Design Consider ations, Modeling and Control of Dual Active Full … · Electric Vehicles Charging...

10
1 Design Considerations, Modeling and Control of Dual Active Full Bridge for Electric Vehicles Charging Applications Fatma Jarraya, Ahmad Khan, Adel Gastli, Lazhar Ben-Brahim, Ridha Hamila Electrical Engineering Department, College of Engineering, Qatar University, P.O. Box 2713, Doha, Qatar * [email protected] Abstract: The Dual Active Full Bridge (DAFB) is one of the promising isolated DC/DC converter topologies that will play a significant role in the future of Electric Vehicle (EV) integration in Smart Grids (SGs). This is due to its inherent soft switching and control simplicity. Therefore, this paper presents first the latest developments related to the design of DAFB converter in EV charging technology. It provides a brief discussion of the crucial recommendations regarding the reliability, efficiency, system configuration, EV charger control scheme, battery lifetime and system materials. Then, it presents a step-by-step modelling approach for a non-ideal DAFB for the purpose of designing its controller. In addition, the model provided by this paper includes all non-idealities due to the High Frequency (HF) transformer, semiconductor switches, passive components and digital system delays. Eventually, the proposed system design and analysis was validated by implementing a 6.1kW prototype on Simulink and Typhoon-HIL real-time simulator. 1 Introduction 1.1 Motivation and incitement The environment and their increasing cost lead to the accelerating growth in Electric Vehicles (EV) technology [1]-[3]. The EVs importance in integration with Smart Grids (SGs) is that they tackle the issues of inherent intermittence and randomness in renewable energy sources by providing a power management solution [4]. Even though, in systems without renewable energy integrations the benefit of using the vehicle battery as a temporary storage is non-existing; still EV bidirectional chargers offer a promising solution to support the power grid during peak demand and contingencies through Vehicle-to-Grid (V2G) battery discharging operation mode [5]-[8]. In SGs, bidirectional EV battery charger is the key interface that controls the different power-flow modes Grid-to-Vehicle (G2V) or/and V2G [9]- [12]. 1.2 Literature review The general common structure of a bidirectional EV battery charging system is shown in Fig. 1 [13]. Fig. 1. Overall block diagram of bidirectional EV charger. The system is mainly composed of bidirectional DC/DC converter cascaded with a bidirectional AC/DC converter (PWM single-phase or three-phase converter). Generally, the most appropriate bidirectional AC/DC converter topology used in this application is the Full-Bridge inverter either three-phase or single-phase topology as it does not require any Power Factor Correction (PFC) circuitry and control [13]. Thus, this paper focuses on the design and control aspects of the bidirectional DC/DC converter that provides the suitable interface between the utility grid and the EV battery. Besides, in G2V and V2G applications, non-isolated (transformerless) designs are not preferred due to the following reasons: Leakage current circulation increases hazards risks which led the EV grid-integration standards to emphasize on isolation requirement for safety assurance [13]-[14]. Large mismatch between the battery and grid nominal voltages. Therefore, matching the voltage levels without using transformers would require increasing the number of batteries connected in-series [15], [16]. However, this increases the probability of batteries State of Charge (SoC%) mismatch occurrences [17]. Therefore, his paper will focus only on the isolated configuration of the Dual Active Full Bridge (DAFB) utilizing a High-Frequency (HF) transformer. 1.3 Contribution and paper organization This paper discusses the design considerations for the DAFB used as a bidirectional EV battery charger. It also presents a modeling approach applied to the DAFB topology with its control techniques. The developed DAFB model and its control techniques are implemented and validated under both G2V and V2G operations using Matlab/Simulink and Hardware in the Loop (HIL). The power flow dynamics and the converter efficiency are also investigated under various operating scenarios. This paper is therefore structured as follows: section 2 presents an overview of the DAFB design considerations and features in-light of G2V and V2G applications; section 3 elaborates on the DAFB converter modeling approach; section 3 discusses key recommendations and design considerations on using the DAFB in EV charging applications; section 5 discusses the simulation and experimental results; finally, section 5 concludes the paper. Power Grid Bidirectional AC-DC Converter Bidirectional DC-DC Converter = = = EV Battery DAFB V2G mode (Discharging G2V mode (Charging mode) ReView by River Valley Technologies The Journal of Engineering 2019/05/31 15:41:05 IET Review Copy Only 2 This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

Transcript of Design Consider ations, Modeling and Control of Dual Active Full … · Electric Vehicles Charging...

  • 1

    Design Considerations, Modeling and Control of Dual Active Full Bridge for Electric Vehicles Charging Applications

    Fatma Jarraya, Ahmad Khan, Adel Gastli, Lazhar Ben-Brahim, Ridha Hamila

    Electrical Engineering Department, College of Engineering, Qatar University, P.O. Box 2713, Doha, Qatar *[email protected]

    Abstract: The Dual Active Full Bridge (DAFB) is one of the promising isolated DC/DC converter topologies that will play a significant role in the future of Electric Vehicle (EV) integration in Smart Grids (SGs). This is due to its inherent soft switching and control simplicity. Therefore, this paper presents first the latest developments related to the design of DAFB converter in EV charging technology. It provides a brief discussion of the crucial recommendations regarding the reliability, efficiency, system configuration, EV charger control scheme, battery lifetime and system materials. Then, it presents a step-by-step modelling approach for a non-ideal DAFB for the purpose of designing its controller. In addition, the model provided by this paper includes all non-idealities due to the High Frequency (HF) transformer, semiconductor switches, passive components and digital system delays. Eventually, the proposed system design and analysis was validated by implementing a 6.1kW prototype on Simulink and Typhoon-HIL real-time simulator.

    1 Introduction

    1.1 Motivation and incitement

    The environment and their increasing cost lead to

    the accelerating growth in Electric Vehicles (EV) technology

    [1]-[3]. The EVs importance in integration with Smart Grids

    (SGs) is that they tackle the issues of inherent intermittence

    and randomness in renewable energy sources by providing a

    power management solution [4]. Even though, in systems

    without renewable energy integrations the benefit of using

    the vehicle battery as a temporary storage is non-existing;

    still EV bidirectional chargers offer a promising solution to

    support the power grid during peak demand and

    contingencies through Vehicle-to-Grid (V2G) battery

    discharging operation mode [5]-[8]. In SGs, bidirectional EV

    battery charger is the key interface that controls the different

    power-flow modes Grid-to-Vehicle (G2V) or/and V2G [9]-

    [12].

    1.2 Literature review

    The general common structure of a bidirectional EV

    battery charging system is shown in Fig. 1 [13].

    Fig. 1. Overall block diagram of bidirectional EV charger.

    The system is mainly composed of bidirectional DC/DC

    converter cascaded with a bidirectional AC/DC converter

    (PWM single-phase or three-phase converter). Generally, the

    most appropriate bidirectional AC/DC converter topology

    used in this application is the Full-Bridge inverter either

    three-phase or single-phase topology as it does not require

    any Power Factor Correction (PFC) circuitry and control

    [13]. Thus, this paper focuses on the design and control

    aspects of the bidirectional DC/DC converter that provides

    the suitable interface between the utility grid and the EV

    battery. Besides, in G2V and V2G applications, non-isolated

    (transformerless) designs are not preferred due to the

    following reasons:

    ▪ Leakage current circulation increases hazards risks which led the EV grid-integration standards to emphasize on isolation requirement for safety assurance [13]-[14].

    ▪ Large mismatch between the battery and grid nominal voltages. Therefore, matching the voltage levels without using transformers would require increasing the number of batteries connected in-series [15], [16]. However, this increases the probability of batteries State of Charge (SoC%) mismatch occurrences [17].

    Therefore, his paper will focus only on the isolated

    configuration of the Dual Active Full Bridge (DAFB)

    utilizing a High-Frequency (HF) transformer.

    1.3 Contribution and paper organization

    This paper discusses the design considerations for the

    DAFB used as a bidirectional EV battery charger. It also

    presents a modeling approach applied to the DAFB topology

    with its control techniques. The developed DAFB model and

    its control techniques are implemented and validated under

    both G2V and V2G operations using Matlab/Simulink and

    Hardware in the Loop (HIL). The power flow dynamics and

    the converter efficiency are also investigated under various

    operating scenarios.

