Demand Response Inverter (DRI)...Performance Monitoring Local performance data storage, downloadable...
Transcript of Demand Response Inverter (DRI)...Performance Monitoring Local performance data storage, downloadable...
Princeton Power Systems Clean power made simple.™
Dem
and
Resp
onse
Inve
rter (
DRI
)
Pre-configured Power Solution The multi-terminal DRI is a 10kW inverter uniquely flexible to be more reliable, more efficient, and more cost-effective than currently available inverters. The DRI’s distinctive E-Quad design combined with its split-phase electrical connections make it ideal for residential applications including residential off-grid systems, electric vehicle charging, and small-commercial applications.
Efficient | Maximize energy.Maximize energy and minimize cost.Improves energy conversion efficiency. Programmable power curves and charge profiles also provide enhanced control for generators, AC loads, and batteries.
Applications | Energy StoragePre-installed energy management applications.Optimize local energy usage and costs with pre-programmed applications including peak-shaving, backup power, time-shifting, and frequency regulation.
Flexible | Integrate quickly and easily.Highly programmable and easily integrated.E-Quad Technology allows power routing to the grid, DC energy storage, and dynamic AC loads. Multiple AC and DC terminals are ideal for microgrid and off-grid systems.
Demand Response Inverter DRI-10Grid-tied, Controllable 4-Terminal Power Conditioner
DC
DC
AC Grid
AC Load
E-QUAD™ Power Flow Control Technology Dynamic control of four bi-directional loads/sources
through a central high-frequency linkF e a t u r e s & O p t i o n s• Ground fault detection and interruption (GFDI optional)
• Web-based performance monitoring.
• Revenue-grade kWh meter (optional)
• Manual AC and DC disconnects and combiner box (optional)
• Utility interface communication modules for Modbus over RS485 and Ethernet (optional).
• Level I/II EV Charging
www.princetonpower.com
Princeton Power DRI
Princeton Power Systems Clean power made simple.™
Demand Response Inverter DRI-10
Grid-tied, Controllable 4-Terminal Power Conditioner
Princeton Power Systems, Inc.
3175 Princeton Pike, Lawrenceville, NJ 08648 USA www.princetonpower.com Tel: (609) 955-5390 • Fax: (609) 751-9225 [email protected] • Press Inquiries: [email protected] • Sales: [email protected]
About Princeton PowerPrinceton Power Systems designs and
manufactures high-performance power electronic converters and systems for
commercial, industrial, and military distributed generation applications.
General SpecificationsPower Rating 10 kWInverter Technology 4-port PWM with central DC linkSize and Weight 19.7 Wx15.8 Dx74.8 H; 440lbsPower Terminals Four (4): 2x DC, 2x AC DC Power Terminal Specifications (x2)Voltage Range 250-600 VDC 254-600VDC Max Power on and off-grid 36-254 VDC Power-Limited On-grid operation (power curve available)PV MPPT Range 260 — 590 VDC Power 10kW PV Array Configuration Positive Grounded/Negative GroundedMax. Current 40 AControl Functions Battery charge/discharge/bulk/float for lead-acid, lithium- ion, and lead-carbon and PV array control
AC Grid Power Terminal SpecificationsVoltage 120/240 VAC +10%/-12% (Split Phase)Maximum Current 46 ARMSPower Factor 0.80 (lag) – 1 – 0.80 (lead) at rated powerLine Frequency 60Hz (57.0 – 63.0Hz)Harmonics <5% THD IEEE 1547 CompliantAC Load Power Terminal SpecificationsVoltage Range 120/240 VAC +10%/-12% (Split Phase)Maximum Current 46 ARMSOverload Capability 150% for 10 seconds, 10-minute duty cycleFrequency Range 60Hz (59.3 – 60.0Hz) compliant with UL 1741Control Functions Parallel operation and generator coordination for intelligent load shedding and generator start.Environmental SpecificationsTemperature Operating: 0 to 40°C Storage: -20 to 60°CHumidity 5 – 95% (non-condensing)Cooling Natural Convection/FanlessRated Max Elevation 3,000 feet (full power) 5,000 feet (de-rated power) Enclosure NEMA 3 Safety FeaturesFaults Over/Under Voltage/Frequency/Current/Temperature Standards Compliance IEEE 1547, CEC, UL 1741*Safety Features Anti-islanding, fused ground fault detection and interrupter,
UL-compliant trip points (factory adjustable), Password protected parameters and Battery over/under-charge protection
User Interface FeaturesFront-Panel Interface Touch screen viewable in and protected from sunlightCommunications MODBUS over RS485 or RS232Performance Monitoring Local performance data storage, downloadable Web-based historical performance data hosting optionsAnalog & Digital I/Os (2) inputs 0-24V, (3) output relays EfficiencyPeak Efficiency 98.0% (PV or Battery to Grid)CEC Efficiency 96.5% (PV or Battery to Grid)Energy-Saving Features Smart load-shedding and Smart Relays
Specifications subject to change without notice, contact manufacturer for updated information.
Copyright © 2013 Princeton Power Systems, Inc. All rights reserved. Printed in the USA
Fo r m o r e o p t i o n s p l e a s e s e e o u r w e b s i t e
Appl
icatio
ns N
ote
(DRI
) Princeton Power Systems Clean power made simple.™
DC
DC AC Backup Loads
AC Grid
AC Grid
Grid-Support Functions • Area Frequency Regulation• Arbitrage• Automatic peak shaving • VAR Support
Princeton Power Systems, Inc. Tel: (609) 955 5390 Fax: (609) 751 9225 [email protected] • [email protected] • [email protected] • www.princetonpower.com
Available Configurations DRI systems are available in several
pre-configured designs or customer specific systems can be designed.
1. 10 kW System • Residential • EV Charging (Level II) 2. 30 kW System • EV Fast Charging (Level III) • Small Commercial
DC Car
DC
DC
AC Grid
Generator
Residential and Commercial Backup • Critical load backup powered by solary/battery• Grid support services• Peak shaving• Time shifting
EV Charging • Enables fast charging 1741• CHAdeMO, SAE Level 1, 2, or 3 • Provides grid support services• Optional PV input for solar charging
Microgrid or Off-grid• AC-coupled for high efficiency• Wide compatibility with
AC generators (diesel, gas, etc.)• Optional PV or Wind inputs• Seamless electric grid interface
DC (Optional)
Common Configurations Key Features
Pre-configured systems are available or specific batteries can be integrated. • Lead-Acid (PbA) • Lithium-ion Phosphate (Li Ph) • Lead-Carbon (PbC) • Sodium Metal Halide (NaMX)
Battery Types DRI systems work with multiple battery types from a variety of manufacturers, including the leading providers of lithium-ion and lead-acid technologies.
120
110
100
90
80
60
40
201 3 5 7 9 11 13 15 17 19 21 23
HOURS
Load
in M
W x
100
00’s
REGULATION
1
0.5
0
-0.5
-1
REG
ULA
TIO
N
TIME(mSec)
BATTERY RESPONSE
0 50 100 150 200 250 300 350 400 450 500
EV Charging
Residential
Small Commercial
Lead-Acid (PbA)
Lithium-ion (Li )
Lead-Carbon (PbC)
AC loads