INSTALLATION VANTAGE E l e c t r o n i c L o a d D i m m e r S t a t i o n M O D E L : E L D S 4 - D I N O v e r v i e w The Vantage ELDS4-DIN, Dimmer Station is a 4 channel dimmer that connects to the Vantage Control System. It is powered from a local line feed, and communicates with the system through the 2-wire station bus. In default mode the ELDS4-DIN supports r e v e r s e phase (trailing edge) dimming. Before the system is programmed, or if communication is lost, the dimmer functions in default mode as an independent dimmer by pressing the buttons on the front of the station. Once the system is programmed any load on the dimmer can be controlled by any other keypad, IR input or timed event. It supports up to 6 contact inputs. S y s t e m S p e c i f i c a t i o n s / R e q u i r e m e n t s D e s c r i p t i o n S p e c i f i c a t i o n Ambient Operating Humidity 5-95% non-condensing Ambient Operating Temperature 0-40°C / 32-104°F g n i m m i D e s a h P e s r e v e R e p y T m i D Dimensions, HWD 86mm x 157mm x 70mm (9 DIN module) LED Indicators Status and Load State Lightning Surge Protection High Voltage IEEE C62.41 (6000V 3000A) Lightning Surge Protection Low Voltage ITU-T K.20 c i n o r t c e l E s e p y T d a o L *Max. Current per Load 4.0A (see load configurations below) *Max. Watts per Load 480W@120V or 960W@240V Attention! Not all channels can be used at max. load see LOAD CONFIGURATIONS below C A V 0 5 2 e g a t l o V . x a M Maximum Line Feeds 1 @ 20A (Maximum) breaker 8A Maximum current per station Mounting 35 mm DIN Rail (EN 50 022: 1977) MOV Protection Built-in Each Load 6 s t c a t n o C y r D f o r e b m u N ) 4 ( r u o F s d a o L f o r e b m u N Overload Protection For recommended load types only, i.e., lighting loads only S h o r t C i r c u i t D e t e c t i o n Prevents Load From Turning ON (Will not protect if shorted while ON – Also see Important Load Information) Station Bus connections 24V / 36V Station Bus Station Bus Wiring 2C 16AWG, non-shield, <30pF per foot Station Bus should be separated a minimum of 18" from other parallel communication and/or high voltage runs. Station Equivalent InFusion 0.36W on IC-24 / 0.54W on IC-36 Station Wiring configuration Daisy-chain/Star/Branch g 5 3 6 t h g i e W L O A D C O N F I G U R A T I O N S L o a d 1 M A X . L o a d 2 M A X . L o a d 3 M A X . L o a d 4 M A X . Normal Loads 120VAC 240W 240W 240W 240W Normal Loads 240VAC 480W 480W 480W 480W Expanded Loads 120VAC 480W D o N o t U s e ! D o N o t U s e ! 480W Expanded Loads 240VAC 960W D o N o t U s e ! D o N o t U s e ! 960W ATTENTION! NOT ALL CHANNELS CAN BE USED ON MAX LOAD For proper heat dissipation: Expanded loads 1 plus 2 or 3 plus 4 must not exceed 480W@120V Expanded loads 1 plus 2 or 3 plus 4 must not exceed 960W@240V. The Do Not Use! loads, may be used, if combined loads 1 and 2 or combined loads 3 and 4 do not exceed the 480W or 960W limits and individual loads do not exceed the limits in the table. CAUTION: D o n o t u s e a n E L D S 4 - D I N t o c o n t r o l a n o u t l e t / p l u g . Any motor or appliance connected to a ELDS4-DIN Dimmer Station requiring “RELAY MODE”, must not be greater t h a n 2 . 0 A , ( 2 4 0 W @ 1 2 0 V o r 4 8 0 W @ 2 4 0 V ) , to reduce the risk of overheating and possible damage. This rating allows most ceiling fans requiring relay mode to work with the Dimmer. To change the default mode to RELAY change the Power Profile to Relay in Software. The Relay Mode change will not take place until the system is programmed and the station is on line. Vantage also recommends using a DIN 8 Channel 10 Amp Relay Station, part #STR8RW201 for relay loads. S y s t e m R e q u i r e m e n t s This station is compatible with InFusion Design Center software version 1.4 or higher. For new projects it is recommended that firmware and software be kept to the most current release. I n s t a l l a t i o n Installation of Vantage products should be performed or supervised by a Certified Vantage Installer. Turn the circuit breaker off and make sure no voltage is present where the dimmer station is to be mounted. Damage caused by failure to disconnect power may void the warranty and is a risk to the installer. H i g h v o l t a g e D I N p r o d u c t s m u s t b e i n s t a l l e d i n s i d e o f a p r o p e r l y v e n t e d a n d c o v e r e d D I N e n c l o s u r e . The ELDS4-DIN dimmer station requires N e u t r a l and G r o u n d connections to operate properly. A standard screw terminal is provided for landing the station bus connector on the dimmer station or connect by using the pins on the side of the station to pass station bus between stations (see drawing last page). I m p o r t a n t L o a d I n f o r m a t i o n N O T E : A fast blinking load LED – Indicates o v e r c u r r e n t / o v e r l o a d or u n s a f e turn-on condition present in the load circuit – Do not turn the load on and eliminate the short or over current problem ASAP. Connecting unloaded magnetic transformers should be avoided. For transformers that have dual secondary coils, each secondary should be equally loaded (i.e., EREA E212SC300SK). S h o r t C i r c u i t D e t e c t i o n – Paralleling transformers on a single channel is allowed as long as each transformer is identical. However, this may compromise short circuit detection. N e u t r a l s Run a separate NEUTRAL for each load connected to dimming devices. Failure to do this may cause static loads to slightly flicker while other loads, sharing the same neutral, are ramping or fading. The potential for flickering occurs with all dimming systems due to the changing load level coupling to the fixed load through the neutral.