    This paper is therefore structured as follows: section

    2 presents an overview of the DAFB design considerations

    and features in-light of G2V and V2G applications; section

    3 elaborates on the DAFB converter modeling approach;

    section 3 discusses key recommendations and design

    considerations on using the DAFB in EV charging

    applications; section 5 discusses the simulation and

    experimental results; finally, section 5 concludes the paper.

    Power Grid

    Bidirectional AC-DC Converter

    Bidirectional

    DC-DC Converter

    =

    = =

    EV Battery

    DAFB V2G mode (Discharging

    mode) G2V mode (Charging mode)

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 2

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 2

    2 Overview of DAFB Design Considerations

    Fig. 2 shows the overall topology of a typical DAFB for

    EV G2V and V2G applications.

    Fig. 2. General DAFB topology

    The use of this topology is proposed for applications

    where automatic bidirectional power flow, power density,

    reliability, efficiency and cost are the primary design

    considerations. The system is mainly composed of

    bidirectional PWM DC/AC inverter followed by a High

    Frequency (HF) transformer feeding a bidirectional AC/DC

    converter, which in turn charges the EV battery. The DAFB

    system bidirectional power-flow between the grid and the

    battery is controlled by adjusting the phase shift (φ) between

    the two bridges’ PWM control signals.

    2.1 Reliability

    Reliability studies of power electronics converters

    focus on the weakest element in the system. Particularly,

    capacitors are considered as the most fragile part of the

    system [18]-[21]. In fact, failures due to capacitors have the

    highest cost/failure ratio since they are difficult to detect and

    hence require a special attention [21]. Particularly, when the

    capacitance requirement is large, it is inevitable to avoid

    using unreliable electrolytic capacitors because it is difficult

    to find commercial reliable non-polarized film capacitors

    with high capacitance values [22]. Moreover, the high

    capacitance requirement is due to the low inertia of the

    system that causes second order voltage harmonics to appear

    on the DC-Link [23]. Even though, this phenomena is severe

    with single-phase systems; yet, any system with an

    instantaneous power that is not constant would possess high

    input capacitance requirement to match this power mismatch.

    Consequently, the lifespan of the system is highly

    deteriorated in case the charger is constructed with single-

    phase topology.

    However, the input capacitance could be reduced

    with single-phase systems by using an appropriate power-

    decoupling scheme [24]. Authors in [25] reviewed the

    power decoupling methods that require extra switches and

    energy storage devices and [26] provides a switchless power

    decoupling method. Yet, adopting a power-decoupling

    control scheme would increase the complexity of overall

    battery charger [27]. Consequently, it is recommended to

    use the DAFB in a three-phase topology to minimize the

    DC-Link capacitance requirement that would reflect

    positively on the system reliability [10], [28]-[30].

    2.2 Battery Lifetime Considerations

    To assure the safe operation of the system and avoid

    damaging the battery due to over-charge or over-discharge,

    the system should monitor the SoC% of the battery to select

    the appropriate operation mode [10]. Fig. 3 depicts the

    different SoC% level and the suitable V2G or G2V

    operation modes. Note that, in the range of (15%-80%) the

    priority of the operation is set by the user. Meaning that, in

    normal operation, V2G mode would be set by a command

    that is provided by the SG; unless, the EV user predefined

    G2V priority for EV charging.

    Fig. 3. Operation modes based on battery SoC%.

    2.3 ZVS, ZCS and Efficiency Considerations

    It is well known that the DAFB has inherent Zero

    Voltage Switching (ZVS) capabilities in case the ratio of the

    voltages applied on the HF transformer sides is equal to the

    transformer ratio [31]. ZVS condition means that the turn-on

    losses are negligible and therefore efficiency is high.

    Nevertheless, many of the recent literatures on the DAFB

    configuration are focused on increasing the ZVS region. For

    instance, [31] investigates the ZVS boundaries if a 3-level

    modulation is adopted. Besides, [32] provides a summary of

    different modulation schemes – Extended-Phase-Shift (EPS)

    [33], Dual-Phase-Shift (DPS) [34], and Triple-Phase-Shift

    (TPS) [35] – that are often used with the DAFB to reduce

    the switching loss and extend the ZVS region. In addition,

    [36] proposed a new modulation technique that is based on

    online optimization algorithm called Half-bridge-Pulse-

    width-modulation-plus-Phase-Shift (HPPS) that is similar to

    TPS of [35]. Also, there are some other control schemes that

    are based on online frequency modulation control to

    optimize the AC-Link reactance such as the control

    proposed by [37]-[39]. Nevertheless, simply controlling the

    DC-Link voltage to assure that the voltage applied on the

    HF transformer sides is equal to the transformer ratio would

    be sufficient to accomplish ZVS conditions [32].

    Unlike the turn-on losses, turn-off losses are non-

    negligible due to the existence of a significant LV-Side

    leakage inductance [28]. In fact, to further increase the

    efficiency, a turn-off RC snubber circuit must be considered;

    especially with the LV-Side bridge MOSFETs to attain Zero

    Current Switching (ZCS) conditions [28].

    On the other hand, MOSFET’s characteristics make

    them attractive to use in EV applications. Specifically, the

    type of the modulation used either on the DAFB or on the

    bidirectional inverter allows harnessing the intrinsic body

    diode of the MOSFET instead of using actual antiparallel

    diodes [40], [41]. As a result, reducing the components

    counts and cost and increasing the reliability. Additionally,

    the nature of the ZVS of the DAFB permits high switching

    frequency operation, which makes the MOSFETs an

    attractive option over IGBTs. However, the drawback of the

    Silicon MOSFETs is the significant on-state loss.

    Consequently, Silicon Carbide (SiC) MOSFETs can be

    adopted in the design to reduce the conduction losses [42].

    Phase shift ()

    C1

    +

    _

    S11

    S12

    S13

    S14

    i1

    HF Filter

    Capacitors

    leg11 leg

    12

    Active Bridge 1

    (Full Bridge)

    Positive Power Flow

    IAC1

    v

    HF1 VHF2

    IAC2

    n:1

    Primary Side/Grid Side Secondary Side/Battery

    Side

    S21

    S22

    S23

    S24

    leg21 leg

    22

    HF Isolation

    Transformer

    C2

    i2

    HF Filter

    Capacitors Active Bridge 2

    (Full Bridge)

    Iout I

    in

    Vin V

    2

    +

    _

    V1

    0% 15%

    80

    % 100

    % G2

    V V2G or G2V V2

    G

    SoC%

    → Operation

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 3

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 3

    2.4 HF Transformer Core Materials

    The HF transformer is required for both isolation and

    voltage matching between the primary and the secondary

    sides of the DAFB. Usually, iron-based nanocrystalline soft-

    magnetic cores are preferred over ferrite cores because they

    have greater saturation magnetic flux density, higher

    magnetic permeability, higher Curie temperature and lesser

    iron loss [15], [32]. Hence, an efficient utilization of the HF

    transformer and pushing the power density further can be

    achieved by designing the core with nanocrystalline

    materials [43].

    3 DAFB Modeling

    The DAFB-based bidirectional EV battery charging

    system configuration is shown in Fig. 4. The system is

    mainly composed of bidirectional PWM DC/AC inverter

    followed by a HF transformer feeding a bidirectional

    AC/DC converter, which in turn charges the EV battery. The

    DAFB system bidirectional power-flow between the grid

    and the battery is controlled by adjusting the phase shift (φ)

    between the two bridges’ PWM control signals. Notice that

    an outer control loop uses a Proportional-Integral (PI)

    controller to regulate the SoC% of the EV battery.

    Fig. 4. DAFB-based bidirectional EV battery charger

    system

    It is important to model the DAFB system in order to

    derive an appropriate transfer function between the DAFB

    output current and the phase shift ratio to design a proper

    controller for the battery charging and discharging operation.

    However, the challenge in modeling the DAFB is that the

    system is highly non-linear due to its HF transformer current

    shape. Even though, there are various types of models in the

    literature, the most used models neglect the magnetization

    inductance and the core losses of the HF transformer [44]-

    [47]. Recently, authors in [48] proposed a better modelling

    methodology that requires less complexity and includes the

    core losses and the effect of the magnetization inductance.

