Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... ·...

15
Demand-Controlled Ventilation When a building is occupied, it is unlikely that every room is at occupant capacity at any given point in time. As the number of people in a zone varies, the quantity of outdoor air required to properly ventilate that zone also varies. However, most buildings are ventilated at design occupancy levels in all spaces at all times, resulting in over-ventilated buildings. Demand-controlled ventilation (DCV) is a strategy that attempts to dynamically reset the outdoor airflow delivered to a zone based on the changing population within that zone. DCV strategies include time-of- day schedules, occupancy sensors, and CO 2 sensors. This article discusses strategies for implementing CO 2 based DCV and how to model these strategies in TRACE 700. Minimum Breathing Zone Requirements ASHRAE Standard 62.1 states that amount of outside air required to properly ventilate a space is the sum of the outside air required to dilute volatile organic compounds (VOCs) given off by paints, wall paper, furniture, etc., and the outside air required to dilute bioeffluents from the occupants in a space. In addition, the standard also permits dynamic reset of intake (outdoor) airflow as operating conditions change, as long as the system provides at least the required breathing zone outdoor airflow whenever a zone is occupied. The minimum breathing zone outdoor airflow (V bz ), is determined using Equation 6-1: V bz = (R p · P z ) + (R a · A z ) Where: V bz = breathing zone outdoor airflow A z = zone floor area: the net occupiable floor area of the ventilation zone ft 2 (m 2 ) R a = outdoor airflow rate required per unit area as determined from Table 6-1 P z = zone population: the number of people in the ventilation zone during typical usage. R p = outdoor airflow rate required per person as determined from Table 6-1

Transcript of Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... ·...

Page 1: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Demand-Controlled Ventilation

When a building is occupied, it is unlikely that every room is at occupant capacity at any given point in time. As the number of people in a zone varies, the quantity of outdoor air required to properly ventilate that zone also varies. However, most buildings are ventilated at design occupancy levels in all spaces at all times, resulting in over-ventilated buildings.

Demand-controlled ventilation (DCV) is a strategy that attempts to dynamically reset the outdoor airflow delivered to a zone based on the changing population within that zone. DCV strategies include time-of-day schedules, occupancy sensors, and CO2 sensors.

This article discusses strategies for implementing CO2 based DCV and how to model these strategies in TRACE 700.

Minimum Breathing Zone Requirements

ASHRAE Standard 62.1 states that amount of outside air required to properly ventilate a space is the sum of the outside air required to dilute volatile organic compounds (VOCs) given off by paints, wall paper, furniture, etc., and the outside air required to dilute bioeffluents from the occupants in a space. In addition, the standard also permits dynamic reset of intake (outdoor) airflow as operating conditions change, as long as the system provides at least the required breathing zone outdoor airflow whenever a zone is occupied.

The minimum breathing zone outdoor airflow (Vbz), is determined using Equation 6-1:

Vbz = (Rp · Pz ) + (Ra · Az )

Where:

Vbz = breathing zone outdoor airflow Az = zone floor area: the net occupiable floor area of the ventilation zone ft2 (m2) Ra = outdoor airflow rate required per unit area as determined from Table 6-1 Pz = zone population: the number of people in the ventilation zone during typical usage. Rp = outdoor airflow rate required per person as determined from Table 6-1

Page 2: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

TRACE Scenario

Let’s take a look at how equation 6-1 comes into play in TRACE, using an example break room that is 20 ft. by 14 ft.

In TRACE, the Apply ASHRAE Std62-1-2004/2007 field must be set to Yes on the Create Rooms-Rooms tab. The values for Ra and Rp are set on the Create Rooms - Airflows tab. In this example, Rp = 5 cfm per person and Ra = 0.06 cfm per square foot.

Area can be calculated from the room dimensions: 𝐴𝑧 = 20 × 14 = 280 𝑠𝑞 𝑓𝑡

Knowing the population density, the design population can also be calculated:

𝑃𝑧 = 280 𝑠𝑞 𝑓𝑒𝑒𝑡 ÷ 200 𝑠𝑞 𝑓𝑒𝑒𝑡 =1.4 𝑝𝑒𝑜𝑝𝑙𝑒

The design ventilation for the break room can then be calculated by solving equation 6-1:

𝑉𝑏𝑧 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.4 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 280 𝑠𝑞 𝑓𝑡) = 23.8 𝑐𝑓𝑚

Page 3: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

The result is a linear relationship between the outdoor air requirement and the zone population.

