Page 1/20
JUMO DICON touchTwo-channel process and program controllerwith paperless recorder and touchscreen
Brief descriptionThe DICON touch is a two-channel universal process and program controller that displays infor-mation on a vibrant screen. The device is easy to operate via a touchscreen.Both control channels use the tried-and-tested JUMO control algorithm with two possible optimi-zation options. These enable a simple and highly-accurate startup. It also enables multiple zonecontrol, cascade control, or other complex control tasks.The block diagram below illustrates the various different hardware options offered by the modularhardware concept. Four analog universal inputs and up to eight external inputs can record a va-riety of physical measured values with high precision. The actuators can be controlled directly inthe device with either an analog or digital setup. These can be expanded further through externaldigital outputs. Interfaces such as Modbus (master/slave), PROFIBUS, or Ethernet with Webserver can be used for the communication with higher-order systems.To ensure secure process operation, the device has a password-protected user administrationwith individual assignment of rights for different levels or control commands. Screen masks forcontrollers, program generators, recording, and for overview screens are ready-made and avail-able. An individual process screen can be created using the configuration software. Using theextra-code recording function, important analog and digital process values can be saved so thatthey are tamper-proof, so that they can be graphically visualized, and so that they can be export-ed via interface or USB stick in a tamper-proof fashion to the PC.The configuration software ensures that the process controller can be easily programmed, thatmath or logical coherences can be described, and that customer-specific linearizations can becreated. In addition, tools for simulating external signals or control paths are included. Thesetools can also record for the duration of the startup.A comprehensive alarm and limit-value concept as well as a flexible digital signal administrationcomplete the "all-in-one" device.
Type 703571/...
Block diagram
Analog input ( In8universal)
Analog input (universal) In10
Relay output OUT1(changeover contact)
70
35
71
8 e
xp
an
sio
n s
lots
Voltage supply- AC 110 to 240 V, +10/-15 %- AC/DC 20 to 30 V
InterfaceRS485 Modbus slave
COM1
Relay output OUT2(changeover contact)
Digital/analog outputsOUT4
OUT3
Digita nalog outputs OUT6
l/a OUT5
Digita nalog outputs OUT8
l/a OUT7
Digita nalog outputs OUT10
l/a OUT9
Digita nalog outputs OUT12
l/a OUT11
Interface COM2RS422/485, PROFIBUS-DP, or Ethernet
USB interfaces - USB device (e.g. setup program)- USB host (e.g. firmware update)
Available ex-worksOption
7 In1 to 7(potential free contact)
Digital inputs
Analog input (universal) In9
Analog input (universal) In11
Special features• Vibrant 3.5-inch color screen,
with 320 × 240 pixels and 256 colors• Easy-to-use program entry and program
control• Interfaces: USB host, USB device, Modbus
(master/slave), PROFIBUS-DP, and Ether-net
• Integrated paperless recorder with tamper-proof data storage (extra code)
• Individual process-screen display with con-figurable edit boxes
• Math and logic functions• Flexible through modular hardware• Password-protected user administration
Five-digit analog value display• Individual operator level• Control loop and output value monitoring• Integrated timer and time switch Service
and operating hours counter• Web server for online visualization via a
Web browser• Alarm transmission by email• Protection type on the front IP66• cUL, GL, DIN EN14597
approval applied for
Approvals / approval marks (see "Technical data")
Data Sheet 703571
2012-04-01/00578870
2012-04-01/00578870
Data Sheet 703571 Page 2/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
DescriptionController typesThe controller can be configured as a two-state controller, three-state controller, three-state modulating controller, continuous con-troller, or continuous controller with integratedposition controller. The cycle time is 150 ms.
Parameter blocksFour parameter blocks can be assigned toeach controller. Each parameter block has 15parameters. The controller structures P, I, PD,PI, and PID can be adjusted.
Self-optimizationSelf-optimization also makes it possible for thecontroller to be matched to the control loop bya user who is not a control technology expert.During this, the reaction of the control path tothe variable change is evaluated. Two differentoptimization processes are available. The os-cillation method is preset as standard methodin the controller.
User levelUp to 25 parameters of any type from the con-figuration or parameter level can be includedin this level. These parameters, for example,often need to be changed or made available tooperating personnel (see "User administra-tion").
User administrationPassword-protected user administration guar-antees safe process operation. This functionallows the individual assignment of rights, en-abling four users to access different levels andcontrol commands.