    Therefore, similar modeling approach is used hereafter. This

    approach is based on averaging the input current of the HV-

    side Bridge (iAC1) and output current of LV-side Bridge (iAC2)

    over half of the switching cycle (denoted here by T=1/2fs).

    In other words, these currents can be represented by

    dependent current sources, with the assumption that the

    other variables are constant over the averaging period as

    depicted in Fig. 5. Note that this model is for the

    conventional SPS control scheme. Nevertheless, before

    going to the small-signal model, the large-signal model is

    first derived.

    3.1 Large-Signal Model

    The dynamics of the large-signal model are

    expressed as follows:

    𝐶1𝑑𝑣1𝑑𝑡

    = 𝑖𝑖𝑛 − 𝑖𝐴𝐶1 (1)

    𝐿𝑖𝑑𝑖𝑖𝑛𝑑𝑡

    + 𝑅𝑖𝑖𝑖𝑛 = 𝑣𝑖𝑛 − 𝑣1 (2)

    𝐶2𝑑𝑣2𝑑𝑡

    = 𝑖𝐴𝐶2 − 𝑖𝑜𝑢𝑡 (3)

    𝐿𝑜𝑑𝑖𝑜𝑢𝑡𝑑𝑡

    + 𝑅𝑜𝑖𝑜𝑢𝑡 = 𝑣2 − 𝑣𝑜𝑢𝑡 (4)

    where all parameters are shown in Fig. 5. The current

    waveforms for iAC1 and iAC2 are obtained by a piecewise

    solution of linear ordinary differential equations (5) and (6).

    𝑣1 + 𝑛𝑣2

    𝐿=𝑑𝑖𝐴𝐶1(𝑡)

    𝑑𝑡+𝑅

    𝐿𝑖𝐴𝐶1(𝑡) ∀ 𝑡 ∈ [0, 𝑑𝑇)

    (5) 𝑣1 − 𝑛𝑣2𝐿

    =𝑑𝑖𝐴𝐶1(𝑡)

    𝑑𝑡+𝑅

    𝐿𝑖𝐴𝐶1(𝑡) ∀ 𝑡 ∈ [𝑑𝑇, 𝑇)

    −𝑛𝑣1 + 𝑛

    2𝑣2𝐿

    =𝑑𝑖𝐴𝐶2(𝑡)

    𝑑𝑡+𝑅

    𝐿𝑖𝐴𝐶2(𝑡) ∀ 𝑡 ∈ [0, 𝑑𝑇)

    (6) 𝑛𝑣1 − 𝑛2𝑣2

    𝐿=𝑑𝑖𝐴𝐶2(𝑡)

    𝑑𝑡+𝑅

    𝐿𝑖𝐴𝐶2(𝑡) ∀ 𝑡 ∈ [𝑑𝑇, 𝑇)

    The current waveforms are therefore following exponential

    patterns as shown in (7) and (8).

    𝑖𝐴𝐶1(𝑡) = {

    𝑣1 + 𝑛𝑣2𝑅

    + (−𝐼1 −𝑣1 + 𝑛𝑣2

    𝑅) 𝑒−

    𝑅𝐿 𝑡 ∀ 𝑡 ∈ [0, 𝑑𝑇)

    𝑣1 − 𝑛𝑣2𝑅

    + (𝐼2 −𝑣1 + 𝑛𝑣2

    𝑅) 𝑒−

    𝑅𝐿( 𝑡−𝑑𝑇) ∀ 𝑡 ∈ [𝑑𝑇, 𝑇)

    (7)

    𝑖𝐴𝐶2(𝑡) =

    {

    𝑛𝑣1 + 𝑛2𝑣2

    𝑅+ (𝑛𝐼1 +

    𝑛𝑣1 + 𝑛2𝑣2

    𝑅) 𝑒−

    𝑅𝐿 𝑡 ∀ 𝑡 ∈ [0, 𝑑𝑇)

    𝑛𝑣1 − 𝑛2𝑣2

    𝑅+ (𝑛𝐼2 −

    𝑛𝑣1 − 𝑛2𝑣2

    𝑅) 𝑒−

    𝑅𝐿( 𝑡−𝑑𝑇) ∀ 𝑡 ∈ [𝑑𝑇, 𝑇)

    (8)

    Note that R is the equivalent resistance of the HF transformer

    and the two bridges that can be approximated by (9), L is the

    equivalent inductance of the HF transformer and expressed

    as in (10), where n is the transformer ratio and d is the phase

    shift ratio (𝑑 =𝜑

    𝜋 ).

    𝑅 = 2𝑅𝐷𝑆 + 𝑅𝐴𝐶−𝐿𝑖𝑛𝑘 + 𝑅1 + 𝑛2𝑅2 + +2𝑛

    2𝑅𝐷𝑆 (9) 𝐿 = 𝐿𝐴𝐶−𝐿𝑖𝑛𝑘 + 𝐿1 + 𝑛

    2𝐿2 (10)

    Note that the RC and LM are very large and they draw an

    insignificant current; thus, their contributions to the

    equivalent resistance and inductance in (9) and (10) are

    neglected. In addition, since the magnetization and the

    demagnetization of the shunt magnetization inductance is

    synchronous during one switching ( 2𝑇 =1

    𝑓𝑠) cycle; the

    average of the current flowing in LM is zero.

    iAC1

    iAC2

    n:1

    Battery

    PWM Generator (50% Duty Cycle)

    Sampling

    Frequency

    fs

    Battery Current PI

    Controller

    Phase Shift

    State of charge

    control

    IBref

    iout

    IB=iout + -

    SoC

    SoC%

    C1 C

    2

    v1 v

    2

    iin

    Full Bridge 1

    Full Bridge 2

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 4

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 4

    Vin VoutC1

    iin iAC1

    R1 n2R2n

    2L2L1

    LM RC

    Lo

    C2

    +v1-

    +v2-

    iAC2 iout

    T3 T1

    T4 T2

    T5

    T6

    T7

    T8

    2RDS 2n2RDS n:1

    RiLi Ro

    LAC-Link RAC-Link

    (a)

    iin

    iAC1 iAC2/n

    n:1 iAC2 iout

    vin vout

    Ri Li Lo Ro

    C1 C2

    iAC1 iAC2/n

    (b)

    Fig. 5. DAFB Model: (a) Large-signal model and (b) Small-signal model

    Moreover, an expression for the two initial current

    conditions I1 and I2 can be found by harnessing the fact that

    the piecewise current waveforms are continuous.

    Furthermore, these two initial conditions represent the

    transformer peak currents. Therefore, using the following

    conditions (11)-(13); I1 and I2 are as determined by (14) and

    (15), respectively.

    −𝑛𝑖𝐴𝐶1(𝑡 = 0) = 𝑖𝐴𝐶2(𝑡 = 0) = −𝐼1 (11) 𝑛𝑖𝐴𝐶1(𝑡 = 𝑇) = 𝑖𝐴𝐶2(𝑡 = 𝑇) = 𝐼1 (12) 𝑛𝑖𝐴𝐶1(𝑡 = 𝑑𝑇) = 𝑖𝐴𝐶2(𝑡 = 𝑑𝑇) = 𝐼2 (13)

    𝐼1 =𝑣1 − 𝑛𝑣2 + 2𝑛𝑣2𝑒

    −𝑅𝐿(𝑇−𝑑𝑇) − (𝑣1 + 𝑛𝑣2)𝑒

    −𝑅𝐿𝑇

    𝑅 (1 + 𝑒−𝑅𝐿𝑇)

    (14)

    𝐼2 =𝑣1 + 𝑛𝑣2 − 2𝑣1𝑒

    −𝑅𝐿𝑑𝑇 + (𝑣1 − 𝑛𝑣2)𝑒

    −𝑅𝐿𝑇

    𝑅 (1 + 𝑒−𝑅𝐿𝑇)

    (15)

    Now averaging (7) and (8) over half the switching

    cycle – 𝑖̇ ̅ =1

    𝑇∫ 𝑖(𝑡)𝑑𝑡 𝑇

    0– yields (16) and (17).

