD-S

RA

OA DA

MA-T

Space Temperature Sensor

ZN-T

SMK-S

SF-O

AHU

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 5 of 13

Page 6: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

124816

32

64

12

8

ON

Address:

6

SA

PW

R

CO

M

+ -

SA BUS

+ -

FC BUS

CO

M

SH

LD

+1

5V

IN 1

ICO

M 1

IN 2

ICO

M 2

+1

5V

IN 3

ICO

M 3

IN 4

ICO

M 4

+1

5V

IN 5

ICO

M 5

IN 6

ICO

M 6

IN 7

ICO

M 7

IN 8

ICO

M 8 Sensor

UNIVERSAL BINARY

FC BUS

BINARY

OU

T4

OC

OM

4

OU

T5

OC

OM

5

OU

T6

OC

OM

6

OU

T7

OC

OM

7

OU

T8

OC

OM

8

OU

T9

OC

OM

9

CONFIGURABLE ANALOG

HO

T

24V

CO

M

PCG-1

OU

T1

OC

OM

1

OU

T2

OC

OM

2

OU

T3

OC

OM

3

FC EOL

IN

TRIAC JUMPERS

OUT1INT

EXT

OUT2 OUT3

XFR-1 : COM

XFR-1 : 24VAC

XFR-1 : COM

1

H

N

G

2

PCG-1 : IN1

PCG-1 : INCOM1DISCHARGE AIR TEMPERATURE

3

4

PCG-1 : IN2

PCG-1 : INCOM2

120VAC

BY OTHERS

XFR-1 : 24vac

XMR-1

MIXED AIR TEMPERATURE

7

8

PCG-1 : IN4

PCG-1 : INCOM4

11

12

PCG-1 : IN8

PCG-1 : INCOM8

5

6

PCG-1 : IN3

PCG-1 : INCOM3

MA-T

DA-T

SPARE

LOW TEMPERATURE DETECTOR

RETURN AIR SMOKE DETECTOR

BACNET BUS BACNET BUS

9

10

PCG-1 : IN7

PCG-1 : INCOM7

SUPPLY FAN STATUS

SF-S

CT

12

4

8

R-1

SAFETY

RELAY

XFR-1 : 24VAC

SMK-S

15XFR-1 : 24vac LTD : LINE 2

16 LTD : M2

LTD : LINE 1

LTD-SLTD : M1

17 SMK : 11

18 SMK : 10

19

RE-1 : 14

TB-1 : 18

20 VFD : F

VFD : P24

TB-1

14XFR-1 :COM SMK : 6

13XFR-1 : 24vac SMK : 5+

-POWER TO SMOKE DETECTOR

RE-2 : 1

RE-2 : 9

7

8

13 14

9

5

1

R-2

FAN

PCG-1 : Out1 XFR-1 : COM14

10

2

6

9

1

5

13

XFR-1 : COM

PCG-1 : Ocom1

TB-1 : 19

TB-1 : 20TB-1 : 27

TB-1 : 24

LOW TEMPERATURE DETECTOR

SAFETY INTERLOCK

SMOKE DETECTOR

SAFETY INTERLOCK

SUPPLY FAN COMMANDSF-C

21

22 VFD : CC

VFD : VIA

PCG-1 : Ocom 7

PCG-1 : OUT 7

SUPPLY FAN SPEEDSF-O

+

-

23 MAD : 1 BLK

24

25 MAD : 3 GRY

MAD : 2 RED

PCG-1 : OUT 8

RE-1 : 6 MIXED AIR DAMPERS

MAD-O

+

-XFR-1 :COM

26 VLV : 1 BLK

27

28 VLV : 3 GRY

VLV : 2 RED

PCG-1 : OUT 9

RE-1 : 5 HEAT/COOL VALVE

HTGCLG-O

+

-XFR-1 :COM

Space Temperature Sensor

SA PWR

COM

+-

SA BUS ZONE SENSOR

AHU 1

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 6 of 13

Page 7: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

124816

32

64

12

8

ON

Address:

6

SA

PW

R

CO

M

+ -

SA BUS

+ -

FC BUS

CO

M

SH

LD

+1

5V

IN 1

ICO

M 1

IN 2

ICO

M 2

+1

5V

IN 3

ICO

M 3

IN 4

ICO

M 4

+1

5V

IN 5

ICO

M 5

IN 6

ICO

M 6

IN 7

ICO

M 7

IN 8

ICO

M 8 Sensor

UNIVERSAL BINARY

FC BUS

BINARY

OU

T4

OC

OM

4

OU

T5

OC

OM

5

OU

T6

OC

OM

6

OU

T7

OC

OM

7

OU

T8

OC

OM

8

OU

T9

OC

OM

9

CONFIGURABLE ANALOG

HO

T

24V

CO

M

PCG-2

OU

T1

OC

OM

1

OU

T2

OC

OM

2

OU

T3

OC

OM

3

FC EOL

IN

TRIAC JUMPERS

OUT1INT

EXT

OUT2 OUT3

XFR-2 : COM

XFR-2 : 24VAC

XFR-2 : COM

1

2

PCG-2 : IN1

PCG-2 : INCOM1DISCHARGE AIR TEMPERATURE

3

4

PCG-2 : IN2

PCG-2 : INCOM2

XFR-2 : 24vac

XMR-2

MIXED AIR TEMPERATURE

7

8

PCG-2 : IN4

PCG-2 : INCOM4

11

12

PCG-2 : IN8

PCG-2 : INCOM8

5

6

PCG-2 : IN3

PCG-2 : INCOM3

MA-T

DA-T

SPARE

LOW TEMPERATURE DETECTOR

RETURN AIR SMOKE DETECTOR

BACNET BUS BACNET BUS

9

10

PCG-2 : IN7

PCG-2 : INCOM7

SUPPLY FAN STATUS

SF-S

CT

12

4

8

R-3

SAFETY

RELAY

XFR-2 : 24VAC

SMK-S

15XFR-2 : 24vac LTD : LINE 2

16 LTD : M2

LTD : LINE 1

LTD-SLTD : M1

17 SMK : 11

18 SMK : 10

19

RE-3 : 14

TB-2 : 18

20 VFD : F

VFD : P24

TB-2

14XFR-2 :COM SMK : 6

13XFR-2 : 24vac SMK : 5+

-POWER TO SMOKE DETECTOR

RE-4 : 1

RE-4 : 9

7

8

13 14

9

5

1

R-4

FAN

PCG-2 : Out1 XFR-2 : COM14

10

2

6

9

1

5

13

XFR-2 : COM

PCG-2 : Ocom1

TB-2 : 19

TB-2 : 20TB-2 : 27

TB-2 : 24

LOW TEMPERATURE DETECTOR

SAFETY INTERLOCK

SMOKE DETECTOR

SAFETY INTERLOCK

SUPPLY FAN COMMANDSF-C

21

22 VFD : CC

VFD : VIA

PCG-2 : Ocom 7

PCG-2 : OUT 7

SUPPLY FAN SPEEDSF-O

+

-

23 MAD : 1 BLK

24

25 MAD : 3 GRY

MAD : 2 RED

PCG-2 : OUT 8

RE-3 : 6 MIXED AIR DAMPERS

MAD-O

+

-XFR-2 :COM

26 VLV : 1 BLK

27

28 VLV : 3 GRY

VLV : 2 RED

PCG-2: OUT 9

RE-3 : 5 HEAT/COOL VALVE

HTGCLG-O

+

-XFR-2 :COM

Space Temperature Sensor

SA PWR

COM

+-

SA BUS ZONE SENSOR

VLV : BLK

VLV : REDPCG-2: OUT2HEATING VALVE FOR

CONFESSIONAL SPACEHTG1-C

+

-PCG-2: Ocom2

AHU 2

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 7 of 13

Page 8: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

QTY. TAG PART NO. DESCRIPTION

1 XMR-1 PSB100AB10-TC CONTROL POWER TRANSFORMER

2 PCG-1 FX-PCG2611 GENERAL PURPOSE CONTROLLER

2 ZN-T NS-BTB7003-0 NETWORK THERMOSTAT

2 DA-T TE-6311M-1 DUCT TEMPERATURE SENSOR

2 MA-T TE-6316M-1 DUCT AVERAGING TEMPERATURE SENSOR

2 SF-S CSD-CA1GO-1 CURRENT SWITCH

1 CP-1 SCE-36N2406 CONTROL ENCLOSURE

4 MAD-O M9208-GGA DAMPER ACTUATOR

2 SMK-S SM-501-N-AP SMOKE DETECTOR