Transcript of DIN - ELECTRONIC DIMMER STATION - ELDS4-DIN · PDF fileINSTALLATION VANTAGE Electronic Load...

Page 1: DIN - ELECTRONIC DIMMER STATION - ELDS4-DIN · PDF fileINSTALLATION VANTAGE Electronic Load Dimmer Station — MODEL: ELDS4-DIN Overview The Vantage ELDS4-DIN, Dimmer Station is a

I N S T A L L A T I O N V A N T A G E

Electronic Load Dimmer Station — MODEL: ELDS4-DIN

Overview The Vantage ELDS4-DIN, Dimmer Station is a 4 channel dimmer that connects to the Vantage Control System. It is powered from a local line feed, and communicates with the system through the 2-wire station bus. In default mode the ELDS4-DIN supports reverse phase (trailing edge) dimming. Before the system is programmed, or if communication is lost, the dimmer functions in default mode as an independent dimmer by pressing the buttons on the front of the station. Once the system is programmed any load on the dimmer can be controlled by any other keypad, IR input or timed event. It supports up to 6 contact inputs. System Specifications/Requirements

Description Specification Ambient Operating Humidity 5-95% non-condensing

Ambient Operating Temperature 0-40°C / 32-104°F

gnimmiD esahP esreveR epyT miD

Dimensions, HWD 86mm x 157mm x 70mm (9 DIN module)

LED Indicators Status and Load State Lightning Surge Protection High Voltage IEEE C62.41 (6000V 3000A)

Lightning Surge Protection Low Voltage ITU-T K.20

cinortcelE sepyT daoL*Max. Current per Load 4.0A (see load configurations below)

*Max. Watts per Load

480W@120V or 960W@240V Attention! Not all channels can be used

at max. load see LOAD CONFIGURATIONS below

CAV052 egatloV .xaM

Maximum Line Feeds 1 @ 20A (Maximum) breaker 8A Maximum current per station

Mounting 35 mm DIN Rail (EN 50 022: 1977) MOV Protection Built-in Each Load

6 stcatnoC yrD fo rebmuN )4( ruoF sdaoL fo rebmuN

Overload Protection For recommended load types only, i.e., lighting loads only

Short Circuit Detection Prevents Load From Turning ON

(Will not protect if shorted while ON – Also see Important Load Information)

Station Bus connections 24V / 36V Station Bus

Station Bus Wiring

2C 16AWG, non-shield, <30pF per footStation Bus should be separated a minimum of 18" from other parallel

communication and/or high voltage runs.