    �̇�𝐴𝐶1̅̅ ̅̅ ̅̅ =𝑣1 + 𝑛𝑣2

    𝑅𝑑 +

    𝑣1 − 𝑛𝑣2𝑅

    (1 − 𝑑)

    +𝐿

    𝑅 𝑇(𝐼1 +

    𝑣1 + 𝑛𝑣2𝑅

    ) (𝑒−𝑅𝐿𝑑𝑇 − 1)

    +𝐿

    𝑅 𝑇(𝑣1 − 𝑛𝑣2

    𝑅− 𝐼2) (𝑒

    −𝑅𝐿(𝑇−𝑑𝑇) − 1)

    (16)

    �̇�𝐴𝐶2̅̅ ̅̅ ̅̅ = −𝑛𝑣1 + 𝑛

    2𝑣2𝑅

    𝑑 +𝑛𝑣1 − 𝑛

    2𝑣2𝑅

    (1 − 𝑑)

    −𝐿

    𝑅 𝑇(𝑛𝐼1 +

    𝑛𝑣1 + 𝑛2𝑣2

    𝑅) (𝑒−

    𝑅𝐿𝑑𝑇 − 1)

    +𝐿

    𝑅 𝑇(𝑛𝑣1 − 𝑛

    2𝑣2𝑅

    − 𝑛𝐼2) (𝑒−𝑅𝐿(𝑇−𝑑𝑇) − 1)

    (17)

    To include the core losses in the model, the averaged current

    �̇�𝐴𝐶2̅̅ ̅̅ ̅̅ in (17) must subtract the averaged current

    �̇�𝑐𝑜𝑟𝑒̅̅ ̅̅ ̅̅ in the shunt core resistance Rc given by:

    𝑖̇𝑐𝑜𝑟𝑒̅̅ ̅̅ ̅̅ ̅ =𝑛2𝑣2𝑅𝐶

    (18)

    Thus, (17) and (18) yield:

    �̇�𝐴𝐶2̅̅ ̅̅ ̅̅ = −𝑛𝑣1 + 𝑛

    2𝑣2𝑅

    𝑑 +𝑛𝑣1 − 𝑛

    2𝑣2𝑛𝑅

    (1 − 𝑑)

    −𝐿

    𝑅 𝑇(𝑛𝐼1 +

    𝑛𝑣1 + 𝑛2𝑣2

    𝑅) (𝑒−

    𝑅𝐿𝑑𝑇 − 1)

    +𝐿

    𝑅 𝑇(𝑛𝑣1 − 𝑛

    2𝑣2𝑅

    − 𝑛𝐼2) (𝑒−𝑅𝐿(𝑇−𝑑𝑇) − 1)

    −𝑛2𝑣2𝑅𝐶

    (19)

    3.2 Small-Signal Model

    After deriving the average current expressions in (16) and

    (19), the small-signal model can be developed by inserting

    the equivalent average and perturbed values (20)-(26) in (1)-

    (4).

    𝑑 = 𝐷 + �̂� (20) 𝑣𝑖𝑛 = 𝑉𝑖𝑛 + �̂�𝑖𝑛 (21)

    𝑣𝑜𝑢𝑡 = 𝑉𝑜𝑢𝑡 + �̂�𝑜𝑢𝑡 (22) 𝑣1 = 𝑉1 + �̂�1 (23) 𝑣2 = 𝑉2 + �̂�2 (24)

    𝑖𝑖𝑛 = 𝐼𝑖𝑛 + 𝑖̇̂𝑖𝑛 (25)

    𝑖𝑜𝑢𝑡 = 𝐼𝑜𝑢𝑡 + 𝑖̇̂𝑜𝑢𝑡 (26)

    As a result, expressions (27)-(30) are yield.

    𝐶1𝑑�̂�1𝑑𝑡

    = 𝑖̇̂𝑖𝑛 − 𝑖̇̂𝐴𝐶1 (27)

    𝐿𝑖𝑑𝑖̇̂𝑖𝑛𝑑𝑡

    + 𝑅𝑖𝑖̇̂𝑖𝑛 = �̂�𝑖𝑛 − �̂�1 (28)

    𝐶2𝑑�̂�2𝑑𝑡

    = 𝑖̇̂𝐴𝐶2 − 𝑖̇̂𝑜𝑢𝑡 (29)

    𝐿𝑜𝑑𝑖̇̂𝑜𝑢𝑡𝑑𝑡

    + 𝑅𝑜𝑖̇̂𝑜𝑢𝑡 = �̂�2 − �̂�𝑜𝑢𝑡 (30)

    However, the only difficulty left is to find the equivalent

    small-signal approximation for the currents �̇̂�𝐴𝐶1 and �̇̂�𝐴𝐶2. For

    that the first order Maclaurin series given by (31) is used,

    which is valid because �̂� is very small.

    𝑒±𝑅𝐿𝑑𝑇 = 𝑒±

    𝑅𝐿(𝐷+�̂�)𝑇 ≈ 𝑒±

    𝑅𝐿𝐷𝑇 (1 ±

    𝑅𝑇

    𝐿�̂�) (31)

    Thus, the currents 𝑖̇̂𝐴𝐶1 and 𝑖̇̂𝐴𝐶2 can be derived as:

    𝑖̇̂𝐴𝐶1 = 𝛼�̂� + 𝛽�̂�1 + 𝛾�̂�2 (32)

    𝑖̇̂𝐴𝐶2 = 𝜀�̂� + 𝜓�̂�1 + 𝜇�̂�2 (33) where the coefficients 𝛼 , 𝛽 , 𝛾 , 𝜀 , 𝜓 and 𝜇 are as given in (34)-(39).

    𝛼 =2𝑛𝑉2𝑅

    −4𝑛𝑉2𝑒

    −𝑅𝐿(1−𝐷)𝑇

    𝑅 (𝑒−𝑅𝐿𝑇 + 1)

    (34)

    𝛽 =1

    𝑅+2𝐿 (𝑒−

    𝑅𝐿𝑇 + 1)

    𝑇𝑅2 (𝑒−𝑅𝐿𝑇 + 1)

    (35)

    𝛾 =𝑛(2𝐷 − 1)

    𝑅+2𝑛𝐿 (𝑒−

    𝑅𝐿𝑇 − 2𝑒−

    𝑅𝐿(1−𝐷)𝑇 + 1)

    𝑇𝑅2 (𝑒−𝑅𝐿𝑇 + 1)

    (36)

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 5

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 5

    𝜀 = −2𝑛𝑉1𝑅

    +4𝑛𝑉1𝑒

    −𝑅𝐿𝐷𝑇

    𝑅 (𝑒−𝑅𝐿𝑇 + 1)

    (37)

    𝜓 =𝑛(1 − 2𝐷)

    𝑅+2𝑛𝐿 (𝑒−

    𝑅𝐿𝑇 − 2𝑒−

    𝑅𝐿𝐷𝑇 + 1)

    𝑇𝑅2 (𝑒−𝑅𝐿𝑇 + 1)

    (38)

    𝜇 = −𝑛2

    𝑅+2𝑛2𝐿 (1 − 𝑒−

    𝑅𝐿𝑇)

    𝑇𝑅2 (1 + 𝑒−𝑅𝐿𝑇)

    −𝑛2

    𝑅𝐶 (39)

    Therefore, (27)-(30) and (32)-(33) represent the small-signal

    model of the DAFB.

    3.3 Output Current to Phase-Shift Ratio Transfer Function

    The purpose of constructing the small-signal model is to

    derive the transfer function of the DAFB output current to

    the phase shift (𝐺𝑜𝑢𝑡(𝑠) =�̂̇�𝑜𝑢𝑡(𝑠)

    �̂�(𝑠) ). Hence, (27)-(30) and (32)-

    (33) are converted into Laplace domain as in (41)-(45).

