Dialog Plus Rack

download Dialog Plus Rack

of 2

Transcript of Dialog Plus Rack

  • 8/6/2019 Dialog Plus Rack

    1/2

    The DIALOG PLUS RACK series comprises the 700-1000-1500-2000-3000VA models and uses doubleconversion technology (VFI).The load is powered continuously by the inverter withan EMI ltered, stabilised and regulated sinewave supply.The input and output EMI lters considerably increasethe immunity of the load to mains disturbances andsurges, even on bypass.The UPS can power the load for long periods (usingbattery extension packs) or provide suf cient runtimeto allow shut-down of the protected computer systemsusing the PowerShield software, supplied as standard,for Windows 95, 98, 2000, Me, XP, Mac OSx, 9.x, LinuxNT 4.0 operating systems.For outstanding power protection and communicationDIALOG PLUS RACK is the best solution for sensitiveand mission-critical applications.

    2-YEAR WARRANTY

    CHARACTERISTICS reliable, stabilized, ltered voltage (double on-line

    conversion technology (VFI according to EN50091-3 speci cations) with lters for the suppression ofatmospheric disturbances

    high level immunity to surges (6kV according to IEC801-5) auto restart at power-up (programmable) power factor correction of the load (UPS input power

    factor, close to 1) low power consumption (programmable Auto

    Power Off function for automatic shut-down of theUPS under no-load conditions)

    simpli ed maintenance battery optimisation: using the Power Share

    function - DLPR70 and DLPR100 - for automatic,software-programmable disconnection of non-criticalloads, after 1 minute of battery back-up or on low

    battery alarm scheduled for timed shut-down (software programmable) high level reliability of the batteries (automatic battery test) high level reliability of the UPS (full microprocessor control) low impact on the mains supply (sinusoidal

    absorption).

    ADVANCED COMMUNICATION advanced, multi-platform communication for all

    operating systems and network environments:PowerShield supervision and shut-down softwareincluded, with SNMP agent, for Windows 95, 98,2000, Me, XP, NT 4.0, Novell, Linux, Mac Os X, MacOs 9.x operating systems. The UPS is equippedwith a cable for direct connection to the PC (Plugand Play)

    RS232 serial port.

    Local Area Networks (LAN)ServersData centersIndustrial PLCsCash registersEmergency devices (lights/alarms)Telecommunication devices

    DIALOG Plus Rack700-3000VA single-phase

    NET-TELRANGE

  • 8/6/2019 Dialog Plus Rack

    2/2

    MODELS DLPR 70 DLPR 100 DLPR 150 DLPR 200 DLPR 300POWER 700VA/450W 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100WINPUTRated voltage 220/230/240 VacInput range 170-276 VacRated frequency 50/60 Hz 5HzFrequency 50 HzMinimum voltage without batteryintervention

    170 Vac (140 Vac with load 50%)

    Maximum current (A) 3.5 5 7.4 10 14.4Rated current (A) 2.5 3.5 5.2 6.8 10.2Power factor > 0.93 > 0.99

    BY PASSVoltage tolerance static 2%Frequency tolerance 0,5%BATTERIESType Maintenance-free sealed lead-acidRecharge time 5 - 7 h 4 - 6 h 5 - 7 hOUTPUTRated voltage 230 Vac selectable 1.5% 220/230/240 Vac selectable 1,5%Waveform SinewaveVoltage distortion < 2%Frequency autoranging 50 or 60 Hz selectableFrequency tolerance 0,5 %Crest factor (Ipeak/Irms) 3 : 1 (up to 100% of load)Overload 150 % In per 2sOutput sockets 2 IEC 320 10A 4 IEC 320 10A 4 IEC 320 10A + 1

    IEC 320 16AENVIRONMENTALAC/AC Ef ciency 89% 90%Batteries (n/V/Ah) 2/12/7 3/12/7 5/12/7 6/12/7 10/12/7Interface ports RS 232Operating temperature 0 - 40 C, ideal for battery +15 -25 CHumidity < 90% non condensingProtection Overload - short-circuit - overvoltage - undervoltage - temperature - low batterySafety compliance EN 50091-1-1 and Directive 73/23/EEC EN 50091 - 2 cl. B and Directive 89/336/EECSurge capability IEC 801-5 6 KV 1.2 / 50 s; 3KA 8/20 s

    Colour Dark grey RAL 5004Noise