Station Equivalent InFusion 0.36W on IC-24 / 0.54W on IC-36

Station Wiring configuration Daisy-chain/Star/Branch

g536 thgieW

LOAD CONFIGURATIONS

Load 1 MAX.

Load 2 MAX.

Load 3 MAX.

Load 4 MAX.

Normal Loads 120VAC 240W 240W 240W 240W

Normal Loads 240VAC 480W 480W 480W 480W

Expanded Loads 120VAC 480W Do Not

Use! Do Not

Use! 480W

Expanded Loads 240VAC 960W Do Not

Use! Do Not

Use! 960W

ATTENTION! NOT ALL CHANNELS CAN BE USED ON MAX LOAD

For proper heat dissipation: • Expanded loads 1 plus 2 or 3 plus 4 must not exceed

480W@120V • Expanded loads 1 plus 2 or 3 plus 4 must not exceed

960W@240V.• The Do Not Use! loads, may be used, if combined loads 1 and 2 or

combined loads 3 and 4 do not exceed the 480W or 960W limits and individual loads do not exceed the limits in the table.

CAUTION: Do not use an ELDS4-DIN to control an outlet/plug. Any motor or appliance connected to a ELDS4-DIN Dimmer Station requiring “RELAY MODE”, must not be greater than 2.0A, (240W @ 120V or 480W @ 240V), to reduce the risk of overheating and possible damage. This rating allows most ceiling fans requiring relay mode to work with the Dimmer. To change the default mode to RELAY change the Power Profile to Relay in Software. The Relay Mode change will not take place until the system is programmed and the station is on line. Vantage also recommends using a DIN 8 Channel 10 Amp Relay Station, part #STR8RW201 for relay loads. System Requirements This station is compatible with InFusion Design Center software version 1.4 or higher. For new projects it is recommended that firmware and software be kept to the most current release. Installation • Installation of Vantage products should be performed or

supervised by a Certified Vantage Installer. • Turn the circuit breaker off and make sure no voltage is

present where the dimmer station is to be mounted. Damage caused by failure to disconnect power may void the warranty and is a risk to the installer.

• High voltage DIN products must be installed inside of a properly vented and covered DIN enclosure.

• The ELDS4-DIN dimmer station requires Neutral and Ground connections to operate properly.

• A standard screw terminal is provided for landing the station bus connector on the dimmer station or connect by using the pins on the side of the station to pass station bus between stations (see drawing last page).

Important Load Information • NOTE: A fast blinking load LED – Indicates over current

/ overload or unsafe turn-on condition present in the load circuit – Do not turn the load on and eliminate the short or over current problem ASAP.

• Connecting unloaded magnetic transformers should be avoided.

• For transformers that have dual secondary coils, each secondary should be equally loaded (i.e., EREA E212SC300SK).

• Short Circuit Detection – Paralleling transformers on a single channel is allowed as long as each transformer is identical. However, this may compromise short circuit detection.

Neutrals Run a separate NEUTRAL for each load connected to dimming devices. Failure to do this may cause static loads to slightly flicker while other loads, sharing the same neutral, are ramping or fading. The potential for flickering occurs with all dimming systems due to the changing load level coupling to the fixed load through the neutral.

Page 2: DIN - ELECTRONIC DIMMER STATION - ELDS4-DIN · PDF fileINSTALLATION VANTAGE Electronic Load Dimmer Station — MODEL: ELDS4-DIN Overview The Vantage ELDS4-DIN, Dimmer Station is a

