Mary Lou Roberts IT’S AN ON DEMAND CONSUMER CONTROLLED WORLD OUT THERE! October 2009.
Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... ·...
Transcript of Demand Controlled Ventilationtranecds.custhelp.com/ci/fattach/get/482/0/filename/... ·...
Demand-Controlled Ventilation
When a building is occupied, it is unlikely that every room is at occupant capacity at any given point in time. As the number of people in a zone varies, the quantity of outdoor air required to properly ventilate that zone also varies. However, most buildings are ventilated at design occupancy levels in all spaces at all times, resulting in over-ventilated buildings.
Demand-controlled ventilation (DCV) is a strategy that attempts to dynamically reset the outdoor airflow delivered to a zone based on the changing population within that zone. DCV strategies include time-of-day schedules, occupancy sensors, and CO2 sensors.
This article discusses strategies for implementing CO2 based DCV and how to model these strategies in TRACE 700.
Minimum Breathing Zone Requirements
ASHRAE Standard 62.1 states that amount of outside air required to properly ventilate a space is the sum of the outside air required to dilute volatile organic compounds (VOCs) given off by paints, wall paper, furniture, etc., and the outside air required to dilute bioeffluents from the occupants in a space. In addition, the standard also permits dynamic reset of intake (outdoor) airflow as operating conditions change, as long as the system provides at least the required breathing zone outdoor airflow whenever a zone is occupied.
The minimum breathing zone outdoor airflow (Vbz), is determined using Equation 6-1:
Vbz = (Rp · Pz ) + (Ra · Az )
Where:
Vbz = breathing zone outdoor airflow Az = zone floor area: the net occupiable floor area of the ventilation zone ft2 (m2) Ra = outdoor airflow rate required per unit area as determined from Table 6-1 Pz = zone population: the number of people in the ventilation zone during typical usage. Rp = outdoor airflow rate required per person as determined from Table 6-1
TRACE Scenario
Let’s take a look at how equation 6-1 comes into play in TRACE, using an example break room that is 20 ft. by 14 ft.
In TRACE, the Apply ASHRAE Std62-1-2004/2007 field must be set to Yes on the Create Rooms-Rooms tab. The values for Ra and Rp are set on the Create Rooms - Airflows tab. In this example, Rp = 5 cfm per person and Ra = 0.06 cfm per square foot.
Area can be calculated from the room dimensions: 𝐴𝑧 = 20 × 14 = 280 𝑠𝑞 𝑓𝑡
Knowing the population density, the design population can also be calculated:
𝑃𝑧 = 280 𝑠𝑞 𝑓𝑒𝑒𝑡 ÷ 200 𝑠𝑞 𝑓𝑒𝑒𝑡 =1.4 𝑝𝑒𝑜𝑝𝑙𝑒
The design ventilation for the break room can then be calculated by solving equation 6-1:
𝑉𝑏𝑧 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.4 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 280 𝑠𝑞 𝑓𝑡) = 23.8 𝑐𝑓𝑚
The result is a linear relationship between the outdoor air requirement and the zone population.
Figure 1
TRACE will recalculate the zone ventilation requirement on an hourly basis during the simulation phase when the system ventilation flag on the Create Systems – Advanced screen is set to ASHRAE Std 62.1 – 2004/2007 w/ Vent Reset.
Because the values for Ra, Rp and the square footage are fixed for a given room, the only variable in equation 6-1 is the zone population (Pz). In this example, the population varies according to the People – Office schedule.
