Differential Protection Scheme for Power Transformer Fault ...
Transcript of Differential Protection Scheme for Power Transformer Fault ...
Differential Protection Scheme for Power
Transformer Fault Analysis using PSCAD
Priyadharshini M 1*, Gayathri K 2
1Assistant Professor, Department of Electrical Engineering, Annamalai University,Annamalai Nagar, Tamil Nadu, India. 2 Assistant Professor, Department of Electrical Engineering, Annamalai University,Annamalai Nagar, Tamil Nadu, India.
Abstract— A power transformer is the most expensive device in the electrical systems. The transformer failure would result in huge
economic loss and unexpected outage of power system; hence a maintenance mechanism is essential to prevent the transformers from
failures. Components may fail due to poor maintenance, poor operation, poor protection, undetected faults, severe lightening, short
circuits, etc. This paper deals with internal faults in large power transformer. The explanation of such faults is followed by the
description of an analytical method of Differential protection scheme. The Differential protection for power transformer is used to
extract the feature from transient signal to accurately identify the fault in the input side of three phases, winding fault and
magnetizing inrush current. Effectiveness of proposed approach tested on a three phase 100 MVA, 33/230 kV, 60Hz, power
transformer is modeled in PSCAD/EMTDC software . The simulation results clearly show that the proposed scheme is reliable,
accurate and faster than the conventional approach.
.
Keywords— Differential Protection, Power Transformer, Magnetizing Inrush current, Fast Fourier Transform, PSCAD.
I. INTRODUCTION
Transformers are essential and important elements of power systems. In the past few years, there has been an increasing
concern about the occurrence of faults in power transformers due to the abnormal operation. It is not always possible to analyze
the transformer behavior under such faults under rated conditions, since the tests are largely destructive. Therefore, in order to
avoid severe damage to Transformer, mathematical models are used for the analysis [1].. Transformer Inrush current may trigger
the over-current protection of power transformers, and the associated power distribution system may get affected. Over sizing the
transformer is a common approach to avoid the inrush current. However, this would dramatically increase the size and cost of
transformer, therefore this project proposes a new technique for isolating the inrush of the transformer and preserving the ability
of the projection circuit [2].
The basic operating principle of differential protection is to calculate the difference between the current entering and leaving
the protected zone. The phenomenon occurred during removal of external through fault t.3]. The protection operates when the
differential current exceed the set bias threshold value. For external faults, the differential current should be zero but error caused
by the CT saturation and CT ration error leads to non-zero value.. The operating threshold is raised by increasing the relay setting.
Mal-operation of the differential protection of power transformer may occur due to magnetizing inrush current and CT saturation
through fault inrush among all these three magnetizing inrush results during excitation of transformer under no load condition. It
can also come during the energization of parallel connected power transformer [4].
Many researchers have proposed various protection schemes power transformers. Ouahdi Dris Farag. et. Al [5] have been
proposed a differential protection using second harmonic restrain and fifth harmonic block schemes for power
transformer protection is presented. Initially analysis the concept of differential protection, then investigate harmonics restrain
scheme and microprocessor based-protection on power transformer differential protection has been developed. Manoj Tripathy et.
al [1] has been proposed Wavelet and Neural Network based power transformer fault analysis. This approach extracted the
feature transient signal and the neural network has been trained by the extracted features of the transient signal. This method
accurately discriminates between the internal fault and magnetizing inrush current.
The Feed forward Back propagation Algorithm (FFBPN) has been applied to identify the transformer faults by. Raja Pandil T
et. al [6]. This methodology addresses the challenging task of detecting magnetizing inrush from internal fault. The algorithm is
evaluated using simulation performed with MATLAB and analysis of power transformer from differential protection using back
propagation neural algorithm.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2257
Stanley E et.al [9] develops a power transformer model to evaluate differential element performance. In this study analyzes
transformer energisation, over excitation, external fault, and internal fault conditions with this model..
Mudita Mathur and Vinay Barhate [8] develops application of artificial neural network based pattern recognition
approach for differential protection of transformer. The power transformer protective relay should block the tripping during
magnetizing inrush and rapidly initiate the tripping during short circuit.ANN based technique for discrimination between
magnetizing inrush and internal fault currents of transformer. Artificial neural network has been proposed and demonstrated by
Paraskar S P [7]. This approach has capability of solving the transformer monitoring and fault detection problem. The proposed
ANN provides an inexpensive, reliable, and noninvasive procedure. to determine inrush fault in the transformer
This article presents a power Transformer unit fault analysis strategy using differential protection approach. This proposed
approach improves the fault identification scheme of power Transformer unit. This approach efficiently analysis the input of the
Transformer unit under fault condition and determine the inrush current fault and winding fault. The simulations are carried out
using PSCAD software.