Setpoint valuesUp to four setpoint values can be entered foreach controller channel. Changeover of thesesetpoint values is controlled by two binary-coded digital signals. However, the setpointvalues for both controllers can also be speci-fied as an external setpoint selection via anadditional analog input or an interface.
Program controller (extra code)Ten programs with 50 sections can be pro-grammed in the program controller. Each pro-gram can be assigned a program name andan icon.Two setpoint values, section run times, controlcontacts, tolerance bands, cycles, and param-eter blocks can be assigned in each programsection.The tolerance band monitoring function moni-tors the actual value in an adjustable bandaround the setpoint value. The output signal ofthe tolerance band monitoring function can, forexample, also be used to stop the program.
Ramp functionThe ramp function allows a continuous changeof the setpoint value to the ramp end value(setpoint selection) for each controller chan-
nel. After power ON, the ramp starts at the cur-rent value. The slope of the ramp isdetermined via different gradients for a risingand falling ramp. The ramp starts at the timethe setpoint value is changed or at the sametime as a digital signal. The ramp function canbe controlled by digital signals or via the func-tional level.
Limit value monitoring16 limit value monitoring functions are avail-able − each has eight selectable alarm func-tions AF1 to AF8. The limit value can be fixedor dependent on another process variable(setpoint value).A wide range of functions can be realized bymeans of additional parameters such as thelocation and value of the switching differential,on and off delay, pulse function, type of ac-knowledgment, and startup alarm suppres-sion. The startup alarm suppression function,for example, can be used to prevent the limitvalue monitoring function from being triggeredduring the startup phase of a process.
Math and logic function (extra code)The math and logic module allows analog and/or digital signals to be operated. The followingmath formulas are available to the operators:+, -, *, /, SQRT(), MIN(), MAX(), SIN(), COS(),TAN(), **, EXP(), ABS(), INT(), FRC(), LOG(),LN(), humidity and moving average, as well as!, &, |, ^, and ( and ).Difference, ratio, and humidity can also beconfigured on the device without extra code.
Analog inputsThe analog inputs (maximum of four) are uni-versal measuring inputs for RTD temperatureprobes, thermocouples, resistors (resistancetransmitters, potentiometers), and standardsignals (current, voltage). Linearizations forover 20 common measuring probes aresaved. A measurement offset or a fine adjust-ment can be carried out to compensate formachine-specific deviations. Due to the measuring circuit monitoring func-tion, out of range (too high or too low), probe/cable break, and probe/cable short circuit aredetected depending on the type of measuringelement so that the system is switched to asafe operating state (configurable) in the eventof a fault.
Customer-specificlinearizationA customer-specific linearization is additional-ly possible. Programming is carried out withthe aid of the setup program, using a value ta-ble with 40 pairs of values or a fourth-orderpolynomial as a formula.
Analog outputsUp to five analog outputs can be realized in thedevice. They can be used, for example, ascontroller outputs, setpoint value outputs, tooutput results of the math formulas, or as cur-rent value outputs. The signals are freely scal-able.
Digital inputsThe signals of the seven standard digital in-puts (potential-free contacts) can be used toinitiate different internal functions (e.g. switch-ing the parameter block, starting self-optimiza-tion, or acknowledging limit value monitoring).
Digital outputsUp to 12 digital outputs can be realized in thedevice (see block diagram). They can be usedas, for example, controller outputs, limit valuemonitoring signals, results of logic operations,or for programmer signals, etc.
External inputsEight external analog inputs and eight externaldigital inputs can each by read via an inter-face. The unit, range limits, and alarms can beadjusted for the external analog inputs.
TimerTwo timer functions are provided as standard.They can be used as relative timers or asweekly time switches (linked to the real-timeclock).
Binary control signalsThere are eight binary control signals with dif-ferent functions (OR operation, BCD opera-tion, delay, inversion). The results are alsoavailable to control internal functions or theycan be output to digital outputs.
Web server (online visualization)This function is available if the Ethernet inter-face is installed in expansion slot COM2. Alldisplays in the device control ring are automat-ically accessible without configuration.
Alarm transmission by emailAn email alarm can be sent to up to three ad-dresses simultaneously via a mail server.Up to five alarm messages can be configured;the sending process is controlled by digital sig-nals. There are five different alarm messagesfor this. These are linked to specific digital sig-nals from the device.
