109/4 Fire Resistant Cables SR 114H Standard - SR 114E Enhanced BS 5839-1 BS 7629-1 BS 6387 BS 8434-1/2 BS 6425 BS 7622 EN 50200

Transcript of df.pdf

Page 1: df.pdf

109/4

Fire

Res

ista

nt C

able

sSR

114H

Sta

ndar

d - S

R 1

14E E

nhan

ced

BS 5839-1BS 7629-1BS 6387

BS 8434-1/2BS 6425BS 7622

EN 50200

Page 2: df.pdf

Firecel SR114 are used in: Data Communication Centres Control Rooms Shopping Centres Hotels Theatres Cinemas Airports Underground Stations

Tunnels Traffic Control Centres Public Address System Marine and Offshore Fire Fighting Systems

The images below show some relevant installations equipped with Firecel cables.

Quality SystemCertificationAssessed to ISO 9001: 2000Certificate number 217

Product CertificationProduct Certificates No. 217f / 217g assessed to BS 7629-1and BS 5839-1: 2002

World-wide recognized high quality cables…

1 Park Tower - Dubai 7 Combined-Cycle Power Plant Komotini - Greece

2 Tupras Izmir Refinery - Turkey 8 Atlantis Hotel - Palm Jumeirah - Dubai

3 Tsing Ma Bridge - Hong Kong 9 New Delhi Metro - India

4 Financial Center - Abu Dhabi 10 Scottish Exhibition & Conference Centre Glasgow - UK

5 Emerald Palace - Palm Jumeirah - Dubai 11 Reebok Stadium - Bolton - UK

6 Airport Terminal 3 - Dubai 12 Rose Rotana Tower - Dubai

Page 3: df.pdf

In order to study new cables, new constructions, verify and certify the required performances, Cavicel has now a new well equipped Fire Laboratory.All Firecel cables can be fully tested according to international standards related to behaviour under fire condition.All test reports are registered in our files and, if required, cables can be supplied with Test Reports and Declaration of Compliance.The pictures below are taken in Cavicel Fire Laboratory and show some tests performed in our laboratory.

...tested and certified by our Fire Laboratory

1 Resistance to fire alone BS 6387 Cat. C, IEC 60331, CEI 20-36 5 Flame retardant test on bunched cables

IEC 60332-3, BS 4066: part 3 9 & 10Test on gas evolved during combustionIEC 60754 part 1-2, BS 6425 part 1-2, EN 50267/2-1 and 2-2

2 Resistance to fire with mechanical shockBS 6387 Cat. X Y Z 6 Cavicel Fire Laboratory 11 Ongoing fire test

3 Resistance to fire with water sprayBS 6387 Cat. W 7

Smoke density testIEC 61034-2, BS 6724, CEI 20-37/3, BS 7622, EN 50268-1 For more information about Fire Tests

see our catalogue Nr. 103.4 Flame retardant test on single wire

CEI 20-35/1, IEC 60332-1, BS 4066 part 1 8 Resistance to fire, mechanical shock and water - BS 5839-1, BS 8434

Page 4: df.pdf

Recommendation for two levels of fire resistance:

• Standard for general use

Firecel SR 114HEN 50200 PH30Temperature: 830 °CFlame and shock for 30 min.BS 8434-1: 2003Temperature: 830 °CFlame and shock for 15 min. + flame, shock and water for 15 min.

• Enhanced when cables might need to operate correctly during a fire for periods in excess of those normally required for single phase evacuation of building

Firecel SR 114EEN 50200 PH120Temperature: 830 °CFlame and shock for 120 min.BS 8434-2: 2003Temperature: 930 °CFlame and shock for 60 min. + flame, shock and water for 60 min.

BS 5839-1 : 2002 recommends “enhanced” fire resistant cables for the following applications:

• in unsprinklered buildings (or parts of buildings) in which the fire strategy involves evacuation of occupants in four or more phases;

• in unsprinklered buildings of greater than 30 m in height;

• in unsprinklered premises and sites in which a fire in one area could affect cables of critical signal paths associated with areas remote from fire, in which it is envisaged people will remain in occupation during the course of the fire;

• in any other buildings in which the designer, specifier or regulatory authority, on the basis of a fire risk assessment that takes fire engineering considerations into account, considers that the use of enhanced fire resisting cables is necessary.