II. TRANSFORMER MATHEMATICAL MODEL
A transformer is a static electrical device that transfers energy by inductive coupling between its winding circuits. A varying
current in the primary winding creates a varying magnetic flux in the transformers core and thus a varying magnetic flux through
the secondary winding [1]. This varying magnetic field at the secondary induces a varying electromotive force (emf).
One of the most important and complex system that has been built by human civilization is the power system. The electric
power system plays a key role in modern society. One of the most important components of any power system is the power
transformer.
The development of the first power transformer significantly changed transmission and distribution systems. Before the
power transformer was invented in 1885 by William Stanley, power was produced and distributed as direct current (DC) at low
voltage. The use of electricity was only limited to urban areas because of voltage drop in the lines. Also, the use of DC voltage
would require the supply voltage to be the same as the supply voltage required by all electrical equipment connected to the power
system. However, it is quite difficult to transform DC power to a lower current and high-voltage form efficiently. The alternating
current (AC) system is able to overcome the limitation of the DC system and distributes electricity efficiently over long distances
to consumers. The use of the AC system allows the use of a multi-voltage level energy delivery system. The AC power, generated
at a low voltage, can be stepped up by using the power transformer for the transmission purpose to higher voltage and lower
current. Thus, voltage drops and transmission energy losses can be reduced. The transformer is the link between the generator of
the power system and the transmission lines. A power transformer is defined in reference as a static piece of apparatus with two or
more windings which by electromagnetic induction, transforms a system of alternating voltage and current into another system of
voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power.
Fig. 1 Transformer Equivalent Circuits
Where:
VP - primary voltage
VS - secondary voltage
IP - primary current
IS - secondary current
RP - primary reactance
RS - secondary reactance
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2258
XP - primary impedance
XS - secondary impedance
NP - number of primary winding
NS - number of secondary winding
IC - current coil
RC - reactance current
IM - magnetizing current
XM - impedance magnetizing
I0 - no load current
A. Basic transformer model
Fig. 2 shows a simple single-phase shell-type transformer with two windings [9].We used a Transformer bank with
three single-phase transformers for testing and modeling purposes. The total flux in Winding 1 is the sum of the mutual flux
(Ф) plus the Winding 1 leakage flux (Ф11). The sum of the mutual flux (Ф) plus the Winding 2 leakage flux (Ф22) determines the
total flux in Winding 2. The following expressions determine the relationship between voltages and mutual flux in the transformer
core.
TNTILIRE .11.11.11 (1)
TNTILIRE .22.22.21 (2)
.2.1.1. NPINP (3)
Fig.2 Single-Phase Two-Winding Transformer
Where;
E1 winding 1 input volt R1 winding of 1 resistance
E2 winding 2 input volt R2 winding of 2 resistance
L1 winding 1 leakage inductance ∆Ι incremental current
L2 winding 2 leakage inductance ∆Φ incremental 1 magnetic flux
I1 winding 1 current ∆Τ incremental of time
I2 winding 2 current N1 winding 1 number of turn
p core permeance N2 winding 2 number of turn
The ratio I / times N determine the leakage inductance (for example, 1
11
I
times N1 determination the
winding 1 leakage inductance) equation 4 shows the matrix representation of equations 1,2 and 3.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2259
01
0
0
222
111
1
21
2
1
2
1
2
1
IRE
IRE
NPNP
NL
NL
T
T
IT
I
(4)
Winding 1 and 2 voltages are the input quantities to the transformer model. We want to Determine the current
values for different transformer operating conditions [7]. The first matrix in right term of equation 4 is the coefficient matrix
equation 5 is the matrix representation of the incremental values of winding 1 and winding 2 currents and the incremental value
of the mutual flux.
All terms in the coefficient matrix have fixed values except the permeance P. The following expression determines the
presence of a given transformer core:
III. TRANSFORMER DIFFERENTIAL PROTECTION
Differential protection is a unit type protection for a specified zone (or) piece of equipment [1]. It is the based on the fact that it
is only in the case of faults internal to the differential currents (difference between input and output current will be high).