    𝑠𝐶1�̂�1(𝑠) = 𝑖̇̂𝑖𝑛(𝑠) − 𝑖̇̂𝐴𝐶1(𝑠) (40)

    𝑠𝐿𝑖𝑖̇̂𝑖𝑛(𝑠) + 𝑅𝑖𝑖̇̂𝑖𝑛(𝑠) = �̂�𝑖𝑛(𝑠) − �̂�1(𝑠) (41)

    𝑠𝐶2�̂�2(𝑠) = 𝑖̇̂𝐴𝐶2(𝑠) − 𝑖̇̂𝑜𝑢𝑡(𝑠) (42)

    𝑠𝐿𝑜𝑖̇̂𝑜𝑢𝑡(𝑠) + 𝑅𝑜𝑖̇̂𝑜𝑢𝑡(𝑠) = �̂�2(𝑠) − �̂�𝑜𝑢𝑡(𝑠) (43)

    𝑖̇̂𝐴𝐶1(𝑠) = 𝛼�̂�(𝑠) + 𝛽�̂�1(𝑠) + 𝛾�̂�2(𝑠) (44)

    𝑖̇̂𝐴𝐶2(𝑠) = 𝜀�̂�(𝑠) + 𝜓�̂�1(𝑠) + 𝜇�̂�2(𝑠) (45) Combining (42), (43) and (45), it is possible to obtain (46).

    𝑖̇̂𝑜𝑢𝑡(𝑠)

    =𝜀�̂�(𝑠)

    𝑠2𝐿𝑜𝐶2 + 𝑠(𝑅𝑜𝐶2 − 𝐿𝑜𝜇) − 𝜇𝑅𝑜 + 1

    +𝜓�̂�1(𝑠)

    𝑠2𝐿𝑜𝐶2 + 𝑠(𝑅𝑜𝐶2 − 𝐿𝑜𝜇) − 𝜇𝑅𝑜 + 1

    −(𝑠𝐶2 − 𝜇)�̂�𝑜𝑢𝑡(𝑠)

    𝑠2𝐿𝑜𝐶2 + 𝑠(𝑅𝑜𝐶2 − 𝐿𝑜𝜇) − 𝜇𝑅𝑜 + 1

    (46)

    From (46), the output current 𝑖̇̂𝑜𝑢𝑡(𝑠) is a function of

    �̂�(𝑠) , �̂�1(𝑠) and �̂�𝑜𝑢𝑡(𝑠) . Nonetheless, since the control

    parameter is the phase-shift ratio ( �̂�(𝑠)), thus, �̂�1(𝑠) and �̂�𝑜𝑢𝑡(𝑠) in (46) are considered as disturbances and can be eliminated by feedforward control. In addition, these

    disturbances originate from power ripples (in case a single-

    phase topology is adopted), unbalanced 3-phase system (if a

    3-phase topology is adopted), or variations in battery voltage

    caused by its charging and discharging processes. As a

    result, the output current relation with the phase-shift ratio is:

    𝐺𝑜𝑢𝑡(𝑠) =𝑖̇̂𝑜𝑢𝑡(𝑠)

    �̂�(𝑠)|�̂�1(𝑠)=�̂�𝑜𝑢𝑡(𝑠)=0

    =𝜀

    𝑠2𝐿𝑜𝐶2 + 𝑠(𝑅𝑜𝐶2 − 𝜇𝐿𝑜) − 𝜇𝑅𝑜 + 1

    (47)

    Note that the poles of the transfer function of (47) show that

    the system is always stable. Even though, there is a negative

    term multiplied by µRo and µLo that might be negative.

    Nevertheless, the factor µ is always negative. Making only

    LHP poles existence in (47)..

    Using (47), the appropriate PI controller gains in

    Fig. 6 can be calculated with the feedforward considerations that were indicated in (46). However,

    practically delays will exist in the system and (47) does not

    accurately represent the plant. The possible causes of these

    delays are: (i) PWM transport, (ii) Zero-Order-Hold (ZOH)

    sampling and (iii) digital controller’s calculations. Each

    introduces a delay of 0.5Ts; therefore, the total delay in the

    system is considered as 1.5Ts. However, this delay can be

    approximated using the second order Padé [49] as in (48).

    𝐺𝑑𝑒𝑙𝑎𝑦(𝑠) =12 − 9𝑇𝑠𝑠 + 2.25𝑇𝑠

    2𝑠2

    12 + 9𝑇𝑠𝑠 + 2.25𝑇𝑠2𝑠2

    ()

    Consequently, Fig. 6 shows the overall controller and plant

    model that includes a realistic delay block inserted after the

    PI controller.

    Fig. 6. DAFB output current-to-phase shift ratio plant

    model with the controller

    Therefore, the closed loop system transfer function (𝐺𝐶𝐿(𝑠)) is

    derived from Fig. 6, as:

    𝐺𝐶𝐿(𝑠) =𝑃𝐼(𝑠)𝐺𝑑𝑒𝑙𝑎𝑦(𝑠)𝐺𝑜𝑢𝑡(𝑠)

    1 + 𝑃𝐼(𝑠)𝐺𝑑𝑒𝑙𝑎𝑦(𝑠)𝐺𝑜𝑢𝑡(𝑠) (49)

    Hence, (49) can be used to design the controller. Note that,

    the delay effects on the feedforwarded signals is not

    significant and can be neglected. In fact, these disturbances

    can be considered constants during the delay duration.

    Besides, the delay will only introduce very far RHP that are

    not dominant; hence, no non-minimum phase response will

    be observed and the system remains stable.

    On the other hand, the dead-time has a considerable

    effect on the power-flow dynamics of the DAFB due to the

    significant error between the effective phase-shift-ratio and

    the commanded phase-shift-ratio as discussed in [50]-[52].

    However, this model does not include the dead-time

    compensation techniques, since dead-time compensation

    methods are only necessary with loads that are rapidly

    changing. In fact, a battery bank as a load possesses a small-

    time constant. Moreover, [53] introduced a methodology to

    effectively reduce the error in the power-flow dynamics by

    compensating the additional phase-shift due to the dead-time

    for applications with rapidly varying loads.

    4 Overall Control Scheme

    The cascaded dual loop control methodology is

    considered as a proper control approach. Specifically, an

    outer voltage regulation loop is used to derive the reference

    current for the inner current regulation loop. This control

    methodology is used on both the bidirectional inverter and

    on the DAFB as shown in Fig. 7 and Fig. 8, respectively.

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 6

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 6

    Fig. 7. Bidirectional inverter controller

    Fig. 8. DAFB controller

    Nevertheless, further modification on the DAFB

    converter control is to consider the SoC% as an extra degree

    of freedom as depicted in Fig. 3. In other words, there will be

    two reference currents for the inner current loop that will be

    selected by using a data selector –Multiplexer– according to

    the predefined priority whether G2V or V2G preference.

    Since the outer voltage loops on both converters –the

    bidirectional inverter and the DAFB– regulate DC

    parameters, the suitable controller type is a simple single PI

    controller for each loop. Similarly, the inner current loop of

    the battery bank current control also uses a PI controller.

    However, the inner grid current control uses a Proportional

    Resonance (PR) controllers when stationary frame is used. Note that, the power-factor is controlled only in V2G

    operation through adjusting the grid d-current component

    (𝑖𝑑(𝐺2𝑉)𝑟𝑒𝑓 ).

    5 Implementation

    5.1 DAFB Testing Prototype

    A 6.1 kW DAFB Hardware prototype is implemented

    using a Typhoon HIL 602 device and STM32

    microcontroller, as shown in Fig. 9. The DAFB ratings are

    depicted in Table 1. The control of the DAFB is based on

    the SPS control scheme. The experiments focus on the

    following: (i) open-loop step response, (ii) power-flow

    dynamics, (iii) closed-loop waveforms observation and (iv)

    converter efficiency.

    5.2 Open-Loop Step Response

    The feasibility of the theoretical analysis in designing the PI

    controller is based on testing the open-loop overall system

    step response.

    (a)

    (b)

    Fig. 9. Laboratory Typhoon HIL experimental setup:

    (a) schematic (b) actual.

    Table 1: DAFB Components values Parameter Symbol Value

    Input voltage (HV-Side) [The HV-Side is adjusted to keep the voltage applied on the HF transformer sides equal to the transformer ratio]

    Vin 317.10 V – 342.8 V

    Output voltage (LV-Side) [Two series connected Li-ion Batteries with 26.6 V nominal voltage and 40 Ah capacity]

    Vout 52.85 V – 57.3 V

    Power rating Po 6.1 kW

    Switching frequency fs 20 kHz

    Dead-time Dt 1.25µs

    Transformer turn ratio N 6:1

    HF transformer inductance L 93.30 µH

    HF transformer resistance R 338.50 mΩ

    Magnetizing inductance Lm 1.76 mH

    Core resistance RC 10 MΩ

    HV-Side capacitor C1 7 mF

    LV-Side capacitor C2 22 mF

    LV-Side snubber capacitor Cs 141 nF

    LV-Side snubber resistance Rs 1.67 mΩ

    HV-Side source resistance Ri 1 mΩ

    HV-Side source inductance Li 1 µH

    LV-Side source resistance Ro 1µΩ

    LV-Side source inductance Lo 1 µH

    This was carried out using both Simulink software and

    the HIL experimental prototyping. In Fig. 10, the step

    response of the battery current was obtained by applying a

    phase-shift-ratio step from 0 to 0.272 at time t=0.8 ms.