Figure 1

TRACE will recalculate the zone ventilation requirement on an hourly basis during the simulation phase when the system ventilation flag on the Create Systems – Advanced screen is set to ASHRAE Std 62.1 – 2004/2007 w/ Vent Reset.

Because the values for Ra, Rp and the square footage are fixed for a given room, the only variable in equation 6-1 is the zone population (Pz). In this example, the population varies according to the People – Office schedule.

24 34

44 54

64 74

84 94

104 114

124

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

Outside Air vs Population

Vot - Vbz

Page 4: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

The hourly ventilation airflow is calculated by multiplying the design ventilation airflow by the percentage from the people schedule. For this example, the hourly weekday ventilation when DCV is enabled is shown in Table 1:

Time Percentage

Design Ventilation

(cfm)

Hourly Ventilation

(cfm)

Mid - 7 am 0 23.8 0

7 am - 8 am 30 23.8 7.14

8 am - 5 pm 100 23.8 23.8

5 pm - 6 pm 30 23.8 7.14

6 pm - 7 pm 1 23.8 0.238

7 pm - Mid 0 23.8 0

Table 1

CO2 Based DCV

Just as our surroundings outgas volatile organic compounds (VOCs), humans are also a source of pollution. This is especially apparent when large numbers of people live or work in enclosed, poorly ventilated areas for extended periods of time.

The substances we emit into the air through normal biological processes are called bioeffluents. Studies have found that bioeffluents emitted from each person into the air can contain as many as 150 volatile substances. Principal among these are acetone, human skin, ethyl alcohol, methyl alcohol, and ethyl acetate.

CO2 based DCV assumes that people produce both bioeffluents and CO2 in proportion to their activity level and as a result, the concentration of CO2 in a space accurately represents the concentration of human bioeffluents. It is also assumed that CO2 based steady-state equations can be used to estimate the people component of the ventilation load.

Equation C-1 in Appendix C of ASHRAE 62.1 provides the following mass balance equation to calculate the outdoor airflow rate needed to maintain the steady-state CO2 concentration below a given limit.

𝑉𝑜 =N

𝐶𝑠 − 𝐶𝑜

Where: Vo = outdoor airflow rate per person N = CO2 generation rate per person Cs = CO2 concentration in the space Co = CO2 concentration in the outdoor air

Page 5: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

CO2 based DCV makes one additional assumption: occupant activity level in a zone (in terms of metabolic rate, m) can be estimated with reasonable accuracy. Then the CO2 generation rate per person (N) can be expressed in terms of metabolic rate (m) and the per person CO2 generation rate (k):

N = m x k

Where: N = CO2 generation rate per person m = activity level of occupants, met k = 0.0084 cfm per met per person for healthy people The outdoor airflow rate per person (Vo ) can be expressed in terms of Vbz and Pz:

𝑉𝑜 = 𝑉𝑏𝑧 𝑃𝑧�

Where: Vbz = the minimum breathing zone outdoor airflow Pz = the zone population Rewriting equation C-1 and substituting for N and Vo yields equation 1:

𝐶𝑠 = 𝑘 × 𝑚𝑉𝑏𝑧

𝑃𝑧�+ 𝐶𝑜

Proportional Control DCV

This control strategy varies the intake airflow in direct proportion to the actual differential CO2 level. Two control points (min CO2 concentration, min ventilation airflow) and (max CO2 concentration, design ventilation airflow) establish a linear relationship between the CO2 concentration in the space and the ventilation airflow. A CO2 sensor in the space measures the concentration and reports this value to a controller programmed with this relationship which resets the outdoor requirement in the space. (See Figure 2)

Figure 2

The minimum CO2 concentration is generally accepted to be that of the outdoor air (350 ppm - 400 ppm). The minimum ventilation airflow and maximum ventilation airflow are

Out

side

Air

(cfm

)

CO2 Concentration

(min CO2, min OA)

(max CO2, design OA)

Page 6: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

calculated using equation 6 -1, selecting Pz values of zero and the design occupancy respectively. The maximum CO2 concentration is calculated using equation 1 as shown in the following example.