Fig. 3 Simple Diagram for Differential Power Transformer Protection
Percentage restraint differential protective relays have been in service for many years. Fig. 3 shows a typical differential
relay connection diagram. Differential elements compare an operating current with a current. The operating current (also called
differential current), Id, can be obtained from the phaser sum of the currents entering the protected element Id is
proportional to the fault current for internal faults and approaches zero for any other operating (ideal) conditions. There
are different alternative for obtaining the restraining current IRT. The most common ones include the following differential
relays perform well for external faults, as long as the CTs reproduce the primary currents correctly. When one of the CTs
saturates, or if both CTs saturate at different levels, false operating current appears in the differential relay and could
cause relay male-operation.
A. Current Differential Relay
The relay consists of three differential elements. Each differential element provides percentage restrained differential
protection with harmonic blocking and unrestrained differential protection [2].
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2260
Fig. 4 Current Differential Relay
The input currents are the CT secondary currents from Winding 1. The relay reduces the magnitude of these currents and
converts them to voltage signals. Low-pass filters remove high-frequency components from the voltage signals. The three
differential elements use the compensated currents from Winding 1 and as inputs to their logics. For example, the Differential
Element 1 uses the compensated currents I1W1F1 and I1W2F1.
IV. RESULT AND DISCUSSION WITH CASE STUDY OF POWER TRANSFORMER DIFFERENTIAL PROTECTION
An important contribution of the modeling of power transformer is magnetically represented in independent phases. The
principle of duality has been used to take into account the magnetizing currents and core configuration when modeling multi-limb
transformers with the EMTP program. Based on these models PSCAD MASTER Library supports transforms for transient
studies, the same is used to develop the simple power systems given in Fig.5. PSCAD/EMTDC is the simulation tool for
analyzing power system transient developed by Manitoba HVDC Research Centre. Currently version of PSCAD-EMTDC
provides magnetically independent phase models also. Various types of winding to ground (Body of Transformer) have been
investigated; the transients for these cases and the protection system response for the same are given in Fig. 6 and 7.
Fig.5 Transformer One Line Diagram
The Protection system performance under different numbers of shorted turns of power transformer, different connections of the
transformer, different values of the fault resistances, and different values of the system parameters was investigated. The results
indicate that the new technique can provide a fast and sensitive approach for identifying minor internal turn-to-turn faults in
power transformers.
Table 1 Specifications of Transformer
Transformer rating 100 MVA
Source type RL
Primary Transformer 33KV
Secondary Transformer 230KV
Primary Winding Star
Secondary Winding Delta
Frequency 60HZ
Leakage reactance 0.1
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2261
Fig. 6 Proposed simulated model Transformer in R Phase Fault
The system under study is a single machine power system connected through a three phase power transformer. A three
phase transformer bank was constructed using three single phase transformers, each of 100 MVA, 33/230 kV. The simulated
power system model is depicted in Fig.6. To validate the model, the steady state operation and the transient behavior during faults
were compared with theoretical calculations.
Case (i) R Phase
The voltage and current transients due to magnetizing inrush current are simulated in PSCAD using simulink models.. In
this model a timed circuited breaker is added, the same is closed at T=1.0 sec it causes inrush current due to energization of
transformer under R phase fault. The fault should be create at T=2.0 sec at tripping signal.
The shape of the validation plot and test plot are the performance in smooth over the wide range of sample points. The
steady-state operation and transient during fault current flow (at-1.0kA to 1.0kA) and voltage flow (-350 kV to 350 kV).
This process signals represented the first, second and third order harmonics to identifying the fault signal. The 1st
Harmonic range is higher than the 2nd harmonics upto 2.00 amp 3rd harmonic range is lower than the 2nd harmonics upto 0-10amp
in Fig. 6.
For the mho relay scheme given in Fig. 7 and 8 the intersection of Rab.Rbc & Rca on the mho cicle is a indication of
fault. Not intersection of Rab, Rbc &Rca on the mho circle is a indication of no fault. The graph is plotted with time on x-axis
with 1 second difference and on y-axis graph is plotted as trip, fault, current and voltage in graph;
Similarly
1unit=1second –time
1unit=1(KA) -current
1 unit=100(KV) –voltage
Fig. 7Current and voltage of R phase Fault
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2262
The power transform with difference vector on over voltage side the signal is injected to differential relay may be brought from
the ideal current transforms. During the fault the relay should trip the breakers. The current is taken as input signal the processing
system and final trip signal is used to control the Three phase breaker. As carried out for R-phase fault winding faults has been
simulated.