Recording function (extra code)Four analog channels and three digital chan-nels can be recorded. They appear as line re-corders with a time stamp. The recorder imageis always present. It is only possible to use the"history" function and to extract the registrydata via PCC, PCA by means of the extra code213 recording function.
2012-04-01/00578870
Data Sheet 703571 Page 3/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Setup programThe setup program makes the controller easyto configure and parameterize using a PC.Data sets can thus be created, edited, andtransferred to the controller − and can be ex-tracted from there. The data can be saved andprinted out. The setup program supports mul-tiple languages, including English, Germanand French,
ER8 external relay module (acces-sories)By connecting two ER8 external relay mod-ules, eight relay or digital outputs (12 V/20 mA)can be added to the device in each case. Theyare controlled via an RS422/RS485 interface.The ER8s can be mounted on a DIN rail andmust be configured using the setup program.Two ER8s can be connected.
2012-04-01/00578870
Data Sheet 703571 Page 4/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Display and control elementsThe DICON touch has no control elements. Instead, it can either be operated via a resistive touchscreen, which responds to finger pressure, or byusing conventional pens with a rounded plastic tip.
Data recording and evaluation 213only available with option
Only available with option 223
Alarm/event listDevice settings menu
2 function keys
(Factory switched off)setting: (F )actory setting: switched off
2012-04-01/00578870
Data Sheet 703571 Page 5/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Controller parametersThe parameters and their meanings are listed in the table. Some parameters may be missing or meaningless for a particular type of controller.Three-state controllers have two controller structures that can be parameterized differently for "heating" and "cooling." Four parameter blocks canbe managed for both of the controller channels.
Parameters Value range Factory setting Meaning
Proportional band Xp1 0 to 9999 digits 0 digits Size of the proportional bandThe controller structure has no effect at 0!In the case of a continuous controller, Xp1 and Xp2 must be > 0
Proportional band Xp2 0 to 9999 digits 0 digits
Derivative time Tv1 0 to 9999 s 80 s Influences the differential component of the controller output signal
Derivative time Tv2 0 to 9999 s 80 s
Reset time Tn1 0 to 9999 s 350 s Influences the integral component of the controller output signal
Reset time Tn2 0 to 9999 s 350 s
Cycle time Cy1 0 to 999.9 s 20.0 s When using a switched output, the cycle time should be chosen so that the energy supply to the process is as continuous as possible without overloading the switching elements
Cycle time Cy2 0 to 999.9 s 20.0 s
Contact spacing Xsh 0 to 999.9 digits 0.0 digits Spacing between the two control contacts for three-state controllers, three-state modulating controllers, and continuous controllers with inte-grated position controller
Switching differential Xd1 0 to 999.9 digits 1.0 digit Hysteresis for switching controllers with proportional band = 0
Switching differential Xd2 0 to 999.9 digits 1.0 digit
Actuator time TT 5 to 3000 s 60 s Used run time range of the control valve for three-state modulating con-trollers
Working point Y0 -100 to +100 % 0 % The output level for P and PD controllers (if x = w then y = Y0)
Output level limits Y1 0 to 100 % 100 % The maximum limit for the output level
Output value limits Y2 -100 to +100 % -100 % The minimum limit for the output level
Minimum relay ON time Tk1 0.000 to 60.00 s 0.000 s Limits the frequency of switching for switched outputs