    Notice that the battery current varied rapidly from 0 to 100A

    with a very short time constant of 706 µs. Comparing the

    open-loop system step responses in Fig. 10 indicates that the

    Simulink model and the HIL model are consistent.

    DC-Link

    Voltage

    Control

    dq

    to

    + _

    + _

    PLL

    abc

    to

    Grid

    Current

    Control

    to abc

    𝑣𝐷𝐶𝑟𝑒𝑓

    𝑣𝐷𝐶

    𝑣𝑔

    𝑖𝑔

    𝑖𝑑𝑟𝑒𝑓

    𝑖𝑞𝑟𝑒𝑓

    PF

    Control

    Mux

    S=0

    S=1

    𝑖𝑑(𝑉2𝐺)𝑟𝑒𝑓

    abc to

    𝑣𝑔 Vg calculation

    𝑉𝑔𝑟𝑒𝑓

    𝑖𝑑(𝐺2𝑉)𝑟𝑒𝑓

    𝑀𝑖

    S=0 for G2V

    S=1 for V2G

    𝑉𝑔

    + _

    + _

    Battery Voltage

    Control 𝑣𝐵𝑟𝑒𝑓

    Mux

    S=0

    S=1 S=0 for G2V S=1 for V2G

    + _

    Battery Current

    Control 𝑖𝐵(𝑉2𝐺)𝑟𝑒𝑓

    𝑖𝐵(𝐺2𝑉)𝑟𝑒𝑓

    SoC%

    SoC

    Observer

    𝑣𝐵 𝑖𝐵

    d 𝑖𝐵𝑟𝑒𝑓

    Waveform

    s

    Display &

    Analysis

    HIL Model upload

    &

    data monitoring link

    Controller code upload

    & data monitoring link

    STM32F

    4

    I/O

    Control

    Signals

    Exchang

    e Oscilloscop

    e

    Oscilloscope

    Typhoon HIL 602

    STM32F4 Controller

    Card Laptop

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 7

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 7

    Fig. 10. DAFB step response: HIL vs. Simulink

    5.3 Power-flow Dynamics

    Another validation tool of the HIL implementation was

    performed by comparing the HIL system power-flow

    dynamics with the theoretical ideal DAFB power-flow

    equation (50) [54][55].

    𝑃 =𝑛𝑉𝑖𝑛𝑉𝑜𝑢𝑡2𝑓𝑠𝐿𝐴𝐶−𝐿𝑖𝑛𝑘

    𝑑 (1 − |𝑑|) (50)

    Fig. 11 shows that there is a good matching between the

    theoretical power-flow and the power-flow dynamics of the

    experimental HIL prototype. However, the curve is not an

    odd function. In other words, the data points for the charging

    portion are not a reflection in the origin for their counter data

    points in the discharging portion. Yet, this small asymmetry

    appears above the intended power ratings (±6.1 kW). In

    addition, the small discrepancy between the theoretical and

    experimental power-flow curves is because (50) does not

    include non-idealities such as the converter deadtime. This

    mismatch is more noticeable around the origin point.

    Fig. 11. 6.1Kw DAFB power-flow dynamics: HIL vs.

    theoretical

    Fig. 12 shows the power-flow dynamics near the origin

    point and considering diverse operating scenarios.

    Different SoC% levels (60% & 90%) with or without

    adjusting the ratio of the applied voltage on the two ports

    of the HF transformer, are presented in Fig. 12.

    Fig. 12. Power-flow dynamics near the origin point with

    and without adjusting the ratio of the voltage applied on the

    two sides of the HF transformer (VD1=Vin)

    Notice that the curves’ transitions between the charging

    and discharging modes are smoother for the adjusted HV-

    Side voltage scenarios and are crossing the origin point. This

    is because the circulating reactive current is reduced with

    adjusted HV-Side voltage. In addition, the minor mismatch

    in the curves with adjusted voltages is due to finite dead-time

    effect. This could be improved further by applying deadtime

    compensation techniques such those presented in [56]-[59].

    5.4 Closed Loop Waveforms

    Fig. 13 and Fig. 14 show the HF transformer voltage

    and current waveforms obtained by Simulink simulation and

    HIL, which are observed in both G2V and V2G modes,

    experiments, respectively. During these tests, the reference

    current 𝑖𝑜𝑢𝑡𝑅𝑒𝑓

    is set to 100A and -100A in G2V and V2G

    modes, respectively.

    Notice that, both Simulink and HIL results are very

    consistent. Note that, when the HV-side voltage (𝑣𝑝) is

    lagging the LV-Side voltage (𝑣𝑠), a voltage drop appears on the AC-Link inductance in the region of the phase shift

    resulting in power injected in the battery bank (G2V). On

    the contrary, when the HV-Side voltage is leading the LV-

    Side voltage, the battery is discharged in V2G operation

    mode.

    5.5 Converter Efficiency

    Fig. 15 shows the variation of the DAFB converter

    efficiency in both G2V and V2G operating conditions as a

    function of the battery charging/discharging power. Notice

    that the peak efficiency in G2V mode is around 96.6% at Po

    = 3.1 kW. Similarly, the highest efficiency achieved in V2G

    mode is approximately 92.7% at PO = 3.4 kW. The

    difference between V2G and G2V efficiency plots is due to

    the LV-Side capacitor C2 that absorbs higher current during

    the battery discharging (V2G) mode.

    Moreover, it can be observed that the optimal

    operating condition is in the range of 2 kW to 6 kW in the

    G2V mode. As well as, in the V2G mode the preferred

    operation range is 2 kW to 6 kW. This is because the

    converter operates around its peak efficiency in these

    specified ranges.

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 8

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 8

    Fig. 13. Simulink DAFB HF Transformer closed-loop

    waveforms

    (a) during charging (G2V) operation mode and (b) during

    discharging (V2G) operation mode

    6 Conclusion

    In conclusion, this paper emphasized on the benefits

    of the DAFB topology in applications related to SGs and EV

    charging. The benefits of the DAFB topology were reviewed

    and compared to those of the existing bidirectional DC/DC

    converter topologies. In addition, brief discussions of the

    reliability, efficiency, system configuration, EV charger

    control scheme, battery lifetime and system materials, were

    presented.

    Furthermore, a non-ideal DAFB small-signal model

    was derived to accurately designing the DAFB controller.

    Finally, a 6.1 kW DAFB prototype was implemented on

    Simulink and Typhoon HIL 602 device. Obtained results

    validate the effectiveness of the DAFB topology for both

    G2V and V2G operations.

    7 Acknowledgment

    This publication was made possible by the National

    Priorities Research Program (NPRP) award [NPRP8-627-2-

    260] from the Qatar National Research Fund (QNRF); a

    member of the Qatar Foundation. Its contents are solely the

    responsibility of the authors and do not necessarily represent

    the official views of QNRF.