Fig. 8 Processed signals
Fig. 9 Transformer fault in R Phase Fault
For the mho relay scheme given in Fig. 9 the intersection of Rab, Rbc and Rca on the mho circle is a indication of fault.
Fig. 10 show not intersection no fault
Fig. 10 Transformer no fault in R Phase
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2263
Case (ii)Y Phase
The voltage and current transients due to magnetizing inrush current are simulated In PSCAD semolina model and shows
Fig. 11. In this model a timed circuited breaker is added, the same is closed at T=1.0 sec it causes inrush current due to in
energization of transformer under Y phase fault. The fault should be create at T=2.0 sec at triping signal.
The shape of the validation plot and test plot are the performance in smooth over the wide range of sample points. The
steady-state operation and transient during fault current flow at -1.0 kA to 1.0 kA and voltage flow -350 kV to 350 kV.
This process signals represented the first, second and third order harmonics to identifying the fault signal. The 1 st
Harmonic range is higher than the 2nd harmonics upto 2.00 amp 3rd harmonic range is lower than the 2nd harmonics upto 0-10amp
in Fig. 12.
For the mho relay scheme given in Fig. 13 and 14 the intersection of Rab. Rbc & Rca on the mho cicle is a indication of
fault. Not intersection of Rab, Rbc & Rca on the mho circle is a indication of no fault. The graph is plotted with time on x-axis
with 1 second difference and on y-axis graph is plotted as trip, fault, current and voltage in graph;
Fig. 11 Current and voltage of Y Phase Fault
The power transform with difference vector on over voltage side the signal is injected to differential relay may be brought from
the ideal current transforms. During the fault the relay should trip the breakers. The current is taken as input signal the processing
system and final trip signal is used to control the Three phase breaker Fig. 13 and 14. As carried out for Y-phase fault winding
faults has been simulated.
Fig. 12 Process signal graph
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2264
Fig. 13 Transformer fault in Y Phase
Fig. 14 Transformer no fault in Y Phase
Case (iii) B Phase
The voltage and current transients due to magnetizing inrush current are simulated. In PSCAD software model and shows in fig
15. In this model a timed circuited breaker is added, the same is closed at T=1.0 sec it causes inrush current due to energization of
transformer under B phase fault. The fault should be create at T=2.0 sec at tripping signal.
The shape of the validation plot and test plot are the performance in smooth over the wide range of sample points. The
steady-state operation and transient during fault current flow (at-1.0KA to 1.0KA) and voltage flow (-350 KV to 350 KV).
This process signals represented the first, second and third order harmonics to identifying the fault signal. The 1st
Harmonic range is higher than the 2nd harmonics up to 2.00 amp 3rd harmonic range is lower than the 2nd harmonics up to 0-
10amp(in Fig. 15).
For the mho relay scheme given in fig 16 and 17 the intersection of Rab. Rbc & Rca on the mho circle is a indication of
fault. Not intersection of Rab, Rbc & Rca on the mho circle is a indication of no fault. The graph is plotted with time on x-axis
with 1 second difference and on y-axis graph is plotted as trip, fault, current and voltage in graph;
The power transform with difference vector on over voltage side the signal is injected to differential relay may be brought
from the ideal current transforms. During the fault the relay should trip the breakers. The current is taken as input signal the
processing system and final trip signal is used to control the Three phase breaker. As carried out for B-phase fault winding faults
has been simulated.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2265
Fig. 15 Current and voltage of B Phase Fault
Fig. 16 Process signal graph
Fig. 17 Transformer fault in B Phase
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2266
Fig. 18 Transformer no fault in B Phase
Case (iv) winding phase
The voltage and current transients due to magnetizing inrush current are simulated. In PSCAD using simulink models. These
shows in Fig. 19. In this model a timed circuited breaker is added, the same is closed at T=1.0 sec it causes inrush current due to
energization of transformer under winding phase fault. The fault should be create at T=2.0 sec at triping signal.
The shape of the validation plot and test plot are the performance in smooth over the wide range of sample points. The
steady-state operation and transient during fault current flow (at-1.0kA to 1.0kA) and voltage flow (-350 kV to 350 kV).
This process signals represented the first, second and third order harmonics to identifying the fault signal. The 1st
Harmonic range is higher than the 2nd harmonics upto 2.00 amp 3rd harmonic range is lower than the 2nd harmonics upto 0-10amp
in Fig. 20.