Minimum relay ON time Tk2 0.000 to 60.00 s 0.000 s
2012-04-01/00578870
Data Sheet 703571 Page 6/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Technical data
Analog inputsGeneral
Thermocouples
Standard number Two universal analog inputs
Optional number Two additional universal analog inputs via optional boards
A/D converter Dynamic resolution up to 16-bit
Description Standard Measuring range Measuring accuracya
a The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
Ambienttemperature influence
Fe-CuNi “L” DIN EN 60584 -200 to +900 °C ≤ 0.25 % ≤ 100 ppm/K
Fe-CuNi “J” DIN EN 60584 -200 to +1200 °C ≤ 0.25 % ≤ 100 ppm/K
Cu-CuNi “U” -200 to +600 °C ≤ 0.25 % from -150 °C ≤ 100 ppm/K
Cu-CuNi “T” DIN EN 60584 -200 to +400 °C ≤ 0.25 % from -150 °C ≤ 100 ppm/K
NiCr-Ni “K” DIN EN 60584 -200 to +1372 °C ≤ 0.25 % ≤ 100 ppm/K
NiCr-CuNi “E” -200 to +1000 °C ≤ 0.25 % from -80 °C ≤ 100 ppm/K
NiCrSi-NiSi “N” DIN EN 60584 -100 to +1300 °C ≤ 0.25 % ≤ 100 ppm/K
Pt10Rh-Pt “S” DIN EN 60584 -50 to 1768 °C ≤ 0.25 % ≤ 100 ppm/K
Pt13Rh-Pt “R” DIN EN 60584 -50 to 1768 °C ≤ 0.25 % ≤ 100 ppm/K
Pt30Rh-Pt6Rh “B” DIN EN 60584 0 to 1820 °C ≤ 0.25 % from 300 °C ≤ 100 ppm/K
W5Re-W26Re “C” 0 to 2320 °C ≤ 0.25 % from 500 °C ≤ 100 ppm/K
W3Re-W25Re “D” 0 to 2495 °C ≤ 0.25 % from 500 °C ≤ 100 ppm/K
Chromel®-Copel GOST R 8.585-2001 -200 to +800 °C ≤ 0.25 % from -80 °C ≤ 100 ppm/K
Chromel®-Alumel® GOST R 8.585-2001 -200 to +1372 °C ≤ 0.25 % from -80 °C ≤ 100 ppm/K
PLII (Platinel II) 0 to 1395 °C ≤ 0.25 % ≤ 100 ppm/K
Fe-CuNi "L" GOST -200 to +800 °C ≤ 0.25 % ≤ 100 ppm/K
Smallest measuring span Type L, J, U, T, K, E, N, Chromel®-Alumel®, PL II; 100 KType S, R, B, D, C, W3Re/W26Re, Chromel®-Copel: 500 K
Measuring range start/end Freely programmable within the limits in steps of 0.1 K
Cold junction GOST R Pt100 internal, thermostat constant or external temperature probe
Reference point accuracy (internal) ± 1 K
Reference point temperature (external) Adjustable from 0 to +100 °C
Sampling cycle Controller 1(2): 150 ms in total
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100 s
Galvanic isolation See “Electrical data” on page 5 and “Overview of the galvanic isolation” on page 16
Resolution > 14-bit
Special features Also programmable in °F
2012-04-01/00578870
Data Sheet 703571 Page 7/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
RTD temperature probe
Description Standard Measuring range Measuring accuracya
a The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
Ambienttemperature influence
Pt50Two-wire circuitThree-wire circuit
DIN EN 60751 -200 to +850 °C ≤ 0.1 % ≤ 50 ppm/K
Pt100Two-wire circuitThree-wire circuit
DIN EN 60751 -200 to +850 °C ≤ 0.05 % ≤ 50 ppm/K
Pt500Two-wire circuitThree-wire circuit
DIN EN 60751 -200 to +850 °C ≤ 0.1 % ≤ 50 ppm/K
Pt1000Two-wire circuitThree-wire circuit
DIN EN 60751 -200 to +850 °C ≤ 0.1 % ≤ 50 ppm/K
Ni100Two-wire circuitThree-wire circuit
DIN EN 43760 -60 to +250 °C ≤ 0.1 % ≤ 50 ppm/K
KTY11-6Two-wire circuit
-50 to +150 °C ≤ 1 % ≤ 50 ppm/K
Pt50Two-wire circuitThree-wire circuit
GOST 6651-99 -200 to +850 °C ≤ 0.1 % ≤ 50 ppm/K
Pt100Two-wire circuitThree-wire circuit
GOST 6651-94 -200 to +850 °C ≤ 0.08 %≤ 0.05 %
≤ 50 ppm/K
Cu50Two-wire circuitThree-wire circuit
GOST 6651-94 -50 to +200 °C ≤ 0.05 % ≤ 50 ppm/K
Cu100Two-wire circuitThree-wire circuit
GOST 6651-94 -50 to +200 °C ≤ 0.36 %≤ 0.24 %
≤ 50 ppm/K
Smallest measuring span 15 K
Measuring current Pt100 approx. 250 μA, Pt1000 approx. 100 μA
Sensor lead resistance Max. 10 Ω per cable for two-wire and three-wire circuits
Lead compensation Not required for three-wire circuit. For a two-wire circuit, the lead resistance can be compensated for in the software by correcting the process value.