Dimmer Station Set Up in Software InFusion: First select the room, then click on Vantage Objects in the Object Explorer and expand Stations, WireLink. From the list of stations double click on the ELDS4-DIN Dimmer Station to place it in the room. In the Object Editor name the station and make sure it is on the correct station bus port. In the Object Editor note that contact inputs 9 and 10 may be assigned to a Vantage IR receiver and LightPoint Sensor respectively. QLink: Please use a standard DIN Dimmer, model SLDS4-DIN for Inductive/Magnetic loads. In QLink, electronic loads connected to the ELDS4-DIN will be fine even when defined in software as an SLDS4-DIN station, however care should be taken to only load the station as described in this installation instruction sheet. Configuration With AC power connected and turned on, when the ELDS4-DIN dimmer station is first connected to the Station Bus, the diagnostic LED will blink twice followed by a pause, meaning that the station is connected correctly but not yet configured. From Design Center, click on the Configure Stations button on the toolbar or From QLink, select System | Configure Stations and click on the radio Configure button in the Online Configuration section from the pull down menu. Highlight the ELDS4-DIN dimmer station. The Status LED will blink 5 times followed by a pause and the button LEDs will blink rapidly indicating that the station is in configuration mode. To finish configuring press any button on the Station 3 times. The station may also be configured by typing the serial number in the project file, using this method the station will automatically be configured when the system is programmed. Once configured the Status LED will blink evenly and the buttons stop blinking. Default Mode The ELDS4-DIN dimmer station has a default mode that operates without programming or being connected to the Vantage System via the four buttons on the front. If a dimmer has been programmed but communication with the controller is lost the dimmer will revert to default operation. When power is restored from a power outage the dimmer will return the loads to the last load level. This will occur whether or not the dimmer is connected to a system. Default Operation

Button Action Load Operation

Single Press

The load toggles between off and the learned level. The turn on ramp time is 1.5 seconds and the turn off

fade time is 5 seconds. Double Press

The load ramps to 100% in 1.5 seconds. The second press must be within 1 second of the first press.

Press and Hold

After a one second delay the load will ramp in the opposite direction from the last press and hold. If the load reaches 0 or 100% it will reverse direction. When

the button is released the current load level will be saved as the new learned level for that button. The

cycle time is 5 seconds from 0-100%. Reset The ELDS4-DIN Dimmer Station stores the Power Profile configuration data locally so that it will continue to operate correctly if communication with the system is lost. This information includes: load profile, last load level, and default learn levels. To reset this information to the factory default, press and hold switch 1 when power is applied to the station. The Status LED will flash rapidly for a few seconds to indicate the station is resetting.

WARNING: After a factory reset the load profile will be Default, the learn levels will be 50%, the loads will all be off, and other settings will be at factory default. When the station is reset and no

programming is present, IR scenes and buttons 1-4 dim loads according to default programs.

Actuator Buttons The four actuator buttons on the front of the ELDS4-DIN station are for local control only and are not programmable through Design Center or QLink software. These buttons will not register in Monitor Button press. Connection Terminals Top Connections:

• Connections 1-4 are dry-contacts. Program the same way you would program any dry-contact.

• Connections 5 and 6 (addressed as 9 and 10) are for dry-contacts or a Vantage remote IR receiver and a Vantage Sensor respectively.

• A +12VDC, 50mA power connection may be used for any device requiring this power profile, i.e., the Vantage Remote IR or Vantage LightPoint Sensor.

• A Station Bus connection to the Vantage system. Bottom Connections:

• Neutral and Line for high-voltage connections. • Load and Neutral connections for loads 1-4.

Side Connections: • Station Bus Pin, (included) Part #VDC-0197.

CAUTION: All Dry-Contacts to third party equipment may produce a ground loop. If a dry contact is connected directly to any Vantage station, and the device is not using the same power source or is far away from the Vantage station, a ground loop or data noise condition may occur. If this condition is suspected, Vantage recommends a third party Opto (optical) Isolation Module. Opto Isolation provides a communications link and is an important consideration if a system uses different power sources, has noisy signals or must operate at different ground potentials. Diagnostic Information The Status LED blinks evenly or flashes 2, 3, 4 or 5 times followed by a pause to indicate status information. Off: The station is not powered. A line voltage connection has not been made or the line feed breaker is off. One Even blink: Station is operating correctly and is configured. Two blinks: Station is operating correctly but is not configured. Three blinks: Station is not communicating with the Main Controller. Verify that station bus wiring conforms to Vantage guidelines. Four blinks: Dimmer problem. Please contact the factory. Five blinks: Configuration mode. Note: A fast blinking load LED – Indicates over current / overload or unsafe turn-on condition present in the load circuit – Do not turn the load on and eliminate the short or over current problem ASAP. If the load shuts down and the LED starts blinking after the load has been on for a few seconds, check the load for an over current / overload condition.