For more information we recommend to consult BS 5839-1 par. 26.

BS 5839-1 : 2002Fire Detection and Fire Alarm Systems for BuildingsPart 1: code of practice for system design, installation, commissioning and maintenancePar. 26 Cables, wiring and other interconnections

Requirements for Circuit Integrity

Standard Enhanced Cables

Features and AdvantagesFlexibleVery flexible construction that makes the installation easier in all conditions.

LSZH (Low Smoke Zero Halogen) ConstructionCombustion gases with very low toxicity, low smoke emission, and no corrosive gas, for the safeguard of human life and electronic equipment.

Flame retardantLimiting the spread of the fire along the cable run, flame barriers can be avoided or reduced.

Protected against electrostatic noiseCable is fully screened and conductors are twisted.

Moisture ResistantNo special terminations are required to prevent moisture absorption. It can be installed in damp environments.

Suitable for data transmissionTwisting of conductors make the cable suitable for clear data transmission.

Low cost installationNo special tools and special training are neccessary. A cheap and effective cable stripper is available to simplify installation. Easy to handle.

Quality AssuranceIn order to satisfy QA requirements, traceability is assured by batch number printed on outer jacket. All reels have the evidence of testing.

Page 5: df.pdf

Cable InstallationAmbient TemperatureFirecel cables are easy to install also at temperature as low as –10 °C.Storage temperature: –40 °C to +80 °C.

Bending RadiusMinimum 6 times the nominal diameter of the cable.

InstallationCable is easy to handle and easy to install without special tools. Cable can be fixed direct to a surface using LSZH coated copper P clips, available together with cables. Plastic clips must not be used. Cable can also be installed in cable tray or in conduits, or direct buried in plaster. Suitable for outdoor installation too, in appropriate protected environments.

GlandsFor standard installation, general purpose nylon glands can be used. In explosion proof area suitable proof glands can be used with armoured cables.

Available colours: white/red.

Nylon Gland Nylon LocknutSize Ref. Packed Ref. Packed

10 mm MP10 100 ML10 10016 mm MP16 100 ML16 10020 mm MP20 100 ML20 10025 mm MP25 100 ML25 10032 mm MP32 100 ML32 100

Current Ratings and Voltage Drop1

installation method: clipped direct installation method: in conduit or in cable tray1 two-core cable 1 three/four-core cable 1 two-core cable 1 three/four-core cable

Size of conductor

currentrating

voltage drop

x A x mcos = 1

currentrating

voltage drop

x A x mcos = 1

currentrating

voltage drop

x A x mcos = 1

currentrating

voltage drop

x A x mcos = 1

(sqmm) A mV A mV A mV A mV1.0 19 45 17 39 17 45 15 391.5 24 30 22 26 22 30 19.5 262.5 33 18 30 15 30 18 26 154.0 45 11 40 10 40 11 35 10

1 Conductor operating temperature: 90 °C; Ambient temperature: 30 °C.

Rating FactorsAmbient temp. (°C) 25 30 35 40 45 50 55 60 65Rating factor 1.04 1.00 0.95 0.90 0.85 0.80 0.74 0.67 0.60For groupingNumber of cables 2 3 4 5 6 8 10 12 14 16 18 20Rating factor 0.80 0.70 0.65 0.60 0.57 0.52 0.48 0.45 0.43 0.41 0.39 0.38

Colours

Insulation2 core + E blue brown3 core + E brown black grey4 core + E blue brown black grey7 cores* centre brown

1st layer brown black 4 white12 cores* centre brown black white

1st layer brown black 7 white19 cores* centre brown

1st layer brown black 4 white2nd layer brown black 10 white

Jacketwhite / red / orange / black. Different colours upon request.

*on request the cores can be identified by printed numbers.