Measuring range start/end Freely programmable within the limits in steps of 0.1 K
Sampling cycle Controller 1(2): 150 ms in total
Input filter Digital filter, 2nd order; filter time constant can be set from 0 to 100 s
Galvanic isolation See “Electrical data” on page eight and “Overview of the galvanic isolation” on page 16
Resolution > 14-bit
Special features Also programmable in °F
2012-04-01/00578870
Data Sheet 703571 Page 8/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Standard signals
Measuring circuit monitoringIn the event of a fault, the outputs change to defined statuses (configurable).
Digital inputs
Description Measuring range Measuring accuracya
a The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
Ambienttemperature influence
Freely scalable voltageInput resistance RE > 500 kΩInput resistance RE > 100 kΩ
DC 0(2) to 10 VDC 0 to 1 V
≤ 0.1 % ≤ 100 ppm/K
Smallest measuring span 5 mV
Measuring range start/end Freely programmable within the limits in steps of 0.01 mV
Current (voltage drop ≤ 2 V), freely scalable DC 0(4) to 20 mA ≤ 0.1 % ≤ 100 ppm/K
Smallest measuring span 0.5 mA
Measuring range start/end Freely programmable within the limits in steps of 0.01 mA
Underrange/overrange According to NAMUR NE 43
Sampling cycle Controller 1(2): 150 ms in total
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 10.0 s
Galvanic isolation See “Electrical data” on page eight and “Overview of the galvanic isolation” on page 16
Resolution > 14-bit
Resistance transmitter Min. 100 Ω, max. 10 kΩ ≤ 0.5 %b
b The accuracy values refer to the maximum measuring range (initial resistance Ra + loop resistance RS + end resistance Re).
≤ 100 ppm/K
Connection type Resistance transmitter: three-wire circuit
Smallest measuring span 60 ΩSensor lead resistance Max. 10 Ω per cable for two-wire and three-wire circuits
Resistance values Freely programmable within the limits in steps of 0.1 ΩSampling cycle Controller 1(2): 150 ms in total
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100 s
Galvanic isolation See “Electrical data” on page eight and “Overview of the galvanic isolation” on page 16
Resolution > 14-bit
Measuring probe Overrange/underrange Probe/cable short circuit Probe/cable break
Thermocouple ls detected ls not detected ls detected
RTD temperature probe ls detected ls detected ls detected
Voltage2 to 10 V0 to 10 V0 to 1 V
ls detectedls detectedls detected
ls detectedls not detectedls not detected
ls detectedls not detectedls not detected
Current4 to 20 mA0 to 20 mA
ls detectedls detected
ls detectedls not detected
ls detectedls not detected
Resistance transmitter ls not detected ls not detected ls detected
Standard number 7
Control Potential-free contact
2012-04-01/00578870
Data Sheet 703571 Page 9/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Analog outputsPer optional board (OUT3, 5, 7, 9, and OUT11 are possible)
Digital outputsStandard
Per optional board
Controllers
Screen
1 analog output (configurable)12-bit resolution
Load resistance RLast Accuracy Ambient temperature influ-ence
Voltage DC 0(2) to 10 VCurrent DC 0(4) to 20 mA
≥ 500 Ω≤ 500 Ω
±0.25 %±0.25 %
±100 ppm/K±100 ppm/K
Two relay outputs (changeover contact)Switching capacityContact life
3 A at AC 230 V, resistive load150,000 operations at rated load, 350,000 operations at 1 A
1 relay output (changeover contact)Switching capacityContact life
3 A at AC 230 V resistive load350,000 operations at rated load, 750,000 operations at 1 A
2 relay outputs (N/O contact)a
Switching capacityContact life
a A combination of mains-voltage and low-voltage circuits in a two-way N/O contact option is not permitted
3 A at AC 230 V, resistive load350,000 operations at rated load, 900,000 operations at 1 A
1 solid-state relaySwitching capacityProtection circuitry
1 A at 230 Vvaristor
1 logic output (supply voltage for transmitter)
DC 0/22 V max. 30 mA (short-circuit proof)
2 logic outputs DC 0/12 V max. 20 mA (short-circuit proof, not galvanically isolated)
2 PhotoMOS® relaysb
b PhotoMOS is a registered trademark of Panasonic Electric Works Co. Ltd.