Applying the proportional control strategy to the break room example the calculations yield the following results:

Minimum CO2 concentration

CO2 min = 400 ppm (Assumed)

Minimum ventilation airflow (Vbz min)

𝑉𝑏𝑧 𝑚𝑖𝑛 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 0 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 24 𝑐𝑓𝑚

Maximum ventilation airflow (Vbz max)

𝑉𝑏𝑧 𝑚𝑎𝑥 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 20 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 124 𝑐𝑓𝑚

To calculate the maximum CO2 concentration it is first necessary to determine the metabolic rate (m) using Figure C-2 from Appendix G in ASHRAE Std. 62.1. Choosing an activity level of “office work” for the break room the metabolic rate is determined to be 1.2 met units. (See Figure C.2)

Page 7: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

The maximum CO2 concentration can now be calculated for the design occupancy using equation 1.

𝐶𝑚𝑎𝑥 =0.0084 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑚𝑒𝑡 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.2 𝑚𝑒𝑡

124 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 20 𝑝𝑒𝑜𝑝𝑙𝑒⁄ × 106 + 400 𝑝𝑝𝑚 = 2025.8 𝑝𝑝𝑚

The resulting ventilation is plotted along with the ASHRAE Std. 62.1 minimum ventilation requirements in Figure 3.

Figure 3

The difference between the two lines is an excess amount of outside air the space will receive for any given population. The reason for the over ventilation is that the controller models the change in CO2 as a linear function. A plot of the total CO2 in the break room versus population shows that it is not. (Refer to Figure 4)

24 34

44 54

64 74

84 94

104 114

124

24

60

80 93

102 108 113 116 119 122 124

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

Outside Air vs Population

Vot - Vbz

Vot - CO2

Page 8: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Figure 4

To understand how the controller determines the ventilation airflow, choose a discrete value for the number of people currently in the space. For this example it will be assumed that there are four people in the break room. The resulting CO2 level in the space will be 1316 ppm. (See Figure 5)

Figure 5

A controller employing proportional control DCV will sense 1316 ppm of CO2 in the space but has no knowledge of the actual population. The only thing it can do is control based on where the CO2 level intersects linear function shown in Figure 4. In this example, the CO2 level of 1316 ppm corresponds to 11.3 people in the space. (Refer to Figure 6)

400

993

1316 1520

1660 1762 1840 1901 1951 1992 2026

0

500

1000

1500

2000

2500

0 5 10 15 20 25

Tota

l CO

2

# of People

Total CO2 vs Population

Co2

Linear

400

993

1316 1520

1660 1762 1840 1901 1951 1992 2026

0

500

1000

1500

2000

2500

0 5 10 15 20 25

Tota

l CO

2

# of People

Total CO2 vs Population

Co2

1316 ppm

Page 9: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Figure 6

Plotting the calculated population of 11.3 people against the minimum ventilation requirements calculated using equation 6-1 results in an outside air requirement (Vot) of 80.3 cfm. (Refer to Figure 7)

Figure 7

The outside air requirement (80.3 cfm) can now be plotted against the break room population of four people. (See Figure 8)

0

500

1000

1500

2000

2500

0 5 10 15 20 25

Tota

l CO

2

# of People

Total CO2 vs Population

24 34

44 54

64 74

84 94

104 114

124

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

Outside Air vs Population

Vot - Vbz

1316 ppm

Page 10: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Figure 8

Plotting the outside air requirements for the entire population results in the curve shown in Figure 9 along with ASHRAE Std. 62.1 minimum ventilation requirements.

Figure 9

24 34

44 54

64 74

84 94

104 114

124

80.3

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

Outside Air vs Population

Vot - Vbz

4 People

24 34

44 54

64 74

84 94

104 114

124

24

60

80 93

102 108 113 116 119 122 124

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

Outside Air vs Population

Vot - Vbz

Vot - CO2

Page 11: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Single Setpoint CO2 DCV This single setpoint strategy requires the user to enter only one value, the zone population for which both the fixed CO2 setpoint and minimum ventilation airflow limit are to be calculated. The controller adjusts the outdoor airflow intake to maintain a fixed CO2 level in the space, thereby maintaining a fixed outdoor airflow rate per person. A minimum ventilation airflow limit is enforced if CO2 levels in the space fall below the setpoint.