ArmouringFirecel cables can be supplied with:

SWA Steel Wire Armour SWB Steel Wire Braid

Page 6: df.pdf

FIRECEL® SR 114H is the long and well established CAVICEL fire resistant cable in the market, since many years.These cables are third party approved by LPCB which certify that FIRECEL® SR 114H cables have complied with the requirements of the following:

BS 7629-1:2008 - 300/500 V fire resistant electric cables having low emission of smoke and corrosive gases when affected by fire - Multicore cables;

Standard fire resistant cables as described in Clause 26.2d) of BS 5839-1:2002 - Fire detection and alarm systems for buildings. Code of practice for system design, installation, commissioning and maintenance;

and achieved:

Class PH30 when tested in accordance with BS EN 50200 - Method of test for resistance to fire of unprotected small cables for use in emergency circuits.

High performance silicone rubber EI 2 to BS 7655:

section 1.1

Aluminium/polyester tape 125% coverage

Thermoplasticzero halogen,

low smoke,flame retardant,

abrasion resistantType LTS3 to

BS 7655: section 6.1

Plain annealed copper to BS 6360• Solid (class 1) for

1 - 1,5 - 2,5 sqmm*• Stranded (class 2)

for 4 sqmm* 1,5 - 2.5 sqmm are available

with stranded conductor (class 2) (SR 114H - R)

Tinned annealed copper to BS 6360 (drain wire for multicore cables)

Electrostatic Screen

Sheath

Conductor

Earth Conductor

Insulation

Electrical CharacteristicsVoltage rating

single or three phase circuit up to 300/500 V r.m.s.

or up to 750 V d.c. circuit

Temperature rating- for insulated conductors only

–40 ÷ +90 °Cmax +200 °C

Cross section (sq mm) 1 1.5 2.5 4

Conductor resistance (Ω / km at 20 °C) 18.1 12.1 7.41 4.61

Insulation resistance (MΩ x km at 20 °C) 300 300 300 300

Nominal Capacitance (pF / m)

- core/core 100 110 130 160

- core/screen 170 190 220 270

Physical CharacteristicsNr. of conductors x section

Size of cond.

Size ofearth wire

Finaldiameter

Netweight

P clips type

(sqmm) (nr./mm) (nr./mm) (mm) (kg/km)

2 x 1.0 1/1.13 1/1.13 7.1 80 AC7

3 x 1.0 1/1.13 1/1.13 8.0 95 AC8

4 x 1.0 1/1.13 1/1.13 8.3 115 AC9

2 x 1.5 1/1.38 1/1.38 8.0 95 AC8

3 x 1.5 1/1.38 1/1.38 8.5 115 AC9

4 x 1.5 1/1.38 1/1.38 9.4 150 AC11

2 x 2.5 1/1.75 1/1.75 9.4 135 AC11

3 x 2.5 1/1.75 1/1.75 10.0 170 AC11

4 x 2.5 1/1.75 1/1.75 11.0 210 AC12

2 x 1.5 7/0.53 7/0.53 8.4 106 AC8

3 x 1.5 7/0.53 7/0.53 8.9 134 AC9

4 x 1.5 7/0.53 7/0.53 9.8 166 AC11

2 x 2.5 7/0.67 7/0.67 9.9 145 AC11

3 x 2.5 7/0.67 7/0.67 10.3 180 AC11

4 x 2.5 7/0.67 7/0.67 11.8 250 AC12

2 x 4.0 7/0.85 7/0.85 11.5 210 AC12

3 x 4.0 7/0.85 7/0.85 12.2 260 AC13

4 x 4.0 7/0.85 7/0.85 13.5 330 AC14

7 x 1.0 1/1.13 1/0.80* 10.0 165 AC11

7 x 1.5 1/1.38 1/0.80* 11.3 225 AC12

12 x 1.0 1/1.13 1/0.80* 12.5 255 AC13

12 x 1.5 1/1.38 1/0.80* 14.5 350 AC15

19 x 1.0 1/1.13 1/0.80* 15.0 380 AC16

19 x 1.5 1/1.38 1/0.80* 17.0 520 AC16

* drain wireNOTE: cables up to 4 cores = Standard Products LPCB Approved.

Page 7: df.pdf

Electrical CharacteristicsVoltage rating

single or three phase circuit up to 300/500 V r.m.s.

or up to 750 V d.c. circuit

Temperature rating- for insulated conductors only

–40 ÷ +90 °Cmax +200 °C

Cross section (sqmm) 1 1.5 2.5 4

Conductor resistance (Ω / km at 20 °C) 18.1 12.1 7.41 4.61

Insulation resistance (MΩ x km at 20 °C) 300 300 300 300

Nominal Capacitance (pF / m)

- core/core 95 100 120 150

- core/screen 160 170 200 250

Physical CharacteristicsNr. of conductors x section

Size ofcond.