DC 50 V, max. 200 mA, (galvanically isolated from each other, not short-circuit proof)AC 35 V, max. 200 mA, (galvanically isolated from each other, not short-circuit proof)
Controller types Inverse/direct two-state controller, three-state controller, three-state modulating con-troller,inverse/direct continuous controller, continuous controller with integrated position controller
Controller structures P, PD, PI, PID
Sampling rate 150 ms
Parameter blocks Four parameter blocks per controller
Resolution, size 320 × 240 pixels, 3.5"
Type, number of colors TFT color screen, 256 colors
Brightness setting Adjustable on the device
Device operation Via resistive touchscreen
Screensaver Via waiting period or control signal
2012-04-01/00578870
Data Sheet 703571 Page 10/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Electrical data
Environmental influences
Case
Approvals / approval marks
Supply voltageConnectionVoltage
At the back via screw terminalsAC/DC 20 to 30 V, 48 to 63 Hz or AC 110 to 240 V +10/-15 %, 48 to 63 Hz
Power consumption At supply voltage 230 V: max. 38.1 VA/11.5 WAt supply voltage 24 V: max. 21.9 VA/11.5 W
Inputs and outputsConnectionConductor cross section
At the back via screw terminalsMax. 2.5 mm2, wire or strand with end sleeve
Electrical safety According to DIN EN 61010-1Overvoltage category III, pollution degree 2
Electromagnetic compatibilityInterference emissionInterference immunity
According to DIN EN 61326-1Class BIndustrial requirement
Ambient/storage temperature range -5 to +55 °C / -30 to +70 °C
Resistance to climatic conditions Humidity 3K3 (DIN EN 61721-3-3 with extended temperature range),rel. humidity ≤ 95 % annual average, no condensation
Electromagnetic compatibilityInterference emissionInterference immunity
According to DIN EN 61326-1Class BIndustrial requirement
Case type Plastic front frame with metal case barrel
Front frame dimensions 96 mm × 96 mm
Panel cut-out 92+0.8 mm × 92+0.8 mm according to DIN IEC 61554
Close mounting Spacing between the panel cut-outs, min. 35 mm horizontally and min. 80 mm verti-cally
Panel thickness Max. 5 mm
Depth behind panel Max. 130 mm
Mounting Four mounting brackets
Operating position(including the viewing angle of the TFT color screen)
AnyHorizontal ±65°, vertical +40 to -65°
Protection type Front IP66, rear IP20, according to DIN EN 60529
Weight (fully fitted) Approx. 1000 g
Approval mark Testing agency Certificate/certification number
Inspection basis Valid for
GL - hardwareGL - software
Germanischer Lloyd Approval submitted Environmental Category CEMC 1
All devices
c UL us Underwriters Laboratories Approval submitted UL 61010-1 All devices
GOST Approval submitted All devices
2012-04-01/00578870
Data Sheet 703571 Page 11/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Connection elements
(1) Analog input IN8 (2) Analog input IN9
(3) Expansion slot for analog input IN10 (4) Expansion slot for analog input IN11
(5) Supply voltageAC 240 V +10/-15 %, 48 to 63 HzAC/DC 20 to 30 V, 48 to 63 Hz
(6) Relay output OUT2
(7) Relay output OUT1 (8) Expansion slot for outputs OUT3/4
(9) Expansion slot for outputs OUT5/6 (10) Expansion slot for outputs OUT7/8
(11) Expansion slot for outputs OUT9/10 (12) Expansion slot for outputs OUT11/12
(13) COM1 interface RS485 (14) Expansion slot for COM2 interface
(15) Digital inputs IN1 to 7
2012-04-01/00578870
Data Sheet 703571 Page 12/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Galvanic isolation
Voltage supplyAC/DC 20 ... 30 V
Analog output
Relay outputs
PROFIBUSRS422/485
Ethernet
Digital 1input
Analog IN11input
Analog input IN8
DC 50 VAC 30 V
�
1 Solid state relay outputAC 250 V, 1 A
AC 2300 V
�
Voltage supplyAC 240 V
1DC 0/22 V, max. 30 mA(short-circuit proof)
Logic output
2 Logic outputsDC 0/12 V, max. 20 mA(short-circuit proof)
Digital(potential freecontact)
7input
DC 50 VAC 30 V
�
DC 50 VAC 30 V
�
DC 50 VAC 30 V
�
AC 2300 V
�
AC 2300 V
�
AC 2300 V
�
DC 50 VAC 30 V
�
DC 50 VAC 30 V
�
DC 50 VAC 30 V
�
2 PhotoMOS® solid state relayU = DC 50 V, I = 200 mAmax. max.
U = AC 35 V, I = 200 mAmax. max.