    Fig. 14. HIL DAFB HF Transformer closed-loop waveforms:

    (a) during charging (G2V) operation mode and (b) during

    discharging (V2G) operation mode

    Fig. 15. DAFB efficiency: (a) G2V mode and (b) V2G mode

    8 References

    [1] Ehsani, M., Gao, Y., Gay S.E., Emadi A.: ‘Modern electric, hybrid electric, and fuel Cell Vehicles’ (Boca Raton, FL: CRC Press; 2005)

    [2] Larminie, J., Lowry, J.: ‘Electric vehicle Technology Explained’ (New York: Wiley; 2003)

    [3] Wirasingha, S.G., Pihef, A.E.: ‘Plug-in hybrid electric factor’, IEEE Trans Veh Technol, 2011, 60, (3), pp. 1279–84

    [4] Wang, Q. and Liang, D.: ‘Research on loss reduction of dual active bridge converter over wide load range for solid state transformer application’, Proc. of the 11th International Conference on Ecological

    (a)

    (b)

    (a)

    (b)

    vp (100 V/div)

    vs (20 V/div)

    ip (20 A/div)

    is (100 A/div)

    vp (100 V/div)

    vs (20 V/div)

    ip (20 A/div)

    is (100 A/div)

    (a)

    (b)

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 9

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 9

    Vehicles and Renewable Energies (EVER), Monte Carlo, 2016, pp. 1-9

    [5] Thomas, P., Sreekanth, P. K., Ganesh, M. and Nair, D.: ‘Design, simulation and comparison of single phase bidirectional converters for V2G and G2V applications’, Proc. of the 2015 Annual IEEE India Conference (INDICON), New Delhi, 2015, pp. 1-6

    [6] Habib, S., Kamran, M., and Rashid, U.: ‘Impact analysis of vehicle-to-grid technology and charging strategies of electric vehicles on distribution networks – A review’, Journal of Power Sources, 1 March 2015, 277, pp. 205-214

    [7] Kondo, R., Higaki, Y., and Yamada, M.: ‘Proposition and experimental verification of a bi-directional isolated DC/DC converter for battery charger-discharger of electric vehicle’, Proc. of the 2016 IEEE Applied Power Electronics Conference and Exposition (APEC), Long Beach, CA, 2016, pp. 1713-1720

    [8] Bhatti, A.R., Salam, Z., Bin Abdul Aziz, M.J., Kong Pui Yee, K.P., Ashique, R. H.: ‘Electric vehicles charging using photovoltaic: Status and technological review’, Renewable and Sustainable Energy Reviews, February 2016, 54, pp. 34-47

    [9] Galus, M.D., Anderson, G.: ‘Demand management of grid connected plug-in hybrid electric vehicles (PHEV)’, Proc. of the IEEE Energy 2030 Conference, ENERGY, 2008, pp. 1–8

    [10] Gago, R. G., Pinto, S.F., and Silva, J.F.: ‘G2V and V2G electric vehicle charger for smart grids’, Proc. of the 2016 IEEE International Smart Cities Conference (ISC2), Trento, 2016, pp. 1-6

    [11] Kesler, M., Kisacikoglu, M., Tolbert, L.: ‘Vehicle to grid reactive power operation using plug-in electric vehicle bidirectional offboard charger’, IEEE Trans. Ind. Electron., Dec. 2014, 61(12), pp. 6778-6784

    [12] Sortomme, E., El-Sharkawi, M.A.: ‘Optimal Combined Bidding of Vehicle-to-Grid Ancillary Services’, IEEE Trans. Smart Grid, Mar. 2012, 3(1), pp. 70-79

    [13] Williamson, S.S., Rathore, A.K., Musavi, F.: ‘Industrial electronics for electric trans- portation: current state-of-the-art and future challenges’, IEEE Trans. Ind. Electron., 2015, 62(5), pp. 3021-32

    [14] Khan, A., Ben-Brahim, L., Gastli, A., Benammar, M.: ‘Review and Simulation of Leakage Current in Transformerless Microinverters for PV Applications’, Renewable and Sustainable Energy Reviews, July 2017, 74(C), pp. 1240-1256

    [15] Zhao, B., Song, Q., Liu, W., and Sun, Y.: ‘A Synthetic Discrete Design Methodology of High-Frequency Isolated Bidirectional DC/DC Converter for Grid-Connected Battery Energy Storage System Using Advanced Components’, IEEE Trans. on Ind. Electron., Oct. 2014, 6(10), pp. 5402-5410

    [16] Xuan, Z., Shenghua, H., and Guoyun, N.: ‘A Three-phase Dual Active Bridge Bidirectional ZVS DC/DC Converter’, Physics Procedia, 2012, 24, pp.139-148

    [17] Morstyn, T., Momayyezan, M., Hredzak, B., and Agelidis, V.G., ‘Distributed Control for State-of-Charge Balancing Between the Modules of a Reconfigurable Battery Energy Storage System’, IEEE Transactions on Power Electronics, Nov. 2016, 31(11), pp. 7986-7995

    [18] Wang H. and Blaabjerg, F.: ‘Reliability of Capacitors for DC-Link Applications in Power Electronic Converters—An Overview’, IEEE Transactions on Industry Applications, Sept.-Oct. 2014, 50(5), pp. 3569-3578

    [19] Wang, H., Liserre, M., and Blaabjerg, F.: ‘Toward Reliable Power Electronics: Challenges, Design Tools, and Opportunities’, IEEE Industrial Electronics Magazine, June 2013, 7(2), pp. 17-26

    [20] Wang, H., Zhou, D., and Blaabjerg, F.: ‘A reliability -oriented design method for p ower electronic converters ," Proc. of the IEEE Appl. Power Electron. Conf. and Expo. , 2013, pp. 2291-2298

    [21] Yang, S., Bryant, A., Mawby, P., Xiang, D., Ran L., and Tavner, P.: ‘An Industry-Based Survey of Reliability in Power Electronic Converters’, IEEE Transactions on Industry Applications, May-June 2011, 47(3), pp. 1441-1451

    [22] Wang, H., Chung, H.S.H., and Liu, W.: ‘Use of a Series Voltage Compensator for Reduction of the DC-Link Capacitance in a Capacitor-Supported System’, IEEE Transactions on Power Electronics, March 2014, 29(3), pp. 1163-1175

    [23] Khan, A., Houchati, M., Ur-Rehman, J., Ben-Brahim, L., and Gastli, A.: ‘Switchless Power Decoupling and Switchless Leakage Current Elimination in Grid-Tied Inverters’, Proc. of the 9th IEEE-GCC Conference and Exhibition (GCCCE), Manama, 2017, pp. 1-6

    [24] Qin, Z., Tang, Y., Loh, P.C., and Blaabjerg, F.: ‘Benchmark of AC and DC Active Power Decoupling Circuits for Second-Order Harmonic Mitigation in Kilowatt-Scale Single-Phase Inverters’, IEEE Journal of Emerging and Selected Topics in Power Electronics, March 2016, 4(1), pp. 15-25

    [25] Sun, Y., Liu, Y., Su, M., Xiong, W., and Yang, J.: ‘Review of Active Power Decoupling Topologies in Single-Phase Systems’, IEEE Transactions on Power Electronics, July 2016, 31(7), pp. 4778-4794

    [26] Serban, I.: ‘Power decoupling method for single-phase H-bridge inverters with no additional power electronics’, IEEE Trans. Ind. Electron, Aug. 2015., 62(8), pp. 4805–4813

    [27] Xue, L., Shen, Z., Boroyevich, D., Mattavelli, P., and Diaz D.: ‘Dual Active Bridge-Based Battery Charger for Plug-in Hybrid Electric Vehicle With Charging Current Containing Low Frequency Ripple’, IEEE Transactions on Power Electronics, Dec. 2015, 30(12), pp. 7299-7307

    [28] Tan, N.M.L., Abe, T., and Akagi, H., ‘Design and Performance of a Bidirectional Isolated DC–DC Converter for a Battery Energy Storage System’, IEEE Transactions on Power Electronics, March 2012, 27(3), pp. 1237-1248

    [29] Wu, T.F., Kuo, C.L., Sun, K.H., and Hsieh, H.C., ‘Combined Unipolar and Bipolar PWM for Current Distortion Improvement During Power Compensation’, IEEE Transactions on Power Electronics, April 2014, 29(4), pp. 1702-1709

    [30] Islam, M., and Mekhilef, S.: ‘A new high efficient transformerless inverter for single phase grid-tied photovoltaic system with reactive power control’, Proc. of the IEEE Applied Power Electronics Conference and Exposition (APEC), 2015, Charlotte, NC, pp. 1666-1671

    [31] Riedel, J., Holmes, D.G., McGrath B.P., and Teixeira, C.: ‘ZVS Soft Switching Boundaries for Dual Active Bridge DC–DC Converters Using Frequency Domain Analysis’, IEEE Transactions on Power Electronics, April 2017, 32(4), pp. 3166-3179