Size ofearth wire

Finaldiameter

Netweight

P clips type

(sqmm) (nr./mm) (nr./mm) (mm) (kg/km)

2 x 1.0 1/1.13 1/1.13 7.9 85 AC8

3 x 1.0 1/1.13 1/1.13 8.4 105 AC9

4 x 1.0 1/1.13 1/1.13 9.3 125 AC11

2 x 1.5 1/1.38 1/1.38 8.8 105 AC11

3 x 1.5 1/1.38 1/1.38 9.3 130 AC11

4 x 1.5 1/1.38 1/1.38 10.3 165 AC11

2 x 2.5 1/1.75 1/1.75 10.2 150 AC11

3 x 2.5 1/1.75 1/1.75 10.8 190 AC11

4 x 2.5 1/1.75 1/1.75 12.0 240 AC12

2 x 1.5 7/0.53 7/0.53 9.2 110 AC9

3 x 1.5 7/0.53 7/0.53 9.4 135 AC11

4 x 1.5 7/0.53 7/0.53 10.5 170 AC11

2 x 2.5 7/0.67 7/0.67 10.3 155 AC11

3 x 2.5 7/0.67 7/0.67 10.9 190 AC11

4 x 2.5 7/0.67 7/0.67 12.1 250 AC12

2 x 4.0 7/0.85 7/ 0.85 12.2 220 AC12

3 x 4.0 7/0.85 7/0.85 13.0 280 AC13

4 x 4.0 7/0.85 7/0.85 14.4 350 AC15

7 x 1.0 1/1.13 1/0.80* 10.5 175 AC11

7 x 1.5 1/1.38 1/0.80* 12.1 230 AC12

12 x 1.0 1/1.13 1/0.80* 14.5 300 AC14

12 x 1.5 1/1.38 1/0.80* 16.0 380 AC16

19 x 1.0 1/1.13 1/0.80* 17.5 470 AC18

19 x 1.5 1/1.38 1/0.80* 19.3 590 AC19

* drain wireNOTE: cables up to 4 cores = Enhanced Products LPCB Approved.

FIRECEL® SR 114E are third party approved by LPCB which certify that FIRECEL® SR 114E cables have complied with the requirements of the following:

BS 7629-1:2008 - 300/500 V fire resistant electric cables having low emission of smoke and corrosive gases when affected by fire - Multicore cables;

Enhanced fire resistant cables as described in Clause 26.2e) of BS 5839-1:2002 - Fire detection and alarm systems for buildings. Code of practice for system design, installation, commissioning and maintenance;

and achieved:

Class PH120 when tested in accordance with BS EN 50200 - Method of test for resistance to fire of unprotected small cables for use in emergency circuits.

Mica tape plus high performance silicone rubber EI 2

to BS 7655: section 1.1

Aluminium/polyester tape 125% coverage

Thermoplasticzero halogen,

low smoke,flame retardant,

abrasion resistantType LTS3 to

BS 7655: section 6.1

Plain annealed copper to BS 6360

• Solid (class 1) for 1 - 1,5 - 2,5 sqmm*

• Stranded (class 2) for 4 sqmm

* 1.5 - 2.5 sqmm are available with stranded conductor (class 2)

Tinned annealed copper to BS 6360 (drain wire for multicore cables)

Electrostatic Screen

Sheath

Conductor

Earth Conductor

Insulation

7

Page 8: df.pdf

CaviCel Spa 20096 Pioltello (Milano) - italy Via Caduti del Lavoro, 18/Aph. +39 - 02 - 921.605.21 fax +39 - 02 - 921.607.53e-mail: [email protected]

CAVICEL firmly believes in the importance of the quality of its products and it undertakes itself to produce them using clean technologies for the respect and the protection of the environment.

FIRECEL® is a CAVICEL registered trademark.All information contained in this brochure is believed to be accurate. Specifications can change at any time, according to technical developments and market changes.