For the mho relay scheme given in Fig. 21 and 22 the intersection of Rab.Rbc & Rca on the mho circle is a indication of
fault. Not intersection of Rab, Rbc & Rca on the mho circle is a indication of no fault. The graph is plotted with time on x-axis
with 1 second difference and on y-axis graph is plotted as trip, fault, current and voltage in graph;
Fig. 19 Current and voltage of Winding Fault
The power transform with difference vector on over voltage side the signal is injected to differential relay may be
brought from the ideal current transforms. During the fault the relay should trip the breakers. The current is taken as input signal
the processing system and final trip signal is used to control the Three phase breaker. As carried out for winding-phase fault
winding faults has been simulated.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2267
Fig. 20 Process Signal graph
Fig. 21 transformer fault in Winding
Fig. 22 Transformer no fault in Winding
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2268
Case (v) Magnetic Inrush
Since the magnetizing branch representing the core appears as a shunt element in the transformer equivalent circuit, the
magnetizing current upsets the balance between the currents at the transformer terminals, and is therefore experienced by the
differential relay as a “false” differential current. The inrush currents simulated in PSCAD is given Fig. 23. It is not able for
protection scheme designed to discriminate inrush from fault currents.
Magnetizing inrush current in transformers results from any abrupt change of the magnetizing voltage. Although usually
considered as a result of energizing a transformer, the magnetizing inrush may be also caused by :
Occurrence of an external fault,
Voltage recovery after clearing an external fault,
Change of the character of a fault (for example when a phase-to-ground fault evolves into a phase-to- phase-to-
ground fault).
Out-of-phase synchronizing of a connected generator.
Certain transients can cause a substantial differential current to flow, when there is no fault, and these differential
currents are generally sufficient to cause a percentage differential relay to trip. However, in these situations, the differential
protection should not disconnect the system because it is not a transformer internal fault. The inrush is one such phenomenon
which happens in the transformer. It has been shown by simulations that the proposed differential protection scheme is able to
protect system from damages under various possible types of faults.
Fig. 23 Phase currents Magnetic Inrush
Fig. 24 Process Signal Graph
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2269
Fig. 25 Transformer fault in Magnetic Inrush
V. CONCLUSIONS
In this research work a magnetic equivalent circuit (UMEC) of the three-limb three-phase transformer core type has been
developed. The arbitrary division of magnetizing current as well as uniform core flux assumptions and lumped leakage reactance
approximations are removed using the UMEC concept. This transformer model provides enough accuracy for differential
protection study purposes. Transformer models without hysteresis modeling reduce model complexity and minimize simulation
time. Relay logic and the algorithm that uses Discreet Fourier transformer for extraction of fundamental and higher harmonics
components of differential current have been reported here. The use of digital protection offers the advantage to implement
complexes algorithms such as DFT to ensure better extraction of fundamental and other harmonics components, then the use of
the second and the fifth harmonics for restraining and blocking, by the differential protection will give a possibility to
discriminate between the faulty and the normal state of power transformer.
The PSCAD/EMTDC software can be successfully used to modeling the disturbances with transformers protection scheme.
It has been shown using PSCAD simulations that Digital current differential relays provide fast and reliable transformer
protection. Further research will focus on the analysis of the extracted FFT signals (Waveforms saved to COMTRADE files)
using soft computing tools.
ACKNOWLEDGMENT
The authors gratefully acknowledge the authorities of Annamalai University for the facilities offered
to carry out this work.
REFERENCES
[1] Manoj Tripathy, Rudra Prakash and Maheshwari“Transformer Differential Protection based on Wavelet and Neural
Network”, International Journal of Electronic and Electrical Engineering.Vol.7, Pp. 685-695, 2014.
[2] L.Madhan kumar, R.Murugan and S.Chandramoghan “Modeling of Power Transformer for Differential Protection
using PSCAD”, International Journal of Advanced Research in Electrical. Vol. 3, Apr 2014
[3] K.Gayathri, N.Kumarappan and S.Guruprasath “EHV Transmission Line Modeling Using PSCAD based on EMTDC
Tecnique”, Proceeding of International Conference on Power System CPRI and IEEE, Bangalore,India.Pp.207.Dec
2007.
[4] Manoj Tripathy and R.P.Maheshwari “Improved Transformer Protection using Probabilistic Neural Network and
Power Differential Method”, International Journal of Engineering Science and Technology. Vol. 2, No.3, Pp. 29-44,
2010.