    [32] Zhao, B., Song, Q., Liu, W., and Sun Y.: ‘Overview of Dual-Active-Bridge Isolated Bidirectional DC–DC Converter for High-Frequency-Link Power-Conversion System’, IEEE Transactions on Power Electronics, Aug. 2014, 29(8), pp. 4091-4106

    [33] Zhao, B., Yu Q., and Sun, W., ‘Extended-Phase-Shift Control of Isolated Bidirectional DC–DC Converter for Power Distribution in Microgrid’, IEEE Transactions on Power Electronics, Nov. 2012, 27, (11), pp. 4667-4680

    [34] Bai, H., and Mi C.: ‘Eliminate Reactive Power and Increase System Efficiency of Isolated Bidirectional Dual-Active-Bridge DC–DC Converters Using Novel Dual-Phase-Shift Control’, IEEE Transactions on Power Electronics, Nov. 2008, 23(6), pp. 2905-2914

    [35] Krismer, F., and Kolar J.W.: ‘Accurate Small-Signal Model for the Digital Control of an Automotive Bidirectional Dual Active Bridge’, IEEE Transactions on Power Electronics, Dec. 2009, 24(12), pp. 2756-2768

    [36] Wang, H., Yan, K., Ling, Z., and Gan, J.: ‘Switching strategy for isolated dual-active-bridge converter’, IET Power Electronics, Jan. 20 2017, 10(1), pp. 29-37

    [37] Guidi, G., Pavlovsky, M., Kawamura, A., Imakubo, T., and Sasaki, Y.: ‘Efficiency optimization of high power density Dual Active Bridge DC-DC converter’, Proc. of the 2010 International Power Electronics Conference - ECCE ASIA -, Sapporo, 2010, pp. 981-986

    [38] Everts, J., Krismer, F., Van den Keybus, J., Driesen, J., and Kolar, J. W.: ‘Charge-based ZVS soft switching analysis of a single-stage dual active bridge AC-DC converter’, Proc. of the 2013 IEEE Energy Conversion Congress and Exposition, Denver, CO, 2013, pp. 4820-4829

    [39] Todorčević, T., Van Kessel, R., Bauer, P., and Ferreira, J.A.: ‘A Modulation Strategy for Wide Voltage Output in DAB-Based DC–DC Modular Multilevel Converter for DEAP Wave Energy Conversion’, IEEE Journal of Emerging and Selected Topics in Power Electronics, Dec. 2015, 3(4), pp. 1171-1181

    [40] Martin, D., Killeen, P., Curbow, W.A., Sparkman, B., Kegley, L.E., and McNutt, T.: ‘Comparing the switching performance of SiC MOSFET intrinsic body diode to additional SiC schottky diodes in SiC power modules’, Proc. of the 2016 IEEE 4th Workshop on Wide Bandgap Power Devices and Applications (WiPDA), Fayetteville, AR, 2016, pp. 242-246

    [41] Hull B., et al.: ‘Reliability and stability of SiC power mosfets and next-generation SiC MOSFETs’, Proc. of the 2014 IEEE Workshop

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 10

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.

  • 10

    on Wide Bandgap Power Devices and Applications, Knoxville, TN, 2014, pp. 139-142

    [42] Burkart, R.M. and Kolar, J.W.: ‘Comparative eta– rho– sigma Pareto Optimization of Si and SiC Multilevel Dual-Active-Bridge Topologies With Wide Input Voltage Range’, IEEE Transactions on Power Electronics, July 2017, 32(7), pp. 5258-5270

    [43] Wang, Y., de Haan, S.W.H., and Ferreira, J.A., ‘Design of low-profile nanocrystalline transformer in high-current phase-shifted DC-DC converter’, Proc. of the 2010 IEEE Energy Conversion Congress and Exposition, Atlanta, GA, 2010, pp. 2177-2181

    [44] Zhao, C., Round, S.D., and Kolar, J.W.: ‘Full-order averaging modellingof zero-voltage-switching phase-shift bidirectional dc-dc converters’, IET Power Electron., 2010, 3(3), pp. 400–410

    [45] Qin, H. and Kimball, J.W.: ‘Generalized average modeling of dual active bridge DC-DC converter’, IEEE Trans. Power Electron. , Apr. 2012, 27(4), pp. 2078–2084

    [46] Bai, H., Chunting, M., Chongwu, W., and Gargies, S.: ‘The dynamic model and hybrid phase-shift control of a dual-active-bridge converter’, Proc. IEEE Ind. Electron. Conf., 2008, pp. 2840–2845

    [47] Bai, H., Nie, Z., and Mi, C.C.: ‘Experimental comparison of traditional phase-shift, dual-phase-shift, and model-based control of isolated bidirectional dc-dc converters’, IEEE Trans. Power Electron., Jun. 2010, 25(6), pp. 1444–1449

    [48] Zhang, K., Shan, Z., and Jatskevich, J., ‘Large- and Small-Signal Average-Value Modeling of Dual-Active-Bridge DC–DC Converter Considering Power Losses’, IEEE Transactions on Power Electronics, March 2017, 2(3), pp. 1964-1974

    [49] Figueres, E., Garcera, G., Sandia, J., Gonzalez-Espin, F., and Rubio, J.C.: ‘Sensitivity study of the dynamics of three-phase photovoltaic inverters with an LCL grid filter’, IEEE Trans. Ind. Electron. , Mar. 2009, 56(3), pp. 706–717

    [50] Akagi, H., and Kitada, R.: ‘Control of a modular multilevel cascade BTB system using bidirectional isolated DC/DC converters’, Proc. of the 2010 IEEE Energy Conversion Congress and Exposition, Atlanta, GA, 2010, pp. 3549-3555

    [51] Akagi, H., and Kitada, R.: ‘Control and Design of a Modular Multilevel Cascade BTB System Using Bidirectional Isolated DC/DC Converters," IEEE Transactions on Power Electronics, Sept. 2011, 26(9), pp. 2457-2464

    [52] Bai, H., Mi, C., Wang, C., and Gargies, S.: ‘The dynamic model and hybrid phase-shift control of a dual-active-bridge converter’, Proc. of the 2008 34th Annual Conference of IEEE Industrial Electronics, Orlando, FL, 2008, pp. 2840-2845

    [53] Segaran, D., Holmes, D.G., and McGrath, B.P.: ‘Enhanced Load Step Response for a Bidirectional DC–DC Converter," IEEE Transactions on Power Electronics, Jan. 2013, 28(1), pp. 371-379

    [54] Kheraluwala, M.N., Gascoigne, R.W., Divan, D.M., and Baumann, E.D.: ‘Performance characterization of a high-power dual active bridge’, IEEE Transactions on Industry Applications, 1992, 28, pp. 1294-1301

    [55] Khan, A., Jarraya, F., Gastli, A., Ben-Brahim, L., Hamila, R., and Rajashekara, K.: ‘Dual Active Full Bridge Implementation on Typhoon HIL for G2V and V2G Applications’, Proc. of the 2017 IEEE Vehicle Power and Propulsion Conference (VPPC), Belfort, 2017, pp. 1-6

    [56] Ben-Brahim, L., Gastli, A., Ghazi, K.A.: ‘Implementation of Iterative Learning Control based Deadtime Compensation for PWM Inverters’, Proc. of the 17th Conference on Power Electronics and Applications, EPE’15-ECCE Europe, Geneva, Switzerland, September 2015, pp. 8-10

    [57] Ben-Brahim, L.: ‘On the compensation of dead time and zero-current crossing for a PWM-inverter-controlled AC servo drive’, IEEE Transactions on Industrial Electronics, , Oct. 2004, 51(5), pp. 1113-1118

    [58] Ben-Brahim, L.: ‘New optimal methods for PWM Inverter Dead-time Compensation’, Proc. of the EPE2001, Graz, Austria, August 2001, pp. 1-6

    [59] Ben-Brahim, L.: ‘The analysis and Compensation of dead-time effects in three phase PWM inverters,’ Proc. of the IEEE IECON'98, vol.2, Germany, August/September 1998, pp.792-797

    ReView by River Valley Technologies The Journal of Engineering

    2019/05/31 15:41:05 IET Review Copy Only 11

    This article has been accepted for publication in a future issue of this journal, but has not been fully edited.Content may change prior to final publication in an issue of the journal. To cite the paper please use the doi provided on the Digital Library page.