24 34
44 54
64 74
84 94
104 114
124
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
Outside Air vs Population
Vot - Vbz
The hourly ventilation airflow is calculated by multiplying the design ventilation airflow by the percentage from the people schedule. For this example, the hourly weekday ventilation when DCV is enabled is shown in Table 1:
Time Percentage
Design Ventilation
(cfm)
Hourly Ventilation
(cfm)
Mid - 7 am 0 23.8 0
7 am - 8 am 30 23.8 7.14
8 am - 5 pm 100 23.8 23.8
5 pm - 6 pm 30 23.8 7.14
6 pm - 7 pm 1 23.8 0.238
7 pm - Mid 0 23.8 0
Table 1
CO2 Based DCV
Just as our surroundings outgas volatile organic compounds (VOCs), humans are also a source of pollution. This is especially apparent when large numbers of people live or work in enclosed, poorly ventilated areas for extended periods of time.
The substances we emit into the air through normal biological processes are called bioeffluents. Studies have found that bioeffluents emitted from each person into the air can contain as many as 150 volatile substances. Principal among these are acetone, human skin, ethyl alcohol, methyl alcohol, and ethyl acetate.
CO2 based DCV assumes that people produce both bioeffluents and CO2 in proportion to their activity level and as a result, the concentration of CO2 in a space accurately represents the concentration of human bioeffluents. It is also assumed that CO2 based steady-state equations can be used to estimate the people component of the ventilation load.
Equation C-1 in Appendix C of ASHRAE 62.1 provides the following mass balance equation to calculate the outdoor airflow rate needed to maintain the steady-state CO2 concentration below a given limit.
𝑉𝑜 =N
𝐶𝑠 − 𝐶𝑜
Where: Vo = outdoor airflow rate per person N = CO2 generation rate per person Cs = CO2 concentration in the space Co = CO2 concentration in the outdoor air
CO2 based DCV makes one additional assumption: occupant activity level in a zone (in terms of metabolic rate, m) can be estimated with reasonable accuracy. Then the CO2 generation rate per person (N) can be expressed in terms of metabolic rate (m) and the per person CO2 generation rate (k):
N = m x k
Where: N = CO2 generation rate per person m = activity level of occupants, met k = 0.0084 cfm per met per person for healthy people The outdoor airflow rate per person (Vo ) can be expressed in terms of Vbz and Pz:
𝑉𝑜 = 𝑉𝑏𝑧 𝑃𝑧�
Where: Vbz = the minimum breathing zone outdoor airflow Pz = the zone population Rewriting equation C-1 and substituting for N and Vo yields equation 1:
𝐶𝑠 = 𝑘 × 𝑚𝑉𝑏𝑧
𝑃𝑧�+ 𝐶𝑜
Proportional Control DCV
This control strategy varies the intake airflow in direct proportion to the actual differential CO2 level. Two control points (min CO2 concentration, min ventilation airflow) and (max CO2 concentration, design ventilation airflow) establish a linear relationship between the CO2 concentration in the space and the ventilation airflow. A CO2 sensor in the space measures the concentration and reports this value to a controller programmed with this relationship which resets the outdoor requirement in the space. (See Figure 2)
Figure 2
The minimum CO2 concentration is generally accepted to be that of the outdoor air (350 ppm - 400 ppm). The minimum ventilation airflow and maximum ventilation airflow are
Out
side
Air
(cfm
)
CO2 Concentration
(min CO2, min OA)
(max CO2, design OA)
calculated using equation 6 -1, selecting Pz values of zero and the design occupancy respectively. The maximum CO2 concentration is calculated using equation 1 as shown in the following example.
Applying the proportional control strategy to the break room example the calculations yield the following results:
Minimum CO2 concentration
CO2 min = 400 ppm (Assumed)
Minimum ventilation airflow (Vbz min)
𝑉𝑏𝑧 𝑚𝑖𝑛 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 0 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 24 𝑐𝑓𝑚
Maximum ventilation airflow (Vbz max)
𝑉𝑏𝑧 𝑚𝑎𝑥 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 20 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 124 𝑐𝑓𝑚
To calculate the maximum CO2 concentration it is first necessary to determine the metabolic rate (m) using Figure C-2 from Appendix G in ASHRAE Std. 62.1. Choosing an activity level of “office work” for the break room the metabolic rate is determined to be 1.2 met units. (See Figure C.2)
The maximum CO2 concentration can now be calculated for the design occupancy using equation 1.