Figure 10 illustrates how CO2 levels will change in response to varying populations in the break room example with a setpoint population of 10 people.

Figure 10

The fixed CO2 setpoint is calculated for the setpoint occupancy using equation 1.

𝐶𝑚𝑎𝑥 =0.0084 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑚𝑒𝑡 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.2 𝑚𝑒𝑡

74 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 10 𝑝𝑒𝑜𝑝𝑙𝑒⁄ × 106 + 400 𝑝𝑝𝑚 = 1762.2 𝑝𝑝𝑚

Where the minimum ventilation airflow (Vbz min)

𝑉𝑏𝑧 𝑚𝑖𝑛 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 10 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 74 𝑐𝑓𝑚

The resulting ventilation is plotted along with the ASHRAE Std. 62.1 minimum ventilation requirements in Figure 11.

400 536

672 809

945 1081

1217 1354

1490 1626

1762 1762

0200400600800

100012001400160018002000

0 5 10 15 20 25

Tota

l CO

2

# of People

Total CO2 vs Population

Co2

Page 12: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Figure 11

The difference between the two lines is the excess amount of outside air the space will receive whenever the space population is above or below the setpoint population. Figures 12 and 13 illustrate how different setpoint populations will affect the amount of excess ventilation for different populations.

Figure 12

0

20

40

60

80

100

120

140

160

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

10 People Single Setpoint

Min 10

Vot

0

50

100

150

200

250

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

5 People Single Setpoint

Min 5

Vot

Page 13: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Figure 13

Modeling CO2 Based DCV in TRACE 700 On the Rooms tab of Create Rooms (or on the thermostat template), select a CO2 Sensor location (either Room or None) for the rooms that will have demand-control ventilation control.

On the Airflows tab of Create Rooms, select Yes in the Apply ASHRAE Std 62.1-2004/2007 field.

0

20

40

60

80

100

120

140

0 5 10 15 20 25

Out

side

Air

(Vot

)

# of People

15 People Single Setpoint

Min 15

Vot

Page 14: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

The DCV Min OA Intake field must now be edited to calculate the appropriate setpoint according to the CO2 based DCV control strategy that is going to be implemented.

DCV Min OA Intake options • % Room Population

Best practice is to select % Room Population for both proportional control and single setpoint DCV.

When % Room Population is selected, the percentage is multiplied times the design occupancy of the space to determine the number of people at which to calculate the minimum ventilation airflow using equation 6.1.

Vbz = (Rp · Pz ) + (Ra · Az )

Where:

Vbz = breathing zone outdoor airflow Az = zone floor area: the net occupiable floor area of the ventilation zone ft2 (m2) Ra = outdoor airflow rate required per unit area as determined from Table 6-1 Pz = zone population: the number of people in the ventilation zone during typical usage. Rp = outdoor airflow rate required per person as determined from Table 6-1

When using Single Setpoint control, the number of people is also used to calculate the fixed CO2 setpoint. (Refer to the Single Setpoint CO2 DCV section of this document.)

• % Dsn OA Airflow

Note: % Dsn OA Airflow is only applicable with proportional control DCV. The reason is that population is required to calculate the fixed CO2 setpoint for single setpoint control.

% Dsn OA Airflow allows the user to calculate a minimum ventilation airflow based on the design outside airflow rather than using equation C-1.

Page 15: Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... · Demand-Controlled Ventilation . When a building is occupied, it is unlikely that every room

Default Values

CO2 based DCV method: None or Proportional Control If the field is left blank, the program will default to 0%

CO2 based DCV method: Single Setpoint If the field is left blank or set to 0%, the program defaults to 40%.

If the value field is left blank the default of zero will be used.

Selecting Proportional Control or Single Setpoint

On the Selection tab of Create Systems, click the Advanced button. Select the option ASHRAE Std 62.1-2004/2007 w/ Vent Reset in the System Ventilation Flag field.

Note: System-level ventilation reset is required for the system to be able to handle zone-level demand-control ventilation. At the bottom of the screen, select the desired C02-based DCV option (None, Proportional Control, or Single Setpoint).