DC 50 VAC 30 V
�
�
2012-04-01/00578870
Data Sheet 703571 Page 13/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Connection diagramThe connection diagram included in the data sheet provides initial information about the connection options. Only use the installation instructionsor the operating manual for the electrical connection. The know-how and the correct technical implementation of the safety warnings/instructionscontained in these documents are the prerequisite for the installation, electrical connection, and initial start as well as for the safety during opera-tion.
Analog inputsInput IN8, IN9 as standardTwo analog inputs can be added to input (IN10), (IN11) optional boards
Analog outputsOne analog output can be added to output OUT 3/4 to 11/12 using optional boards
Connection (Connection ele-ment)Input
Symbol and terminal designation
Thermocouple (1) IN8(2) IN9(3) IN10(4) IN11
3
4
RTD temperature probeTwo-wire circuit
2
4
RTD temperature probeThree-wire circuit
2
3
4
Voltage DC 0(2) to 10 V 1
4
Voltage DC 0 to 1 V 2
4
Current DC 0(4) to 20 mA 3
4
Resistance transmitter
A = StartE = EndS = Slider
2
3
4
Connection (Connection ele-ment)Input
Symbol and terminal designation
One analog outputDC 0/2 to 10 V or DC 0/4 to 20 mA(configurable)
(8) OUT3/4(9) OUT5/6(10) OUT7/8(11) OUT9/10(12) OUT11/12
1
2
U+
-x
U+
-x
I+
-x
E
S
A
+
-x IxU ,
2012-04-01/00578870
Data Sheet 703571 Page 14/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Digital inputsInput IN1 to 7 as standard (cannot be extended)
Digital outputsOUT1 and OUT2 as standardThe controller is fitted with two relay outputs (changeover contacts) as standard.
Connection (Connection ele-ment)Input
Symbol and terminal designation
Digital input, potential-free contactas standard
(15) IN1 to 7 3, 4, 5, 6, 7, 8, 9
10
Connection (Connection ele-ment)Output
Symbol and terminal designation
Relay output (changeover contact) (6) OUT2(7) OUT1
1
2
3
2012-04-01/00578870
Data Sheet 703571 Page 15/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Outputs OUT 3/4 to 11/12 can be expanded using the following optional boards
Connection (Connection ele-ment)Output
Symbol and terminal designation
1 relay output (changeover contact) (8) OUT3/4(9) OUT5/6(10) OUT7/8(11) OUT9/10(12) OUT11/12
1
2
3
2 relay outputs (N/O contact)1
2
3
4
1 solid-state relayAC 230 V, 1 A
1
2
1 logic output DC 0/22 V max. 30 mA(short-circuit proof)
1
2
2 logic outputs DC 0/12 V max. 20 mA(short-circuit proof, not galvanically isolated from each other)
1
2
3
4
2 PhotoMOS® relaysa
max. DC 50 V, 200 mAmax. AC 35 V, 200 mA(galvanically isolated)
a PhotoMOS is a registered trademark of Panasonic Electric Works Co. Ltd.