𝐶𝑚𝑎𝑥 =0.0084 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑚𝑒𝑡 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.2 𝑚𝑒𝑡
124 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 20 𝑝𝑒𝑜𝑝𝑙𝑒⁄ × 106 + 400 𝑝𝑝𝑚 = 2025.8 𝑝𝑝𝑚
The resulting ventilation is plotted along with the ASHRAE Std. 62.1 minimum ventilation requirements in Figure 3.
Figure 3
The difference between the two lines is an excess amount of outside air the space will receive for any given population. The reason for the over ventilation is that the controller models the change in CO2 as a linear function. A plot of the total CO2 in the break room versus population shows that it is not. (Refer to Figure 4)
24 34
44 54
64 74
84 94
104 114
124
24
60
80 93
102 108 113 116 119 122 124
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
Outside Air vs Population
Vot - Vbz
Vot - CO2
Figure 4
To understand how the controller determines the ventilation airflow, choose a discrete value for the number of people currently in the space. For this example it will be assumed that there are four people in the break room. The resulting CO2 level in the space will be 1316 ppm. (See Figure 5)
Figure 5
A controller employing proportional control DCV will sense 1316 ppm of CO2 in the space but has no knowledge of the actual population. The only thing it can do is control based on where the CO2 level intersects linear function shown in Figure 4. In this example, the CO2 level of 1316 ppm corresponds to 11.3 people in the space. (Refer to Figure 6)
400
993
1316 1520
1660 1762 1840 1901 1951 1992 2026
0
500
1000
1500
2000
2500
0 5 10 15 20 25
Tota
l CO
2
# of People
Total CO2 vs Population
Co2
Linear
400
993
1316 1520
1660 1762 1840 1901 1951 1992 2026
0
500
1000
1500
2000
2500
0 5 10 15 20 25
Tota
l CO
2
# of People
Total CO2 vs Population
Co2
1316 ppm
Figure 6
Plotting the calculated population of 11.3 people against the minimum ventilation requirements calculated using equation 6-1 results in an outside air requirement (Vot) of 80.3 cfm. (Refer to Figure 7)
Figure 7
The outside air requirement (80.3 cfm) can now be plotted against the break room population of four people. (See Figure 8)
0
500
1000
1500
2000
2500
0 5 10 15 20 25
Tota
l CO
2
# of People
Total CO2 vs Population
24 34
44 54
64 74
84 94
104 114
124
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
Outside Air vs Population
Vot - Vbz
1316 ppm
Figure 8
Plotting the outside air requirements for the entire population results in the curve shown in Figure 9 along with ASHRAE Std. 62.1 minimum ventilation requirements.
Figure 9
24 34
44 54
64 74
84 94
104 114
124
80.3
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
Outside Air vs Population
Vot - Vbz
4 People
24 34
44 54
64 74
84 94
104 114
124
24
60
80 93
102 108 113 116 119 122 124
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
Outside Air vs Population
Vot - Vbz
Vot - CO2
Single Setpoint CO2 DCV This single setpoint strategy requires the user to enter only one value, the zone population for which both the fixed CO2 setpoint and minimum ventilation airflow limit are to be calculated. The controller adjusts the outdoor airflow intake to maintain a fixed CO2 level in the space, thereby maintaining a fixed outdoor airflow rate per person. A minimum ventilation airflow limit is enforced if CO2 levels in the space fall below the setpoint.
Figure 10 illustrates how CO2 levels will change in response to varying populations in the break room example with a setpoint population of 10 people.
Figure 10
The fixed CO2 setpoint is calculated for the setpoint occupancy using equation 1.