[5] Ouahdi Dris, Farag and M.Elmareimi Rekina Fouad “Transformer Differential Protection Scheme with Internal
Faults Detection Algorithm using Second Harmonics Restrain and Fifth Harmonics Blocking Logic”, International
Journal of Engineering Science and Technology. Vol.2, No. 3, Pp. 29-44 , Jan 10 2013.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2270
[6] T.Raja Pandi and MKNM.Sakthi Nagaraj “The Analysis of Power Transformer from Differential Protection using
Back propagation Neural Algorithm”, International Journal of Innovative Research in Computer and Communication
Vol.2, Mar 2014.
[7] S.R.Paraskar and M.A.Beg “Discrimination between Inrush and Fault in Transformer ANN Approach,” International
Journal of Advancements in Technology.Vol.2, Pp.24-31, April 2011.
[8] Mudita Mathur and Vinay Barhate “ANN based Technique for Discrimination between Magnetizing Inrush and
Internal Fault Currents in Transformer”, International Journal of Science and Technology Vol. 2, Pp.17-21, Jan 2013.
[9] Stanley and Armando Guzmán “Transformer Modeling as Applied to Differential Protection”, International Journal
of Engineering Science and Technology. Vol. 2, No.3, Pp. 29-44, 2010.
[10] M.E.Hamedani , Gloshan and H.Samit “A New Differential Protection Algorithm based on Rising Rate Variation of
Second Harmonic Current,” Iranian Journal of Science and Technology. Vol.30,No.B6, Pp 643-654 2006.
[11] Maofa Gong and Guoliang Li “Study on a New Method of Transformer Differential Protection”, International
Journal of Communications in Information Science and Management Engineering. Vol. 3, Pp. 531-539, Nov 2013.
[12] M.P.Thakre and V.S.Kale “Distance Protection For Long Transmission Line Using PSCAD”, International Journal
of Advances in Engineering and Technology. Vol. 2, No. 3, Pp. 39-54 Jan. 2014.
[13] M.A.El-Sharkawy “Overview of Neural Network Application to Power Systems”, Proceedings of 5-th,
MEPCON’97, Alexandria, Egypt, Jan 1997.
[14] T.Dalsten and T.Friedrick “Multi-Neural Network based Fault Area Estimation for High Speed Protective Relaying”,
IEEE Trans. on Power Delivery,Vol.11, No.2, April 1996.
[15] Stanley E. Zocholl, Armando Guzmán, Daqing Hou “Transformer Modeling as Applied to Differential Protection”
pages;108-114 vol.1.ISSN;0840-7789 may 1996.
[16] Nita R.Patne,K.L .Thakre Turk J , “Effect of transformer on stochastic estimation of voltage sag due to faults in the
power system,” a PSCAD/EMTDC simulation Elec Eng& comp sci, vol.18,no.1,2010.
[17] Inagaki, K. & Higaki, M.. “Digital protection method for power transformers based on an equivalent circuit
composed of inverse inductance”, IEEE T-PWRD, 3(4), 1501.pages(1501-1510)ISSN;08885-8977, 1988.
[18] Mohamed A. Abd-Elaziz , and Ebrahim A, “A general approach for internal faults representation of three-phase three
winding transformer in EMTP-ATP” (An ISO 3297: 2007 Certified Organization) Vol. 2, ISSN (Print) : 2320 – 3765 September 2013.
[19] A. Smolarczyk, and E. Bartosiewicz “Modeling Differential Protections of Power Transformers and Their Testing
Using PSCAD/EMTDC” Software International journal of systems applications, engineering & development
Issue 3, Volume 7, 2013.
[20] Mayurdhvajsinh P. Gohil, Jinal Prajapati, and Ankit Rabari. “Differential Protection Of Y-Y And Δ-Δ Connected
Power Transformer” Issn: 2321-9939 International Journal Of Engineering Development And Research Ijedr)
January 2014.
[21] Manoj Tripathy, Rudra Prakash Maheshwari, and Neha Nirala “Transformer Differential Protection Based on
Wavelet and Neural Network” International Journal of Electronic and Electrical Engineering .ISSN 0974-2174
Volume 7, pp. 685-695 Number 7 2014.
JASC: Journal of Applied Science and Computations
Volume 5, Issue 11, November/2018
ISSN NO: 1076-5131
Page No:2271