![Page 1: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/1.jpg)
Demand control ventilation: maximize savings with practical approaches
Scott Hackel, Principal Engineer
February 23, 2015
![Page 2: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/2.jpg)
Minnesota Conservation Applied Research and Development
(CARD) Grant Program
Acknowledgement
![Page 3: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/3.jpg)
• Quality DCV design
• Field study results
• (Re)commissioning
Today’s topics
![Page 4: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/4.jpg)
Background on DCV FIELD STUDY
Sensor
VAV Boxes
Central and/or Zone Control
AHU
Source: http://i.stack.imgur.com/4WKDC.jpg
SA OA
RA
![Page 5: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/5.jpg)
Quality DCV design
![Page 6: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/6.jpg)
• Specific sequence - CO2 setpoint - Outside airflow lower limit
• CO2 sensor location
• Airflow measurement req.
Choose responsible party Be complete:
Mechanical engineer Controls contractor Other (vendor, …)
Be thorough DCV DESIGN
![Page 7: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/7.jpg)
1. Direct OA flow control a. Zone CO2 sensors
b. Return CO2 sensor
Slight potential for imperfect IAQ…
More potential for imperfect IAQ…
SA
OA
RA
BAS
BAS
Sequence options DCV DESIGN
![Page 8: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/8.jpg)
2. Ventilation reset a. OA flow reset
b. Zone, then OA flow reset
c. Zone, then OA flow reset, with occupancy sensors
BAS
Sequence options DCV DESIGN
![Page 9: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/9.jpg)
4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00
OAFlow
Rate(cfm
)
DesignOA
SeparationbetweenOAlowerlimit andDesignOAdrivesenergysavings
Upper limit Freeze protection Mitigates failures
Lower limit Save energy Maintain press.
Elements of sequence DCV DESIGN
![Page 10: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/10.jpg)
CO2 setpoint Setpoint(s) per: 𝐶↓𝑅 = 𝐶↓𝑂𝐴 + 8400𝐸↓𝑍 ×𝑚𝑒𝑡/𝑅↓𝑃 + 𝑅↓𝑎 ×(𝑠𝑓/𝑝 )
Proportional or single setpoint
Elements of sequence DCV DESIGN
![Page 11: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/11.jpg)
Ideally in zone • At breathing height (3-6 ft.) • Not below a thermostat
Common return • Limited situations
Show on drawings!
CO2 sensor location DCV DESIGN
![Page 12: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/12.jpg)
Use occupancy sensors! • Occ. sensor = VAV savings, aside from DCV
AFMS on drawings
Consider OA diversity in sizing
DCV: not just a ‘Yes / No’ choice • Control portion of zones • Strategically use common return • Use 2-way dampers • Mix approaches
Other considerations DCV DESIGN
![Page 13: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/13.jpg)
Field study results
![Page 14: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/14.jpg)
Characterization of approaches FIELD STUDY
96 systems around Minnesota:
![Page 15: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/15.jpg)
Approaches (sequences):
1a. Direct OA flow control, return sens.
1b. Direct OA flow control
2a. Ventilation reset
2b. Zone box, then ventilation reset
2c. Zone min. reset, w/ occ. sensors 19%
22%
15%
26%
19%
Characterization of approaches FIELD STUDY
![Page 16: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/16.jpg)
Measured savings per design OA rate (cfm) Occ. + CO2 sensing
High lower limit
With ERV
Median = $0.50/cfm
Results FIELD STUDY
![Page 17: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/17.jpg)
Results FIELD STUDY
therms/cfm kWh/cfm $/cfmMedian 0.80 0.64 0.59
ChangefromMSPresults 27% -34% 18%
SavingsperDesignOAFlow
We also scaled the results to a Duluth climate
![Page 18: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/18.jpg)
Deficiencies
Recommissioning FIELD STUDY
![Page 19: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/19.jpg)
Recommissioning results FIELD STUDY
Half the systems saved more, an average of 54%
![Page 20: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/20.jpg)
Economics FIELD STUDY
![Page 21: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/21.jpg)
(Re)commissioning
![Page 22: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/22.jpg)
• Conduct when hot, or very cold outside • Review CO2 and OA flow trends:
CO2 (ppm) OA flow (cfm)
Find lower limit (also look for upper)
CO2 follows occupancy
OA flow increases per sequence
Virtual performance checks Cx
![Page 23: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/23.jpg)
• Determine control: 1) OA damper position vs. 2) OA flow measurement (if available)
• Check for rogue DCV zones
• Check CO2 sensor reading at unoccupied
• Determine OA damper schedule
• Recognize that savings is from heating (gas)
- Economizer negates cooling savings
• Verify economizer operation
Virtual performance checks Cx
![Page 24: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/24.jpg)
Meet the operator on-site; discuss system operation
Validate measured points: • Temperatures: SA, MA, RA, OA (brief traverse) • Valve positions (visual, temp) • OA damper position (visual) • Supply fan speed (VFD)
Spot checks Cx
![Page 25: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/25.jpg)
CO2 sensors • Calibrate or replace
• Recalculate setpoint per Standard 62.1 • Auto calibration valid?
Sensors Cx
![Page 26: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/26.jpg)
Perform basic system performance tests § AHU § Key VAV boxes Correct deficiencies found in tests Optimize:
à OA upper / lower limit, CO2 setpoint, OA schedule
SPT and Sequence Optimization Cx
![Page 27: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/27.jpg)
Report any changes made Add any needed trending Complete handover missed at install • Document the
sequence • Plan for future
monitoring
4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00
OAFlow
Rate(cfm
)
DesignOA
SeparationbetweenOAlowerlimit andDesignOAdrivesenergysavings
Hand over to operators Cx
![Page 28: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/28.jpg)
Sequences • Basic: EDR 2007
• Ventilation reset: Trane 2005
• With occupancy sensors: Taylor 2014. Demand control ventilation for multiple zone VAV systems – problem solved (from ASHRAE Annual Meeting, Seattle 2014; seminar available for a fee)
Code requirements Code Notes 2012 IECC Demand Control Ventilation
AFMS: Fisk 2009
CO2 sensor performance: Shrestha 2009
For more information Cx
![Page 29: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):](https://reader036.fdocuments.net/reader036/viewer/2022071019/5fd387c4076d2d49842ee427/html5/thumbnails/29.jpg)
Download the study Stay tuned for a fact sheet and the full report: seventhwave.org/dcv
Contact me [email protected] 608.210.7129