𝐶𝑚𝑎𝑥 =0.0084 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑚𝑒𝑡 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 1.2 𝑚𝑒𝑡
74 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 10 𝑝𝑒𝑜𝑝𝑙𝑒⁄ × 106 + 400 𝑝𝑝𝑚 = 1762.2 𝑝𝑝𝑚
Where the minimum ventilation airflow (Vbz min)
𝑉𝑏𝑧 𝑚𝑖𝑛 = (5 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛 × 10 𝑝𝑒𝑜𝑝𝑙𝑒) + (0.06 𝑐𝑓𝑚 𝑝𝑒𝑟 𝑠𝑞 𝑓𝑡 × 400 𝑠𝑞 𝑓𝑡) = 74 𝑐𝑓𝑚
The resulting ventilation is plotted along with the ASHRAE Std. 62.1 minimum ventilation requirements in Figure 11.
400 536
672 809
945 1081
1217 1354
1490 1626
1762 1762
0200400600800
100012001400160018002000
0 5 10 15 20 25
Tota
l CO
2
# of People
Total CO2 vs Population
Co2
Figure 11
The difference between the two lines is the excess amount of outside air the space will receive whenever the space population is above or below the setpoint population. Figures 12 and 13 illustrate how different setpoint populations will affect the amount of excess ventilation for different populations.
Figure 12
0
20
40
60
80
100
120
140
160
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
10 People Single Setpoint
Min 10
Vot
0
50
100
150
200
250
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
5 People Single Setpoint
Min 5
Vot
Figure 13
Modeling CO2 Based DCV in TRACE 700 On the Rooms tab of Create Rooms (or on the thermostat template), select a CO2 Sensor location (either Room or None) for the rooms that will have demand-control ventilation control.
On the Airflows tab of Create Rooms, select Yes in the Apply ASHRAE Std 62.1-2004/2007 field.
0
20
40
60
80
100
120
140
0 5 10 15 20 25
Out
side
Air
(Vot
)
# of People
15 People Single Setpoint
Min 15
Vot
The DCV Min OA Intake field must now be edited to calculate the appropriate setpoint according to the CO2 based DCV control strategy that is going to be implemented.
DCV Min OA Intake options • % Room Population
Best practice is to select % Room Population for both proportional control and single setpoint DCV.
When % Room Population is selected, the percentage is multiplied times the design occupancy of the space to determine the number of people at which to calculate the minimum ventilation airflow using equation 6.1.
Vbz = (Rp · Pz ) + (Ra · Az )
Where:
Vbz = breathing zone outdoor airflow Az = zone floor area: the net occupiable floor area of the ventilation zone ft2 (m2) Ra = outdoor airflow rate required per unit area as determined from Table 6-1 Pz = zone population: the number of people in the ventilation zone during typical usage. Rp = outdoor airflow rate required per person as determined from Table 6-1
When using Single Setpoint control, the number of people is also used to calculate the fixed CO2 setpoint. (Refer to the Single Setpoint CO2 DCV section of this document.)
• % Dsn OA Airflow
Note: % Dsn OA Airflow is only applicable with proportional control DCV. The reason is that population is required to calculate the fixed CO2 setpoint for single setpoint control.
% Dsn OA Airflow allows the user to calculate a minimum ventilation airflow based on the design outside airflow rather than using equation C-1.
Default Values
CO2 based DCV method: None or Proportional Control If the field is left blank, the program will default to 0%
CO2 based DCV method: Single Setpoint If the field is left blank or set to 0%, the program defaults to 40%.
If the value field is left blank the default of zero will be used.
Selecting Proportional Control or Single Setpoint
On the Selection tab of Create Systems, click the Advanced button. Select the option ASHRAE Std 62.1-2004/2007 w/ Vent Reset in the System Ventilation Flag field.
Note: System-level ventilation reset is required for the system to be able to handle zone-level demand-control ventilation. At the bottom of the screen, select the desired C02-based DCV option (None, Proportional Control, or Single Setpoint).