1
2
3
4
P
P
+
-x IxU ,
+
-x IxU ,
+
-x IxU ,
2012-04-01/00578870
Data Sheet 703571 Page 16/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
InterfacesUSB device, USB host and COM1 interfaces as standard
COM2 interface can be expanded using optional boards
Connection (Connection ele-ment)
Symbol and terminal designation
USB device interface (setup)
(21)
USB host (firmware update)
(20)
COM1 serial interface RS485(galvanically isolated)
(13) 1 TxD+/RxD+2 TxD-/RxD-
Transmission/received data +Transmission/received data -
Connection (Connection ele-ment)
Symbol and terminal designation
Ethernet (14) 1 TX+2 TX-3 RX+6 RX-
Transmission data +Transmission data -Received data +Received data -
Serial interface RS422(galvanically isolated)
1 RxD+2 RxD-3 TxD+4 TxD-
Received data +Received data -Transmission data +Transmission data -
Serial interface RS485(galvanically isolated)
3 TxD+/RxD+4 TxD-/RxD-
Transmission/received data +Transmission/received data -
PROFIBUS-DP 3 RxD/TxD-P (B)5 DGND6 VP (+5 V)8 RxD/TxD-N (A)
Transmission/received data +GroundVoltage supplyTransmission/received data -
81
6 7 8 9
2 3 4 51
2012-04-01/00578870
Data Sheet 703571 Page 17/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Dimensions
Scope of delivery• 1 controller in the ordered version• 1 operating manual B 703571.0• 1 panel seal 4 retaining elements for panel installation
(20) USB host interface (21) USB device interface for setup
(22) Panel cut-out
92 +0.8
92+
0.8 (22)
(20) (21)
130.9 - panel thicknessPanel thickness
2012-04-01/00578870
Data Sheet 703571 Page 18/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Order details(1) Basic type
703571 JUMO DICON touch - two-channel process and program controller with RS485 interface
(2) Version
8 Standard with factory settings
9 Customer-specific configuration (specifications in plain text)
(3) National language of display texts
01 German
02 English
03 French
(4) Input 3 (IN10)
00 Not used
10 Analog input (universal)
(5) Input 4 (IN11)
00 Not used
10 Analog input (universal)
(6) Output 3 (OUT3/4)
00 None
11 1 relay (changeover contact)
12 2 relays (N/O contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays®a
(7) Output 4 (OUT5/6)
00 None
11 1 relay (changeover contact)
12 2 relays (N/O contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(8) Output 5 (OUT7/8)
00 None
11 1 relay (changeover contact)
12 2 relays (N/O contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(9) Output 6 (OUT9/10)
00 None
11 1 relay (changeover contact)
12 2 relays (N/O contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
2012-04-01/00578870
Data Sheet 703571 Page 19/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
17 2 PhotoMOS® relays
(10) Output 7 (OUT11/12)
00 None
11 1 relay (changeover contact)
12 2 relays (N/O contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(11) Supply voltage
23 AC 110 to 240 V +10/-15 %, 48 to 63 Hz
25 AC/DC 20 to 30 V, 48 to 63 Hz
(12) COM2 interface
00 Not used
08 Ethernet
54 RS422/485 Modbus RTU
64 PROFIBUS-DP
(13) DIN-tested
000 Without approval
056 With DIN approval
(14) GL-tested
000 Without approval
062 With GL approval
(15) Extra codes
000 Without extra code
213 Recording function
214 Math and logic module
223 Program controller
a PhotoMOS is a registered trademark of Panasonic Electric Works Co. Ltd.
(1) / (2) - (3) - (4) (5) - (6) (7) (8) (9) (10) - (11) - (12) / (13) , (14) , (15)
Order code / - - - - - / , , , ...a
a List extra codes in sequence, separated by commas.
Order example 703571 / X - X - X X - X X X X X - X - X / X , X , X
2012-04-01/00578870
Data Sheet 703571 Page 20/20
JUMO GmbH & Co. KGDelivery address: Mackenrodtstraße 14
36039 Fulda, GermanyPostal address: 36035 Fulda, GermanyPhone: +49 661 6003-0Fax: +49 661 6003-607E-mail: [email protected]: www.jumo.net
JUMO Instrument Co. Ltd.JUMO HouseTemple Bank, RiverwayHarlow, Essex CM20 2DY, UKPhone: +44 1279 635533Fax: +44 1279 635262E-mail: [email protected]: www.jumo.co.uk
JUMO Process Control, Inc.6733 Myers RoadEast Syracuse, NY 13057, USAPhone: 315-437-5866
1-800-554-5866Fax: 315-437-5860E-mail: [email protected]: www.jumousa.com
Accessories
General accessories
Article Part no.
Assembly groups for option slots:
1 analog input (universal) 00581159
1 relay output (changeover contact) 00581160
2 relay outputs (N/O contact) 00581162
1 logic output DC 0/22 V max. 30 mA 00581165
2 logic outputs DC 0/12 V max. 20 mA 00581168
1 solid-state relay AC 230 V, 1 A 00581164
2 PhotoMOS® relaysa
DC 50 V, max. 200 mA,AC 35 V, max. 200 mA
a PhotoMOS is a registered trademark of Panasonic Electric Works Co. Ltd.
00581171
1 analog output (universal) 00581169
Ethernet interface 00581174
Serial interface RS422/RS485 00581172
PROFIBUS-DP interface 00581173
Article Part no.
DVD with setup program and program editor