2 STS-10-AP SAMPLING TUBE

2 VA9208-GGA-3 VALVE ACTUATOR

2 LTD-S A70GA-1C LOW TEMPERATURE DETECTOR

SUPPLY FAN CONTROL:

The constant speed supply fan (SF-C) will be started based on occupancy schedule. When the supply fan

status (SF-S) indicates the fan started, the control sequence will be enabled. Upon a loss of airflow (SF-S), the

system will attempt to automatically restart until positive status is received. .

ECONOMIZER CONTROL:

When the outdoor air (OA-T) is cooler than the economizer setpoint, cooling will be provided by the OA damper

as required.

When outside air damper (MAD-O) is greater than the exhaust damper enable setpoint, the two position

exhaust damper (EAD-C) will open.

MINIMUM OA CONTROL:

The fresh air intake of the unit will be limited to prevent the mixed air temperature (MA-T) from falling below the

low limit setpoint (OALT-SP).

TEMPERATURE CONTROL:

The discharge air temperature setpoint (DAT-SP) will be reset as the zone temperature (ZN-T) changes.

OCCUPIED MODE:

The occupancy mode will be controlled via a network input (OCC-SCHEDULE). The occupancy mode can also

be overridden by a network input (OCC-OVERRIDE) or a temporary occupancy switch (ZN-TOCC) on the zone

temperature sensor (ZN-T).

UNOCCUPIED MODE:

The unit will cycle to maintain unoccupied zone setpoints (CLGUNOCC-SP & HTGUNOCC-SP) during

unoccupied periods.

HEATING/COOLING COIL:

The heating/cooling coil will modulate to maintain the discharge air temperature setpoint (DAT-SP). The

summer/winter switchover will be accomplished using a network command (SUMWIN-C). When the unit is

shutdown, the heating/cooling coil will be commanded to a preset position should the outdoor air temperature

fall below the low outdoor air temperature setpoint (OALT-SP). Upon a loss of airflow, the heating/cooling coil

will be commanded to a preset position should the outdoor air temperature fall below the low outdoor air

temperature setpoint (OALT-SP).

UNIT PROTECTION:

Low Temperature Alarm (LT-A) - When in "Alarm", the control sequence will stop running, the valve(s) will

open and the fan(s) will be disabled via a hard wired shutdown circuit.

Return Air Smoke Detector (RA-SD) - Disables the fan(s) via a hard wired shutdown circuit.

ADDITIONAL POINTS MONITORED BY THE FMS:

Return Air Smoke Alarm (RA-SD)

AHU 1 & AHU 2

Sequence of Operation

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 8 of 13

Page 9: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

124816

32

64

12

8

ON

Address:

6

SA

PW

R

CO

M

+ -

SA BUS

+ -

FC BUS

CO

M

SH

LD

+1

5V

IN 1

ICO

M 1

IN 2

ICO

M 2

+1

5V

IN 3

ICO

M 3

IN 4

ICO

M 4

+1

5V

IN 5

ICO

M 5

IN 6

ICO

M 6

IN 7

ICO

M 7

IN 8

ICO

M 8 Sensor

UNIVERSAL BINARY

FC BUS

BINARY

OU

T4

OC

OM

4

OU

T5

OC

OM

5

OU

T6

OC

OM

6

OU

T7

OC

OM

7

OU

T8

OC

OM

8

OU

T9

OC

OM

9

CONFIGURABLE ANALOG

HO

T

24V

CO

M

PCG-1

OU

T1

OC

OM

1

OU

T2

OC

OM

2

OU

T3

OC

OM

3

FC EOL

IN

TRIAC JUMPERS

OUT1INT

EXT

OUT2 OUT3

XFR-1 : COM

XFR-1 : 24VAC

XFR-1 : COM

XFR-1 : 24VAC

1

2

PCG-1 : IN1

PCG-1 : INCOM1BOILER 1 SUPPLY TEMPERATURE

18

19

PCG-1 : OUT1

20

21

30PCG-1 : OUT9

3

4

PCG-1 : IN2

PCG-1 : INCOM2

120VAC

BY OTHERS

XFR-1 : 24vac

RE-1

BOILER 1 ENABLE

HOT/CHILLED PUMP 2 SPEED

XMR-1

BOILER 2 SUPPLY TEMPERATURE

7

8

PCG-1 : IN4

PCG-1 : INCOM4

11

12

PCG-1 : IN6

PCG-1 : INCOM6

5

6

PCG-1 : IN3

PCG-1 : INCOM3

BLR2LW-T

BLR1LW-T

BLDGR-T

BUILDING RETURN TEMPERATURE

BUILDING SUPPLY TEMPERATURE

HOT/CHILLED WATER DP

PCG-1 : OCOM9

BACNET BUS BACNET BUS

31

9

10

PCG-1 : IN5

PCG-1 : INCOM5

OUTSIDE AIR TEMPERATURE

28PCG-1 : OUT8

HOT/CHILLED PUMP 1 SPEED

PCG-1 : OCOM8 29

BLR1-EN

P1-O

P2-O

BLDGS-T

R-1 : WHT/BLU

R-1 : WHT/YEL

RE-2

BOILER 2 ENABLE

BLR2-EN

22

23

RE-3

HOT/CHILLED PUMP 1 ENABLE

P1-EN

24

25P2-EN

XFR-1 : COM

C

WHT/BLU

WHT/YEL

BLR ENABLE

BLR ENABLE ORANGE

YELLOW

RE-1, RE-2

13XFR-1 : 24VAC

OUT

COM

POWER

BLDG-DP

XFR-1 : COM

C

WHT/BLU

WHT/YEL

VFD ENABLE

VFD ENABLE ORANGE

YELLOW

RE-3, RE-4

FIELD VERIFY BOILER TERMINATIONS WIRE

N.O. TO THE BOILER ENABLE TERMINALS

MOUNT RIB RELAY AT STARTERP1-S

CT

OA-T

14

15

PCG-1 : IN7

PCG-1 : INCOM7

HOT CHILLED PUMP 1 STATUS

P2-S

CT

16

17

PCG-1 : IN8

PCG-1 : INCOM8

HOT CHILLED PUMP 2 STATUS

FIELD VERIFY TERMINATIONS

XFR-1 : COM

XFR-1 : COM

XFR-1 : COM

PCG-1 : OUT2

PCG-1 : OUT3

PCG-1 : OUT4

R-2 : WHT/BLU

R-2 : WHT/YEL

R-3 : WHT/BLU

R-3 : WHT/YEL

R-4 : WHT/BLU

R-4 : WHT/YEL

26

27P3-EN

XFR-1 : COM

PCG-1 : OUT5 R-5 : WHT/BLU

R-5 : WHT/YEL

RE-4

HOT/CHILLED PUMP 2 ENABLE

RE-5

CHILLER PUMP 3 ENABLE

C

WHT/BLU

WHT/YEL

AUTO

AUTO ORANGE

YELLOW

RE-5

FIELD VERIFY STARTER TERMINATIONS WIRE

N.O. TO THE AUTO SIDE OF THE STARTER

MOUNT RIB RELAY AT STARTER

FIELD VERIFY TERMINATIONS

AT VFD

MOUNT OA SENSOR

ON A NORTH FACING

EXPOSURE

BOILER PANEL

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 9 of 13

Page 10: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

124816

32

64

12

8

ON

Address:

SA

FC

+1

5V

IN 1

ICO

M 1

IN 2

ICO

M 2

+1

5V

IN 3

ICO

M 3

IN 4

ICO

M 4

+1

5V

IN 5

ICO

M 5

IN 6

ICO

M 6

IN 7

ICO

M 7

IN 8

ICO

M 8

UNIVERSAL BINARY

SA/FC BUS

BINARY

OU

T4

OC

OM

4

OU

T5

OC

OM

5

OU

T6

OC

OM

6

OU

T7

OC

OM

7

OU

T8

OC

OM

8

OU

T9

OC

OM

9

CONFIGURABLE ANALOG

HO

T

24V

CO

M

PCX-1

OU

T1

OC

OM

1

OU

T2

OC

OM

2

OU

T3

OC

OM

3

FC EOL

IN

TRIAC JUMPERS

OUT1INT

EXT

OUT2 OUT3

SA

PW

R

CO

M

+ -

+ - CO

M

SH

LD

SA/FC BUS

XFR-1 : 24VAC

XFR-1 : COM

SA BUS ON

PCG-1

5

P3-S

CT

32

33

PCX-1 : IN1

PCX-1 : INCOM1

CHILLED WATER PUMP 3 STATUS

PCX-1 : IN2HEAT

MODEPCX-1 : ICOM2

PCX-1 : IN3COOL

MODEPCX-1 : ICOM3

3 POSITION

SWITCH MOUNT

ON PANEL FACE

PCX-1 : IN8 OCCUPIED

OVERRIDE

TIMERPCX-1 : ICOM8

SPRING WOUND WIND

UP TIMER MOUNT ON

PANEL FACE

QTY. TAG PART NO. DESCRIPTION

1 XMR-1 PSB100AB10-TC CONTROL POWER TRANSFORMER

1 PCG-1 FX-PCG2621 GENERAL PURPOSE CONTROLLER

1 PCX-1 FX-PCX4711 GENERAL PURPOSE EXPANSION

3 R-X RIBU1C CONTROL RELAY

1 BLDG-DP PWLX04S VERIS PRESSURE TRANSMITTER

4 TE-631AM-1 WELL TEMPERATURE SENSOR

4 TE-6300W-101 THERMAL WELL

1 SW-1 W22S3-HW 3 POS SWITCH 2 N.O.

1 OA-T TE-6313P-1 OUTSIDE AIR TEMPERATURE SENSOR

3 PX-S CSD-CA1GO-1 CURRENT SWITCH

1 CP-1 CONTROL ENCLOSURE

1 TMR-1 FD6HW WIND UP TIMER

SW-1 TMR-1

PCX-1 : IN8 OCCUPIED

OVERRIDE

TIMERPCX-1 : ICOM8

SPRING WOUND WIND

UP TIMER MOUNT IN

SACRISTY

TMR-2

PCX-1 : IN4 OCCUPIED

TEMPERATURE

OVERRIDEPCX-1 : ICOM4

TEMPERATURE

SETPOINT OVERIDE

MOUNT IN SACRISTY

STPT-1

1 TMR-2 FD6HW WIND UP TIMER

1 STPT-1 TE-67NT-1B00 REMOTE SETPOINT OVERRIDE

SET PT

SET PT COM

BOILER PANEL EXPANSION

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 10 of 13

Page 11: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

WIRELESS RECEIVER

Space Temp/Humidity SensorWest side of Church

Address: 201

124816

32

64

12

8

ON

Address:

2

SA

PW

R

CO

M

+ -

SA BUS

+ -

FC BUS

CO

M

SH

LD

+1

5V

IN 1

ICO

M 1

IN 2

ICO

M 2

+1

5V

IN 3

ICO

M 3

IN 4

ICO

M 4

+1

5V

IN 5

ICO

M 5

IN 6

ICO

M 6

IN 7

ICO

M 7

IN 8

ICO

M 8

Sensor

UNIVERSAL BINARY

FC BUS

BINARY

OU

T4

OC

OM

4

OU

T5

OC

OM

5

OU

T6

OC

OM

6

OU

T7

OC

OM

7

OU

T8

OC

OM

8

OU

T9

OC

OM

9

CONFIGURABLE ANALOG

HO

T

24V

CO

M

PCG2621

OU

T1

OC

OM

1

OU

T2

OC

OM

2

OU

T3

OC

OM

3

FC EOL

IN

TRIAC JUMPERS

OUT1

INT

EXT

OUT2 OUT3

BOILER PCG

Note:Mount Receiver Around Sanctuary Area. Mount

roughly at same height as wireless Temperature

sensors.

Notes: 1.)WiFi access points should be mounted at least 20 ft from any FX-WRZ Series Sensor or FX-WRZ7860 Receiver2.)FX-WRZ Series Sensors should not be mounted less than 3 ft from a FX-WRZ7860 Receiver

Space Temperature SensorChoir Loft

Address: 202

Space Temperature SensorNarthex

Address: 203

Space Temperature SensorAltar

Address: 204

QTY. TAG PART NO. DESCRIPTION

1 WR-1 FX-WRZ7860-0 ONE TO ONE WIRELESS RECEIVER

1 ZN1-T FX-WRZTHN00-0 TEMPERATURE HUMIDITY SENSOR

3 ZN3,4,5-T FX-WRZTTR00-0 TEMPERATURE SENSOR

1 CBL-1 CBL-NETWORK100 100' MODULAR JACK SA BUS CABLE

WR-1

ZN1-T ZN2-T ZN3-T ZN4-T

CBL-1

WIRELESS SENSORS

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 11 of 13

Page 12: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

DOWN TO FC#30 LADIES TOILET

BUS1 DOWN TO

FX-60

DOWN TO AHU-1 & 2

DOWN TO FC#31 MENS TOILET

BUS1 DOWN TO

BOILER PCG

Remote Twist Timer

Remote Setpoint Adjust

BACNET BUS 1

BACNET BUS 2

NOTE: SET ALL DEVICES FOR A BAUD RATE OF 38400

ADD #32

ADD #33

ADD #4ADD #5

ADD #6

ADD #39

ADD #8

ADD #9

ADD #10

ADD #7ADD #28

WR

-1CBL-1

ADD #35

ADD #27

ADD #22

ADD #20

ADD #19

ADD #21

ADD #26

ADD #25

ADD #24ADD #23

ADD #18

ADD #17

ADD #16ADD #15

ADD #14

ADD #12

ADD #13

ADD #11

ADD #29

FIRST FLOOR LAYOUT

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 12 of 13

Page 13: Direct Digital Control System - Pittsburgh Air Systems Control Wiring Diagrams.pdfDirect Digital Control System Index of Drawings ... 9 Boiler Panel ... If the default value is desired,

Boiler Panel

AHU PANEL

DOWN FROM FCU 16

UP TO FCU 15DOWN FROM

FCU 29

E.O.L

FX-60

FROM FCU 1

FROM FCU 2

DOWN FROM FCU 28

E.O.L

BACNET BUS 1

BACNET BUS 2

NOTE: SET ALL DEVICES FOR A BAUD RATE OF 38400

ADD #30

ADD #31 ADD #5 ADD #6

ADD #38

BASEMENT LAYOUT

Pittsburgh Air Systems, Inc.

208 Bilmar Dr

Pittsburgh, PA

412.539.1234 412.539.1245 F

www.PittsburghAirSystems.com

06/04/2013

11" x 17"

CHECKED BY DRAWN BY REV

J. Konley B. Woods 1

SCALE NONE Job# SHEET 13 of 13